The DP Transmitter should be installed at a
lower position than the orifice plate. The impulse
lines should be filled with condensed water to
prevent damage to the transmitter. Temperature
at the measuring cell should be less than100C.
The impulse piping should have a minimum
fall of 1:20, run over the same route preferably
clipped together and unlagged. It should have
a minimum O/D of (12.7mm) and be of a
suitable pressure and temperature rating for
the application.
The impulse piping should follow a route to prevent
any elbows where air or non condensable gases
could accumulate. This could cause serious
errors in the DP Transmitter reading.
The recommended layout of the system can
be seen in Fig 6
Isolation valves
Flow
Impulse
piping
Square
edge upstream
Carrier
rings
Gaskets
Transmitter
Pipe flanges
Fig 4
IM-P176-05 MI Issue 3
!"#$%$&'$$
!
!
"##
$%
Block 4 Flowmetering
Instrumentation
A steam flowmeter comprises two parts:
1. The primary device or pipeline unit, such as an orifice plate, located in the steam flow.
2. The secondary device, such as a differential pressure cell, that translates any signals into a
usable form.
In addition, some form of electronic processor will exist which can receive, process and display
the information. This processor may also receive additional signals for pressure and / or temperature
to enable density compensation calculations to be made.
Figure 4.4.1 shows a typical system.
Temperature
transducer
Pressure
transducer
Flow
Downstream
pressure
tapping
Upstream
pressure
tapping
DP cell and
transmitter
(secondary element)
Flow processor
or computer
DP cell
Downstream
pressure cap
Dielectric oil filling
Measuring
diaphragm
Measuring cell
Isolating
diaphragm
Output
4.4.2