Академический Документы
Профессиональный Документы
Культура Документы
CQM
Automatic Tube Cleaning System
in
Taikoo Place
by
Wallace Wu & Dave Chan
Page 1 of 20
:
:
:
:
ATAL Engineering Ltd. was appointed by Swire to carry out the contract work.
Project Description
The contract work includes the supply & installation of CQM to the following chillers :Oxford House
Chiller : Chiller No.1 & 3
Tonnage of each chiller : 700 ton
Model of CQM : CQM-10
Fig. 1
Lincoln House
Chiller : Chiller No.1 ,2 & 3
Tonnage of each chiller : 400 ton
Model of CQM : CQM-10
Fig. 2
Dorset House
Chiller : Chiller No.1 ,2 & 3
Tonnage of each chiller : 1540 ton
Model of CQM : CQM-18
Fig. 3
Page 2 of 20
Somerset House
Chiller : Chiller No.1 ,2 & 3
Tonnage of each chiller : 780 ton
Model of CQM : CQM-12
Fig. 4
Page 3 of 20
Fig. 5
Compressor
Fig. 6
Overall Transfer
Coefficient
Thickness Scale
Approx.
Increase in Heat
Transfer Area Reqd.
(mm)
(Approximate %)
Clean Tube
850
0.0005
595
0.15
45
0.001
460
0.3
85
0.002
315
0.6
170
0.003
240
0.9
250
130%
120%
110%
100%
0.3
0.6
0.9
1.2
CQM automatic tube condenser cleaning system clean the condenser tubes and eliminate tubing
fouling by removing debris from tube surfaces as often as they are deposited. This enables the
condensers and heat exchanger to operate at 100% of rated capacity.
Page 4 of 20
In addition, the energy saving of the system is calculated by measuring the improvement in Coefficient
of Performance (COP) before and after installation..
Qe = e Cp (te'tl ' )....................................(2)
WD = 3 V I p. f ......................................(3)
Qe
COP =
......................................................(4)
WD
1
1
Where,
Qe
Me
Cp
te
tl
WD
V
I
p.f.
COP
Tc
Tco
T
Page 5 of 20
Oxford House
Condensing Water Inlet Temperature between 27 and 28
T between condensing refrigerant
and condensing water outlet ()
7
6
5
4
3
2
1
0
0
100
200
300
400
500
600
Figure 7.1 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Oxford House with condensing water inlet temperature between 27 and 28
Page 6 of 20
7
6
5
4
3
2
1
0
0
100
200
300
400
500
600
Figure 7.2 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Oxford House with condensing water inlet temperature between 28 and 29
100
200
300
400
500
600
Figure 7.3 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Oxford House with condensing water inlet temperature between 29 and 30
After the installing CQM in Oxford House, the fouling factor has been improved by 181% with
average T decreased by 2.77.
Page 7 of 20
Lincoln House
Condensing Water Inlet Temperature between 27 and 28
T between condensing
refrigerant and condensing
water outlet ()
12
10
0
0
50
100
150
200
250
300
350
Figure 8.1 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Lincoln House with condensing water inlet temperature between 27 and 28
50
100
150
200
250
300
350
Figure 8.2 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Lincoln House with condensing water inlet temperature between 28 and 29
Page 8 of 20
9
8
7
6
5
4
3
2
1
0
0
50
100
150
200
250
300
350
Figure 8.3 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Lincoln House with condensing water inlet temperature between 29 and 30
In Lincoln House, the fouling factor has been improved by 77% with average T greatly
reduced from 6.39 to 1.42 (i.e. 4.97 improvement).
Dorset House
Condensing Water Inlet Temperature between 27 and 28
T between condensing
refrigerant and condensing water
outlet ()
12.0
10.0
8.0
6.0
4.0
2.0
0.0
0
200
400
600
800
1000
1200
1400
Figure 9.1 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Dorset House with condensing water inlet temperature between 27 and 28
Page 9 of 20
200
400
600
800
1000
1200
1400
Figure 9.2 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Dorset House with condensing water inlet temperature between 28 and 29
9.0
8.0
7.0
6.0
5.0
4.0
3.0
2.0
1.0
0.0
0
200
400
600
800
1000
1200
1400
Figure 9.3 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Dorset House with condensing water inlet temperature between 29 and 30
In Dorset House, the average T is reduced from 6.72 to 4.84 and the fouling factor has
reduced by 28.%.
Page 10 of 20
Somerest House
Condensing Water Inlet Temperature between 27 and 28
T between condensing refrigerant and
condensing water outlet ()
9
8
7
6
5
4
3
2
1
0
0
100
200
300
400
500
600
Figure 10.1 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Somerest House with condensing water inlet temperature between 27 and 28
100
200
300
400
500
600
Figure 10.2 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Somerest House with condensing water inlet temperature between 28 and 29
Page 11 of 20
9
8
7
6
5
4
3
2
1
0
0
100
200
300
400
500
600
Figure 10.3 the temperature difference between the condensing refrigerant and condensing water outlet against
electrical power input in Somerest House with condensing water inlet temperature between 29 and 30
In Somerset House, the average T is reduced by 1.35 and the average improvement on
fouling factor is 26%.
Page 12 of 20
Coefficient of Performance
The comparisons between the COP before and after CQM installation at different condensing
temperature are shown in the following figures. All the COP have been greatly improved except the
chillers at Oxford Housing where the chiller water set point has been changed during the data
recording period.
Lincoln House
Condensing Water Inlet Temperature between 27 and 28
6
5
COP
4
3
50
100
150
200
250
300
350
Figure 11.1 the coefficient of performance before and after CQM installation in Lincoln House with condensing
water inlet temperature between 27 and 28
Page 13 of 20
COP
5
4
3
2
1
0
0
50
100
150
200
250
300
350
Figure 11.2 the coefficient of performance before and after CQM installation in Lincoln House with condensing
water inlet temperature between 28and 29
COP
4
3
2
1
0
0
50
100
150
200
250
300
350
Figure 11.3 the coefficient of performance before and after CQM installation in Lincoln House with condensing
water inlet temperature between 29 and 30
In Lincoln House, the average COP improvement under the condensing temperature range
between 27 and 30 is 21.2%.
Page 14 of 20
Dorset House
Condensing Water Inlet Temperature between 27 and 28
7.0
6.0
COP
5.0
4.0
3.0
2.0
1.0
0.0
0
200
400
600
800
1000
1200
1400
Figure 12.1 the coefficient of performance before and after CQM installation in Dorset House with condensing
water inlet temperature between 27 and 28
COP
5.0
4.0
3.0
2.0
1.0
0.0
0
200
400
600
800
1000
1200
1400
Figure 12.2 the coefficient of performance before and after CQM installation in Dorset House with condensing
water inlet temperature between 28 and 29
Page 15 of 20
COP
5.0
4.0
3.0
2.0
1.0
0.0
0
200
400
600
800
1000
1200
1400
Figure 12.3 the coefficient of performance before and after CQM installation in Dorset House with condensing
water inlet temperature between 29 and 30
The average COP of the chiller in Dorset House has improved by 9.88%.
Somerest Hosue
COP
4
3
2
1
0
0
100
200
300
400
500
600
Figure 13.1 the coefficient of performance before and after CQM installation in Somerset House with
condensing water inlet temperature between 27 and 28
Page 16 of 20
COP
5
4
3
2
1
0
0
100
200
300
400
500
600
Figure 13.2 the coefficient of performance before and after CQM installation in Somerest Housing with
condensing water inlet temperature 28 and 29
COP
4
3
2
1
0
0
100
200
300
400
500
600
Figure 12.3 the coefficient of performance before and after CQM installation in Somerest Housing with
condensing water inlet temperature between 29 and 30
Page 17 of 20
Oxford House
Condensing Water Inlet Temperature between 27 and 28
6
5
COP
4
3
2
1
0
0
100
200
300
400
500
600
Figure 13.1 the coefficient of performance before and after CQM installation in Oxford House with condensing
water inlet temperature between 27 and 28
COP
3
2
1
0
0
100
200
300
400
500
600
Figure 13.2 the coefficient of performance before and after CQM installation in Oxford House with condensing
water inlet temperature between 28 and 29
Page 18 of 20
COP
5
4
3
2
1
0
0
100
200
300
400
500
600
Figure 13.3 the coefficient of performance before and after CQM installation in Oxford House with condensing
water inlet temperature between 29 and 30
In Oxford House, the average COP is only improved by 0.03%. However, we find that the chiller
supply set point in 2002 was 8 while the set point in 2003 was reduced to 7.4. As we do not have
a exact figures from Carrier, we would estimate that the 0.6 decreased in chiller supply temperature
set point had imposed more than 10% burden on COP of the chiller. From the improvement on
condenser T ( 2.77 ), we would project the saving by interrelating it with Lincoln , i.e.
Improvement in COP in Oxford = 2.77 / 4.97 * 21.2% = 11.8%.
Payback Analysis
From the above analysis, we can see that CQM provide a significant improvement on COP. The
projected energy saving can be estimated by the following formula
Annual Energy Saving = Rated Power Input * working hour per day * working days per year *
diversity factor * Electricity charge * % saving on COP
Assumption : Working hour per day = 12 hours
Working days per year = 5 1/2 days * 52 weeks = 286
Diversity Factor = 0.5
Electricity charge = HK$ 0.94 per kwh
Simple Payback Period = Cost of CQM / (Annual energy saving annual maintenance )
Page 19 of 20
Power
Input
(kw)
300
509
1080
553
Saving
(%)
21.2%
11.8%
9.88%
13.1%
Annual
Energy saving
( HK$)
$ 102,589
$ 96,882
$ 172,117
$ 116,853
Cost of
CQM
( HK$ )
$ 160,000
$ 145,000
$ 290,000
$ 200,000
Annual
Maintenance
( HK$ )
$ 10,000
$ 10,000
$ 12,000
$ 12,000
Simple
Payback
Period
1.72 year
1.66 year
1.81 year
1.91 year
Summary
From the above analysis, it proves that CQM Automatic Tube Cleaning System can greatly improve
the heat transfer efficiency of the condenser tube and save significant amount of energy in watercooled chiller. Besides, from the economic analysis, it shows that the payback is less than 2 years.
Page 20 of 20