HYDRAULIC HOSEREEL CALCULATION


1.

The hosereel design is based on BS 5306 Part 1 : 1976

2.

Water required at each hosereel outlet : 6.6 igpm

3.

Static pressure required at each hosereel : 100 ft.head

4.

Design assumed 3 hosereel point run at one time, therefore the flow rate:
= 3 x 6.6 igpm
= 19.8 igpm
Allowed 30% safety factor
= 1.3 x 19.8 igpm
= 25.74
say 30 igpm

5.

Pipeline frictional loss calculation


Item

Description

Quantity

Equivalent Length
(m)

1.

Pipe Measurement

2.

Bend

1.5

3.

Tee

4.

Check Valve

5.

Gate Valve

0.9

6.

Flexible Joint

3
TOTAL

Pipe loss factor at design flow rate of 30 igpm (m/100m) =


Total equivalent length x frictional loss

=
=

418.3 x 3.8
100
14.39

3.8

6.

Total pressure head of pump will be :


i. Static pressure outlet

30

ii. Static head

10

iii. Frictional Loss

14.39

54.39

=
say =
=

59.83
60.00
196.80

m
m
ft

* Total pressure head of pump


Adding 10% of safety factor

7.

The pump size will be

= Igpm x Total head


3960 x 0.6
=

2.5 Hp

say =

2.5 Hp

GI CADANGAN PEMBANGUNAN

T DAN 1 UNIT RUMAH SAMPAH

40150 SHAH ALAM,SELANGOR

Total Equivalent
Legth (m)
350
9
6
6
1.8
6
378.8

CADANGAN TAMBAHAN DAN PERUBAHAN DAN MENUKAR KEGUNAAN BANGUNAN DARIPADA


KEDAI PEJABAT KEPADA HOTEL BUDGET YANG MENGANDUNGI 36 BILIK PADA KEDAI 3
TINGKAT SEDIADA DI ATAS LOT PT 52 DAN LOT 53 PEKELILING BUSINESS CENTRE, JALAN
65C OFF JALAN PAHANG BARAT, KUALA LUMPUR , WILAYAH PERSEKUTUAN.
HYDRAULIC HOSEREEL CALCULATION
1. The hosereel design is based on BS 5306 Part 1 : 1976
2. Water required at each hosereel outlet : 6.6 igpm
3. Static pressure required at each hosereel : 100 ft.head
4. Design assumed 3 hosereel point run at one time, therefore the flow rate:
= 3 x 6.6 igpm
= 19.8 igpm
Allowed 30% safety factor
= 1.3 x 19.8 igpm
= 25.74
say 30 igpm
5. Pipeline frictional loss calculation

Quantity

Equivalent
Length (m)

Total
Equivalen
t Legth
(m)

Item

Description

1.

Pipe Measurement (2.0")

2.

Bend

1.1

5.5

3.

Tee

2.3

6.9

4.

Check Valve

6.7

6.7

5.

Gate Valve

0.9

1.8

6.

Flexible Joint

250

Total

276.9

1.

Pipe Measurement (2.5")

2.

Bend

0.9

3.

Tee

TOTAL

Pipe loss factor at design flow rate of 30 igpm (m/100m) =


against 2.5" Dia pipe
Total equivalent length x frictional loss

1.0

Pipe loss factor at design flow rate of 30 igpm (m/100m) =


against 2" Dia pipe
Total equivalent length x frictional loss

3.8

10.5222

i. Static pressure outlet

30

ii. Static head

12

iii. Frictional Loss

10.52

52.52

=
=
=

57.77
60.00
196.80

m
m
ft

6. Total pressure head of pump will be :

* Total pressure head of


Adding 10% of safety factor
say

7. The pump size will be

= Igpm x Total head


3960 x 0.6
=
say =

2.5 Hp
2.5 Hp