Cast-in items such as weld plates, frequently have reinforcement bars welded to them to transfer loads
into the body of the concrete. This is commonly used in precast concrete for connections. Traditionally
these were designed by experience and welds were generally over specified, with failures being very
rare indeed. The common type of weld used to attach a nominally round bar to a flat section is a flare
bevel fillet weld as shown below.
Useful guidance on designing welds is hard to come by, and the guidance that exists is not very helpful.
Until 2006, the relevant standard was BS 7123:1989 Metal arc welding of steel for concrete
reinforcement. Clause 10.9.2 of this standard contained the following equation for the length of flare
bevel fillet weld to carry the full tensile load of a reinforcing bar:
The
same standard limits the throat thickness to a maximum of 0.3 x bar dia. Thus, by taking 0.87 fy = 435
N/mm2 and fw =160 N/mm2, the required weld length to give the bar capacity can be calculated from the
equation above.
Column 5 gives the required length of a single weld. However, most bars are welded both sides to avoid
eccentricity, and column 6 gives the required length of full area double welds. Welds however are not
square ended, and an allowance (col 7) must be made for non-effective weld of smaller area, usually
called run-off. Typically this is (/ 2), giving final values as shown in column 8.
The
current standard, BS EN ISO 17660-1:2006 Welding of reinforcing steel Part 1: Load bearing welded
joints simplifies this design further by simply stating that a weld length of four x bar dia (col 9) will give
full bar capacity. Comparison of cols 8 & 9 show the close similarity of the results. The current standard
refers to these welds as side lap welds, rather than using the traditional terminology. Unfortunately the
2013 Cliff Billington on behalf of J&P Building Systems Ltd