Applications
Presentation
058579N
Our Fusarc CF, Solfuse, Tpfuse and MGK fuses make up a broad, consistent
and uniform range of high breaking capacity fuses and current limitors.
They are all of combined type and are manufactured so that they can be installed
both indoors and outdoors (depending on the type).
Merlin Gerin fuses provide protection to medium voltage distribution devices
(from 3 to 36 kV) from both the dynamic and thermal effects of short-circuit currents
greater than the fuses minimum breaking current.
Considering their low cost and their lack of required maintenance, medium voltage
fuses are an excellent solution to protect various types of distribution devices:
b medium voltage current consumers (transformers, motors, capacitors, etc.),
b public and industrial electrical distribution networks.
Public distribution
058580N
They offer dependable protection against major faults that can occur either
on medium or low voltage circuits.
This protection can be further enhanced by combining the fuses with low voltage
protection systems or with an overcurrent relay.
Selection table
Depending on the equipment to be protected and its voltage rating, the table below
gives the range of fuses which are best suited to the protection application.
Voltage
(kV)
3.6
7.2
Motor protection
12
17.5
24
36
MGK
(UTE standard;
motor protection)
Fusarc CF
(DIN standard;
transformer, motor and
capacitor protection)
Tpfuse
(UTE standard;
voltage transformer
protection)
058578N
Solfuse
(UTE standard;
transformer protection)
Motors
Power
transformers
Fusarc CF Fusarc CF
MGK
Fusarc CF Fusarc CF
MGK
Solfuse
Fusarc CF Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Fusarc CF
Solfuse
Capacitors
Fusarc CF
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Voltage
transformers
Fusarc CF
Fusarc CF
Tpfuse
Fusarc CF
Tpfuse
Fusarc CF
Tpfuse
Fusarc CF
Solfuse
Tpfuse
Fusarc CF
Presentation
Main characteristics
PE55711
Key characteristics
The most significant features provided by our range of fuses are as follows:
b high breaking capacity,
b high current limitation,
b low I2t values
b dependable breaking of critical currents,
b low breaking overvoltage,
b low dissipated power,
b no maintenance or ageing,
b for indoor and outdoor applications,
b with a thermal striker,
b low minimum breaking current values.
Standards
Our fuses are designed and manufactured according to the following standards:
b IEC 60282-1, IEC 60787 (Fusarc CF, Solfuse,Tpfuse, MGK),
b DIN 43625 (Fusarc CF),
b VDE 0670-402 (Fusarc CF),
b UTE C64200, C64210 (Solfuse, Tpfuse).
Routine testing
During manufacture, each fuse is subject to systematic routine testing, with the aim
of checking its quality and conformity:
b dimensional control and weight control,
b visual control of markings, labelling and external appearance,
b electrical resistance measurement: a key point to ensure that fuses have
the required performance levels at the end of the production process and to check
that no damage has occurred during assembly.
Measurement of the room temperature resistance of each fuse is therefore carried
out in order to check that they are in line with values, according to their rated voltage
and rated current.
Presentation
Main characteristics
Key definitions
DE55750
Fuses
Construction
DE55751EN
Force (N)
Together with the enclosure, they form an assembly which must remain intact
before, during and after breaking the current. This is why they have to withstand
mechanical stresses and sealing stresses due to overpressure caused by arcing.
The stability of the internal components must also be ensured over time.
80
70
60
Enclosure (2)
50
This part of the fuse must withstand certain specific stresses (related to what
has already been mentioned):
b thermal stresses: the enclosure has to withstand the rapid temperature rise
that occurs when the arc is extinguished.
b electrical stresses: the enclosure has to withstand the restoring of current after
breaking.
b mechanical stresses: the enclosure has to withstand the increase in pressure
caused by the expansion of the sand when breaking occurs.
40
30
20
10
0
10
15
20 23 Travel
(mm)
Core (3)
This is a cylinder surrounded by ceramic fins onto which the fuse element is wound.
The striker control wire together with the latter are fitted in the cyclinder. They are
insulated from the fuse elements.
PE55713
PE55712
1
2
3
4
5
6
MV limiting fuses
with thermal striker
Fuses
Construction
PE55714
The thermal protection system integrated in Merlin Gerin fuses, whilst not able to
break fault covercurrents less than I3 and greater than the rated current ( I1) still have
a device which actuates the conventional striker in the presence of these currents.
Therefore, the above-mentioned currents are either visually detected or detected by
combining the fuses with suitable breaking devices, thus avoiding any incidents due
to over-heating.
In this way, the fuse not only works as a current limiter but also as a temperature limiter
when combined with an external breaking device.
These types of fuses, which integrate a thermal striker, are fully compatible with
standard Back UP type fuses.
Technical/economic/safety advantages:
The use of a thermal protector in our fuses provides the following advantages:
b Protecting the fuses and their environment from unacceptable temperature rises
in installations equipped with a disconnecting switch with the possibility of automatic
opening.
b Providing a response to unexpected operating conditions, to frequent or
longlasting overloads, or to mistakes in selecting the fuse rating, or even concerning
restricted ventilation conditions within the installation.
b Indicating and protecting against overloads caused by overcurrents below the
minimum breaking current (I3) of the installed fuse and which can cause dangerous
operating temperatures.
b Reducing operating costs due to destruction of equipment or excess costs caused
by loss of quality of service (repair time, staff, etc.)
This thermal protector safety feature, significantly reduces the risk of damage
and accidents in installations and therefore increases the power distribution quality
of service.
PE55717
The characteristics of the thermal striker fuse (breaking capacity, fuse curves,
limiting values, striker force, etc.) do not vary relative to our fuses without
thermal protection.
Fusarc CF
Fuses
Dimensions (mm)
DE55753
Figure 4
Fusarc CF
Striker
*
45
33
33
L*
23
Fusarc CF
Fuses
Table no.1
Reference
757372 AR
51311 006 M0
51006 500 M0
51006 501 M0
51006 502 M0
51006 503 M0
51006 504 M0
51006 505 M0
51006 506 M0
51006 507 M0
51006 508 M0
51006 509 M0
51006 510 M0
757352 BN
757352 BP
757352 BQ
757374 BR
51311 007 M0
51006 511 M0
51006 512 M0
51006 513 M0
51006 514 M0
51006 515 M0
51006 516 M0
51006 517 M0
51006 518 M0
51006 519 M0
51006 520 M0
51006 521 M0
757364 CN
757354 CP
757354 CQ
51006 522 M0
51006 523 M0
51006 524 M0
51006 525 M0
51006 526 M0
51311 008 M0
51006 527 M0
51006 528 M0
51006 529 M0
51006 530 M0
51006 531 M0
51006 532 M0
51006 533 M0
51006 534 M0
51006 535 M0
51006 536 M0
51006 537 M0
51108 807 M0
51108 808 M0
51108 813 M0
51108 814 M0
51108 809 M0
51108 810 M0
51311 009 M0
51006 538 M0
51006 539 M0
51006 540 M0
51006 541 M0
51006 542 M0
51006 543 M0
51006 544 M0
51006 545 M0
51006 546 M0
51006 547 M0
51006 548 M0
51311 010 M0
51006 549 M0
51006 550 M0
51006 551 M0
51006 552 M0
51006 553 M0
51006 554 M0
51006 555 M0
51006 556 M0
51006 557 M0
Rated
voltage (kV)
3.6
7.2
12
17.5
24
36
Operating
Rated
Max. breaking Min. breaking
voltage (kV) current (A) current I1 (kA) current I3 (A)
3/3.6
250
50
2.000
4
20
6.3
36
10
34
16
50
20
62
25
91
31.5
63
101
3/7.2
40
135
50
180
63
215
80
280
100
380
125
650
160
50
1.000
200
1.400
250
2.200
4
20
6.3
36
10
34
16
50
20
62
25
91
31.5
63
101
6/12
40
135
50
180
63
215
80
280
100
380
125
650
160
40
1.000
200
1.400
10
34
16
50
25
91
31.5
101
40
135
4
20
6.3
40
36
10
34
10/17.5
16
50
20
62
25
91
31.5
101
40
135
50
180
63
32
215
80
330
100
450
10
36
16
50
20
62
25
91
31.5
101
40
135
4
40
20
6.3
36
10/24
10
34
16
50
20
62
25
91
31.5
101
40
135
50
180
63
32
215
80
330
100
450
4
20
6.3
36
10
34
16
50
20
62
20/36
25
20
91
31.5
101
40
135
50
200
63
250
Length
(mm)
292
192
292
Diameter Weight
(mm)
(kg)
86
3.4
50.5
55
1.3
76
2.1
86
442
292
442
3.4
5
50.5
1.2
55
1.8
76
3.2
86
50.5
1.2
76
3.2
50.5
1.5
55
2.2
76
3.9
86
50.5
4.6
1.5
55
2.2
292
367
367
76
442
537
3.9
50.5
1.7
55
2.6
76
4.5
86
5.7
50.5
1.9
55
3.1
76
5.4
86
6.5
Fusarc CF
Fuses
250 A
160 A
125 A
100 A
31.5 A
40 A
50 A
63 A
80 A
10 A
16 A
20 A
25 A
6.3 A
1000
8
6
4
4A
DE55755
Time (s)
8
1000
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
2
10
100
8
10000
Current (A)
8
6
4
Ia
8
1.
Ik
Is
Ik
250 A
200 A
160 A
125 A
100 A
80 A
63 A
50 A
40 A
10
8
31.5 A
25 A
20 A
16 A
6
4
10 A
6.3 A
2
1
8
4A
6
4
0.1
0.1
10
100
Solfuse
Fuses
Electrical characteristics
Table no. 2
Reference
757328 BC
757328 BE
757328 BH
757328 BK
757328 BN
757328 CM
757328 DL
757328 EC
757328 EE
757328 EH
757328 EJ
757328 EK
757331EC**
757331EE**
757331EH**
757331EJ**
757331EK**
757328 FC
757328 FD
757328 FE
757328 FF
757328 FG
757328 FH
Rated voltage
(kV)
Operating voltage
(kV)
7.2
3.6/7.2
12
17.5
7.2/12
13.8/17.5
24
10/24
24
10/24
36
30/33
Rated current
(A)
6.3
16
31.5
63
125
100
80
6.3
16
31.5
43
63
6.3
16
31.5
43
63
6.3
10
16
20
25
31.5
31.5
80
157.5
315
625
500
400
31.5
80
157.5
215
315
31.5
80
157.5
215
315
31.5
50
80
100
125
157.5
Cold resistance *
(m)
158.6
51.7
24.5
11.3
4.8
7.7
15.1
445.9
93.2
45.8
38.5
18.9
447.3
147.4
67.9
39
19.3
618.9
252.9
207.8
133.2
124
93
50
50
40
30
30
20
Dimensions (mm)
DE55752
Figure 5
Striker
520
55
35
450
23 max.
Weight: 2.3 kg
10
Solfuse
Fuses
1000
8
6
4
16 A
20 A
25 A
31.5 A
43 A
63 A
80 A
6.3 A
10 A
DE55757
Time (s)
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
2
10
100
8
1000
8
10000
Current (A)
8
6
4
Ia
8
1.
Ik
Is
Ik
2
125 A
100 A
80 A
63 A
10
43 A
31.5 A
25 A
20 A
16 A
10 A
8
6
4
6.3 A
2
1
8
6
4
0.1
0.1
10
100
11
Tpfuse, Fusarc CF
Fuses
Characteristics
Table no. 3
Type
Tpfuse
Fusarc CF
Reference
781825 A
781825 B
51311 002 MO
51311 000 MO
51311 003 MO
51311 011 MO
51311 001 MO
51311 004 MO
51311 005 MO
Rated
voltage
(kV)
12
24
7.2
Operating
voltage
(kV)
< 12
13.8/24
3/7.2
12
6/12
17.5
10/17.5
24
10/24
36
20/36
Rated
current
(A)
Max. breaking
current
I1 (kA)
Min. breaking
current
I3 (A)
0.3
40
40
2.5
1
2.5
2.5
1
2.5
2.5
63
9.5
40
20
Cold
Length
resistance *
(m)
(mm)
6.1
301
11.6
1278
192
3834
292
1917
2407
367
4815
442
2407
3537
537
Diameter
Weight
(mm)
(kg)
27.5
0.9
1.2
50.5
50.5
DE55765
DE55759
45
33
Tpfuse (figure 7)
1000
8
6
4
Time (s)
1 A (Fusarc CF)
0.3 A (Tpfuse)
Fusarc CF (figure 6)
1.8
DE55760
331
100
8
6
4
27.5
2
15
301
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
1
10
8
100
Current (A)
12
1.5
1.6
Dimensions (mm)
0.4
MGK
Fuses
MGK fuses are intended to protect medium voltage motors at 7.2 kV (indoor application).
Dimensions (mm)
Electrical characteristics
Figure 8
Striker
Table no. 4
Reference
81
DE55761
Rated
Min. breaking Max. breaking Cold
current current
current
resistance *
(A)
I3 (A)
I1 (kA)
(m)
757314
100
360
50
6.4
757315
125
570
50
4.6
757316
7.2
y 7.2
160
900
50
2.4
757317
200
1400
50
1.53
757318
250
2200
50
0.95
* Resistances are given at 10% for a temperature of 20C.
55
438
Rated
voltage
(kV)
Operating
voltage
(kV)
Weight: 4.1 kg
200 A
1000
8
6
4
160 A
100 A
125 A
DE55762
Time (s)
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
2
10
100
8
1000
8
10000
Current (A)
100
8
6
4
Ia
1.
Ik
Is
Ik
2
250 A
200 A
160 A
125 A
100 A
10
8
6
4
1
8
6
4
0.1
0.1
10
100
13
Fuses
General
Transformer protection
General
DE55764
According to their specific characteristics, the various types of fuses (Fusarc CF,
Solfuse, Tpfuse and MGK) provide real protection for a wide variety of medium
and high voltage equipment (transformers, motors, capacitors).
It is of the utmost importance to always remember the following points:
b Un of the fuse must be greater than or equal to the network voltage.
b I1 of a fuse must be greater than or equal to the network short circuit current.
b the characteristics of the equipment to be protected must always be taken into
consideration.
Icc
Short circuit
current
Transformer protection
A transformer imposes three main stresses on a fuse. This is why the fuses must
be capable of:
I3
(1)
Closing
In
In
Fuse
Transformer
14
Fuses
Transformer protection
Selection table
Fusarc CF fuses/DIN standard for transformer protection (rating in A) (1) (2) (3)
Table no. 6
Operating Rated
voltage
voltage
(kV)
(kV)
3
5
6
6.6
10
11
13.2
13.8
15
20
22
7.2
7.2
7.2
7.2
12
12
17.5
17.5
17.5
Transformer power
(kVA)
25
50
75
16
25
31.5
40
50
63
63
80
20
31.5 40
50
63
80
80
100
100
125
125
25
40
16
50
25
63
31.5
80
31.5
100
40
100
50
160
80
160
63
125
63
10
20
31.5 40
40
50
63
80
80
100
16
25
16
40
20
50
25
50
31.5
63
40
80
40
100
50
100
63
10
20
25
31.5 40
50
50
63
80
25
16
31.5
20
40
25
63
31.5
63
40
80
50
100
50
100
63
80
20
25
31.5 31.5 40
50
63
63
80
100
100
25
31.5
40
16
40
20
50
25
63
31.5
80
31.5
80
40
100
50
63
125
63
10
16
20
25
31.5 40
40
50
63
80
16
20
10
25
16
31.5
20
40
25
50
31.5
63
40
80
50
100
50
16
20
25
31.5 31.5 40
50
63
20
10
25
16
31.5
16
40
20
40
25
63
31.5
80
40
16
20
20
25
31.5 31.5 40
6.3
10
25
10
25
16
31.5
20
40
25
10
16
10
6.3
6.3
4
10
10
4
4
24
24
50
25
30
50
31.5
100
125
125 160
160
160
63
125
80
80
100
100
200
250
125 125
160
200
250
125 125
160
200
250
80
80
100
125
125
160
100
63
100
125
63
80
80
100
125
125
160
80
50
100
50
100
63
125
50
63
63
80
80
63
40
80
50
80
50
100
63
100
125
20
25
31.5 31.5 40
50
63
63
80
80
25
16
31.5
16
40
40
25
63
40
80
40
80
50
100
63
100
63
80
80
80
100
50
31.5
16
20
20
25
31.5 40
50
50
63
10
16
20
25
10
25
16
31.5
16
40
20
50
25
63
31.5
63
31.5
80
40
50
6.3
10
10
16
20
20
25
31.5 40
40
50
63
63
16
20
10
25
10
25
16
31.5
20
40
25
50
31.5
63
40
10
16
16
20
25
31.5 31.5 40
50
20
10
25
16
31.5
16
40
40
25
10
16
20
20
25
16
20
25
10
25
16
10
10
16
16
20
6.3
6.3
6.3
100
16
10
36
40
25
200 250
6.3
6.3
36
50
25
160
20
10
10
25
50
25
10
6.3
10
100
100
100
100
80
80
100
100
63
100
50
80
50
63
63
80
80
63
40
100
100
40
80
50
31.5 40
50
50
63
63
63
31.5
16
40
50
25
63
31.5
63
40
40
50
20
20
25
31.5
40
50
50
63
25
25
31.5
40
50
50
25
50
31.5
100
63
63
100
63
63
Solfuse fuses/UTE standard for transformer protection (rating in A) (1) (2) (3)
Table no. 7
Operating Rated
voltage
voltage
(kV)
(kV)
3
3.3
4.16
5.5
6
6.6
10
11
13.8
15
20
22
30
7.2
7.2
7.2
7.2
7.2
7.2
12
12
17.5/24
17.5/24
24
24
36
Transformer power
(kVA)
25
50
16
16
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
16
16
16
16
16
16
6.3
6.3
6.3
6.3
6.3
6.3
100
31.5
31.5
31.5
16
16
16
16
16
16
16
6.3
6.3
6.3
125
160
200
250
315
400
500
630
800
63
31.5
31.5
31.5
31.5
16
16
16
16
16
6.3
6.3
6.3
63
63
31.5
31.5
31.5
31.5
16
16
16
16
16
16
6.3
63
63
63
31.5
31.5
31.5
31.5
16
16
16
16
16
16
80
80
63
63
63
31.5
31.5
31.5
16
16
16
16
16
100
80
80
63
63
63
31.5
31.5
31.5
31.5
16
16
16
100
100
80
63
63
63
43
31.5
31.5
31.5
31.5
16
16
125
125
100
80
80
80
43
43
31.5
31.5
31.5
31.5
16
125
100
100
80
63
63
43
43
43
31.5
31.5
125
100
100
80
63
63
43
43
31.5
31.5
125
125
80
80
63
63
63
43
31.5
100
100
80
80
63
43
80
63
(1) Fuse ratings correspond to open air installation with a transformer overload of 30%, or to an indoor installation without transformer overload.
(2) If the fuse is incorporated in a distribution switchboard, please refer to the selection table provided by the manufacturer of this device.
(3) although the ratings shown in bold type are the most appropriate, the others also protect transformers in a satisfactory manner.
15
Fuses
Motor protection
Fusarc CF selection
for motor protection
Table no. 8
Maximum Start-up
operating current
voltage
(kV)
3.3
6.6
11
16
Motor protection
20
(A)
1410
1290
1140
1030
890
790
710
640
610
540
480
440
310
280
250
240
230
210
180
170
160
148
133
120
110
98
88
83
73
67
62
57
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
125
100
100
100
100
80
80
80
80
63
63
63
50
50
50
50
250
250
250
250
250
200
200
200
160
160
160
160
160
125
125
125
125
100
100
100
100
80
80
80
80
63
63
63
50
50
50
250
250
250
250
250
200
200
200
160
160
160
160
160
125
125
125
125
100
100
100
100
80
80
80
80
63
63
63
50
50
50
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
100
100
100
100
100
80
80
80
63
63
63
63
50
50
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
100
100
100
100
100
80
80
80
80
63
63
63
50
50
250
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
100
100
100
100
100
80
80
80
80
63
63
63
50
Fuses
Motor protection
Selection charts
= motor efficiency
The three charts given below enable the fuse rating to be determined when we know
the motor power (P in kW) and its rated voltage (in kV).
Chart 1: this gives the rated current In (A) according to P (kW) and Un (kV).
Chart 2: this gives the start-up current Id (A) according to In (A).
Chart 3: this gives the appropriate rating according Id (A) and the start-up duration
time Td (s).
Comments
b chart 1 is plotted for a power factor of 0.92 and an efficiency of 0.94.
For values different to this, use the following equation:
P
In = --------------------------h 3Ua pf
b chart 3 is given in the case of 6 start-ups spread over an hour or 2 successive
startups.
For n successive start-ups (n > 6), multiply Td by n
--- .
6
p
For p successive start-ups (p > 2), multiply Td by --- (see selection table).
In the absence of any information, take Td = 10 s. 2
100
10
Id (A)
1000
10000
100
100
3
1 2
Td (s)
2x250A
Td (s)
Example
2x200A
250A
200A
10
10
50A
160A
63A
80A
125A
1650 kW
100
P (kW)
1000
100A
10000
1000 A
10
10
In (A)
x12
In (A)
DE55766EN
b if the motor start-up is not direct, the rating obtained using the charts below may
be less than the full load current of the motor. In this case, we have to choose a rating
20% over the value of this current, to take account of the cubicle installation.
Fuses with a rating chosen using these charts will satisfy fuse ageing tests according
to recommendations in IEC 60644.
11kV
x10
10kV
x8
6.6kV
100
x6
6kV
5.5kV
100
167 A
x4
4.16kV
3.3kV
3kV
1000
100
P (kW)
1000
10000
10
100
1000
Id (A)
10000
17
Fuses
18
Fuses
Order form
Fuses
Quantity
Electrical characteristics
Rated voltage
(kV)
Operating voltage
(kV)
Rated current
Power
(A)
Transformer
Motor
(kVA)
Dimensions
Fuse length
(mm)
Cap diameter
(mm)
Other characteristics
Operating conditions
Open air
Cubicle
Fuse chamber
Other
Standards
Reference
19