Canalis KSA
100 - 1000 A
Busbar trunking systems
Aluminium

Canalis KSA

Contents

Index 4
Presentation 8

Straight components

15

Feed unit and end covers

47

Tap-off units

55

Characteristics 83

Canalis KSA contents


Index and presentation
Presentation

Index of commercial numbers

page 8

page 4

Straight components
DD230586.eps

page 16

Rising mains
DD230604.eps

Straight lengths without tap-off outlets

DD230588.eps

Straight lengths with tap-off outlets

page 20

page 23

Feed units and end covers


Protected feed units

page 48

Flange feed units


DD210306.eps

DD206148.eps

DD230599.eps

Feed units and end covers

page 51

page 52

Tap-off units
DD230603.eps

page 62

For Compact NSX


DD206149.eps

For modular devices


DD230602.eps

Empty tap-off units

page 63

page 64

Characteristics
Design guide
page 84

Electrical characteristics
page 88

Specifications
page 90

Accessories

DD206151.eps

DD202082.eps

Fixing systems
DD210317.eps

Changing direction

page 26

page 42

page 38

Plaque 1.eps

Accessories

page 53

Accessories
DB414462.eps

For fuses

DD206150.eps

DD230603.eps

For measurements and metering

page 72

Recommandations for special applications


page 92

page 82

page 74

Coordinations
page 104

Maintenance
page 112

Index of commercial numbers

Canalis KS

Cat. no.

08000

Designation

Page

08903

Set of 12 labels (height 24 mm)

82

08905

Set of 12 label-holders (height


24 mm)

82

08907

Set of 12 divisible labels (height


24 mm)

82

13000
13136

Screw-on plate for adapting


65 x 85 mm power-socket bases

71

13137

Screw-on plate for blanking of


unused openings

71

13940

Modular blanking plate divisible


set of 10 x 5

82

81140

Household NF sockets

71

81141

Household Schuko sockets

71

81000
KFB

KFBCA81200

CANTILEVER ARM, 100 MM

39, 41

KFBCA81300

CANTILEVER ARM, 300 MM

39

JOINTING DEVICE 400 A

39

KSA25

KSA25HD502

KSA40

KSA40HD502

KSA80

Cat. no.

Designation

Page

KSA250ABGD5

END FEED BOX 250 A LEFT SIDE CIRCUIT


BREAKER PROTECTION

51

KSA250ABT4

CENTRE FEED BOX 250 A

50

KSA250ABTZFL21 FL21 MOUNTING PLATE FEED BOX

53

KSA250ABZFL21

FL21 MOUNTING PLATE FEED BOX

53

KSA250AE4

FLANGE FEED UNIT 250 A

52

KSA250DLC4A

ELBOW 250 A MADE TO MEASURE

31

KSA250DLC4B

ELBOW 250 A MADE TO MEASURE

32

KSA250DLC4CF

ELBOW 250 A MADE TO MEASURE WITH


FIRE BARRIER

34
29

KSA250DLC40

ELBOW 250 A

KSA250DLE4A

ELBOW 250A MADE TO MEASURE NEUTRAL 31


INTERIOR

KSA250DLE4B

ELBOW 250 A MADE TO MEASURE

32

KSA250DLE4CF

ELBOW 250 A MADE TO MEASURE WITH


FIRE BARRIER

34
29

KSA250DLE40

ELBOW 250 A

KSA250DLF4A

ELBOW 250 A MADE TO MEASURE NEUTRAL 31


EXT

KSA250DLF4B

ELBOW 250 A MADE TO MEASURE

KSA250DLF4CF

ELBOW 250 A MADE TO MEASURE

34

KSA250DLF40

ELBOW 250 A

29

KSA250DMBK4A

MULTIPLE ELBOW 250 A MADE TO MEASURE 36

32

KSA250DMBK4CF MULTIPLE ELBOW 250 A MADE TO MEASURE 37


KSA250DMBL4A

MULTIPLE ELBOW 250 A MADE TO MEASURE 36

KSA250DMBL4CF MULTIPLE ELBOW 250 A MADE TO MEASURE 37


KSA250DMCK4A

MULTIPLE ELBOW 250 A MADE TO MEASURE 36

KSA250DMCK4CF MULTIPLE ELBOW 250 A MADE TO MEASURE 37


JOINTING DEVICE 400 A

79

KSA250DMCL4A

MULTIPLE ELBOW 250 A MADE TO MEASURE 36

KSA250DMCL4CF MULTIPLE ELBOW 250 A MADE TO MEASURE 37


KSA250DTC40

TEE ELBOW 250 A

29

KSA250DXC40

CROSS ELBOW 250 A

30

KSA80EZ3

FIXING BRACKET

40

KSA250DZCG4A

ZED ELBOW 250 A MADE TO MEASURE

33

KSA80EZ5

FIXING BRACKET

40

KSA250DZCG4CF

ZED 250 A MADE TO MEASURE

35

KSA80ZG20

FIXING BRACKET

40

KSA250DZCH4A

ZED ELBOW 250 A MADE TO MEASURE

33

KSA250DZCH4CF

ZED 250 A MADE TO MEASURE

35

KSA250DZE4A

ZED ELBOW 250 A MADE TO MEASURE

33

KSA250DZE4CF

ZED 250 A MADE TO MEASURE

35

KSA250ED4081

RISER DISTRIBUTION LENGTH 0.8M 10 250A 25

KSA250ED4156

STRAIGHT DISTRIBUTION LENGTH 1M50


250 A

KSA250ED4208

STRAIGHT DISTRIBUTION LENGTH 2M 250 A 17

KSA250ED4306

STRAIGHT DISTRIBUTION LENGTH 3M 250 A 17

KSA250ED43012

STRAIGHT DISTRIBUTION LENGTH 3M 250 A 18

KSA250ED45010

STRAIGHT DISTRIBUTION LENGTH 5M 250 A 17

KSA250ED45020

STRAIGHT DISTRIBUTION LENGTH 5M 250 A 18

KSA100
KSA100AB4

END FEED BOX 100 A

KSA100ED4081

RISER DISTRIBUTION LENGTH 0.8M 10 100A 25

KSA100ED4306

STRAIGHT DISTRIBUTION LENGTH 3M 100 A 17

KSA100ED43012

STRAIGHT DISTRIBUTION LENGTH 3M 100 A 18

KSA100ED45010

STRAIGHT DISTRIBUTION LENGTH 5M 100 A 17

KSA100ED45020

STRAIGHT DISTRIBUTION LENGTH 5M 100 A 18

KSA100EV4203

RISER DISTRIBUTION LENGTH 2M 3O 100A

KSA100EV4254

RISER DISTRIBUTION LENGTH 2.5M 4O 100A 24

KSA125
KSA125HD5

KSA160

TAP OFF UNIT 125A FUSE T00

49

24

79

KSA160ED4306

STRAIGHT DISTRIBUTION LENGTH 3M 160 A 17

KSA160ED43012

STRAIGHT DISTRIBUTION LENGTH 3M 160 A 18

KSA160ED45010

STRAIGHT DISTRIBUTION LENGTH 5M 160 A 17

KSA160ED45020

STRAIGHT DISTRIBUTION LENGTH 5M 160 A 18

KSA250
KSA250AB4

END FEED BOX 250 A

KSA250ABCB4

Communication box for KS feeder 250 A 49

KSA250ABDD4

END FEED BOX 250A RIGHT SIDE CIRCUIT


BREAKER PROT

51

KSA250ABDD5

END FEED BOX 250A RIGHT SIDE CIRCUIT


BREAKER PROTECTION

51

KSA250ABGD4

END FEED BOX 250 A LEFT SIDE CIRCUIT


BREAKER PROTECTION

51

49

17

KSA250ET4A

MADE TO MEASURE LENGTH 250 A

21

KSA250ET4AF

FIRE BARRIER LENGTH 400 A

22

KSA250EV4AF

RISER FOOT WITH FIRE BARRIER

22

KSA250EV4203

RISER DISTRIBUTION LENGTH 2M 3O 250A

24

KSA250EV4254

RISER DISTRIBUTION LENGTH 2.5M 4O 250A 24

KSA250FA4

OLD KS 250A ADAPTER

44

KSA250ZJ4

JOINTING DEVICE 400 A

43

KSA400AB4

END FEED BOX 400 A

49

KSA400ABCB4

Communication box for KS feeder 400 A 49

KSA400ABDD4

END FEED BOX 400A RIGHT SIDE CIRCUIT


BREAKER PROTECTION

51

KSA400ABDD5

END FEED BOX 400A RIGHT SIDE CIRCUIT


BREAKER PROTECTION

51

KSA400ABGD4

END FEED BOX 400 A LEFT SIDE CIRCUIT


BREAKER PROT

51

KSA400ABGD5

END FEED BOX 400 A LEFT SIDE CIRCUIT


BREAKER PROT

51

KSA400

Cat. no.

Designation

Page

Cat. no.

Designation

Page

KSA400ABT4

CENTRE FEED BOX 400 A

50

KSA500ET4AF

FIRE BARRIER LENGTH 500 A

22

KSA400ABTZFL21 FL21 MOUNTING PLATE FEED BOX

53

KSA500ET430

TRANSPORT LENGTH 3M 500A

21

KSA400ABZFL21

FL21 MOUNTING PLATE FEED BOX

53

KSA500ET450

TRANSPORT LENGTH 5M 500A

21

KSA400AE4

FLANGE FEED UNIT 400 A

52

KSA500EV4153

RISER DISTRIBUTION LENGTH 1,5M 3O 500A 24

KSA400AF1

END COVER 400 A

44

KSA500EV4203

RISER DISTRIBUTION LENGTH 2M 3O 500A

KSA400DLC4A

ELBOW 400 A MADE TO MEASURE

31

KSA500EV4254

RISER DISTRIBUTION LENGTH 2.5M 4O 500A 24

KSA400DLC4B

ELBOW 400 A MADE TO MEASURE

32

KSA500FA4

OLD KS 500A ADAPTER

44

KSA400DLC4CF

ELBOW 400 A MADE TO MEASURE WITH


FIRE BARRIER

34

KSA500FR425

REDUCTION SIZE2 TO SIZE1

44

29

KSA630

KSA630ABD4

END FEED BOX 630 A RIGHT SIDE

49

KSA630ABG4

END FEED BOX 630 A LEFT SIDE

49

KSA630ABT4

CENTRE FEED BOX 630 A

50

KSA400DLC40

ELBOW 400 A

KSA400DLE4A

ELBOW 400 A MADE TO MEASURE NEUTRAL 31


IINT

KSA400DLE4B

ELBOW 400 A MADE TO MEASURE

32

KSA400DLE4CF

ELBOW 400 A MADE TO MEASURE WITH


FIRE BARRIER

34

KSA400DLE40

ELBOW 400 A

29

KSA400DLF4A

ELBOW 400 A MADE TO MEASURE NEUTRAL 31


INT

KSA400DLF4B

ELBOW 400 A MADE TO MEASURE

32

KSA400DLF4CF

ELBOW 400 A MADE TO MEASURE

34

KSA400DLF40

ELBOW 400 A

29

KSA400DMBK4A

MULTIPLE ELBOW 400 A MADE TO MEASURE 36

KSA400DMBK4CF MULTIPLE ELBOW 400 A MADE TO MEASURE 37


KSA400DMBL4A

MULTIPLE ELBOW 400 A MADE TO MEASURE 36

KSA400DMBL4CF MULTIPLE ELBOW 400 A MADE TO MEASURE 37


KSA400DMCK4A

MULTIPLE ELBOW 400 A MADE TO MEASURE 36

KSA400DMCK4CF MULTIPLE ELBOW 400 A MADE TO MEASURE 37


KSA400DMCL4A

MULTIPLE ELBOW 400 A MADE TO MEASURE 36

KSA400DMCL4CF MULTIPLE ELBOW 400 A MADE TO MEASURE 37


KSA400DTC40

TEE ELBOW 400 A

29

KSA400DXC40

CROSS ELBOW 400 A

30

KSA400DZCG4A

ZED ELBOW 400 A MADE TO MEASURE

33

KSA400DZCG4CF

ZED 400 A MADE TO MEASURE

35

KSA400DZCH4A

ZED ELBOW 400 A MADE TO MEASURE

33

KSA400DZCH4CF

ZED 400 A MADE TO MEASURE

35

KSA400DZE4A

ZED ELBOW 400 A MADE TO MEASURE

33

KSA400DZE4CF

ZED 400 A MADE TO MEASURE

35

KSA400ED4081

RISER DISTRIBUTION LENGTH 0.8M 10 400A 25

KSA400ED4156

STRAIGHT DISTRIBUTION LENGTH 1M50


400 A

17

KSA400ED4208

STRAIGHT DISTRIBUTION LENGTH 2M 400 A 17

KSA400ED4306

STRAIGHT DISTRIBUTION LENGTH 3M 400 A 17

KSA400ED33012

STRAIGHT DISTRIBUTION LENGTH 3M 400 A 19

KSA400ED35020

STRAIGHT DISTRIBUTION LENGTH 5M 400 A 19

KSA400ED43012

STRAIGHT DISTRIBUTION LENGTH 3M 400 A 18

KSA400ED45010

STRAIGHT DISTRIBUTION LENGTH 5M 400 A 17

KSA400ED45020

STRAIGHT DISTRIBUTION LENGTH 5M 400 A 18

KSA400ET4A

MADE TO MEASURE LENGTH 400 A

21

KSA400ET4AF

FIRE BARRIER LENGTH 400 A

22

KSA400ET430

TRANSPORT LENGTH 3M 400A

21

KSA400ET450

MADE TO MEASURE LENGTH 400 A

21

KSA400EV4AF

FIRE BARRIER LENGTH 400 A

22
24

KSA400EV4203

RISER DISTRIBUTION LENGTH 2M 3O 400A

KSA400EV4254

RISER DISTRIBUTION LENGTH 2.5M 4O 400A 24

KSA400FA4

OLD KS 400A ADAPTER

44

KSA400ZJ4

JOINTING DEVICE 400 A

43

KSA500

KSA500ED3306

STRAIGHT DISTRIBUTION LENGTH 3M 500 A 19

KSA500ED4306

STRAIGHT DISTRIBUTION LENGTH 3M 500 A 17

KSA500ED35010

STRAIGHT DISTRIBUTION LENGTH 5M 500 A 19

KSA500ED43010

STRAIGHT DISTRIBUTION LENGTH 3M 500 A 18

KSA500ED45010

STRAIGHT DISTRIBUTION LENGTH 5M 500 A 17

KSA500ED45018

STRAIGHT DISTRIBUTION LENGTH 5M 500 A 18

KSA630ABTZFL21 FL21 MOUNTING PLATE FEED BOX

24

53

KSA630ABZFL21

FL21 MOUNTING PLATE FEED BOX

53

KSA630AE4

FLANGE FEED UNIT 630 A

52

KSA630DLC4A

ELBOW 630 A MADE TO MEASURE

31

KSA630DLC4B

ELBOW 630 A MADE TO MEASURE

32

KSA630DLC4CF

ELBOW 630A MADE TO MEASURE WITH FIRE 34


BARRIER

KSA630DLC40

ELBOW 630 A

KSA630DLE4A

ELBOW 630 A MADE TO MEASURE NEUTRAL 31


INT

29

KSA630DLE4B

ELBOW 630 A MADE TO MEASURE

KSA630DLE4CF

ELBOW 630A MADE TO MEASURE WITH FIRE 34


BARRIER

32

KSA630DLE40

ELBOW 630 A

KSA630DLF4A

ELBOW 630A MADE TO MEASURE NEUTRAL 31


EXT

29

KSA630DLF4B

ELBOW 630 A MADE TO MEASURE

KSA630DLF4CF

ELBOW 630 A MADE TO MEASURE

34

KSA630DLF40

ELBOW 630 A

29

KSA630DMBK4A

MULTIPLE ELBOW 630 A MADE TO MEASURE 36

32

KSA630DMBK4CF MULTIPLE ELBOW 630 A MADE TO MEASURE 37


KSA630DMBL4A

MULTIPLE ELBOW 630 A MADE TO MEASURE 36

KSA630DMBL4CF MULTIPLE ELBOW 630 A MADE TO MEASURE 37


KSA630DMCK4A

MULTIPLE ELBOW 630 A MADE TO MEASURE 36

KSA630DMCK4CF MULTIPLE ELBOW 630 A MADE TO MEASURE 37


KSA630DMCL4A

MULTIPLE ELBOW 630 A MADE TO MEASURE 36

KSA630DMCL4CF MULTIPLE ELBOW 630 A MADE TO MEASURE 37


KSA630DTC40

TEE ELBOW 630 A

29

KSA630DXC40

CROSS ELBOW 630 A

30

KSA630DZCG4A

ZED ELBOW 630 A MADE TO MEASURE

33

KSA630DZCG4CF

ZED 630 A MADE TO MEASURE

35

KSA630DZCH4A

ZED ELBOW 630 A MADE TO MEASURE

33

KSA630DZCH4CF

ZED 630 A MADE TO MEASURE

35

KSA630DZE4A

ZED ELBOW 630 A MADE TO MEASURE

33

KSA630DZE4CF

ZED 630 A MADE TO MEASURE

35

KSA630ED3306

STRAIGHT DISTRIBUTION LENGTH 3M 630 A 19

KSA630ED4081

RISER DISTRIBUTION LENGTH 0.8M 10 630A 25

KSA630ED4154

STRAIGHT DISTRIBUTION LENGTH 1M50


630 A

KSA630ED4206

STRAIGHT DISTRIBUTION LENGTH 2M 630 A 17

KSA630ED4306

STRAIGHT DISTRIBUTION LENGTH 3M 630 A 17

KSA630ED35010

STRAIGHT DISTRIBUTION LENGTH 5M 630 A 19

KSA630ED43010

STRAIGHT DISTRIBUTION LENGTH 3M 630 A 18

KSA630ED45010

STRAIGHT DISTRIBUTION LENGTH 5M 630 A 17

KSA630ED45018

STRAIGHT DISTRIBUTION LENGTH 5M 630 A 18

17

KSA630ET4A

MADE TO MEASURE LENGTH 630 A

KSA630ET4AF

FIRE BARRIER LENGTH 630 A

21
22

KSA630ET430

TRANSPORT LENGTH 3M 630A

21

KSA630ET450

TRANSPORT LENGTH 5M 630A

21

KSA630EV4AF

FIRE BARRIER LENGTH 630 A

22

KSA630EV4153

RISER DISTRIBUTION LENGTH 1,5M 3O 630A 24

Index of commercial numbers

Canalis KS

Cat. no.

Designation

Page

Cat. no.

Designation

Page

KSA630EV4203

RISER DISTRIBUTION LENGTH 2M 3O 630A

24

KSA1000DZE4CF

ZED 1000 A MADE TO MEASURE

35

KSA630EV4254

RISER DISTRIBUTION LENGTH 2.5M 4O 630A 24

KSA1000ED4081

JOINTING DEVICE 630 A

RISER DISTRIBUTION LENGTH 0.8M 10


1000A

25

KSA630ZJ4

KSA1000ED4154

STRAIGHT DISTRIBUTION LENGTH 1M50


1000 A

17

KSA1000ED4206

STRAIGHT DISTRIBUTION LENGTH 2M


1000 A

17

KSA1000ED4306

STRAIGHT DISTRIBUTION LENGTH 3M


1000 A

17

KSA1000ED45010

STRAIGHT DISTRIBUTION LENGTH 5M


1000 A

17
21

KSA800

43

KSA800ED3306

STRAIGHT DISTRIBUTION LENGTH 3M 800 A 19

KSA800ED4306

STRAIGHT DISTRIBUTION LENGTH 3M 800 A 17

KSA800ED35010

STRAIGHT DISTRIBUTION LENGTH 5M 800 A 19

KSA800ED43010

STRAIGHT DISTRIBUTION LENGTH 3M 800 A 18

KSA800ED45010

STRAIGHT DISTRIBUTION LENGTH 5M 800 A 17

KSA800ED45018

STRAIGHT DISTRIBUTION LENGTH 5M 800 A 18

KSA800ET4AF

FIRE BARRIER LENGTH 800 A

22

KSA800ET430

TRANSPORT LENGTH 3M 800A

21

KSA800ET450

TRANSPORT LENGTH 5M 800A

21

KSA800EV4153

RISER DISTRIBUTION LENGTH 1,5M 3O 800A 24

KSA1000ET4A

MADE TO MEASURE LENGTH 1000 A

KSA1000ET4AF

FIRE BARRIER LENGTH 1000 A

22

KSA1000ET430

TRANSPORT LENGTH 3M 1000A

21
21

KSA1000ET450

TRANSPORT LENGTH 5M 1000A

KSA1000EV4AF

RISER FOOT WITH FIRE BARRIER

22

KSA1000EV4153

RISER DISTRIBUTION LENGTH 1,5M 3O


1000A

24

KSA800EV4203

RISER DISTRIBUTION LENGTH 2M 3O 800A

KSA800EV4254

RISER DISTRIBUTION LENGTH 2.5M 4O 800A 24

KSA1000EV4203

RISER DISTRIBUTION LENGTH 2M 3O 1000A 24

KSA800FA4

OLD KS 800A ADAPTER

44

KSA1000EV4254

RISER DISTRIBUTION LENGTH 2.5M 4O


1000A

24

KSA1000ZJ4

JOINTING DEVICE 1000 A

43

CONNECTOR 16A FUSE E14

76

CONNECTOR 20A FUSE BS88A1

78

KSA1000

24

KSA1000ABD4

END FEED BOX 1000 A RIGHT SIDE

49

KSA1000ABG4

END FEED BOX 1000 A

49

KSA1000ABT4

CENTRE FEED BOX 1000 A

50

KSA1000ABTZFL21 FL21 MOUNTING PLATE FEED BOX

53

KSB16
KSB16CN5

KSB20

KSA1000ABZFL21 FL21 MOUNTING PLATE FEED BOX

53

KSA1000AE4

FLANGE FEED UNIT 1000 A

52

KSA1000AF1

END COVER 1000 A

44

KSA1000DLC4A

ELBOW 1000 A MADE TO MEASURE

31

KSA1000DLC4B

ELBOW 1000 A MADE TO MEASURE

32

KSA1000DLC4CF

ELBOW 1000A MADE TO MEASURE WITH


FIRE BARRIER

34

KSA1000DLC40

ELBOW 1000 A

29

KSA1000DLE4A

ELBOW 1000A MADE TO MEASURE


NEUTRAL INTERIOR

31

KSA1000DLE4B

ELBOW 1000 A MADE TO MEASURE

32

KSA1000DLE4CF

ELBOW 1000A MADE TO MEASURE WITH


FIRE BARRIER

34

KSA1000DLE40

ELBOW 1000 A

29

KSA1000DLF4A

ELBOW 1000A MADE TO MEASURE


NEUTRAL EXTERIOR

31

KSA1000DLF4B

ELBOW 1000 A MADE TO MEASURE

32

KSB32CP35

TAP OFF UNIT 32A WITH 2 POWER SOCKETS 71

KSA1000DLF4CF

ELBOW 1000 A MADE TO MEASURE

34

KSB32SG4

CONNECTOR 32A FUSE BS88A1

KSA1000DLF40

ELBOW 1000 A

29

KSA1000DMBK4A MULTIPLE ELBOW 1000 A MADE TO


MEASURE

36

KSA1000DMBK4CF MULTIPLE ELBOW 1000 A MADE TO


MEASURE

37

KSA1000DMBL4A

MULTIPLE ELBOW 1000 A MADE TO


MEASURE

36

KSA1000DMBL4CF MULTIPLE ELBOW 1000 A MADE TO


MEASURE

37

KSA1000DMCK4A MULTIPLE ELBOW 1000 A MADE TO


MEASURE

36

KSA1000DMCK4CF MULTIPLE ELBOW 1000 A MADE TO


MEASURE

37

KSA1000DMCL4A

MULTIPLE ELBOW 1000 A MADE TO


MEASURE

36

KSA1000DMCL4CF MULTIPLE ELBOW 1000 A MADE TO


MEASURE

37

KSA1000DTC40

TEE ELBOW 1000 A

29

KSA1000DXC40

CROSS ELBOW 1000 A

30

KSA1000DZCG4A

ZED 1000 A MADE TO MEASURE

33

KSA1000DZCG4CF ZED 1000 A MADE TO MEASURE

35

KSA1000DZCH4A

33

ZED ELBOW 1000 A MADE TO MEASURE

KSA1000DZCH4CF ZED 1000 A MADE TO MEASURE

35

KSA1000DZE4A

33

ZED ELBOW 1000 A MADE TO MEASURE

KSB20CG5

KSB25
KSB25SD4

TAP OFF UNIT 25A FUSE E27

76

KSB25SD5

TAP OFF UNIT 25A FUSE E27

76

KSB32CF5

CONNECTOR 32A FUSE 10X38

74

KSB32CM55

CONNECTOR 32A 5 MODULES

63

KSB32CP

TAP OFF UNIT 32A FOR 2 POWER SOCKETS 71

KSB32

KSB32CP11D

TAP OFF UNIT 32A WITH 2 POWER SOCKETS 71

KSB32CP11F

TAP OFF UNIT 32A WITH 2 POWER SOCKETS 71

KSB32CP15D

TAP OFF UNIT 32A WITH 2 POWER SOCKETS 71

KSB32CP15F

TAP OFF UNIT 32A WITH 2 POWER SOCKETS 71

KSB50

78

KSB50SF4

TAP OFF UNIT 50A FUSE 14X51

74

KSB50SF5

TAP OFF UNIT 50A FUSE 14X51

74

KSB50SN4

TAP OFF UNIT 50A FUSE E18

76

KSB50SN5

TAP OFF UNIT 50A FUSE E18

76

KSB50SV4

TAP OFF UNIT 50A EMPTY

62

KSB50SV5

TAP OFF UNIT 50A EMPTY

62

KSB63EGP

Plate for tap-off unit with EGX


equipment

62

KSB63PMP

Plate for tap-off unit with PM


equipment

62

KSB63

KSB63SD4

TAP OFF UNIT 63A FUSE E33

76

KSB63SD5

TAP OFF UNIT 63A FUSE E33

76

KSB63SM48

TAP OFF UNIT 63A 8 MODULES

62, 63

KSB63SM58

TAP OFF UNIT 63A 8 MODULES

62, 63

TAP OFF UNIT 80A FUSE BS88A1

78

KSB80
KSB80SG4

Cat. no.

KSB100
KSB100SE4

Designation
TOU 100A FUSE T00

Page
75, 77

KSB100SE5

TOU 100A FUSE T00

75, 77

KSB100SF4

TOU 100A FUSE 22X58

74

Cat. no.

Designation

Page

KSB400ZF1

FIXING BRACKET 400 A

40

KSB400ZFKP1

VERTICAL PENDANT KIT 400A

39

KSB400ZV1

BOTTOM SUPPORT FOR RISER 400A

41

80

KSB630

KSB100SF5

TOU 100A FUSE 22X58

74

KSB100SM412

TAP OFF UNIT 100A 12 MODULES

63

KSB630SE4

TAP OFF UNIT 630A FUSE

KSB100SM512

TAP OFF UNIT 100A 12 MODULES

63

KSB630SE5

TAP OFF UNIT 630A FUSE

80

KSB100SV4

TAP OFF UNIT 100A EMPTY

62

KSB630ZV1

BOTTOM SUPPORT FOR RISER 630A

41

KSB100SV5

TAP OFF UNIT 100A EMPTY

62

KSB160

KSB1000
KSB1000ZB1

TAP OFF BLANKING PLATE 1000 A IP55

43

KSB160DB412

TAP OFF UNIT 160A COMPACT NSX

66

KSB1000ZB2

SPRINKLER KIT JOINT PACK KS T3

43

KSB160DB512

TAP OFF UNIT 160A COMPACT NSX

66

KSB1000ZF1

FIXING BRACKET 1000 A

40

KSB160DC4

TAP OFF UNIT 160A COMPACT NSX

65

KSB1000ZFKP1

VERTICAL PENDANT KIT 1000A

39

KSB160DC5

TAP OFF UNIT 160A COMPACT NSX

65

KSB1000ZP1

43

KSB160DD411

TAP OFF UNIT 160A COMPACT NSX

67

Feed unit and jointing screws


sealing kit

KSB160SDF4

TAP OFF UNIT 160A FUPACT INF

81

KSB1000ZP2

Tap-off outlet sealing kit

43

KSB160SDF5

TAP OFF UNIT 160A FUPACT INF

81

KSB1000ZV1

BOTTOM SUPPORT FOR RISER 1000A

41

KSB160SE4

TAP OFF UNIT 160A FUSE T00

75, 77

KSB160SE5

TAP OFF UNIT 160A FUSE T00

75, 77

KSB160SF4

TAP OFF UNIT 160A FUSE T0

75

KSB160SF5

TAP OFF UNIT 160A FUSE T0

75

KSB160SFZFL21

FL21 GLAND PLATE

82

KSB160SG4

TAP OFF UNIT 160A FUSE BS88

78

KSB160SM413

TAP OFF UNIT 160A 13 MODULES

68

KSB160SM424

TAP OFF UNIT 160A 24 MODULES

73

KSB160SM513

TAP OFF UNIT 160A 13 MODULES

68

KSB160SM524

TAP OFF UNIT 160A 24 MODULES

73

KSB160SV4

TAP OFF UNIT 160A EMPTY

62

KSB160SV5

TAP OFF UNIT 160A EMPTY

62

KSB250
KSB250DC4

TAP OFF UNIT 250A COMPACT NSX

65

KSB250DC4SP

TAP OFF UNIT 250A COMPACT NSX SPECIAL 69

KSB250DC4TRE

TAP OFF UNIT 250A COMPACT NSX TRE

72

KSB250DC5

TAP OFF UNIT 250A COMPACT NSX

65

KSB250DC5TRE

TAP-OFF UNIT 250A COMPACT NSX TRE

72

KSB250DCZFL21

FL21 GLAND PLATE

82

KSB250DD412

TAP OFF UNIT 250A COMPACT NSX

67

KSB250SDF4

TAP OFF UNIT 250A FUPACT INF

81

KSB250SDF5

TAP OFF UNIT 250A FUPACT INF

81

KSB250SE4

TAP OFF UNIT 250A FUSE T1

75, 77

KSB250SE5

TAP OFF UNIT 250A FUSE T1

75, 77

KSB250SM428

TAP OFF UNIT 250A 25 MODULES

64

KSB250ZV1

BOTTOM SUPPORT FOR RISER 250A

41

KSB400

KSB1000ZV2

UNIVERSAL FLOOR GUIDE

41

KSB1000ZV3

FLOOR SUPPORT FOR RISER

41

KSBQPF

Connector with surge arrester


quick-PF

70

KSBQPRD

Tap-off unit with surge arrester


quick-PRD

70

KV

KV025YA4

tap-off joint

45

KV031AB40001

End feed unit

45

KV031AB70001

End feed unit

45

KV031AB40002

End feed unit

45

KV031AB70002

End feed unit

45

KV031YA4

tap-off joint

45

KV040CB71103E

tap-off unit bolted

45

KV040YA41

tap-off joint

45

KV040YA42

tap-off joint

45

KV063AB40001

End feed unit

45

KV063AB70001

End feed unit

45

KV063AB40002

End feed unit

45

KV063AB70002

End feed unit

45

KV063YA4

tap-off joint

45

KV080AB40001

End feed unit

45

KV080AB70001

End feed unit

45

KV080AB40002

End feed unit

45

KV080AB70002

End feed unit

45

KV080YA4

tap-off joint

45

PKY16F723

Industrial sockets 16 A, 200-250 V AC,


2P + T, 65 x 85

71

PKY16F725

Industrial sockets 16 A, 200-250 V AC,


3P + N + T, 90 x 100

71

PKY16F733

Industrial sockets 16 A, 380-415 V AC,


2P + T, 65 x 85

71

PKY16F735

Industrial sockets 16 A, 380-415 V AC,


3P + N + T, 90 x 100

71

PKY32F723

Industrial sockets 32 A, 200-250 V AC,


2P + T, 90 x 100

71

PKY32F725

Industrial sockets 32 A, 200-250 V AC,


3P + N + T, 90 x 100

71

PKY32F733

Industrial sockets 32 A, 380-415 V AC,


2P + T, 90 x 100

71

PKY32F735

Industrial sockets 32 A, 380-415 V AC,


3P + N + T, 90 x 100

71

PKY

KSB400DB412

TAP OFF UNIT 400A COMPACT NSX

66

KSB400DB512

TAP OFF UNIT 400A COMPACT NSX

66

KSB400DC4

TAP OFF UNIT 400A COMPACT NSX

65

KSB400DC4TRE

TAP OFF UNIT 400A COMPACT NSX TRE

72

KSB400DC5

TAP OFF UNIT 400A COMPACT NSX

65

KSB400DC5TRE

TAP-OFF UNIT 400A COMPACT NSX TRE

72

KSB400DCZFL21

FL21 GLAND PLATE

82

KSB400DD411

TAP OFF UNIT 400A COMPACT NSX

67

KSB400SDF4

TAP OFF UNIT 400A FUPACT INF

81

KSB400SDF5

TAP OFF UNIT 400A FUPACT INF

81

KSB400SE4

TAP OFF UNIT 400A FUSE T2

75, 77

KSB400SE5

TAP OFF UNIT 400A FUSE T2

75, 77

KSB400ZB1

TAP OFF BLANKING PLATE 400 A IP55

43

KSB400ZB2

SPRINKLER KIT JOINT PACK KS T1

43

KSB400ZC1

DOOR MICROSWITCH

82

Advantages of the
Canalis...

Optimum system performance...

is part of a comprehensive
offering of Schneider Electric
products designed to operate
together.
In particular, this offering
covers all low and medium
voltage electrical distribution
components.

is ensured by coordination between the protection circuit


breakers and the Canalis prefabricated busbar trunking
used for decentralised distribution.

PD202357_r2.eps

Decentralised electrical distribution with total


coordination perfectly satisfies all your requirements in
terms of safety, continuity of service, upgradeability
and simplicity.

At the end of the catalogue, we present the selection guide


tables that ensure coordination between circuit breakers
and Canalis busbar trunking.
8

Schneider Electric system


Trunking protection

Tap-off units
b The Canalis tap-off units of the Schneider Electric system satisfy operator
needs in terms of:
v installation upgradeability without production downtime
v continuity of service
v safety.

PD202333_r1.eps

PD202332_r2.eps

Our circuit breakers offer:


b overload and short-circuit protection
b coordination between protective devices and Canalis busbar trunking
systems (BTS):
v total discrimination:
- from 1 to 6300 A between all circuit breakers
v cascading:
- reinforcement of low and medium-power BTS short-circuit protective devices
to handle all possible short-circuit levels
- tap-off unit protection using standard circuit breakers regardless of where
the tap-off unit is placed on the Canalis BTS
b simplification of the design process, while ensuring a high degree
of dependability
b quick and easy fault tracking
b simple reclosing (resetting) once the fault has been eliminated by the operator.

PD202334_r1.eps

b The tap-off units:


v can be connected and disconnected under energised conditions
without risk to the operator
v are designed for installation at one-meter intervals on the distribution BTS.

Distribution switchboards
Our protection switchgear optimises switchboard functions.
b Schneider Electric guarantees upstream device coordination:
v between Masterpact, Compact circuit breakers and between Compact and
Acti 9 circuit breakers
v between electrical distribution circuit breakers and industrial control circuit
breakers (motor circuit breaker, Integral, etc.) for industrial control application.
b Switch-disconnectors comply with the IEC 60947-3 standard and are
designed to ensure AC23 load breaking and isolation.
Their protection is guaranteed by coordination with the upstream circuit
breakers.

Canalis
Prefabricated busbar trunking
from 100 to 1000 A

Electrical energy available


troughout your installation.

10

11

Presentation

Canalis KS means business!

71427827_7_r.eps

dv1576116.eps

57284363_r.eps

As an electrical engineering specialist in service sector and industrial buildings,


you want to offer optimal continuity of service and safety for your customers
while controlling your costs and deadlines.
Canalis KS is a range of prefabricated busbar trunking and tap-off units specially
designed for you and your customers.

Schneider Electric know-how


at your disposal

Safety of personnel and


of electrical equipment
above all
With Canalis KS, you have a reliable electrical system,
because the prefabricated busbar trunking has been
optimized and tested in accordance with the
IEC 61439-2 standard.
The whole Canalis KS range contains neither halogen
nor PVC. This means that in the event of a fire, the
busbar trunking will release no fumes or toxic gases.
The fire-break elements confine the fire for two hours, in
vertical and horizontal positions.

12

DD202130_r.eps

DD202144_r.eps

DD202143_r.eps

DD202131_r.eps

Rugged and safe, the Canalis KS range offers you a


high degree of protection:
>> IP55 (on edge or flat)
>> IK08
>> IPxxD
>> sprinkler test.

The manufacturing, packing and distribution processes


have been designed to limit the environmental impact of
our products.
In service, KS busbar trunking dissipates less than 0.1 %
of the total power circulating in the product.
At end of life, over 90 % of the materials used can be
recycled by crushing or dismantling.
PD240003_R.eps

With Canalis KS, you obtain all the modularity, engineering


design and innovation developed by the world leader in
electricity distribution.
This range of busbar trunking comprises:
>> a large choice of ratings
>> customized elements adapted to your installation
constraints
>> protection devices to ensure continuity of service and the
safety of personnel and equipment.

An environmentally friendly
life cycle

Design

Recycling

Industrialization

Exploitation

Schneider Electric has employed all its expertise to optimize


the energy consumption of your electricity distribution system.
With Canalis KS, reduce the CO2 impact of your system.
> Losses:
bb Canalis KS 250 A: 3.5 kWh / 100 m
bb 250 A cables: 5.7 kWh / 100 m
bb difference: 2.2 kWh / 100 m,
i.e. for one year = 19272 kWh / year / 100 m.
> Discharge of CO2 / 100 m = 19272 x 0.64 (1) kg / kWh =

12.3 tonnes / year / 100 m.

> Saving achieved = 19272 x 0.084 (2) =

1619 / year / 100 m.

With Canalis KS, environmental conservation


rhymes with energy savings.
(1) CO2 emissions per kWh: 0.64 kg CO2 / kWh (source: International
Energy Agency).
(2) I ndustrial cost of 1 kWh = 0.084 (source: Eurostat, January 2006),
for an annual consumption of 2000 MWh, excluding VAT.

For more information, the environmental


profile of the Canalis KS range is available
on: www.schneider-electric.com.

Light and easy to handle

Canalis KS equipped with aluminium conductors is 40 % lighter.


The low weight of Canalis KS simplifies installation and greatly reduces the
time required. Fewer workers and resources are required, whatever the type
of installation.

PD202192_r.eps

Our performance...
your values

Excellent contact

Contacts are silver-plated.


The level of performance remains the same throughout the life of the product.

Incomparable scalability

The electrical busbar trunking has a high density of tap-off points even in
rising mains, due to the absorption of differential expansion by the junctions.
The tap-off units are removable and can be handled live.

Easy handling and installation

Because the available space in technical ducts is limited, Canalis KS gives the
advantage to use significantly less room compared to a centralised
distribution system using cables.
Installation is made easy due to the design of the jointing units that facilitate
alignment of the straight lengths.

Maintenance free

All sliding jointing contacts are lubricated for the life of the product.

Very flexible

The floor-distribution components in the Canalis KS range offer 3 or 4 tap-off


outlets per floor, enough to have reserve outlets for future upgrades.

Protected feed units

These provide line protection.


They make it possible to perform operations on a line by de-energizing it,
without interrupting the power supply of the whole system.

A complete range of tap-off units

>> The range covers all needs from 25 to 400 A.


>> Protection is possible using circuit breakers, fuses or surge arresters.
>> Also available are 32 A tap-off units equipped with household and industrial
power sockets.

Intelligent tap-off units

PD202207_r1.eps

>> They monitor the installation to avoid overloads and ensure continuity of
service.
>> They can meter the energy consumed for precise management (cost
allocation for each consumer).

13

Canalis tools
Technical datasheets
p In exhibition center: KD0C00CTAFEEN
p In electronics factories: KD0C00CTAUEEN
p In tiles factories: DEBU005EN
p In automobile industry: KD0C98CTAAUEN
p Reduce electromagnetic emissions: DESWED113001EN

Solution for Data Center


p iBusway for Data Center catalogue:
DEBU028EN
p iBusway for Data Center brochure:
DEBU027EN

Low voltage distribution

iBusway for
Data Center

Invest for today,


plan for tomorrow

Catalogue
2010

iBusway for Data Centers


Monitored busway system
for rack power distribution

Solution for lighting management


p iBusway for lighting management:
Canalis-DALI technical installation guide,
DEBU032EN

iBusway for Lighting


management

Lighting management
has never been so easy
and economical

Canalis - DALI technical and installation guide

iBusway for Lighting Management

p Brochure iBusway for lighting management:


DESWED112002EN

Application datasheets / Guide


p In cruise ships: DESWED105014EN
p In livestock production buildings: DESWED105010EN

Canalisations Electriques Prfabriques

Canalis
Dans les parkings
Fiche application

p In logistic centers: DESWED105011EN


p In car parks: DESWED108011EN
p In greenhouses: DESWED105013EN
p In garages: DESWED106004EN
p In hypermarkets: KD0C98CTAHYEN

+
14

All these documents are available on Schneider Electric web site: www.schneider-electric.com

Canalis KS

Straights components
Contents

Index of commercial numbers


4
Presentation 8

Straight lengths with tap-off outlets

16

Straight lengths without tap-off outlet

20

Straight lengths without tap-off outlet with fire barrier

22

Rising mains

23

Changing direction

26

Made-to-measure changing direction

31

Made-to-measure changing direction with fire barrier

34

Multiple changing direction

36

Multiple changing direction with fire barrier

37

Fixing systems

38

Fixing systems for horizontal trunking

39

Fixing systems for rising mains

41

Accessories

42

From 100 to 1000 A


From 100 to 800 A
From 100 to 1000 A
From 100 to 1000 A
From 100 to 1000 A
From 100 to 1000 A
From 100 to 1000 A
From 100 to 1000 A
From 100 to 1000 A
From 100 to 1000 A

For horizontal trunking and rising mains from 100 to 1000 A


From 100 to 1000 A
From 100 to 1000 A

For horizontal trunking and rising mains From 100 to 1000 A


200 to 800 A KV replacement or add-on units

16
18
20
22
23
26
31
34
36
37
38
39
41
42
45

Feed units and end covers


47
Tap-off units
55
Characteristics 83

15

Description

Straight lengths with tap-off


outlets
From 100 to 1000 A

Canalis KS is designed for medium-power distribution with high tap-off densities in


industrial and commercial buildings.
The range is available in eight Ratings: 100, 160, 250, 400, 500, 630, 800 and 1000 A.
Tap-offs are implemented by tap-off units from 25 to 400 A that may be removed in
complete safety under energised conditions,
from 25 to 400 A.
Busbar trunking rated 100 to 400 A may be equipped with tap-off units up to 250 A.
Busbar trunking with higher Rating may be equipped with the entire range of tap-off
units.
All the insulating and plastic materials are halogen-free and have enhanced
fire-withstand capabilities (incandescent wire test as per standard IEC 60695-2:
960 C for components in contact with live parts and 650 C for other components).

DD210264.eps

The degree of protection of the busbar trunking is IP55 for indoor installations.
For the sprinkler protection, it is necessary to add a sealing kit (see page 43).

These components carry the current and supply loads up to 1000 A.


They constitute the basic structure of the line and are made up of:
1 a casing, crimp closed, made of hot-galvanised sheet steel, pre-lacquered
RAL 9001 white. This casing, shaped and ribbed by roller burnishing, provides
excellent resistance to bending and twisting.
Two sizes cover the entire range of Rating:

500 to 1000 A

DD230589.eps

100 to 400 A

Dimensions
DD230598.eps

Rating

height

width

length

146 mm

54 mm

1500, 2000, 3000


and 5000 mm

146 mm

113 mm

1500, 2000, 3000


and 5000 mm

2 silver-plated aluminium/copper bimetal laminate for the 100 and 160 A


ratings
For the 100 and 160 A Rating: silver-plated aluminium/copper bimetal laminate.
For the 250 to 1000 A Rating: aluminium equipped with silver-plated
aluminium/copper bimetall laminate contacts electrically welded at junctions and
tap-off points.
3 a protective conductor (PE) sized u 50% with respect to the cross-section of
phases. It is connected to the casing at each junction.
4 tap-off outlets from 0.5 to 1 meter on both sides of the trunking.
5 a mechanical and electrical jointing system
Electrical jointing is ensured by a block with flexible grip contacts made of silver-plated
copper. This block equally absorbs the difference in conductor and casing thermal
expansion for each length.
For the 100 to 250 A Rating, the jointing system ensures automatic and simultaneous
jointing of all live conductors and the continuity of the protective earth conductor.
For the 400 to 1000 A Rating, electrical jointing is ensured by a quarter-turn locking
mechanism for each conductor.
16

Commercial numbers
and dimensions

Straight lengths with tap-off


outlets
From 100 to 1000 A

Straight lengths 3L + N + PE
DD230597.eps

Rating
(A)

Straight lengths from 100 to 400 A.

Length
(mm)

Standard components
100
5000
3000
160
5000
3000
250
5000
3000

DD230587.eps

400

DB403573.eps

Straight lengths from 500 to 1000 A.

Connection of a tap-off unit onto a tap-off outlet.

5000
3000
500
5000
3000
630
5000
3000
800
5000
3000
1000
5000
3000
Special components
100 to 250
2000
1500
400
2000
1500
500 to 630
2000
1500
800 to 1000 2000
1500

Number of outlets

Cat. no.

Weight
(kg)

10
6
10
6
10
6

KSA100ED45010
KSA100ED4306
KSA160ED45010
KSA160ED4306
KSA250ED45010
KSA250ED4306

19.20
12.10
21.40
13.40
25.20
15.70

10
6
10
6
10
6
10
6
10
6

KSA400ED45010
KSA400ED4306
KSA500ED45010
KSA500ED4306
KSA630ED45010
KSA630ED4306
KSA800ED45010
KSA800ED4306
KSA1000ED45010
KSA1000ED4306

32.85
20.40
54.50
34.90
58.20
36.40
69.20
43.10
89.50
55.20

8
6
8
6
6
4
6
4

KSA250ED4208
KSA250ED4156
KSA400ED4208
KSA400ED4156
KSA630ED4206
KSA630ED4154
KSA1000ED4206
KSA1000ED4154

10.85
8.55
13.90
10.85
26.00
20.50
38.50
29.90

DD210290.eps

KSApppED45010 from 100 to 400 A

DD202023.eps

KSApppED45010 from 500 to 1000 A

KSApppED4306 from 500 to 1000 A


DD202024.eps

DD210291.eps

KSApppED4306 from 100 to 400 A

KSApppED4206 from 500 to 1000 A


DD202025.eps

DD210292.eps

KSApppED4208 from 100 to 400 A

KSApppED4154 from 500 to 1000 A


DD202026.eps

DD210293.eps

KSApppED4156 from 100 to 400 A

17

Straight lengths with tap-off


outlets

Commercial numbers
and dimensions

From 100 to 800 A


Straight lengths 3L + N + PE
DD230597.eps

Rating
(A)
100
160
250
Straight length from 100 to 400 A.

DD230587.eps

400
500
630
800

Number of outlets

Cat. no.

Weight
(kg)

5000
3000
5000
3000
5000
3000

20
12
20
12
20
12

KSA100ED45020
KSA100ED43012
KSA160ED45020
KSA160ED43012
KSA250ED45020
KSA250ED43012

19.20
12.10
21.40
13.40
25.20
15.70

5000
3000
5000
3000
5000
3000
5000
3000

20
12
18
10
18
10
18
10

KSA400ED45020
KSA400ED43012
KSA500ED45018
KSA500ED43010
KSA630ED45018
KSA630ED43010
KSA800ED45018
KSA800ED43010

32.85
20.40
54.50
34.90
58.20
36.40
69.20
43.10

KSApppED45020 (100-400 A)
DD206152.eps

Straight length from 500 to 1000 A.


DB403573.eps

Length
(mm)

135

500

365

500

500

500

500

500
500

500

500

500

500

500
500

500
500

500
500

365
500

135

Connection of a tap-off unit onto a tap-off outlet.

DB413611.eps

KSApppED45018 (500-800 A)

237

500

513

500
500

500

500

500

500

750
500

500
750

500

5000

DD230169.eps

KSApppED43012 (100-400 A)

135
365

500

500
500

500
500

500
500

365

500
500

500

135

3000

DB413612.eps

KSApppED43010

237
513

500

500
500

750
750

3000

18

513

500
500

500

237

500
500

500
500

513
237

Straight lengths 3L + PE
DD230597.eps

Rating
(A)
400
500
630
Straight length from 100 to 400 A.

Number of outlets

Cat. no.

Weight
(kg)

5000
3000
5000
3000
5000
3000
5000
3000

20
12
10
6
10
6
10
6

KSA400ED35020
KSA400ED33012
KSA500ED35010
KSA500ED3306
KSA630ED35010
KSA630ED3306
KSA800ED35010
KSA800ED3306

30.75
19.14
49.55
31.93
53.25
33.43
64.25
40.13

DD230587.eps

800

Length
(mm)

Straight length from 500 to 1000 A.

DD206154.eps

KSA400ED35020

135

500

365

500
500

500
500

500
500

500
500

500
500

500
500

500
500

500
500

365
500

135

DB403573.eps

5000

DD206155.eps

KSApppED35010 (500-800 A)

Connection of a tap-off unit onto a tap-off outlet.

DD230576.eps

KSA400ED33012

135
365

500

500
500

500
500

500
500

365

500
500

500

135

DD230579.eps

KSApppED3306 (500-800 A)

19

Description

Straight lengths without


tap-off outlet
From 100 to 1000 A

Canalis KS is designed for medium-power distribution with high tap-off densities


in industrial and commercial buildings.
The range is available in eight Rating: 100, 160, 250, 400, 500, 630, 800 and 1000 A.
These components do not have tap-off outlet.
The straight lengths without tap-off outlet are available in different lengths:
bb in standard with 2 lengths: 2 and 3 metres
bb made-to-measure.
The elements allow the line to be adjusted between two changes of direction and can
ensure connection between a MLVSB and a storey electrical distribution board.
All the insulating and plastic materials are halogen-free and have enhanced
fire-withstand capabilities (incandescent wire test as per standard IEC 60695-2:
960 C for components in contact with live parts and 650 C for other components).

DD230594.eps

The degree of protection of the busbar trunking is IP55 for indoor installations.
For the sprinkler protection, it is necessary to add a sealing kit (see page 43).

1 Custom-length run components


bb Used to adjust the length of a line (e.g. between two changes in direction).
bb These components are made to order and do not have tap-off outlets.
2 Fire barrier
bb This type of length is used to transit a fire-proof wall (e.g. between two rooms in
a building).
bb It has been tested in a certified laboratory and complies with standard EN 1363-1.
The laboratory report lists the following results:
vv thermal insulation: u120 minutes
vv resistance to flames: u120 minutes
vv stability: u120 minutes.

20

Straight lengths without


tap-off outlet

Commercial numbers
and dimensions

From 100 to 1000 A


Straight lengths 3L + N + PE
DD230585.eps

Rating
(A)
400
500
630
800

Straight lengths 400 A.


DD230591.eps

1000

Length
(mm)

Cat. no.

Weight
(kg)

5000
3000
5000
3000
5000
3000
5000
3000
5000
3000

KSA400ET450
KSA400ET430
KSA500ET450
KSA500ET430
KSA630ET450
KSA630ET430
KSA800ET450
KSA800ET430
KSA1000ET450
KSA1000ET430

32.85
20.40
54.50
34.90
58.20
36.40
69.20
43.10
69.20
43.10

Length
(mm)

Cat. no.

Weight
(kg)

500 to 1995
500 to 1995
500 to 1995
500 to 1995

KSA250ET4A
KSA400ET4A
KSA630ET4A
KSA1000ET4A

2.50
3.25
12.00
15.00

DD230600.eps

KSApppET4p0 400 A.

Straight lengths from 500 to 1000 A.


DD202048.eps

KSApppET4p0 from 500 to 1000 A.

Made-to-measure straight lengths 3L + N + PE or 3L + PE


Rating
(A)
100 to 250
400
500 to 630
800 to 1000

DD230600.eps

KSApppET4A from 100 to 400 A.

DD202048.eps

KSApppET4A from 500 to 1000 A.

Dimension l

500 to 1995 mm

21

Straight lengths without tap-off


outlet with fire barrier

Commercial numbers
and dimensions

From 100 to 1000 A


Straight lengths with fire barrier 3L + N + PE or 3L + PE
DD230584.eps

Rating
(A)
100 to 250
400
500

Length
(mm)

Cat. no.

Weight
(kg)

900 to 2190
900 to 2190
900 to 2340

KSA250ET4AF
KSA400ET4AF
KSA500ET4AF

8.40
9.90
16.60

630

900 to 2340

KSA630ET4AF

18.00

800
1000

900 to 2340
900 to 2340

KSA800ET4AF
KSA1000ET4AF

19.50
24.20

DD230590.eps

Straight length with fire barrier from 100 to 400 A.

DD230601.eps

KSApppET4AF from 100 to 400 A.

DD202048.eps

KSApppET4AF from 500 to 1000 A.


Straight length with fire barrier from 500 to 1000 A.

Dimensions
Rating
(A)

Dimensions (mm)
l
900 to 2190
900 to 2340

100 to 400
500 to 1000

X
900 to 1740
900 to 1890

Bottom support with fire barrier


DD230609.eps

Rating
(A)
100 to 250
400
500 to 630
800 to 1000

Length
(mm)
1150
1150
1150
1150

Max. permissible
weight (kg)
680
680
1760
1760

Max. permissible
height (m)
40
30
50
40

Cat. no.

Weight
(kg)
KSA250EV4AF 10.00
KSA400EV4AF 12.00
KSA630EV4AF 25.00
KSA1000EV4AF 25.00

E
255
C

DB414039.eps

KSApppEV4AF

92

Dimensions
Rating
(A)
100 to 400
500 to 1000

22

Dimensions (mm)
A
B
750
67
700
124

C
166
169

D
1200
1151

E
223
293

Description

Rising mains

DD210675.eps

From 100 to 1000 A

Canalis KS risers distribute power to each floor in multi-level buildings (office


buildings, hotels, hospitals, car parks and ships).
In this application, Canalis KS offers its many advantages:
b aluminium conductors, equipped with bimetal aluminium/silver-plated copper
contacts at junctions and tap-off points
b a mechanical and electrical jointing system that ensures automatic and
simultaneous jointing of all live conductors and the continuity of the protective earth
conductor, as well as its connection with the casing. This jointing block also absorbs
the difference in conductor and casing thermal expansion for each length
b tap-off outlets with automatic shutters.
When installed vertically, the Canalis KS degree of protection is IP55 for indoor
installations.
For the sprinkler protection, it is necessary to add a sealing kit (see page 43).

How to build rising mains


A Use an end feed unit, type KSA pppABD4 in order the have the neutral on
the right-hand side in the riser.
B Two solutions are available to support the riser.
Rating (A) Max.
Max.
B1 Use the KSB pppZV1 bottom
recommended recommended
support for risers. Placed at the
height
weight by
bottom of the riser and secured to
support
the wall, this support takes the
100 and 250 40 m
680 kg
entire weight of the rising mains.
400
30 m
680 kg
Consequently, depending on the
500
70 m
1760 kg
rating, the maximum height of the
630
50 m
1760 kg
rising mains is limited as indicated
800
50
m
1760 kg
opposite.
1000

40 m

1760 kg

B2 Use floor supports KSBpppZV3, only compatible with specials elements


KSApppET4AF and KSApppZV3. They are used to support the riser on each floor
of the building, for enhanced flexibility in carrying out the various installation
phases. With this support, riser sections can be installed even when the lower
floors have not been completed.
Floor supports must never be used together with a bottom support.
Rating (A)
All

Max. height
150 m

Max. weight by support


440 kg

Above 100 m, avoid the use of fixed components (e.g. elbows) and supply power
using cables wherever possible.
C Use custom-length fire barriers to block fire propagation between floors. They
also provide the means to adjust to the distance between floors (see page 22).
D Use standard straight lengths, 2 or 2.50 metres long. Lengths and fire barriers
can be combined to provide:
Solution 1: for a distance of 2900 mm to 4300 mm between floors, three tap-off
outlets with KSA pppEV4203 straight lengths,
Solution 2 : for a distance of 3400 mm to 4800 mm between floors, four tap-off
outlets with KSA pppEV4254 straight lengths,
E Use KSB1000ZV2 fixings to guide the riser on each floor.

Riser components
D Straight lengths for distribution
Specially designed for rising mains, they are available in two lengths (2 and 2.5
metres).
They have three or four tap-off outlets, all on the same side. The outlets are
positioned to enable connection of up to three 160 A tap-off units for Compact
NSX circuit breakers on the two-metre lengths and up to four on the 2.5-metre
lengths.
C Custom-length fire-barrier lengths (see page 22)
Installed at each floor level, these lengths eliminate any risk of fire propagation
from one floor to another via the trunking. These fire barriers have been tested in
a certified laboratory and comply with standard EN 1363-1. The laboratory report
lists the following results:
b thermal insulation: u120 minutes
b resistance to flames: u120 minutes
b stability: u120 minutes.
Provided in custom lengths, these barriers are used with the straight lengths to
adjust to the exact height of each floor.

23

Rising mains

Commercial numbers
and dimensions

From 100 to 1000 A

Riser mains 3L + N + PE or 3L + PE
DB403573.eps

Rating
(A)
100
250
400
Connection of a tap-off unit onto a tap-off outlet.

500

630

800

1000

Length
(mm)

Number of outlets

Cat. no.

Weight
(kg)

2000
2500
2000
2500
2000
2500
1500
2000
2500
1500
2000
2500
1500
2000
2500
1500
2000
2500

3
4
3
4
3
4
3
3
4
3
3
4
3
3
4
3
3
4

KSA100EV4203
KSA100EV4254
KSA250EV4203
KSA250EV4254
KSA400EV4203
KSA400EV4254
KSA500EV4153
KSA500EV4203
KSA500EV4254
KSA630EV4153
KSA630EV4203
KSA630EV4254
KSA800EV4153
KSA800EV4203
KSA800EV4254
KSA1000EV4153
KSA1000EV4203
KSA1000EV4254

8.10
10.40
10.85
13.35
13.90
17.40
17.45
25.20
30.70
18.20
25.30
30.80
21.55
30.50
37.00
30.10
38.60
47.10

It is also possible to use standard 1.5 metre long straight lengths (KSA pppED4156).

Dimensions
A
B
C

400 A
150
485
865

KS1000EV4153

250

24

1500

500

500

DD230161.eps

264

DD230160.eps

KS500ED4051
DD202077.eps

DD202076.eps

From 500 to 1000 A

100/250 A
135
500
865

250

DD202092.eps

DB414464.eps

From 100 to 400 A


KSApppEV4203

Distribution length at foot riser


Rating
(A)
100
250
400
500 to 630
800 to 1000

Length
(mm)

Number of outlets

Cat. no.

Weight
(kg)

800
800
800
800
800

1
1
1
1
1

KSA100ED4081
KSA250ED4081
KSA400ED4081
KSA630ED4081
KSA1000ED4081

5.40
5.40
7.00
12.10
18.20

From 500 to 1000 A


DD230024.eps

DB414463.eps

KSApppED4081
From 100 to 400 A

25

Changing direction

Description

From 100 to 1000 A

All components for changing direction are supplied with a junction block.
The degree of protection of the busbar trunking is IP55 for indoor installations.
For the sprinkler protection, it is necessary to add a sealing kit (see page 43).

Elbows

DD230595r.eps

Standards
1 Edgewise: one model for turning right or left.
2 Flat : two models, one for turning up and the other for turning down.

Made-to-measure

bb Simple
3 Edgewise: one model for turning right or left.
4 Flat : two models, one for turning up and the other for turning down.

DD230500.eps

3
4

DD230574.eps

bb Made-to-measure angle
5 Edgewise: one model for turning right or left.
6 Flat : two models, one for turning up and the other for turning down.
5
6

bb With fire barrier


Changes of direction fitted with fire breaks, located at the level of the slab or
the partition, eliminate any risk of fire spreading via the busbar trunking.

DD230503.eps

7 Edgewise: one model for turning right or left.


8 Flat : two models, one for turning up and the other for turning down.

26

Multiples

bb Simples
9 Edgewise: two models for turning down. One for turning right and the other for
turning left.
10 Flat: two models for turning up. One for turning right and the other for turning left.
DD230507.eps

10

DD230509.eps

bb With fire barrier


11 Edgewise: two models for turning down. One for turning right and the other for
turning left.
12 Flat: two models for turning up. One for turning right and the other for turning left.

11

12

Tee
DD230596.eps

13 It enables to create branches perpendicular to the main line.


13

27

Changing direction

Description

From 100 to 1000 A

Cross

DD230573.eps

14 It enables to create branches perpendicular to the main line.


14

Zeds
The Z-connections allow you to get around obstacles.

Made-to-measure

bb Simples
15 Edgewise: two models for turning right or left.
16 Flat: one model for turning up or down.

DD230559.eps

16

15

DD230560.eps

bb With fire barrier


17 Edgewise: two models for turning right or left.
18 Flat: one model for turning up or down.

17

18

28

Changing direction

Commercial numbers
and dimensions

From 100 to 1000 A

Rating
(A)

DB404099.eps

DB404098.eps

Elbows 3L + N + PE or 3L + PE
100 to 250

400

500 to 630
Elbow to turn up or down
from 100 to 400 A.

Elbow to turn up or down


from 500 to 1000 A.

Elbow to turn right or left from


500 to 1000 A.

Weight
(kg)

Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward

KSA250DLC40
KSA250DLE40
KSA250DLF40
KSA400DLC40
KSA400DLE40
KSA400DLF40
KSA630DLC40
KSA630DLE40
KSA630DLF40
KSA1000DLC40
KSA1000DLE40
KSA1000DLF40

3.15
5.00
5.00
3.80
5.60
5.60
13.40
12.10
12.10
19.00
16.70
16.70

KSApppDLC40
From 100 to 400 A

KSApppDLE40
From 100 to 400 A

KSApppDLF40
From 100 to 400 A

From 500 to 1000 A

From 500 to 1000 A

From 500 to 1000 A

DD202058.eps

Elbow to turn right or left


from 100 to 400 A.

Cat. no.

DD210311.eps

DB404101.eps

DB404100.eps

800 to 1000

Direction (edgewise)

Tees 3L + N + PE or 3L + PE
DB404102.eps

Rating
(A)

Direction (edgewise)

100 to 250
Perpendicular
400
Perpendicular
500 to 630
Perpendicular
800 to 1000
Perpendicular
(1) Supplied without end cover.

Weight
(kg)

KSA250DTC40
KSA400DTC40
KSA630DTC40
KSA1000DTC40

4.30
5.20
15.80
22.60

KSApppDTC40

Tee from 100 to 400 A.


DD210312.eps

From 500 to 1000 A


DD202059.eps

From 100 to 400 A

DB404103.eps

Cat. no. (1)

Tee from 500 to 1000 A.

29

Changing direction

Commercial numbers
and dimensions

From 100 to 1000 A

Cross 3L + N + PE or 3L + PE
DB404104.eps

Rating
(A)
100 to 250
400
500 to 630
800 to 1000

Direction (edgewise)

Cat. no.

Weight
(kg)

Perpendicular and continous


Perpendicular and continous
Perpendicular and continous
Perpendicular and continous

KSA250DXC40
KSA400DXC40
KSA630DXC40
KSA1000DXC40

4.50
7.00
11.00
11.50

DD230148.eps
DD230149.eps

165

KSApppDTC40

KSApppDTC40

Dimensions
Rating
(A)
100 to 400
500 to 1000

30

Dimensions (mm)
A
54
113

B
330
580

C
330
580

Made-to-measure changing
direction
From 100 to 1000 A
Cross 3L + N + PE or 3L + PE
DB404105.eps

Rating
(A)
100 to 250

400

500 to 630
Elbow to turn right or left.
DB404106.eps

800 to 1000

Direction
(edgewise)
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward

Cat. no.
KSA250DLC4A
KSA250DLE4A
KSA250DLF4A
KSA400DLC4A
KSA400DLE4A
KSA400DLF4A
KSA630DLC4A
KSA630DLE4A
KSA630DLF4A
KSA1000DLC4A
KSA1000DLE4A
KSA1000DLF4A

Weight
(kg/m)
4.00
4.00
4.00
6.80
6.80
6.80
12.20
12.20
12.20
14.40
14.40
14.40

KSApppDLC4A

147

From 500 to 1000 A

46

DD413932.eps

From 100 to 400 A

Elbow to turn up or down.

From 500 to 1000 A

DD230506.eps

KSApppDLE4A or KSApppDLF4A
From 100 to 400 A

Dimensions
Rating
(A)
100 to 400
500 to 1000

Direction
(edgewise)
Right or left
Upward or downward
Right or left
Upward or downward

Dimensions (mm)
A
B
200 to 695
200 to 695
250 to 745
250 to 745
290 to 785
290 to 785
290 to 785
290 to 785

31

Made-to-measure changing
direction

Commercial numbers
and dimensions

From 100 to 1000 A


Elbow with a made-to-measure angle 3L + N + PE or 3L + PE
DB404107.eps

Rating
(A)
100 to 250

Direction
(edgewise)
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward

400

500 to 630
Elbow with a made-to-measure angle
to turn right or left.
DB404108.eps

800 to 1000

Cat. no.
KSA250DLC4B
KSA250DLE4B
KSA250DLF4B
KSA400DLC4B
KSA400DLE4B
KSA400DLF4B
KSA630DLC4B
KSA630DLE4B
KSA630DLF4B
KSA1000DLC4B
KSA1000DLE4B
KSA1000DLF4B

Weight
(kg/m)
4.00
4.00
4.00
6.80
6.80
6.80
12.20
12.20
12.20
14.40
14.40
14.40

KSApppDLC4B

147

From 500 to 1000 A

46

DD413932.eps

From 100 to 400 A

Elbow with a made-to-measure angle to turn


upward or downward.

From 500 to 1000 A

DD230505.eps

KSApppDLE4B or KSApppDLF4B
From 100 to 400 A

Dimensions
Rating
(A)
100 to 400

Direction
(edgewise)

Right or left
Upward ou Downward
500 to 1000 Right or left
Upward ou Downward

32

Dimensions (mm)
A
B
200 to 695
200 to 695
250 to 745
250 to 745
290 to 785
290 to 785
290 to 785
290 to 785

W (each 5)
90 to 180
90 to 180
90 to 180
90 to 180

Made-to-mesure zed 3L + N + PE or 3L + PE
DB404109.eps

Rating
(A)

Zed to turn right or left.

Direction
(edgewise)

Cat. no.

Weight
(kg/m)

100 to 250

Right or left

400

Upward or downward
Right or left

500 to 630

Upward or downward
Right or left

800 to 1000

Upward or downward
Right or left

KSA250DZCH4A
KSA250DZCG4A
KSA250DZE4A
KSA400DZCH4A
KSA400DZCG4A
KSA400DZE4A
KSA630DZCH4A
KSA630DZCG4A
KSA630DZE4A
KSA1000DZCH4A
KSA1000DZCG4A
KSA1000DZE4A

4.00
4.00
4.00
6.80
6.80
6.80
12.20
12.20
12.20
14.40
14.40
14.40

DB404110.eps

Upward or downward

147

DD413934.eps

KSApppDZCH4A or KSApppDZCG4A
From 100 to 400 A

Zed to turn upward or downward.

117

167

DD230562.eps

From 500 to 1000 A

118

DD413936.eps

46

From 500 to 1000 A

167

147

DD413937.eps

KSApppDZE4A
From 100 to 400 A

Dimensions
Rating
(A)
100 to 400

Direction (edgewise)

Right or left
Upward or downward
500 to 1000 Right or left
Upward or downward

Dimensions (mm)
A
B
200 to 695
200 to 395
250 to 745
200 to 395
290 to 785
200 to 575
290 to 785
200 to 575

C
200 to 695
250 to 745
290 to 785
290 to 785

33

Made-to-measure changing
direction with fire barrier

Commercial numbers
and dimensions

From 100 to 1000 A


Made-to-measure elbows with fire barrier 3L + N + PE ou 3L + PE
DB404111.eps

Rating
(A)
100 to 250

400

500 to 630

800 to 1000

DB404112.eps

Elbow with fire barrier to turn right or left.

Direction
(edgewise)
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward

Cat. no.
KSA250DLC4CF
KSA250DLE4CF
KSA250DLF4CF
KSA400DLC4CF
KSA400DLE4CF
KSA400DLF4CF
KSA630DLC4CF
KSA630DLE4CF
KSA630DLF4CF
KSA1000DLC4CF
KSA1000DLE4CF
KSA1000DLF4CF

Weight
(kg/m)
8.40
8.40
8.40
9.90
9.90
9.90
18.00
18.00
18.00
24.20
24.20
24.20

KSApppDLC4CF

147

From 500 to 1000 A

46

DD413933.eps

From 100 to 400 A

Elbow with fire barrier to turn upward or downward.

From 500 to 1000 A

DD206217.eps

KSApppDLE4CF or KSApppDLF4CF
From 100 to 400 A

Dim.
A

Fire barrier location (mm)


900 to 1200
- with X > 450 mm
- with A - X > 450 mm

900 to 1200
- with X > 450 mm
- with B - X > 450 mm

DD230583.eps

DD230582.eps

Position of the fire break


The fire break is 400 mm long. It can be positioned on
any branch of the change of direction, which will then
have different minimum and maximum lengths.
The X dimension indicates the centreline of the fire
break.

Rating
(A)
100 to 400
500 to 1000

34

Direction
(edgewise)
Right or left
Upward or downward
Right or left
Upward or downward

Dimensions (mm)
cote A
cote B
200 to 695
200 to 695
250 to 745
250 to 745
290 to 785
290 to 785
290 to 785
290 to 785

DB404113.eps

Made-to-measure zed with fire barrier 3L + N + PE ou 3L + PE


Rating
(A)
100 to 250

Direction
(edgewise)
Right or left

400

Upward or downward
Right or left

500 to 630

Upward or downward
Right or left

800 to 1000

Upward or downward
Right or left

Cat. no.
KSA250DZCH4CF
KSA250DZCG4CF
KSA250DZE4CF
KSA400DZCH4CF
KSA400DZCG4CF
KSA400DZE4CF
KSA630DZCH4CF
KSA630DZCG4CF
KSA630DZE4CF
KSA1000DZCH4CF
KSA1000DZCG4CF
KSA1000DZE4CF

Upward or downward
Zed with fire barrier to turn right or left.

Weight
(kg/m)
8.40
8.40
8.40
9.90
9.90
9.90
18.00
18.00
18.00
24.20
24.20
24.20

From 500 to 1000 A


DD206219.eps

117

147

DD206218.eps

From 100 to 400 A

167

DB404114.eps

KSApppDZCH4CF or KSApppDZCG4CF

Zed with fire barrier to turn upward or downward.

111

46

DD413938.eps

From 500 to 1000 A

146

147

DD413935.eps

KSApppDZE4CF
From 100 to 400 A

Dim. Fire barrier location (mm)


A
900 to 1200
- with X > 450 mm
- with A - X > 450 mm
B

DD230583.eps

DD230582.eps

Position of the fire break


The fire break is 400 mm long. It can be positioned on
any branch of the change of direction, which will then
have different minimum and maximum lengths.
The X dimension indicates the centreline of the fire
break.

Dimensions
Rating
(A)
100 to 400

Direction
(edgewise)

Right or left
Upward or downward
500 to 1000 Right or left
Upward or downward

Dimensions (mm)
A
B
250 to 745
200 to 395
200 to 695
200 to 395
290 to 785
200 to 575
290 to 785
200 to 575

C
250 to 745
200 to 695
290 to 785
290 to 785

900 to 1200
- with X > 450 mm
- with B - X > 450 mm
900 to 1200
- with X > 450 mm
- with C - X > 450 mm

35

Multiple changing direction

Commercial numbers
and dimensions

From 100 to 1000 A

Multiple elbows 3L + N + PE or 3L + PE
DB404115.eps

Rating
(A)
100 to 250

1st direction
(edgewise)
Downward
Upward

400

Downward
Upward

500 to 630

Downward
Upward

Elbow to turn down then to turn right.


DB404116.eps

800 to 1000

Downward
Upward

2nd direction
(flat)
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left

Cat. no.
KSA250DMBK4A
KSA250DMCK4A
KSA250DMBL4A
KSA250DMCL4A
KSA400DMBK4A
KSA400DMCK4A
KSA400DMBL4A
KSA400DMCL4A
KSA630DMBK4A
KSA630DMCK4A
KSA630DMBL4A
KSA630DMCL4A
KSA1000DMBK4A
KSA1000DMCK4A
KSA1000DMBL4A
KSA1000DMCL4A

KSApppDMBK4A or KSApppDMCK4A
From 500 to 1000 A

KSApppDMBL4A or KSApppDMCL4A
From 100 to 400 A

From 500 to 1000 A

DD230508.eps

From 100 to 400 A

DD230556.eps

DB404117.eps

Elbow to turn down then to turn left.

DB404118.eps

Elbow to turn up then to turn right.

Elbow to turn up then to turn left.

Dimensions
Rating
(A)
100 to 400
500 to 1000

36

Dimensions (mm)
A
250 to 795
290 to 785

B
200 to 445
200 to 575

C
250 to 695
290 to 785

Weight
(kg/m)
4.00
4.00
4.00
4.00
6.80
6.80
6.80
6.80
12.20
12.20
12.20
12.20
14.40
14.40
14.40
14.40

Multiple changing direction with


fire barrier
From 100 to 1000 A
Multiple elbowswith fire barrier 3L + N + PE or 3L + PE
DB404119.eps

Rating
(A)
100 to 250

1st direction
(edgewise)
Downward
Upward

400

Downward
Upward

500 to 630

Downward
Upward

DB404120.eps

Elbow with fire barrier to turn down then to turn right.


800 to 1000

Downward
Upward

2nd direction
(flat)
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left

Cat. no.
KSA250DMBK4CF
KSA250DMCK4CF
KSA250DMBL4CF
KSA250DMCL4CF
KSA400DMBK4CF
KSA400DMCK4CF
KSA400DMBL4CF
KSA400DMCL4CF
KSA630DMBK4CF
KSA630DMCK4CF
KSA630DMBL4CF
KSA630DMCL4CF
KSA1000DMBK4CF
KSA1000DMCK4CF
KSA1000DMBL4CF
KSA1000DMCL4CF

Weight
(kg/m)
8,40
8,40
8,40
8,40
9,90
9,90
9,90
9,90
18,00
18,00
18,00
18,00
24,20
24,20
24,20
24,20

KSApppDMBK4CF or KSApppDMCK4CF
From 500 to 1000 A

KSApppDMBL4CF or KSApppDMCL4CF
From 100 to 400 A

From 500 to 1000 A

DD230558.eps

From 100 to 400 A

DD230557.eps

DB404121.eps

Elbow with fire barrier to turn down then to turn left.

Elbow with fire barrier to turn up then to turn right.

Dim. Fire barrier location (mm)


A
900 to 1200
- with X > 450 mm
- with A - X > 450 mm
B

DD230583.eps

DD230582.eps

Position of the fire break


The fire break is 400 mm long. It can be positioned on
any branch of the change of direction, which will then
have different minimum and maximum lengths.
The X dimension indicates the centreline of the fire
break.

900 to 1200
- with X > 450 mm
- with B - X > 450 mm
900 to 1200
- with X > 450 mm
- with C - X > 450 mm

Dimensions
Rating
(A)
100 to 400
500 to 1000

Dimensions (mm)
A
250 to 745
290 to 785

B
200 to 445
200 to 575

C
250 to 695
290 to 785

37

Fixing systems

Description

DD230605.eps

DB403574.eps

For horizontal trunking and rising mains


from 100 to 1000 A

The maximum recommended fixing distance is three metres.


1 Universal fixing bracket
For attachment of the busbar trunking to the structure of the building, either
directly or via a threaded rod, brackets, etc.
Suspension using chains or steel cables is not advised.
2 Pendant kit
The pendant kit includes:
bb a perforated pendant used to suspend a KS line from the building structure, an
IPN or the ceiling.
Length: 1 meter
Width: 80 mm
bb a cantilever arm that supports the cable tray under the KS line
bb the mounting hardware required to secure the KS bracket and the cantilever
arm to the pendant.
Two kits are available:
bb KS Rating up to 400 A: 200 mm cantilever arm
bb KS Rating from 500 A to 1000 A: 300 mm cantilever arm.
If necessary, additional cantilever arms can be ordered.
3 Bottom support
This component attaches to the first jointing unit at the base of the riser and is
secured to the wall by two brackets. It supports the entire riser (see height
limitations on the previous page).
Note: The foot of the riser is a special jointing unit to which a wall bracket is
installed.
4 Guides
These guides, clipped to the riser, maintain it in the vertical position on each floor.
They not block access to the tap-off outlets.
5 Floor supports
Secured to the floor or wall (via Canalis 200 mm cantilever arms), they attach to
the sides of a special component (with or without fire barrier).

38

Fixing systems for horizontal


trunking

Commercial numbers
and dimensions

From 100 to 1000 A


Pendant kit
DD202196.eps

Rating
(A)
100 to 400
500 to 1000

Max.
load (kg)
80
80

Mounting
Under ceiling or I-beam (1)
Under ceiling or I-beam (1)

Order in Cat. no.


multiple of
4
KSB400ZFKP1
4
KSB1000ZFKP1

Weight
(kg)
2.70
2.80

(1) Maximun recommended distance between fixings: 3 meters.


KSB1000ZFKP1
DD202198.eps

DB403871.eps

KSB400ZFKP1

Pendant kit.

328

428

Cantilever arm, 200 mm


DD210317.eps

Rating
(A)
100 to 400

Max. load
(kg)

Mounting

Order in Cat. no.


multiple of

220

Wall or pendant

Max. load
(kg)

Mounting

Order in Cat. no.


multiple of

200

Wall or pendant

KFBCA81200

Weight
(kg)
0.40

Cantilever arm, 200 mm.

DD202193.eps

KFBCA81200

Cantilever arm, 300 mm


DD202197.eps

Rating
(A)
500 to 1000

KFBCA81300

Weight
(kg)
0.60

Cantilever arm, 300 mm.

DD202199.eps

KFBCA81300

39

Fixing systems for horizontal


trunking

Commercial numbers
and dimensions

From 100 to 1000 A


Fixing bracket
DD210298.eps

Rating
(A)

DD202296.eps

Fixing bracket from 100 to 400 A

Max. load
(kg)

Mounting

100 to 400

70

500 to 1000

70

100 to 400

100 to 400

All

Wall or suspended on
threaded rod (1)
Wall or suspended on
threaded rod (1)
Wall or suspended on
threaded rod (1)
Wall or suspended on
threaded rod (1)
Floor

Order in Cat. no.


multiples
of
10
KSB400ZF1

DD210301.eps

Fixing bracket from 500 to 1000 A

DD202297.eps

KSB1000ZF1

DD230686.eps

KSA80EZ5

40

0.30

10

KSB1000ZF1

0.40

10

KSA80EZ3

0.30

10

KSA80ZG20

0.30

KSA80EZ5

0.70

(1) Maximun recommended distance between fixings: 3 meters.


KSB400ZF1

Weight
(kg)

Fixing systems for rising mains


From 100 to 1000 A

Bottom support
Rating
(A)
250
400
500 to 630
800 to 1000

Max. permissible weight


(kg)
680
680
1760
1760

Cat. no.

Weight
(kg)
4.50
5.00
7.00
7.30

KSB250ZV1
KSB400ZV1
KSB630ZV1
KSB1000ZV1

KSBpppZV1
DB414465.eps

55 mm y Z y 105 mm

Floor guide
Used with the bottom support.
Rating
(A)
All

Cat. no.

Weight
(kg)
0.70

KSB1000ZV2

For floors higher than 3.5 metres, it is advised to use two guides per floor.
KSB1000ZV2
DD210643.eps

65 mm y A y 95 mm

Floor supports
Set of 2 floor supports.
Rating Max. permissible Mounting
(A)
weight (kg)
Set of 2 floor supports

Cat. no.

Order in
Weight
multiple of (kg)

All
440
Cantilever arm, 200 mm

Floor or cantilever arm KSB1000ZV3

1.80

All

Wall

KFBCA81200

0.40

220

For floors higher than 3.5 metres, it is advised to use a floor guide in addition to the support.
KFBCA81200
DD230606.eps

DB414469.eps

KSB1000ZV3

41

Description

Accessories

For horizontal trunking and rising mains


From 100 to 1000 A

DD205043.eps

Lead-sealing system

This prohibits access to live parts. Two systems are available: one is installed either
on the power supply box or on the busbar connector, and the other on the tap-off
points.

Spare parts
Sprinkler kit
To comply with the sprinkler tests (guaranteeing operation under vertically and
horizontally sprayed water for 50 minutes), each electrical jointing system should be
fitted with a reinforced protection kit (the jointing sleeve).
Separate parts
Electrical and mechanical connecting plates
These are blocks fitted with elastic contacts in silver-plated copper.
They automatically provide electrical connection of all conductors.
IP55 plugs
These plugs protect the busbar trunking tap-off points.

Adapters

These parts allow Canalis KS busbar trunking to be connected to previous KS


generation busbar trunking.

Selection guide of adapters and jointing units


KSA250ZJ4

KSA1000ZJ4
KSA630ZJ4 or
KSA1000ZJ4

KSA500FR425

Beginning of line

End of line

Line power

100 A

160 A

100 A

100 A

250 A

100 A

160 A

100 A

100 A

250 A

100 A

100 A

160 A

250 A

160 A

250 A

160 A

160 A

1000 A

800 A

800 A

800 A

1000 A

800 A

500 A

630 A

500 A

500 A

800 A

500 A

500 A

1000 A

500 A

630 A

500 A

500 A

800 A

500 A

500 A

1000 A

500 A

500 A

630 A

800 A

630 A

630 A

1000 A

630 A

800 A

630 A

630 A

1000 A

630 A

630 A

400 A

500 A

400 A

500 A

400 A

400 A

630 A

400 A

400 A

800 A

400 A

400 A

1000 A

400 A

400 A

400 A

630 A

630 A

400 A

800 A

800 A

400 A

1000 A

1000 A

Reducer element

These part allow connection of KS busbar trunking of different sizes and ratings
(Size 1 = from 100 to 400 A; Size 3 = from 500 to 1000 A).

Protection end-pieces

The protection end-pieces insulate and protect the connectors at the end of busbar
trunking. They are installed on the last busbar trunking of the distribution line.

42

Accessories

Commercial numbers
and dimensions

For horizontal trunking and rising mains


From 100 to 1000 A

Lead sealing kits


DB403577.eps

Rating
(A)
All

For
Feed unit cover and jointing
screws
Tap-off outlets

Order in
multiple of
20

Cat. no.
KSB1000ZP1

Weight
(kg)
0.0035

20

KSB1000ZP2

0.002

Cat. no.

Weight
(kg)

KSA250ZJ4
KSA400ZJ4
KSA630ZJ4
KSA1000ZJ4

1.60
2.00
3.50
4.50

KSB400ZB1
KSB1000ZB1

0.015
0.020

KSB400ZB2
KSB1000ZB2

1.00
1.00

DB403578.eps

KSB1000ZP1

KSB1000ZP2

Rating
(A)

DD202020.eps

DD202019.eps

Spare parts

Electrical and mechanical jointing unit


100 to 250
1
400
1
500 to 630
1
800 to 1000
1
IP55 outlet plug
100 to 400
15
500 to 1000
15
Sprinkler proofing accessory
100 to 400
1
500 to 1000
1

KSA400ZJ4

DD202060.eps

KSA250ZJ4

Order in
multiple of

DD202053.eps

KSA250ZJ4 and KSA400ZJ4

DD202021.eps

DD202061.eps

KSA1000ZJ4

KSB400ZB1

KSB1000ZB1

KSB1000ZB2

KSB400ZB2

KSB1000ZB2
DD205042.eps

KSB400ZB2

DD205044.eps

DD205045.eps

DD205041.eps

DD202062.eps

KSA630ZJ4

43

Accessories

Commercial numbers
and dimensions

For horizontal trunking and rising mains


From 100 to 1000 A

Adapters
DD202054.eps

DD202068.eps

Rating
(A)
100 to 250
250
400
500
630 to 800
KSA250FA4

KSA400FA4

Cat. no.

Connection to old KS lines


Connection to old KS lines
Connection to old KS lines
Connection to old KS lines
Connection to old KS lines

KSA250FA4
KSA250FA4
KSA400FA4
KSA500FA4
KSA800FA4

Weight
(kg)
1.35
1.35
2.90
3.65
4.00

DD202082.eps

DD202087.eps

KSA250FA4

For

KSA500FA4

DD206163.eps

DD202088.eps

KSA400FA4

KSA800FA4

DD202089.eps

KSA500FA4 and KSA800FA4

Reducer element
Cat. no.
KSA500FR425

Weight
(kg)
1.60

DD230143.eps

KSA500FR425

DD230142.eps

DD230144.eps

Rating For
(A)
All
Connecting 400 A busbar trunking to 500 to 1000 A
trunking
KSA500FR425

76
142

Protection end-pieces
DD230040.eps

Rating
(A)
100 to 400
500 to 1000

For

Cat. no.

Protecting and insulating conductor end-pieces.


Protecting and insulating conductor end-pieces.

KSA400AF1
KSA1000AF1

44

Dimensions (mm)
A
B

DD206208.eps

186

KSApppAF1

DD206207.eps

KSApppAF1

KSA400AF1
KSA1000AF1
B

102
147

67
124

Weight
(kg)
0.25
0.40

Accessories

200 to 800 A KV replacement


or add-on units
Replacement or add-on units
DB414398.eps

Rating
3L + N + PE
(A)
Cable-connection feed unit N1
200/315
KV031AB40001
400/630
KV063AB40001
800
KV080AB40001
Cable-connection feed unit N2
200/315
KV031AB40002
400/630
KV063AB40002
800
KV080AB40002
Single-feeder tap-off unit (1)
400
Standard joint kits
200/315
400/630
800
Joint/tap-off kits
200/315
400/630
800

KV0ppCB71103E

KV0ppYApp

3L + N + PER

Weight
(kg)

KV031AB70001
KV063AB70001
KV080AB70001

4.00
7.70
14.70

KV031AB70002
KV063AB70002
KV080AB70002

4.00
7.70
14.70

KV040CB71103E

7.00

KV031YA4
KV063YA4
KV080YA4

1.50
2.40
3.10

KV025YA4
KV040YA41
KV040YA42

1.50
2.40
3.10

(1) Can be used for 250 A and 400 A.

630 and 800 A

20

10

30

20
70

20

67

10

DB414036.eps

400 and 500 A

20

DB414035.eps

8,5

DB414034.eps

Rating
200 and 315 A

40

15
h
60

60

50

Tap-off unit dimensions according to rating


Rating
(A)
200 and 315
400 and 500
630 and 800

H
44
71
114

Dimensions (mm)
A
B
200
650
200
700
200
700

C
300
400
450

D
450
500
500

Y
150
170
190

DB414037.eps

Configuration examples

Cabling between the KV/KS feed units.


DB414038.eps

DB414033.eps

Dimensions of pads connecting the feed units via a cable

Connection through KV feed units.

45

46

Canalis KS

Feed units and end covers


Contents

Index of commercial numbers


4
Presentation 8
Straights components
15

Feed units and end covers

48

Feed units

49

Centre feed units

50

Protected feed units

51

Flange feed units

52

Accessories for feed units

53

From 100 to 1000 A


From 100 to 1000 A
From 100 to 1000 A
From 100 to 1000 A
From 100 to 1000 A

48
49
50
51
52

Tap-off units
55
Characteristics 83

47

Description

Feed units and end covers


From 100 to 1000 A

DD206221.eps

Used to feed a KS line by cables or directly from the busbars in a switchboard. They can
be mounted at the end of a line (end feed, left or right) or in the middle (central feed).
Feed units with circuit breaker protection (not supplied) are also available.

1 End feed unit for KS 100 A trunking


For KS 100 A trunking only.
It can be mounted on either side of a straight length.
It is equipped with a PG 29 cable gland (equivalent to M32) and supplied with
an end cover.
2 End feed unit for horizontal or vertical trunking
For 250 to 400 A rating, it can be mounted on the end of a straight length.
For 500 to 1000 A rating, two type of end feed units are available:
bb left or top end feed unit: ABG or ABDG
bb right or bottom end feed unit: ABD or AABDD.
Supplied with with end cover.
3 Communication box
The measurement is performed by an energy meter, visible on the front of the
feed unit.
The measuring system consists of current transformers and a PM5350 for the
monitoring of electrical heights of busbar trunking lines. Communication with
supervision systems is done by modbus TCP through a EGX300 gateway.
4 Centre feed unit
Using a single cable, it is possible to feed both the right and left-hand sections.
It is mounted between two straight lengths in the line and is supplied with two end
covers.
5 Flange feed unit
Equipped with splayed bars and a mounting plate for direct connection to the
busbars of a switchboard.
It can be mounted on either end of a component and is supplied with an end cover.
6 End cover
The end cover protects and isolates the ends of the conductors. It is mounted
on the last component. Supplied with end feet unit and feed unit.
7 Protected end feed unit for horizontal trunking
It can be mounted on either side of a straight element.
It can be equipped with a Compact NSX or NS circuit breaker and Micrologic.
Control units are designed to protect power circuits and loads. Measurements of
current, voltage, frequency, power and power quality optimize continuity of
service and energy management. It is supplied with an end cover.
48

Feed units

Commercial numbers
and dimensions

From 100 to 1000 A

End feed unit


DD210294.eps

Rating Mounting
(A)
100

Max. size (mm2) Cat. no.


Flexible or rigid
5 x 16
KSA100AB4

Connection

Right or left

Terminals

Weight
(kg)
1.85

DD210296.eps

KSA100AB4

KSA100AB4

End feed units


DD210295.eps

Rating Mounting
(A)
100 to
250
400

Right

800 to
1000

Right

Left

Left

Lugs
(M10 screws)
Lugs
(M10 screws)
Lugs
(M12 screws)
Lugs
(M12 screws)
Lugs
(M12 screws)
Lugs
(M12 screws)

Cat. no.

Weight
(kg)

KSA250AB4

7.20

KSA400AB4

8.80

KSA630ABD4

18.50

KSA630ABG4

18.50

1 x 300
or 2 x 120
1 x 300
or 2 x 240
1 x 300
or 2 x 240
4 x 240

1 x 300
or 2 x 120
1 x 300
or 2 x 240
1 x 300
or 2 x 240
4 x 300

KSA1000ABD4 24.50

4 x 240

4 x 300

KSA1000ABG4 24.50

DD202028.eps

KSA630ABG4

KSA1000ABD4
DD202063.eps

KSA1000ABG4
DD202072.eps

KSA630ABD4
DD202070.eps

Max. size (mm2)


Flexible
Rigid
240
240

KSA400AB4
DD210642.eps

DD210297.eps

Right or left

500 to
630

KSAjjpppAB4
KSA250AB4

Right or left

Connection

Cable exit.

Communication box for KS feeder


DB405239.eps

Rating
(A)

Designation

Cat. no.

KSA250ABCB4 4.8
KSA400ABCB4 5.3

350

DB405241.eps

DB405240.eps

250
Communication box for KS feeder 250 A
400
Communication box for KS feeder 400 A
KSA250ABCB4
KSA400ABCB4

Weight
(kg)

411,5

KSAABCB4

127

bb It is designed to install measurement system (PM5350) and protection (Acti 9).


bb It is fixed to replace the lids of end feed units KSA250AB4 and KSA400AB4.
bb The equipment must be ordered separately depending on the installation.

49

Centre feed units

Commercial numbers
and dimensions

From 100 to 1000 A

Centre feed units


DD210304.eps

Rating Mounting
(A)

KSAjjpppABT4
From 100 to 400 A.

100 to
250

Central

400

Central

500 to
630
800 to
1000

Central
Central

DD202049.eps

DB416316.eps

KSA250ABT4

KSAjjpppABT4
From 500 to 1000 A.
DB416317.eps

KSA400ABT4

DD202051.eps

KSA630ABT4

DD202064.eps

KSA1000ABT4

Cable exit.

50

Connection
Lugs
(M10 screws)
Lugs
(M10 screws)
Lugs
(M10 screws)
Lugs
(M12 screws)

Max. size (mm2)


Flexible
Rigid
240
240

Cat. no.

Weight
(kg)

KSA250ABT4

12.90

2x 240

2x 240

KSA400ABT4

15.50

3 x 240

3 x 300

KSA630ABT4

30.50

4 x 240

4 x 300

KSA1000ABT4 41.50

Protected feed units


From 100 to 1000 A

Protected feed units 3L + N + PE

400

NSX 250
Curve N. H or L
Rotary handle 29338
NSX 400
Curve N, H or L
Rotary handle 32598

Cat. no.

Right
Left

NSX
NSX

KSA250ABDD4 16.50
KSA250ABGD4 16.50

Right

NSX

KSA400ABDD4 22.00

Left

NSX

KSA400ABGD4 22.00

DD230542.eps

KSA250ABDG4

309
353

KSAjjpppABpD4

DD230541.eps

KSA250ABDD4

232
276

645
742

232
276

645
742

KSA400ABDG4

346
393

DD230540.eps

KSA400ABDD4
DD230539.eps

Weight
(kg)

353
309

250

Mounting Connection

232
276

764
860

393
346

DD230173.eps

Rating Type of circuit breaker


(A)
(not included)

232
276

764
860

Cable exit.

Protected feed units 3L + PE

250

NSX 250 Courbe N. H ou L


Commande rotative 29338

400

NSX 400 Curve N, H or L


Rotary handle 32598

Mounting Connection

Cat. no.

Weight
(kg)

Right
Left
Right
Left

KSA250ABDD5
KSA250ABGD5
KSA400ABDD5
KSA400ABGD5

17.00
17.00
23.00
23.00

NSX
NSX
NSX
NSX

645
742

645
742

232
276

KSA400ABDG5

393
346

DD230548.eps

KSA400ABDD5

232
276

309
353

DD230550.eps

KSA250ABDG5

353
309
232
276

DD230549.eps

KSAjjpppABpD5

DD230551.eps

KSA250ABDD5

764
860

346
393

DD230173.eps

Rating Type of circuit breaker


(A)
(not included)

764
860

232
276

Cable exit.

51

Flange feed units

Commercial numbers
and dimensions

From 100 to 1000 A

Flange feed units


DD210306.eps

Rating
(A)
100 to 250
400
500 to 630
800 to 1000

Mounting

Connection

Cat. no.

Right or left
Right or left
Right or left
Right or left

Bars (M10 screws)


Bars (M10 screws)
Bars (2 x M10 screws)
Bars (4 x M12 screws)

KSA250AE4
KSA400AE4
KSA630AE4
KSA1000AE4

DD202050.eps

KSAjjpppAE4
From 100 to 400 A.

DD230005.eps

KSA250AE4 and KSA400AE4

Dimensions
A
B
C
D
E

KSAjj630AE4
From 630 to 1000 A.

DD202052.eps

KSA630AE4 and KSA1000AE4

52

100 to 250 A
243
261.5
108
278
294

400 A
261
279.50
117
318
334

Weight
(kg)
1.70
1.90
4.70
6.60

Accessories for feed units

FL21 gland plates

FL21 gland plates

DB414710.eps

Designation

Rating Type of Cat. no.


(A)
feed unit of the feed
unit

For feed units 250


400
500 to
630
800 to
1000

End
Central
End
Central
End
Central
End
Central

Dimensions Cat. no
KSA250ABZFL21
A
300
B
168.5
C
198
D
69

DB414711.eps

No. of
holes
of the
gland plate
KSA250AB4
1
KSA250ABT4 1
KSA400AB4
1
KSA400ABT4 1
KSA630AB4
2
KSA630ABT4 2
KSA1000AB4 2
KSA1000ABT4 2

KSA250ABTZFL21
391
168.5
198
69

Cat. no.

Weight
(kg)

KSA250ABZFL21
KSA250ABTZFL21
KSA400ABZFL21
KSA400ABTZFL21
KSA630ABZFL21
KSA630ABTZFL21
KSA1000ABZFL21
KSA1000ABTZFL21

0.30
0.45
0.50
0.75
0.78
0.72
1.08
0.91

KSA400ABZFL21
340
208.5
198
69

KSA400ABTZFL21
491
208
198
69

DB414712.eps

KSA250ABZFL21 - KSA250ABTZFL21
KSA400ABZFL21 - KSA400ABTZFL21

Dimensions Cat. no
KSA630ABZFL21
A
446
B
276
C
198
D
69
E
50

KSA1000ABZFL21
446
358
198
69
70

Dimensions Cat. no
KSA630ABTZFL21
A
502
B
227
C
198
D
69
E
30

KSA1000ABTZFL21
552
252
198
69
50

DB414713.eps

KSA630ABZFL21 - KSA1000ABZFL21

KSA630ABTZFL21 - KSA1000ABTZFL21

53

Commercial numbers
and dimensions

54

Canalis KS

Tap-off units
Contents

Index of commercial numbers


4
Presentation 8
Straights components
15
Feed units and end covers
47

Tap-off units

56

Compatibility of tap-off units and busbar trunkings

60

50 to 160 A empty tap-off units

62

32 to 100 A tap-off units for modular devices

63

250 A tap-off unit for Compact NSX circuit breaker


and modular devices

64

160 to 400 A tap-off units for Compact NSX circuit breaker

65

160 A tap-off units for NG modular devices

68

Tap-off units equipped withasurge arrester

70

32 A tap-off units with power sockets protected


by modular devices

71

250 and 400 A tap-off units


for measurements and metering

72

32 to 160 A tap-off units

73

32 to 100 A tap-off units cylindrical fuses

74

100 to 400 A tap-off units for NF fuses

75

16 to 63 A tap-off units for DIN fuses

76

100 to 400 A tap-off units for DIN fuses

77

20 to 160 A tap-off units for BS fuses

78

125, 250 and 400 A tap-off units


for switch fuse disconnectors

79

630 A tap-off units for fuses

80

Canalis KS, 100 to 1000 A

81

Accessories for tap-off units

82

From 100 to 1000 A

Busbar trunking for medium-power distribution

56

81

Characteristics 83

55

Tap-off units

Description

From 100 to 1000 A

Tap-off units
For rapid connection of loads or secondary lines, in compliance with installation standards IEC 60364 and regulations, whatever the system
earthing arrangement (TT, TNS, TNC or IT).
They can be handled and removed under off-load conditions with the trunking energised.
The tap-off outlets are automatically opened or closed when tap-off units are connected or removed.
With the cover open, no live parts are accessible.
The degree of protection is IPxxB (protected against access with a finger).

Tap-off units from 160 to 400 A are made of sheet


steel (C):
bb Colour: RAL 9001 white for the casing, RAL 9005
black for the grip zones (100 % polyester paint on
galvanised sheet steel).
b 400 A tap-off units can be only installed on straight
lengths u 500 A.
bb Other characteristics:
vv removable cover with hinges enabling opening up to
120, vertically bevelled cover with double bends for
enhanced rigidity, polyurethane gaskets
vv equipped with cable-gland plates marked every
25mm and designed for maximum access.
Disconnection principle:
Disconnection by unplugging the tap-off unit.
The access to the electrical devices and the terminals
is possible only when the tap-off unit is unplugged
(i.e. not energised).
A safety device prevents connection to the trunking
when the cover has been removed.
Disconnection of tap-off units with fuses and modular
devices (category AC22 to AC20) is obtained by
opening the tap-unit cover.
Tap-off unit disconnection by opening or closing
the cover should be carried out only if the
downstreamload is de-energised.

56

DD210278.eps
DD210280.eps

DD210279.eps
DD210281.eps

bb Colour: RAL 9001 white for the casing and the grip
zones and transparent green for the cover,The fixing
mechanisms are in RAL 7016.
bb Material: self-extinguishing, halogen free insulating
plastic (fire resistant and very high temperature
withstand).
bb Other characteristics: cable gland drilling zone,
stainless steel screws and the door can be lead sealed.

DD210461.eps

Tap-off units (A) and tap-off units with isolators (B)


up to 100 A are made of plastic:

DD210277.eps

DD206164.eps

DD206165.eps

The degree of protection is IP55 for indoor installations as standard (noaccessories are required).

For tap-units with circuit breakers, a number of safety devices prevents from:
bb plugging and unplugging in the tap-off unit when the cover is closed
bb closing the cover before the tap-off unit is locked onto the trunking
bb having access to the electrical equipment and the terminals when energised
bb opening the cover in the position ON (tap-off units equipped with a Compact
NSX or NG circuit breaker)
bb the tap-off units accept modular devices in multiples of 18 mm wide modules.
These tap-off units can be equipped with certain accessories such as circuit-opening
contacts on the cover, lead seals, etc.

Tap-off units for circuit breakers (not equipped)


DD210282.eps

Tap-off unit covers can be lead sealed to prevent circuit-breaker switching by


unauthorised persons.
Tap-off unit for modular devices
This tap-off unit can be equipped with most modular devices of the Acti 9 type:
b rated current: 32 A
b capacity: 5 modules
b with a window in front for visual and physical access to the devices. A transparent
cover seals the window.

DD210283.eps

Tap-off units, with isolators, for modular devices


These tap-off units accept most modular devices of the Acti 9 type. They have a
window in front for visual and physical access to the devices. A transparent cover
seals the window.
Two rating are available:
b maximum rated current 63 A for eight modules
b maximum rated current 100 A for twelve modules.

DD210284.eps

Tap-off units, with isolators, for NG type modular devices


These tap-off units are equipped with a DIN rail.
The devices are operated by rotary handles that prevent door opening with the circuit
breaker in On position.
b maximum rated current: 160 A
b capacity: 13 modules (accepts NG125 or NG160 devices equipped with
Vigi modules).
Tap-off units, with isolators, for Compact NSX circuit breaker
These tap-off units are equipped with mounting plates and upstream connections for
Compact NSX circuit breakers:
b rated current: 100 to 400 A, N, H or L versions
b fixed, front connection, rotary handle
b for Compact NSX + Vigi module, use tap-off units for measurements and metering
(see below).
Note: For options such as withdrawable circuit breakers, earth-leakage protection, etc, call your
SchneiderElectric contact.

Tap-off units for measurements and metering (not equipped)


DD210286.eps

They are equipped with:


b a mounting plate for a Compact NSX type circuit breaker with an extended rotary
handle and a Compact NSX current transformer module
b a DIN rail for installation of a Powerlogic PM810, a set of terminals, etc.
These tap-off units are used for sub-billing and monitoring of secondary lines. The
values measured by the TI module of the Compact NSX are transmitted to the
power-monitoring unit that forwards the information to a central unit via a bus
(see Special measurement and metering applications).

DB414226-40.eps

DD230656.eps

Under severe operating conditions (> 40 C ambient temperature), we recommend


using a PM810 without a display.
Possibility to install a metering tap-off unit using those equipments:
bb empty tap-off unit
bb window for modular equipment (IP65)
bb mounting plate
bb current transformer
bb iC60N circuit-breaker.

57

Description

Tap-off units

From 100 to 1000 A

Tap-off units for power sockets (not equipped)


DD210302.eps

Tap-off unit covers can be lead sealed to prevent circuit-breaker switching by


unauthorised persons.
Canalis 32 A tap-off unit for power sockets
For the supply of portable loads equipped with household or industrial plugs in a
garage, maintenance workshop, laboratory, battery charging room, etc.
For installation on trunking mounted on a wall for better access.
For easy access, install on trunking mounted at an appropriate height on the wall.
Flexibility, upgradeability: positioned as close as possible to the loads, extension
leads are not required
Degree of protection: IP55, IK08.
Safety of persons: IPxxD, earth-leakage protection.

DD210459.eps

Rated current: 32 A
Capacity: 8 modules in multiples of 18 mm wide
Two versions are available:
b pre-equipped with a power sockets
b customisable:
v two 90 x 100 mm openings for PK-type (screw connections) or PratiKa (fast and
reliable connection without stripping) industrial or household sockets
v direct mounting for industrial IEC 16 A 5P or IEC 32
A 3, 4 or 5P sockets
v mounting on a 65 x 85 mm clip-on adapter plate for industrial IEC 16 A 3P or 5P
and household 10/16 A 2P + PE sockets.

Tap-off units for fuses (not equipped)


For protection of the tap-off by fuses (not supplied).
1 Tap-off unit with fuse holders
This tap-off unit exists in three versions:
b for NF 10 x 38 fuses
b for BS type 88 A1 fuses
b for DIN type Neozed E14 fuses.

DD210288.eps

2a and 2b Tap-off units, with isolator, for fuses


There are two types of tap-off units:
Plastic tap-off units (2a) equipped with fuse holders for:
b NF 50 to 100 A cylindrical fuses
b BS 32 to 80 A screw fuses
b DIN 25 to 63 A screw fuses
b 100 A blade-type fuses.
Sheet-metal tap-off units (2b) equipped with fuse holders for 160 to 400 A blade-type
fuses.

58

DB403839.eps

Tap-off units (with and without isolators) equipped with a surge arrester
These tap-off units (with and without isolators) are pre-equipped with a modular Type
2 surge arrester, with integrated disconnection device.
2 versions of 3P+N protection are available, based on Quick PF10 or Quick PRD40r.
These units are ready for use, can be plugged directly into the busbar trunking and
do not require any additional wiring.
They should be positioned at least 30 m upstream of each load to be protected.
Tap-off unit covers can be lead sealed to prevent the surge arrester being tampered
with by unauthorised persons.

59

Compatibility of tap-off units


and busbar trunkings

Description

The number of tap-off units presented below corresponds to an installation on a single side of the Canalis prefabricated busbar trunking
system.
This number is doubled for installations in which the tap-off units can be mounted on both sides.

Tap-off units with wander sockets


5 modules

KSB63SM8 (1)

8 modules

KSB100SM12 (1)

12 modules

KSB160SM24 (1)

24 modules

DD230630.eps

DD230629.eps

DB405627.eps

DD230627.eps

KSB32CM55 (1)

Tap-off units with panel mountings


8 modules

KSB160SM24 (1)

24 modules

DD230632.eps

DD230631.eps

KSB32CP (1)

(1) For more details on tap-off units, refer to the Canalis 20 to 1000 A prefabricated busbar trunking system catalogue (reference DEBU022EN).
: Outlets not usable for this type of tap-off.

60

From 100 to 400 A

From 500 to 800 A

Tap-off outlets usable for the tap-off units from 16 to 125 A

Tap-off outlets usable for the tap-off units from 16 to 400 A


DB416226.eps

DB416224.eps

Rising mains for 2 m or 2.5 m lenght

Tap-off outlet not usable for KSB400Dpppp tap-off units.

61

50 to 160 A empty tap-off units

Commercial numbers
and dimensions

Empty tap-off units


TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit
DB414730.eps

Tap-off polarity
Tap-off diagram
(e.g. fuse protection)

TNC
TNC
3L + PEN
DB414731.eps

DD206168.eps

Earthing system
arrangement

KSBpppSVp
DD210472.eps

Rating
(A)
50
100
160

Cat. no.

Cat. no.

Weight
(kg)

KSB50SV4
KSB100SV4
KSB160SV4

KSB50SV5
KSB100SV5
KSB160SV5

2.20
4.80
8.00

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
KSB50SVp, KSB100SVp
50 A
356
153
167
309
103
202

100 A
444
178
202
397
128
220

32

182

KSB160SVp

300

X = 432.5 (KSB50SVp)
X = 545.5 (KSB100SVp)
X = 630.5 (KSB160SVp)

Dim.
A
B
C
D
E
F

DD230577.eps

DD2020081.eps

DD230553.eps

KSB160SVp

32

395
450

257

Cable exit
Centre line of tap-off outlets

(1) Protruding

Plate for feed units


DB413893.eps

Designation
For feed units

Rating (A)

Cat. no of
tap-off units

Mounting

50

KSB100SV4
KSB100SV5
KSB63SM48
KSB63SM58

Fixing with power meter KSB63PMP


equipments
Fixing with
KSB63EGP
equipements type EGX

63

KSB63PMP

62

Cat. no

32 to 100 A tap-off units


for modular devices
Tap-off units
DD210450.eps

Disconnection by unplugging the tap-off unit.


Earthing system
arrangement

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit
DB414732.eps

Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)
KSB32CM55
Rating
(A)

Number of
18 mm
modules (3)

Connection

32

Pre wired

Max. size
(mm)

Cable gland (4) Cat. no.


(not supplied)

Flexible Rigid
6
10
ISO 32 max.

Weight
(kg)

KSB32CM55

0.60

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Supplied with blanking plate (1 x 5 divisible).
(4) Maximum diameter for a multipolar cable.
KSB32CM55
DD210453.eps

Cable exit
Centre line of tap-off
outlets
Protruding

Tap-off units with isolator

KSB63SM p8
KSB100SM p12

Rating
(A)

Number of
18 mm
modules (3)

63

100

12

Connection

TT-TNS-TNC-IT (1) TNC


TT-TNS-TNS-IT (1) TNC

Busbar trunking
Tap-off unit

Max. size
(mm)

Flexible Rigid
Copper cable 16
16
lugs
Copper cable 35
35
lugs

3L + N + PE (2)

3L + PEN
DD414772.eps

Earthing
system
arrangement
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)

DD414771.eps

DD210454.eps

Disconnection by opening the tap-off unit cover.

Cable gland (4) Cat. no. (5)


(not supplied)

Cat. no. (5)

Weight
(kg)

ISO 50 max.

KSB63SM48

KSB63SM58

ISO 63 max.

KSB100SM412

KSB100SM512 5.00

2.40

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed).
(3) Supplied with blanking plates: (1 x 5 divisible (8 modules) or 2 x 5 divisible (12 modules)).
(4) Maximum diameter for a multipolar cable.
(5) Not compatible with NG circuit breaker, see page 68.

Dim.
A
B
C
D
E
F

DD210455.eps

DD2020081.eps

KSB63SM p8, KSB100SM p12

X = 432.5 (KSB63SMp8)
X = 545.5 (KSB100SMp12)

Cable exit
Centre line of tap-off outlets

63A
357
158
167
309
108
202

100A
444
183
202
397
133
220

(5) Protruding

63

250 A tap-off unit


for Compact NSX circuit
breaker and modular devices

Commercial numbers
and dimensions

28-module tap-off unit for Compact NSX circuit breakers and modular devices
DD206166.eps

Supplied with 2 DIN rails for 28-modules mounting.


Protection degree: IP31.
The rear panel of the tap-off unit has a particular shape for the fixing above a tap-off
outlet.
The cover of the tap-off unit may be opened only when the main circuit breaker is in
the On/Off position.
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

KSB250SM428

Rating
(A)

Type of circuit
breaker

250

NSX 250
Curve N, H or L

Connection

Max. size (mm2)


Flexible
70

NSX

Rigid
150

DB414732.eps

Earthing system arrangement Busbar trunking


Tap-off unit
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker protection)

Cable gland (3)


(not supplied)

Cat. no.

Weight
(kg)

ISO 32 max.

KSB250SM428

13.50

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.

DB414409.eps

DD230164.eps

KSB250SM428

Cable exit
Centre line of tap-off outlets

64

(4) Protruding
(5) 6 modules
(6) 8 modules

160 to 400 A tap-off units


for Compact NSX circuit breaker
Tap-off units for Compact NSX, fixed, front-connected circuit breakers

Earthing system
arrangement

TT-TNS-TNC-IT (1) TNC


TT-TNS-TNS-IT (1) TNC
3L + PEN
3L + N + PE (2)

Busbar trunking
Tap-off unit
DB414732.eps

Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)

DD414762.eps

DD210461.eps

The cover of the tap-off unit may be opened only when the circuit breaker is in the
On/Off position.

KSBpppDCp
Max. size
(mm2)

Cable gland (3) Cat. no.


(not supplied)

NSX

Flexible Rigid
70
70

ISO 32 max.

NSX

150

150

NSX

240

240

Rating Type of circuit


(A)
breaker

Connection

160

NSX 100 or NSX 160


Curve N, H or L
Rotary handle 29338

250

NSX 250
Curve N, H or L
Rotary handle 29338
NSX 400
Curve N, H or L
Rotary handle 32598

400

Cat. no.

Weight
(kg)

KSB160DC4

KSB160DC5

9.00

ISO 40 max.

KSB250DC4

KSB250DC5

12.50

ISO 50 max.

KSB400DC4

KSB400DC5

18.00

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.

DD210462.eps

DD2020081.eps

KSB160DCp

X = 625.5 (KSB160DCp)
X = 726.5 (KSB250DCp)
X = 976.5 (KSB400DCp)
DD210463.eps

KSB250DCp

DD210464.eps

KSB400DCp

Cable exit
Centre line of tap-off outlets

(4) Protruding

65

160 to 400 A tap-off units


for Compact NSX circuit breaker

Commercial numbers
and dimensions

Tap-off units for Compact NSX, fixed, circuit breakers with electrical handle

KSBpppDBp12

Type of circuit
breaker

160

NSX 160
Curve N, H or L
NSX 400
Curve N, H or L

400

DB414732.eps

Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)

Rating
(A)

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit

TNC
TNC
3L + PEN
DD414762.eps

DD413939.eps

Earthing system
arrangement

Max. size
(mm2)

Cable gland (3) Cat. no.


(not supplied)

NSX

Flexible Rigid
70
70

ISO 32 max.

KSB160DB412

KSB160DB512 13.50

NSX

240

ISO 50 max.

KSB400DB412

KSB400DB512 19.00

Connection

240

Cat. no.

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.

532
500

DD413940.eps

DD2020081.eps

KSB160DBp12

73

X = 727.5 (KSB160DBp12)
X = 973.5 (KSB400DBp12)

303
250

532
500

DD413941.eps

KSB400DBp12
732
700

400

732
700

Cable exit
Centre line of tap-off outlets

66

(4) Protruding

Weight
(kg)

160 to 400 A tap-off units


for Compact NSX circuit breaker
Tap-off units for Compact NSX, plug-in, circuit breakers
DD413942.eps

The cover of the tap-off unit may be opened only when the circuit breaker is in the
On/Off position. Tap-off units KSB250DD412 includes 2 opening for type FL21 cable
gland plate (not supplied) (see page 82).
Earthing system
arrangement

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit
DB414732.eps

Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)

KSB160DD411
Rating
(A)

Type of circuit
breaker

160

NSX 160 plug-in


Curve N, H ou L
Rotary handle
NSX 250 plug-in
Curve N, H or L
Motorized handle
NSX 400 plug-in
Curve N, H or L
Rotary handle

250
400

Connection

Max. size
(mm2)

Cable gland (3)


(not supplied)

Cat. no.

Weight
(kg)

NSX

Flexible
70

Rigid
70

ISO 32 max.

KSB160DD411

13.50

NSX

150

150

ISO 40 max.

KSB250DD412

16.00

NSX

240

240

ISO 50 max.

KSB400DD411

20.00

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
KSB250DD412

450

DD413943.eps

632
600

DD413944.eps

DD2020081.eps

KSB160DD411

73

X = 727 (KSB160DD)
X = 877 (KSB250DD)
X = 1073 (KSB400DD)

632
600
106

310

360

360
310

73

450
418

DD413945.eps

KSB400DD411
732
702.5

400

732
702.5

Cable exit
Centre line of tap-off outlets

(4) Protruding

67

160 A tap-off units


for NG modular devices

Commercial numbers
and dimensions

Tap-off units for NG modular devices

Earthing system
arrangement

Busbar trunking
Tap-off unit

DB414732.eps

Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

TNC
TNC
3L + PEN
DD414762.eps

DD202154.eps

The cover of the tap-off unit may be opened only when the circuit breaker is in the
On/Off position.

KSB160SMp13
Rating
(A)

Type of circuit breaker Connection

160

Rotary handle
28060 - NG160

Max. size
(mm2)

Cable gland (3) Cat. no.


(not supplied)

Cat. no.

Weight
(kg)

Flexible Rigid
NG

Rotary handle
19088 - NG125

70

70

ISO 32 max.

KSB160SM413

KSB160SM513 8.50

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.

DD202155.eps

DD2020081.eps

KSB160SMp13

X = 625.5

Cable exit
Centre line of tap-off outlets

68

(4) Protruding

250 A tap-off unit


for Compact NSX circuit
breaker and other devices
Tap-off unit to mount on jointing unit for Compact NSX circuit breakers and other devices
DD230165.eps

Supplied with 2 DIN rails for 25-modules mounting.


The rear panel of the tap-off unit has a particular shape for the fixing above a tap-off
outlet.
The cover of the tap-off unit may be opened only when the main circuit breaker is in
the On/Off position.
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Type of circuit
breaker

250

NSX 250
Curve N, H or L

Connection

Max. size (mm2)


Flexible
70

NSX

Rigid
150

Cable gland (3)


(not supplied)

Cat. no.

Weight
(kg)

ISO 32 max.

KSB250DC4SP

13.50

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
KSB250DC4SP
DD230166.eps

Rating
(A)

DD230167.eps

KSB250DC4SP

DB414732.eps

Earthing system arrangement Busbar trunking


Tap-off unit
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker protection)

Cable exit
Centre line of tap-off outlets

(4) Protruding

69

Tap-off units equipped


withasurge arrester

Commercial numbers
and dimensions

Tap-off units equipped with a surge arrester


Earthing system arrangement Busbar trunking

TT - TNS - TNC

Tap-off polarity
Diagram

3L + N + PE (1)
DD414763.eps

DD205753.eps

Disconnection by unplugging the tap-off unit.

L1 L2 L3 N PE

KSBQPF
Protection Lightning arrester
type
cartridges
(supplied)

Permissible
short-circuit

Cat. no.

Max. discharge
current

Weight
(kg)

Isc (kA)
Imax (kA)
Pre-wired
6
10
KSBQPF
1.3
SPD (Surge Protection Device) installed: Quick PF10 SPD, 3P+N, cat. no. 16618 (Type 2
monoblock surge arrester, with fixed cartridges and integrated disconnection device, certified
IEC 81643-1, EN 61643-11).
(1) Also suitable for tap-off unit 3L + PE (N not distributed).

Fixed

DD511623.eps

Type 2

Connection

(5) Side projection.

Centre line of tap-off outlets

Tap-off units with isolator equipped with a surge arrester


DD205754.eps

Disconnection by opening the tap-off unit cover.


Earthing system
arrangement
Tap-off polarity
Diagram

Busbar trunking

TT - TNS - TNC

DD414763.eps

3L + N + PE (1)

L1 L2 L3 N PE

KSBQPRD

Type 2

Removable

Connection

Permissible
short-circuit

309
357
Centre line of tap-off outlets

70

Cat. no.

Weight
(kg)

Isc (kA)
Imax (kA)
Pre-wired
25
40
KSBQPRD
3.40
Surge arrester installed: Quick PRD40r surge arrester, 3P+N, cat. no. 16294 (Type 2
monoblock surge arrester, with fixed cartridges and integrated disconnection device, certified
IEC 81643-1, EN 61643-11).
(1) Also suitable for tap-off unit 3L + PE (N not distributed).

167

DD202008.eps

X= 432.5

Max. discharge
current

202

Surge arrester
cartridges
(supplied)

DD511624.eps

Protection
type

108
158
(5) Side projection.

32 A tap-off units with power


sockets protected by modular
devices
Tap-off units for power sockets
Earthing system arrangement
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker protection)

KSB32CPppp

Tap-off unit wiring


depends on the
sockets used

Cat. no.

Weight
(kg)

2P + T

KSB32CP11D

2.90

230

2P + T

KSB32CP11F

2.90

Household socket 10/16


NF

230

2P + T

KSB32CP15F

3.00

Industrial socket

415

3P+N+T

Household socket 10/16


Schuko

230

2P + T

KSB32CP15D

3.00

Industrial socket

16

415

3P+N+T

Industrial socket

16

230

2P + T

KSB32CP35

3.10

Industrial socket

16

415

3P+N+T
KSB32CP

2.70

Designation Rating Number of


(A)
18 mm
modules (2)

Equipment
Q. (3) Type

Tap-off
unit with
flushmounted
power
sockets

Household socket 10/16


Schuko

230

Household socket 10/16


NF

Empty
tap-off unit

32

32

TT-TNS-TNC (1)
TT-TNS-TNS (1)
3L + N + PE

Busbar trunking
Tap-off unit
DD414764.eps

DD210456.eps

Disconnection by unplugging the tap-off unit.

Current
(A)

16

Voltage Polarity
(V)

To be equipped

DD210459.eps

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Supplied with blanking plate (1 x 5 divisible).
(3) Quantity.

DD210460.eps

KSB32CPppp

KSB32CP
(4) Protruding

Centre line of tap-off outlets

Power sockets
PG149203.eps

Designation
Industrial sockets
Pratika

Rated current
(A)
16

Rated voltage
(V AC)

Number of poles Dimensions


Cat. no.
(W x H in mm)

200-250

2P + T
3P + N + T
2P + T
3P + N + T
2P + T
3P + N + T
2P + T
3P + N + T
2P + T
2P + T

380-415
32 (5)
PKY16F723

200-250
380-415

Household NF sockets
Household Schuko sockets
Screw-on plate

10 to 16
250
10 to 16
250
For blanking of unused openings
For adapting 65 x 85 mm power-socket bases

65 x 85
90 x 100
65 x 85
90 x 100
90 x 100
90 x 100
90 x 100
90 x 100
65 x 85
65 x 85

PKY16F723
PKY16F725
PKY16F733
PKY16F735
PKY32F723
PKY32F725
PKY32F733
PKY32F735
81140
81141
13137
13136

Weight
(kg)
0.10
0.09

(5) The sum of currents in the 2 sockets installed on the tap-off unit y 32 A.

71

250 and 400 A tap-off units


for measurements
and metering

Commercial numbers
and dimensions

Tap-off units for measurements and metering

Earthing system
arrangement

Busbar trunking
Tap-off unit

DB414732.eps

Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)

KSBpppDCpTRE
Rating
(A)

Type of circuit breaker Connection

250

NSX 250 Type N, H


or L
Rotary handle 29338
NSX 400 Type N, H
or L
Rotary handle 32598

400

TT-TNS-TNC-IT (1) TNC


TT-TNS-TNS-IT (1) TNC
3L + PEN
3L + N + PE (2)
DD414762.eps

DD210465.eps

The cover of the tap-off unit may be opened only when the circuit breaker is in the
On/Off position.

Max. size
(mm2)

Cable gland (3) Cat. no.


(not supplied)

Cat. no.

Flexible Rigid
NSX CT block 150
150

ISO 40 max.

KSB250DC4TRE KSB250DC5TRE 13.50

NSX CT block 240

ISO 50 max.

KSB400DC4TRE KSB400DC5TRE 19.50

240

DD2020081.eps

(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.

DD202085.eps

KSB250DCpTRE

X = 726.5 (KSB250DCpTRE)
X = 976.5 (KSB400DCpTRE)

DD202086.eps

KSB400DCpTRE

Cable exit
Centre line of tap-off outlets

72

Weight
(kg)

(4) Protruding

32 to 160 A tap-off units

Disconnector units
Earthing system
arrangement

Busbar trunking

TT-TNS-TNC-IT (1)

Tap-off

TT-TNS-TNS-IT (1)

TNC

3L + N + PE (2)

3L + PEN

KSB160SM424

Rating
(A)

Number
of 9mm
mod.

Number of
18mm (3)
mod.

160

48

24

Connection

Max. crosssection (mm2)

Cable gland
(4) (not
supplied)

Cat. no.

Cat. no.

Weight
(kg)

Rigid
Not
ISO 50 max. KSB160SM424
KSB160SM524 10.69
used
(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system.
(2) Also suitable for 3L + PE tap-off (N not distributed).
(3) Supplied with blanking plate 1 x 5 divisible (8 modules) or 2 x 5 divisible (12 modules).
(4) Max. diameter for a multipole cable.
Lugs

Flexible
16

DD414765.eps

Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker protection)

TNC

DD414766.eps

DD206222.eps

Disconnection by opening the tap-off unit door.

DD230652.eps

DD230657.eps

KSB160SM424

303

DD230847_r.eps

X = 650

32

395
450
494

177
230
308

Cable outlet
Tap-off outlet axis

73

32 to 100 A tap-off units


cylindrical fuses

Commercial numbers
and dimensions

Tap-off units for cylindrical fuses


DD202010.eps

Disconnection by unplugging the tap-off unit.


Earthing system arrangement

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit
DD414767.eps

Tap-off polarity
Tap-off diagram (e.g. fuse protection)

KSB32CF5
Rating
(A)

For fuses
(not supplied)

Connection

32

NF 10 x 38
Type gG: 25 A max.
Type aM: 32 A max.

Cable clamp terminals

Max. size
(mm2)

Cable gland (3) Cat. no.


(not supplied)

Flexible Rigid
6
10

ISO 32 max.

Weight
(kg)

KSB32CF5

0.60

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.
KSB32CF5
DD202011.eps

Cable exit
Centre line of tap-off outlets
(4) Protruding

Tap-off units with isolator for cylindrical fuses


Earthing system
arrangement

Rating
(A)

For fuses
(not supplied)

Connection

50

NF 14 x 51
Type gG, 50 A max.
Type aM, 50 A max.

Cable clamp
terminals

100

NF 22 x 58
Type gG, 100 A max.
Type aM, 100 A max.

Copper cable
lugs

DD414768.eps

Tap-off polarity
Tap-off diagram (e.g. fuse
protection)

KSBpppSFp

TT-TNS-TNC-IT (1) TNC


TT-TNS-TNS-IT (1) TNC
3L + PEN
3L + N + PE (2)

Busbar trunking
Tap-off unit

DD414769.eps

DD210466.eps

Disconnection by opening the tap-off unit cover.

Max. size
(mm2)

Cable gland (3) Cat. no.


(not supplied)

Flexible Rigid
25
25

ISO 50 max.

50

ISO 63 max.

50

Cat. no.

Weight
(kg)

KSB50SF4

KSB50SF5

2.40

KSB100SF4

KSB100SF5

5.00

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.

DD2020081.eps

DD210467.eps

KSB50SFp, KSB100SFp

X = 432.5 (KSB50SFp)
X = 545.5 (KSB100SFp)

74

Dim.
A
B
C
D
E
F
Cable exit
(4) Protruding
Centre line of tap-off outlets

50 A
356
153
167
309
103
202

100 A
444
178
202
397
128
220

100 to 400 A tap-off units


for NF fuses
Tap-off units with isolator for blade-type fuses
Earthing system
arrangement

Busbar trunking

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC


3L + PEN
3L + N + PE (2)

KSB160SEp
KSB250SEp
KSB400SEp

DD414768.eps

Tap-off polarity
Tap-off diagram
(e.g. fuse protection)

DD414769.eps

DD210472.eps

Disconnection by opening the tap-off unit cover.

Cable gland Cat. no.


(not supplied)

Cat. no.

ISO 63 (3)
max.

KSB100SE4 (5)

KSB100SE5 (5) 5.00

70

ISO 32 (4)
max.

KSB160SE4

KSB160SE5

11.00

70

70

ISO 32 (4)
max.

KSB160SF4

KSB160SF5

11.00

Copper cable
lugs

150

150

ISO 40 (4)
max.

KSB250SE4

KSB250SE5

20.00

Copper cable
lugs

240

240

ISO 50 (4)
max.

KSB400SE4

KSB400SE5

29.20

Rating
(A)

For blade-type
fuses
(not supplied)

Connection

Max. size
(mm2)

100

Size 00
Type gG, 100 A max.
Type aM, 100 A max.

Copper cable
lugs

160

Size 00
Type gG, 160 A max.
Type aM, 160 A max.

Copper cable
lugs

70

Size 0
Type gG, 160 A max.
Type aM, 160 A max.

Copper cable
lugs

250

Size 1
Type gG, 250 A max.
Type aM, 250 A max.

400

Size 2
Type gG, 400 A max.
Type aM, 400 A max.

Flexible Rigid
35
50

Weight
(kg)

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100 A dimensions, see Tap-off units with insulators for cylindrical fuses, page 74,
cat. no. KSB100SFp.

Dim.
A
B
C
D
E
F
G
H

DD210473.eps

DD2020081.eps

KSB160Spp, KSB250SEp

X = 577.5 (KSB160Spp)
X = 777 (KSB250SEp)
X = 855 (KSB400SEp)

Cable exit of KSB160Spp


Cable exit of KSB250SEp

160 A
450
257
300
395
207
032
032
182

250 A
600
308
400
548
258
032
032
192

Centre line of tap-off outlets


(6) Protruding

DD210474.eps

KSB400SEp

Cable exit
Centre line of tap-off outlets

(6) Protruding

75

16 to 63 A tap-off units
for DIN fuses

Commercial numbers
and dimensions

Tap-off units for screw-type fuses


DD202010.eps

Disconnection by unplugging the tap-off unit.


Earthing system
arrangement

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit
DD414767.eps

Tap-off polarity
Tap-off diagram (e.g. fuse
protection)

KSB16CN5
Rating
(A)

For fuses
(not supplied)

Connection

16

Neozed E14

Tunnel terminals

Max. size
(mm2)
Flexible
6

Rigid
10

Cable gland (3)


(not supplied)

Cat. no.

Weight
(kg)

ISO 32 max.

KSB16CN5

0.60

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.
KSB16CN5
DD202295.eps

Cable exit
Centre line of tap-off outlets
(4) Protruding

Tap-off units with isolator for screws-type fuses


Earthing system
arrangement

Rating
(A)

For fuses
(not supplied)

25
50
63

Diazed E27
Neozed E18
Diazed E33

Connection

DD414768.eps

Tap-off polarity
Tap-off diagram
(e.g. fuse protection)

KSBpppSpp

TT-TNS-TNC-IT (1) TNC


TT-TNS-TNS-IT (1) TNC
3L + PEN
3L + N + PE (2)

Busbar trunking
Tap-off unit

Max. size
(mm2)

Flexible
Tunnel terminals 25
Tunnel terminals 25
Tunnel terminals 25

Rigid
25
25
25

DD414769.eps

DD210466.eps

Disconnection by opening the tap-off unit cover.

Cable gland (3) Cat. no.


(not supplied)
ISO 50 max.
ISO 50 max.
ISO 63 max.

KSB25SD4
KSB50SN4
KSB63SD4

Cat. no.

Weight
(kg)

KSB25SD5
KSB50SN5
KSB63SD5

2.40
2.40
2.40

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.

Dim.

DD205037.eps

DD2020081.eps

KSBpppSpp

X = 432.5 (KSB25SDp, KSB50SNp)


X = 545.5 (KSB63SDp)

76

A
B
C
D
E
F
Cable exit
Centre line of tap-off outlets
(4) Protruding

25 and 50 A 63 A
356
153
167
309
103
202

444
178
202
397
128
220

100 to 400 A tap-off units


for DIN fuses
Tap-off units with isolator for blade-type fuses
Earthing system
arrangement

Busbar trunking

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC


3L + PEN
3L + N + PE (2)
DD414768.eps

Tap-off polarity
Tap-off diagram (e.g.
fuse protection)

DD414769.eps

DD210472.eps

Disconnection by opening the tap-off unit cover.

KSB160SEp
KSB250SEp
Cable gland Cat. no.
(not supplied)

Cat. no.

ISO 63 (3)
max.

KSB100SE4 (5)

KSB100SE5 (5) 5.00

70

ISO 32 (4)
max.

KSB160SE4

KSB160SE5

11.00

150

150

ISO 40 (4)
max.

KSB250SE4

KSB250SE5

20.00

240

240

ISO 50 (4)
max.

KSB400SE4

KSB400SE5

29.20

Rating
(A)

For blade-type
fuses
(not supplied)

Connection

Max. size
(mm2)

100

Size 00
Type gG, 100 A max.
Type aM, 100 A max.

Copper cable
lugs

160

Size 00
Type gG, 160 A max.
Type aM, 160 A max.

Copper cable
lugs

70

250

Size 1
Type gG, 250 A max.
Type aM, 250 A max.

Copper cable
lugs

400

Size 2
Type gG, 400 A max.
Type aM, 250 A max.

Copper cable
lugs

Flexible Rigid
35
50

Weight
(kg)

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100 A dimensions, see Tap-off units with insulators for cylindrical fuses, page 74,
cat. no. KSB100SFp.
KSB160SEp, KSB250SEp
DD2020081.eps

DD210473.eps

Dim.
A
B
C
D
E
F
G
H

X = 577.5 (KSB160SEp)
X = 777 (KSB250SEp)
X = 855 (KSB400SEp)

Cable exit of KSB160SEp


Cable exit of KSB250SEp

160 A
450
257
300
395
207
032
032
182

250 A
600
308
400
548
258
032
032
192

Centre line of tap-off outlets


(6) Protruding

DD210474.eps

KSB400SEp

Cable exit
Centre line of tap-off outlets

(6) Protruding

77

20 to 160 A tap-off units


for BS fuses

Commercial numbers
and dimensions

Tap-off units for screw-mounted type fuses


DD202010.eps

Disconnection by unplugging the tap-off unit.


Earthing system
arrangement

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit
DD414767.eps

Tap-off polarity
Tap-off diagram (e.g. fuse
protection)

KSB20CG5
Rating
(A)

For fuses
(not supplied)

20

BS88 A1

Connection
Cable clamp terminals

Max. size (mm2) Cable gland (3)


(not supplied)
Flexible Rigid
6
10
ISO 32 max.

Cat. no.

Weight
(kg)

KSB20CG5

0.60

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.
KSB20CG5
DD202295.eps

Cable exit
Centre line of tap-off outlets
(4) Protruding

Tap-off units with isolator for screw-mounted type fuses


DD202013.eps

Disconnection by opening the tap-off unit cover.


Earthing system
arrangement

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit

DD202014.eps

KSB160SG4

DD414768.eps

Tap-off polarity
Tap-off diagram (e.g. fuse
protection)

Rating
(A)

For fuses
(not supplied)

Connection

32
80

BS88 A1
BS88 A1 ou A3

Cable clamp terminals


Copper cable lugs

Max. size
Flexible or rigid
25
50

160

BS88 B1 ou B2

Copper cable lugs

50

Cable gland
(not supplied)

Cat. no.

Weight
(kg)

ISO 50 max.(3)
ISO 63 max.(3) or
ISO 20 max.(4)
ISO 25 max.(4)

KSB32SG4
KSB80SG4

2.40
5.00

KSB160SG4

11.00

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed).
(3) Maximum diameter for a multipolar cable.
(4) Maximum diameter for a unipolar cable.

DD2020081.eps

DD202267.eps

KSB32SG4, KSB80SG4
KSBppSG4

X = 432.5 (KSB32SG4)
X = 545.5 (KSB80SG4)
X = 577.5 (KSB160SG4)

78

DD202015.eps

KSB160SG4

Dim.
A
B
C
D
E
F

32 A
356
153
167
309
103
202

80 A
444
178
202
397
128
220

Cable exit
Centre line of tap-off outlets
(5) Protruding

125, 250 and 400 A tap-off


units for switch fuse
disconnectors
IP30 tap-off units for fuses
DD230153.eps

Disconnection by unplugging the tap-off unit.


Earthing system
arrangement

DD414767.eps

Tap-off polarity
Tap-off diagram
(e.g. fuse protection)

DD206167.eps

KSB125HD5

Rating
(A)

For fuses (not


supplied)

125

NHL 00 IN U5U5
Type 00
NHL 1 IN U5U5
Type 1
NHL 00 IN U5U5
Type 2

250
KSBppHD502

400

Connection

Cable clamp
terminals
Cable clamp
terminals
Cable clamp
terminals

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit

Max. size
(mm2)

Cable gland (3)


(not supplied)

Cat. no.

Weight
(kg)

Flexible Rigid
50
50

ISO 63 max.

KSA125HD5

2.00

185

185

KSA25HD502

9,00

240

240

KSA40HD502

9,00

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.

DD2020081.eps

DD230155.eps

KSB125HD5

DD230608.eps

X = 622.5 (KSB125HD5)
X = 763 (KSBppHD502)

DD230181.eps

KSBppHD502

Dim.
A

KSA25HD502
42

KSA40HD502
50

Cable exit
Centre line of tap-off outlets

79

630 A tap-off units for fuses

Commercial numbers
and dimensions

Tap-off units with isolator for fuses

Earthing system
arrangement

TT-TNS-TNC-IT (1) TNC


TT-TNS-TNS-IT (1) TNC
3L + PEN
3L + N + PE (2)

Busbar trunking
Tap-off unit
DD414768.eps

Tap-off polarity
Tap-off diagram
(e.g. fuse protection)

DD414769.eps

DD230607.eps

Disconnection by opening the tap-off unit cover.


Assembly on 500 to 1000 A straight components only, supplied with two end covers
and a KSA1000ZJ4 junction block compatible with 800 and 1000 A components.

KSB630SEp
Rating
(A)

For fuses (not


supplied)

630 (4)

Size 3

Connection

Copper cable
lugs

Max. size
(mm2)

Cable gland Cat. no.


(not supplied)

Flexible Rigid
2x240 2x240 ISO 40 (3)
max.

KSB630SE4

Cat. no.

Weight
(kg)

KSB630SE5

59,00

DD2020081.eps

(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a unipolar cable.
(4) Derating coefficient to apply: 0.9.

DD230552.eps

KSB630SEp

X = 1106.5

Centre line of the busbar trunking

80

Canalis KS, 100 to 1000 A

Busbar trunking for medium-power


distribution
250 to 400 A tap-off units for Fupact INF
switch-disconnector fuses
Tap-off units for Fupact INF, fixed, front-connected switch-disconnector fuses
Earthing system
arrangement

TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)

Busbar trunking
Tap-off unit
DB413052.eps

Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)

TNC
TNC
3L + PEN
DB413053.eps

DB413054.eps

The cover of the tap-off unit may be opened only when the INF is in the Off position.

KSB pppSDFp
Rating
(A)

Type of Fupact
(not supplied)

160

INFD160 or INFB250
with extended rotary
handle
INFD 250 or INFB 250
with extended rotary
handle 49619
INFD 400 or INFB 400
with extended rotary
handle LV480540

250
400

Connection

Max. size
(mm2)

Cable gland
(3)

Cat. no.

Cat. no.

Weight
(kg)

(not supplied)

INF

Flexible Rigid
70
70

ISO 32 max.

KSB160SDF4

KSB160SDF5

9,00

INF

70

150

ISO 32 max.

KSB250SDF4

KSB250SDF5

12.50

INF

150

240

ISO 40 max.

KSB400SDF4

KSB400SDF5

18.00

(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.

KSB250SDFp
DB413055.eps

X = 577.5 (KSB160SDFp)
X = 726.5 (KSB250SDFp)
X = 976.5 (KSB400SDFp)

KSB400SDFp
DB413056.eps

DD202008.eps

DB414227.eps

KSB160SDFp

Cable exit
Centre line of tap-off outlets

(4) Protruding.

81

Commercial numbers
and dimensions

Accessories for tap-off units

For all tap-off units for modular devices


Designation
Modular blanking plat
Adhesive label (1)

Description
Divisible set of 10 x 5
Set of 12 label-holders (H = 24 mm - L = 180 mm)
Set of 12 labels-holders (H = 24 mm - L = 432 mm)
Set of 12 divisible labels-holders (H = 24 mm - L = 650 mm)

Cat. no.
unitaire

Weight
(kg)

13940
08905
08903
08907

0.08
0.50
0.50
0.50

(1) Self-adhevise support complete with transparent cover and paper label.

For sheet-metal tap-off units


DB414462.eps

Designation
Cover contact
(break before opening)

For tap-off unit


KSB100Sp to KSB400Sp

Order in multiple of

Cat. no.

Weight
(kg)

KSB400ZC1

0.03

FL21 gland plates


Designation
For tap-off units

Rating
(A)
160

250

400

82

Cat. no. of
tap-off units

No. of holes of the


gland plates

KSB160SFp
KSB160DCp
KSB160DDp
KSB250SFp
KSB250DCp
KSB250DDp
KSB400SFp
KSB400DCp
KSB400DDp

1
1
1
1
1
1
2
2
2

Cat. no.
KSB160SFZFL21

KSB250DCZFL21

KSB400DCZFL21

Weight
(kg)
0.20
0.20
0.20
0.30
0.30
0.30
0.40
0.40
0.40

Canalis KS

Characteristics
Contents

Index of commercial numbers


4
Presentation 8
Straights components
15
Feed units and end covers
47
Tap-off units
55

Simplified design guide forpower distribution

84

Electrical characteristics

88

Technical specifications

90

Harmonic currents

92

Direct current

94

Frequencies

96

Fire resistance

97

How Canalis compensate for thermal expansion

98

Power distribution via Canalis


Determining the degree of protection
From 100 to 1000 A
Horizontal trunking
Rising mains

400 Hz

84
86

88
90
91

96

Sprinkler test certification

101

Measurements and metering

103

Trunking protection

104

Circuit breaker/trunking coordination

107

Canalis part of StruxureWare


Overload protection
Short-circuit protection

Non-limiting or time-delayed circuit breakers


Limiting circuit breakers

103
104
106
107
108

BTS protection by Compact NSX limiting circuit breakers 109


Selection guide

110

Maintenance recommendations for your installation

112

83

Design guide

Simplified design guide


forpower distribution
Power distribution via Canalis

Except for the most extreme environments, there is no


reason to hesitate. Canalis can be installed
everywhere.

The procedure presented below describes the steps in creating a simple installation.
For a detailed design study, it is necessary to use the suitable tools, approved by
certification organisations and in compliance with local installation standards.
Ecodial software, published by Schneider Electric, is perfectly suited to the task.

Procedure
1
2
3
4

Identify external influences.


Layout the Canalis structure in the building according to the load locations.
Carry out a power sum.
Size the busbar trunking.

1 - Identify external influences


The ambient temperature, the presence of dust or condensation, etc. are all factors
in defining the degree of protection for the room containing the electrical installation.
Canalis prefabricated busbar trunking provides an IP55 degree of protection for
indoor installations and can be installed on virtually all sites.
b Examples:
v mechanical workshops: IP32
v warehouses: IP30
v poultry farms: IP35
v greenhouses: IP23
v ...

DD210067.eps

22 - Layout of Canalis busbar trunking

Layout of the distribution lines depends on load and source locations as well as
trunking fixing possibilities.
b A single distribution line can supply a zone four to six metres long.
b Load protection is located in the tap-off units, as close as possible to the loads.
b A single Canalis feeder can supply a set of loads with different power ratings.

DD414770.eps

33 - Power sum

Once the busbar trunking has been laid out, calculate the currents drawn by the
Canalis lines.
Calculation of the total operational current drawn by the line
(In) is equal to the sum of the currents drawn by the loads (Ib): In = Ib.
The loads do not all operate at the same time or continuously at full rated load, i.e. it
is necessary to calculate the diversity coefficient (KS): In = (Ib x KS).
Diversity coefficient as a function of the number of loads
Application
Lighting, heating
Distribution
(Mechanical workshop)

Number of loads
KS coefficient
1
2...3
0.9
4...5
0.8
6...9
0.7
10...40
0.6
40 or more
0.5
Caution. For industrial installations, remember to allow for changes in types and numbers of
machines. Similar to a switchboard, a margin of 20 % is recommended: In = Ib x KS x 1.2.

Selection of busbar trunking rating as a function of the operational current total In


Operational current total In (A)
0...40
40...63
63...100
100...160
160...250
250...400
400...500
500...630
630...800
800...1000

84

Busbar trunking
KNA40
KNA63
KNA100 or KSA100
KNA160 or KSA160
KSA250
KSA400
KSA500
KSA630
KSA800
KSA1000

4 - Sizing the busbar trunking

Overload criterion
Ambient temperature
Canalis busbar trunking is sized for an ambient temperature of 35 C. For higher
temperatures, the trunking must be derated as per the data in the tables on the
technical characteristics.
Example: Canalis 400 A KSA at 45 C: In = 400 x 0.94 = 376 A.
Installation method
Canalis KN and KS trunking is designed to be installed edgewise.
In certain cases, it can also be installed flat (false floors) or vertically (KS rising
mains).
These installation methods do not require derating for the KN and KS trunking.
Protection against trunking overloads
To enable future extensions, protection for prefabricated busbar trunking is generally
sized for the rated current Inc (or the permissible current Iz if coefficient K1 is applied
as a function of the ambient temperature).
b Protection using gG (gI) flues:
v determine the standardised rated current In of the fuse such that In y Inc/1,1
(K1=1,1 for the fuses)
v select the standardised rating In equal to that value or just below.
Check that In u (Ib x KS). If that is not the case, select the busbar trunking with the
next highest rating.
Note: Protection using gI fuses results in a reduction of the permissible current in the trunking.

b Circuit-breaker protection: select the setting current Ir for the circuit breaker such
that (Ib x KS) y Ir y Inc.
Note: Circuit-breaker protection means Canalis busbar trunking can be used to the full rated
load.

Voltage-drop criterion

The voltage drop between the head and any other point in the installation must not
exceed the values in the table below:
Installation supplied by a distribution network
LV public system
High voltage

Lighting
3%
6%

Other application
5%
8%

For Canalis, voltage drops are indicated in V/100 m/A in the Characteristics
section.
U = (Ib x KS) x L / 100

Short-circuit current criterion

For typical applications with power ratings up to 630 kVA, a Schneider Electric
solution including the low-voltage electrical switchboard, circuit breakers and
Canalis busbar trunking ensures an installation sized to handle all short-circuit levels
encountered.
To check the configuration of your installation (Isc up to 150 kA), refer to the
coordination tables on pages 110 and 111.
We also invite you to discover Ecodial, our complete design software for low-voltage
installations (selection of circuit breakers and cables, calculation of breaking
capacities, short-circuit currents and voltage drops, etc.), available from your
Schneider Electric representative.

85

Design guide

Simplified design guide

Determining the degree of protection

Standard IEC 60364-5-51 categorises a large number of external influences to which


electrical installations can be subjected, for instance the presence of water, solid
objects, shocks, vibrations and corrosive substances.
The importance of these influences depends on the installation conditions.
Forexample, the presence of water can vary from a few drops to total immersion.

Degree of protection IP

Standard IEC 60529 (February 2001) indicates the degree of protection provided by
electrical equipment enclosures against accidental direct contact with live parts and
against the ingress of solid foreign objects or water.
This standard does not apply to protection against the risk of explosion or conditions
such as humidity, corrosive gases, fungi or vermin.
The IP code comprises 2 characteristic numerals and may include an additional letter
when the actual protection of persons against direct contact with live parts is better
than that indicated by the first numeral.
The first numeral characterises the protection of the equipment against penetration
of solid objects and the protection of people.
The second numeral characterises the protection of the equipment against
penetration of water with harmful effects.

Remarks concerning the degree of protection IP


b The degree of protection IP must always be read and understood numeral by
numeral and not as a whole.
For example, an IP31 enclosure is suitable for an environment that requires a
minimum degree of protection IP21. However an IP30 wall-mount enclosure is not
suitable.
b The degrees of protection indicated in this catalogue are valid for the enclosures
as presented. However, the indicated degree of protection is guaranteed only when
the installation and device mounting are carried out in accordance with professional
standard practice.

Additional letter
Protection of persons against direct contact with live parts.
The additional letter is used only if the actual protection of persons is higher than that
indicated by the first characteristic numeral of the IP code.
If only the protection of persons is of interest, the two characteristic numerals are
replaced by the letter X, e.g. IPXXB.

Degree of protection IK

Standard IEC 62262 defines a coding system (IK code) indicating the degree of
protection provided by electrical equipment enclosures against external mechanical
impact.
Installation standard IEC 60364 provides a cross-reference between the various
degrees of protection and the environmental conditions classification, relating to the
selection of equipment according to external factors.

IKpp code
The IK code comprises 2 characteristic numerals (e.g. IK05).
Practical guide UTE C 15-103 shows, in the form of tables, the characteristics
required for electrical equipment (including minimum degrees of protection),
according to the locations in which they are installed.

86

Meaning of the numerals and letters representing the degree of protection IP.

Protected against direct


contact with a 1 mm diameter
wire.

5
6

Protected against rain at an


angle of up to 60.
Protected against splashing
water in all directions.
Protected against water jets
in all directions.

Protected against powerful


jets of water and waves.

Protected against the effects


of temporary immersion.

Protected against the effects


of prolonged immersion
under specified conditions.

Additional letter
Corresponds to protection of persons against direct contact
with live parts.

3
4
5

DB414739.eps
DB414740.eps
DB414741.eps

DB414742.eps

Protected against dripping


water at an angle of up to
15.

DB414743.eps

Protected against direct


contact with a 1 mm diameter
wire.

DB414744.eps

Protected against direct


contact with a 1 mm diameter
wire.

Protected against vertical


dripping water
(condensation).

DB414745.eps

Dust tight.

Protected against direct


contact
with a 2.5 mm diameter tool.

DB414733.eps

Protected against direct


finger contact.

DB414734.eps

Protected against the


penetration of solid objects
having a diameter greater than
or equal to 12.5 mm.
Protected against the
penetration of solid objects
having a diameter greater than
or equal to 2.5 mm.
Protected against the
penetration of solid objects
having a diameter greater than
1 mm.
Dust protected
(no harmful deposits).

DB414735.eps

Protected against direct


contact with the back of the
hand (accidental contact).

DB414736.eps

Protected against the


penetration of solid objects
having a diameter greater than
or equal to 50 mm.

Non-protected

DB414737.eps

Non-protected

DB414738.eps

Non-protected

2nd characteristic numeral: corresponds to


protection of equipment against penetration of
water with harmful effects.
Protection of equipment

DB414746.eps

1st characteristic numeral: corresponds to protection of equipment against


penetration of solid objects and protection of persons against direct contact with live
parts.
Protection of equipment
Protection of persons

With the back of the hand.

A
B
C
D

With the finger.


With a 2.5 mm diameter tool.
With a 1.0 mm diameter tool.

Degrees of protection IK against mechanical impact


Weight
(kg)

DD210130.eps

DD210533.eps

The IK code comprises 2 characteristic numerals corresponding


to a value of impact energy, in joules.

00
01
02
03
04
05
06
07
08
09
10

Height
(cm)

Energy
(J)

7.50

0.15

10

0.20

17.50

0.35

25

0.50

Non-protected
0.20

35

0.70

0.50

20

40

1.70

30

20

10

40

20

The Canalis KN and KS busbar trunking products


are designed to provide IP55D and IK08 protection.

87

Electrical characteristics

Electrical characteristics
From 100 to 1000 A
IP55
Ue = 230690 V

Run component characteristics


Rating of trunking (A)

KS

100

250

400

500

630

800

1000

IP
IK
Inc
Ui
Ue
Uimp
f

A
V
V
kV
Hz

IEC/EN 61439-6
55
55
08
08
100
160
690
690
690
690
8
8
50/60 50/60

55
08
250
690
690
8
50/60

55
08
400
690
690
8
50/60

55
08
500
690
690
8
50/60

55
08
630
690
690
8
50/60

55
08
800
690
690
8
50/60

55
08
1000
690
690
8
50/60

R20
R1
X1
Z1

m/m
m/m
m/m
m/m

1.19
1.59
0.15
1.6

0.55
0.77
0.15
0.79

0.28
0.39
0.16
0.42

0.15
0.21
0.14
0.25

0.11
0.15
0.07
0.16

0.09
0.13
0.07
0.15

0.06
0.09
0.06
0.11

0.04
0.06
0.06
0.09

m/m
mm

0.42
4

0.42
4

0.35
22

0.19
50

0.07
222

0.07
222

0.07
222

0.06
252

R0 ph/N
X0 ph/N
Z0 ph/N
R0 ph/PE
X0 ph/PE
Z0 ph/PE
Rb0 ph/ph
Rb0 ph/N
Rb0 ph/PE
Rb1 ph/ph
Rb1 ph/N
Rb1 ph/PE
Xb ph/ph
Xb ph/N
Xb ph/PE

m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m

4.85
0.95
4.94
2.75
1.11
2.96
2.4
2.44
1.87
3.19
3.21
2.38
0.31
0.45
0.58

2.32
0.95
2.5
2.01
0.93
2.22
1.15
1.21
1.3
1.55
1.57
1.46
0.31
0.45
0.42

1.28
0.86
1.54
1.34
0.7
1.51
0.65
0.74
0.78
0.78
0.82
0.91
0.32
0.45
0.42

0.74
0.67
1
0.88
0.67
1.11
0.41
0.51
0.55
0.57
0.7
0.76
0.28
0.39
0.39

0.5
0.36
0.62
0.4
0.48
0.63
0.25
0.3
0.31
0.35
0.41
0.43
0.14
0.2
0.24

0.45
0.35
0.57
0.51
0.55
0.75
0.23
0.28
0.3
0.32
0.39
0.41
0.14
0.2
0.24

0.32
0.31
0.45
0.35
0.43
0.56
0.18
0.23
0.28
0.25
0.32
0.39
0.13
0.18
0.23

0.23
0.27
0.36
0.32
0.4
0.51
0.15
0.2
0.26
0.21
0.28
0.37
0.12
017
0.22

Ipk

kA
106 A2s
kA

15.7
6.8
2.6

22
20.2
4.45

28
100
10

49.2
354
18.8

55
733
26.2

67.5
1225
32.1

78.7
1758
37.4

78.7
1758
37.4

General characteristics
Compliance with standards
Degree of protection:
Mechanical impacts
Rated current at an ambient temperature of 35 C
Rated insulation voltage
Rated operational voltage
Rated impulse voltage
Rated frequency

Conductor characteristics

Phase conductors
Mean resistance at an ambient temperature of 20 C
Mean resistance at Inc and 35 C
Mean reactance at Inc, 35 C and 50 Hz
Mean impedance at Inc, 35 C and 50 Hz
Protective conductor (PE)
Mean resistance at an ambient temperature of 20 C
Copper cross-section

Fault loop characteristics

Symmetrical
components
method

Ph/N
at 20 C
Ph/PE
at 20 C

Impedance
method

At 20 C

For Inc at 35 C

For Inc at 35 C
and 50 Hz

Other characteristics

Mean resistance
Mean reactance
Mean impedance
Mean resistance
Mean reactance
Mean impedance
Mean
Ph/Ph
resistance
Ph/N
Ph/PE
Mean
Ph/Ph
resistance
Ph/N
Ph/PE
Mean
Ph/Ph
reactance
Ph/N
Ph/PE

Short-circuit withstand capacity


Rated peak withstand current
Maximum thermal limit I2t (t = 1 s)
Rated short-time withstand current (t = 1 s)
Voltage drop

For a power factor of

Icw

160

Composite voltage drop (hot state) expressed in V/100 m/A (50 Hz) with the load
uniformly distributed over the run. If the load is concentrated at one end of the run,
the voltage drop is twice the value indicated in the table.
1
V/100 m/A 0.138 0.067 0.034 0.018 0.013 0.011
0.008 0.005
0.9
V/100 m/A 0.130 0.066 0.036 0.022 0.014 0.013 0.009 0.007
0.8
V/100 m/A 0.118
0.061 0.035 0.022 0.014 0.013 0.009 0.007
0.7
V/100 m/A 0.106 0.056 0.034 0.021 0.013 0.012 0.009 0.008
This calculation table applies to the three-phase system.
To obtain the single-phase voltage drop, the three-phase voltage drop shown above is divided by
1.732.

Radiated magnetic field


Radiated magnetic field strength 1 metre from the trunking
B
0.22
0.41
T
Product selection when harmonics are present (for details, see the Special Applications section)
THD y 15 %
100
160
Operational current as a function of 3rd harmonic content
15 % < THD y 33 %
80
125
THD > 33 %
63
100
Permissible current as a function of ambient temperature
Ambient temperature
C
< 35
35
Cfficient K1
%
n/a
1

88

0.69

1.00

0.66

0.89

1.12

1.27

250
200
160

400
315
250

500
400
315

630
500
400

800
630
500

1000
800
630

40
0.97

45
0.94

50
0.91

55
0.87

Tap-off unit characteristics


General characteristics
Degree of protection
Mechanical impacts
Rated insulation voltage (1)
Rated operational voltage (1)
Rated impulse voltage
Rated frequency
(1) For 690 V, please see your sales office.

IP
IK
Ui
Ue
Uimp
f

V
V
kV
Hz

55
08
400, 500 depending on protective device
400, 500 depending on protective device
6.8
50/60

Radiated electromagnetic fields

Magnetic induction generated by KSA

100

10

1
B(T)

DB414131.eps

According to the WHO (World Health Organisation), exposure to radiated


electromagnetic fields above 0.2 micro Tesla can be dangerous causing a risk of
cancer over the long term. Some countries have standardised the limit: Sweden =
0.2 T, at a distance of 1 metre.
All electrical conductors generate a magnetic field, the strength of which is
proportional to the distance between them. The Canalis busbar trunking concept
(metal casing and conductors near together) helps to considerably reduce radiated
electromagnetic fields.
In specific cases where particularly low values are required (computer rooms,
hospitals, some offices), it is important to keep in mind the following:
bb the induction generated around 3-phase distribution. This is proportional to the
current and the distance between the conductors, and inversely proportional to the
square of the distance with respect to the busbar trunking and the screening effect of
the case
bb the induction generated around busbar trunking. This is less than the induction
generated around an equivalent cable distribution
bb Canalis steel casing. This attenuates the induction more than an equivalent
aluminium casing of the same thickness (screening effect)
bb the induction generated around busbar trunking with sandwiched bars. This is
particularly low because of the short distance between the bars and the additional
attenuation provided by the steel casing.

0,1

0,01

0,001

10

100
1000
Distance from the busbar (mm)

10000

KSA100
KSA160
KSA250
KSA400
KSA500
KSA630
KSA800
KSA1000

89

Specifications

Technical specifications

PD202340.eps

Horizontal trunking

Complies with standards IEC 61439-6.


Complies with sprinkler tests, guaranteeing operation under vertically and
horizontally sprayed water for 50 minutes.
Degree of protection: IP55.
Number of live conductors: 4.
Rated insulation voltage: 690 V.
Rated current (Inc): 100 A, 160 A, 250 A, 400 A, 500 A, 630 A, 800 A and 1000 A.
The cross-sectional area of the protective conductor is at least 50 % that of the
phases.

Fire resistance:
b fire barriers as per standard ISO 834 (DIN 4102-part 9) for passages through
partitions.
b resistant to flame propagation in compliance with standard IEC 60332 - part 3.
b materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
All plastic components are halogen free.
b The enclosure (1), made of sheet steel, galvanised and pre-lacquered RAL 9001
white.
b The four aluminium conductors are mounted on fibreglass reinforced polyester
insulators. All electrical contacts are made of silver-plated copper.
b The straight lengths have a tap-off unit (2) every metre on both sides.
The tap-off outlets are equipped with automatic shutters that avoid accidental contact
with live parts. The protective conductor is electrically connected to the enclosure at
each jointing unit.
b Electrical contact between two components is ensured by flexible contacts
designed to adapt to the difference in expansion between the conductors and the enclosure.
It is possible to check visually that the electrical contact is effective.
The mechanical junction between two components is ensured by four captive screws.
The jointing unit (3) is maintenance free.
b The rigidity of the straight lengths is sufficient that fixing points (4) are required only
every three metres (excepting special conditions).
b Special components (5) are available to change direction or avoid obstacles.
b The tap-off units (6) have the following characteristics:
v connection and disconnection are possible only with the cover open
v the contact of the protective conductor ensures automatic opening of the shutters
and feeds the tap-off unit
v there is no access to live parts when the cover of the tap-off unit is open
(no finger access, IPxxD)
v when the tap-off unit is plugged in, the earthing contact connects first, followed by
the phases
v it is not possible to close the cover before the tap-off unit is mechanically locked on
the trunking, tap-off units can be equipped with fuses, modular devices or moulded
case circuit breakers.

90

PD202341_r.eps

Rising mains

Complies with standards IEC 61439-2.


Complies with sprinkler tests, guaranteeing operation under vertically and
horizontally sprayed water for 50 minutes.
Degree of protection: IP55.
Number of live conductors: 4.
Rated insulation voltage: 690 V.
Rated current (Inc): 100 A, 250 A, 400 A, 500 A, 630 A, 800 A and 1000 A.
The cross-sectional area of the protective conductor is at least 50 % that of the
phases.

Fire resistance:
b fire barriers as per standard ISO 834 (DIN 4102-part 9) for passages through
partitions (slabs for exemple).
b resistant to flame propagation in compliance with standard IEC 60332 - part 3.
b materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
All plastic components are halogen free.
b The enclosure (1), made of sheet steel, galvanised and pre-lacquered RAL 9001
white.
b The four aluminium conductors are mounted on fibreglass reinforced polyester
insulators. All electrical contacts are made of silver-plated copper.
b The straight lengths have a tap-off unit (2) every 0.5 metre on one side. There are
four tap-off units per floor for floor heights between 3.5 and 4.8 metres, or three
tap-off units per floor for floor heights less than 3.5 metres. The tap-off outlets are
equipped with automatic shutters that avoid accidental contact with live parts.
The protective conductor is electrically connected to the enclosure at each jointing
unit.
b Electrical contact between two components is ensured by flexible contacts
designed to adapt to the difference in expansion between the conductors and the
enclosure. It is possible to check visually that the electrical contact is effective.
The mechanical junction between two components is ensured by four captive screws.
The jointing unit (3) is maintenance free.
b A fire barrier (4) can be installed when the riser passes through a slab to avoid any
risk of fire propagation from one floor to another.
Two-hour fire resistance (A120) is provided in compliance with standard ISO834
(DIN 41-2-part 9).
b Special components (5) are available to change direction or avoid obstacles.
b The riser can be maintained by a special bottom support (6) or a spring-based
fixing device on each floor of the building (depending on the height of the building).
b The tap-off units (7) have the following characteristics:
v connection and disconnection are possible only with the cover open
v the contact of the protective conductor ensures automatic opening of the shutters
and feeds the tap-off unit
v there is no access to live parts when the cover of the tap-off unit is open
(no finger access, IPxxD)
v when the tap-off unit is plugged in, the earthing contact connects first, followed by
the phases
v it is not possible to close the cover before the tap-off unit is mechanically locked on
the trunking, tap-off units can be equipped with modular devices or moulded case
circuit breakers.

91

Harmonic currents

Recommendations
for special applications

Origin of harmonic currents


Harmonic currents are caused by non-linear loads connected to distribution systems,
i.e. by loads that draw current with a waveform different that that of the voltage that
supplies them.
The most common non-linear loads are equipment including rectifiers, fluorescent
lighting and computer hardware.
In installations with a distributed neutral, non-linear loads may cause significant
overloads in the neutral conductor due to the presence of third-order harmonics.
DD210679.eps

Harmonic order
The order is the ratio
between the harmonic
frequency fn and the
fundamental frequency
(generally the power
frequency, 50 or 60 Hz):
n = fn / f1
By definition, the
fundamental f1 is order 1
(H1).
Third-order harmonics
(H3) have a frequency of
150 Hz (when f1 = 50 Hz).

Estimating THD (total harmonic distortion)


The presence of third-order harmonics depends on the applications involved.
It is necessary to carry out an in-depth study on each non-linear load to determine
the level of H3:
ih3 (%) = 100 x i3 / i1
b i3 = rms current of H3
b i1 = rms current of the fundamental
Assuming that H3 is preponderant among harmonics, the THD is close to the value
of H3: ih3 (%).

92

PD202029_r.eps

PD202028_r.eps

There are two decisive factors:


b the types of connected devices:
v disturbing loads: fluorescent lighting, computer hardware, rectifiers, arc furnaces,
etc.
v non-disturbing loads: heating, motors, pumps, etc.
b the ratio between the two types of disturbing loads.

Workshops
Mix of disturbing loads (computers,
UPSs, fluorescent lighting) and
non-disturbing loads (motors, pumps,
heating).

Offices
Numerous disturbing loads (computers,
UPSs, fluorescent lighting).

Low probability of harmonics


THD y 15 %.

High probability of harmonics


15 % < THD y 33 %.

Effects of harmonics on Canalis busbar trunking


DD206181.eps

Fundamental frequency: ih1 (50 Hz)


No current in the neutral.
The conductors are correctly sized.

DD210680.eps

Fundamental frequency: ih1 (50 Hz) and 33 % of H3


Abnormal temperature rise in the conductors caused by
current at a higher frequency in the phases (skin effect)
and current in the neutral caused by summing of the H3
harmonics.

DD210682.eps

DD210680.eps

Fundamental frequency:
ih1 (50 Hz) and
33 % H3

DD210683.eps

The only effective solution

Reduce the current density


in ALL conductors by
using appropriately sized
trunking.

Busbar-trunking selection
THD y 15 %
25
40

15 % < THD y 33 %
20
32

THD > 33 %
16
25

Busbar trunking Rating (A)


KBA / KBB
25
KBA / KBB
40
KN
40
63
50
40
KN
63
100
80
63
KN
100
KS
100
160
125
100
KS
160
250
200
160
KS
250
400
315
250
KS
400
500
400
315
KS
500
630
500
400
KS
630
800
630
500
KS
800
1000
800
630
KS
1000
Example. For a total rms current of 376 A, (estimation based on power drawn by loads, including
harmonics), the operational current is 400 A.
THD is estimated at 30 %. The appropriate trunking is KS 500 A.

For more information on harmonics


See the Cahier Technique publications on the Schneider Electric web site:
www.schneider-electric.com

93

Recommendations
for special applications

Direct current

Determining the DC current value

Thermal effect

Rule
The total power dissipated as heat must remain constant in the duct:
Pac = Pdc
Where:
bb the power dissipated as heat: Pac = 3 x R x Iac where:
vv R= resistance of a conductor
vv Iac = conductor rms current
bb the dissipated power for 4 conductors: Pdc = 4 x R x Idc where:
vv Idc = direct current.

Selection table

bb 1 source
Case of 2 conductors in parallel for the + and 2 conductor in parallel for the (only
1 circuit in the busbar trunking):

DD210893.eps

Idc = 1,732 x Iac

DD210894.eps

bb 2 sources
Case of 1 conductor for the + and 1 conductor for the (2 circuits possible in the
same busbar trunking):
Idc = 0,866 x Iac

Rating (A)
100
160
250
400
500
630
800
1000

94

1 source
173
277
433
693
866
1091
1386
1732

2 sources
87
139
217
346
433
546
693
866

Protection

With DC, there is no zero crossing point of the voltage and current to facilitate arc
extinction in the protective device.
The arcing time is longer and the energy that has to be absorbed is higher than for
AC.
The voltage of the DC arc must rise to the source voltage very quickly in order to
"put out" the short-circuit current.
"Shortened" electrical equation: U network = R x Isc + Uarc where:
bb Isc = U network - Uarc / R
bb Isc = 0 when Uarc = U network.

Use with specific switchgear

A quick rise in arcing voltage can be achieved by using series fuses, one fuse on
the + and one fuse on the of each circuit.
For some current rating and fuse characteristics, the placing of two fuses in series
on each polarity may be specified (highly inductive circuit).
In some cases, two fuses must be placed in parallel for each polarity.

95

Recommendations
for special applications

Frequencies

KS busbar trunking derating at 400 Hz

Values at 35 C.
Application of a derating coefficient at 400 Hz combined with that for temperature
derating.

400 Hz

Busbar trunking derating at 400 Hz


KSA100 KSA160 KSA250 KSA400 KSA500 KSA630 KSA800 KSA1000

Voltage drop

In (A)

92

146

221

342

403

514

621

745

Coefficient K at
400 Hz

0.92

0.91

0.88

0.85

0.81

0.82

0.78

0.74

3-phase voltage drop, in millivolts per metre and per amp 400 Hz with load spread
over the run.
For a concentration of load at the end of a run (transport), the voltage drops are
double those shown in the table below.
Voltage drop when frequency is 400 Hz in millivolts per meter and per ampere
KSA100 KSA160 KSA250 KSA400 KSA500 KSA630 KSA800 KSA1000

Conductor characteristics

Cos = 1.0

0.992

0.641

0.550

0.388

0.225

0.226

0.201

0.160

Cos = 0.9

0.975

0.627

0.546

0.388

0.223

0.225

0.200

0.159

Cos = 0.8

0.968

0.622

0.545

0.387

0.222

0.224

0.200

0.159

Conductor impedance at 400 Hz


KSA100 KSA160 KSA250 KSA400 KSA500 KSA630 KSA800 KSA1000

96

Average ohmic
1.564
resistance of
phase and neutral
conductors at In
Rb1ph (m/m)

0.687

0.320

0.249

0.120

0.118

0.113

0.110

Average
resistance at In
Xph (m/m)

1.207

1.264

0.942

0.535

0.551

0.506

0.405

1.203

Fire resistance

As required by standards, busbar trunking complies with:


1 - material resistance to abnormal temperatures,
2 - flame propagation resistance,
3 - fire barrier function when going through a partition wall,
4 - conservation of all circuits for 1h30 in an insulating sheath.

Definition of tests

1 - Insulating material resistance test to abnormal


temperatures
Objective
To check a material will not be suspected as being the origin of a secondary fire
outbreak.
As defined in standards 9.2 IEC 61439-6 and IEC 60695-2-10 and 2-13.
Method
Application of an incandescent wire for 30 seconds on the insulating materials in
contact with live parts.
Result criteria
The specimen is considered to have passed the incandescent wire test if:
bb if there is no visible flame and no sustained incandescence
bb the specimens flames and incandescence go out within 30 seconds of the
incandescent wire being removed.

2 - Flame propagation resistance test


Objective
To check a busbar trunking will not create secondary fire outbreaks.
As defined in standards 9.101 IEC 61439-6 and IEC 60332 part 3.
Method
bb Application of a flame for 40 minutes on a straight length of busbar trunking
whose centre is located 2.5 metres from the edge of the burner.
Result criteria
The specimen is considered to have passed the test if:
bb combustion does not occur
bb the maximum extent of the burned part (external and internal) of the busbar
trunking does not go beyond 2.5 metres above the lower edge of the burner.

3 - Fire barrier test through a partition wall

Objective
To check a busbar trunking will not propagate a fire from one room to another by
crossing a fire barrier wall for 60, 120, 180, or 240 minutes.
As defined in standard EN 1366-3; EN 1363-1; ISO 834; DIN 4102 part 9.
Method
The fire barrier busbar trunking section to be tested is placed in an oven which
executes a standardised temperature-time curve.
Result criteria
The specimen is considered to have passed the test if:
bb there are no flames behind the fire barrier
bb there is no smoke or gas behind the fire barrier (not requested by the standard;
can appear as a remark in the test report)
bb the temperature rise of the casing behind the fire barrier does not exceed 180 C.

4 - Conservation of all circuits in fire conditions test

Objective
To check all the busbar trunkings electrical circuits are preserved in fire conditions.
As defined in standard DIN 4102 part 12.
Method
Its entire length inserted, the busbar trunking is taken as a specimen in an
insulating sheath.
Result criteria
The specimen is considered to have passed the test if:
bb conductor continuity is preserved
bb there is no short-circuit between conductors.
97

Recommendations
for special applications

How Canalis compensate


for thermal expansion

Foreword
Prefabricated electrical trunking components expand and contract due to:
b changes in ambient temperature (e.g. summer and winter)
b current flowing in the conductors (e.g. 0 to In)
For example, consider a 30 metre long 800 A Canalis KS line equipped with ten
160 A tap-off units and installed under the roof of a building where the ambient
temperature varies by more than 30 C between summer and winter:
b just the change in the ambient temperature results in an expansion of 20 mm for
the conductors and the 10 mm for the casing
b at a constant ambient temperature, the temperature rise in the conductors every
morning when the installation is started (increase in current from 0 to In = 800 A)
results in an expansion of 55 mm for the conductors and 7 mm for the casing.

PD202309_r.eps

The lengths of the sheet steel (1) and the aluminium conductors (2) therefore vary as
a function of the changes in temperature and their specific thermal expansion
coefficients.

For this reason, Canalis components are designed so that these phenomena do not
affect their installation or operation.

How Canalis trunking components effectively compensate for the effects of conductor thermal expansion

DD202281.eps

Inside a trunking section, the conductors are fixed (1) at a single point in the casing
and, due to the change in temperature, expand (V) on either side of that point.
The zones affected by expansion and considered critical from the electrical
standpoint are the jointing system (2) and tap-off outlets (3).

98

How Canalis trunking components effectively compensate for the effects of conductor thermal expansion

DD202282.eps

b The Canalis jointing system mechanically and electrically connects components


(e.g. two straight lengths), but allows for the expansion and contraction of the
conductors (4).
The system is made up of springs (1) and an area of sliding contacts (2) that allow
conductor movement (
) while maintaining outstanding electrical contact.
Contact quality is ensured by two parts made of silver-plated copper (3). Sufficient
pressure between the two parts for good contact is maintained by the springs.
This system is used at each end of the straight lengths, every three metres.

1 Spring of clamps.
2 Copper area.
3 Silver plated copper.

DD202283.eps

b At the tap-offs, conductor expansion is compensated for by a contact zone (4)


made of silver-plated copper on which the clamps of the tap-off unit can slide.

Conclusion: at both the jointing system and the tap-off outlets, sliding contacts can
handle the expansion of the conductors.
These maintenance-free silver-plated contacts are guaranteed for life.
Only the expansion of the sheet steel must be taken into account for Canalis
installation, however the problem is minor because both trials and
calculations show that expansion is only approximately 1 mm for every
three-metre length under extreme operating conditions.

99

Recommendations
for special applications

How Canalis compensate


for thermal expansion

Few precautionary measures used to compensate for the effects of thermal expansion in the casing,
depending on how the line is installed.
Horizontal line

For a trunking line made up exclusively of straight lengths, as noted above, the
effects of thermal expansion are not significant (only 1 mm for 3 m).
To avoid all risk of problems, Canalis trunking supports allow movement of the
casing, i.e. no fixed points.
For a fixed point caused by a blocked elbow, for example, the casings compensate
their expansion by slight lateral movement (0.7 mm maximum) on either side of the
longitudinal axis. This movement has no impact on the contact quality of the jointing
system or on the IP.

PD202310_r.eps

Conclusion: the only precautionary measure is to prevent distortion by avoiding


having a number of fixed points on a single line.

DD202285.eps

Vertical line (rising mains)

The effects of thermal expansion depend on the different installation methods.


Rising mains with just one bottom support (1)
With a bottom support attached to the wall, the riser expands upwards. At each floor,
the sheet steel slides naturally through the floor.
The only precautionary measure is to avoid creating any other fixed points.
Rising mains with spring-based fixing devices (2)
For rising mains with spring-based fixing devices only, the riser expands both
upwards and downwards. At each floor, the casing sides naturally through the fire
barriers.
Rising mains with more than one bottom support (1)
More than one bottom support should not be used on a single riser to avoid creating
a number of fixed points that block thermal expansion of the casing, in which case a
component in the line may break.
If more than one bottom support is necessary, it is advised to break the riser into a
number of sections, interconnected by cables and feed boxes, to allow thermal
expansion (see section above on Rising mains with just one bottom support).

Installation of rising mains does not require any particular precautionary


measures. All the above solutions have been simulated by calculations and
tested in a laboratory. Schneider Electric guarantees that they will maintain the
safety and reliability of your installation.

100

Sprinkler test certification

What is a sprinkler?
DD205065_r.eps

A sprinkler is a sprinkling device blanked off by a heat-sensitive component. It is


designed to deliver water when the temperature to which it is subjected exceeds its
calibration value.
The main aim of the installation is to lower the temperature in the accident area by
wetting the ignited and adjacent materials by spraying water in the form of fine
droplets.
The transformation of these droplets into water vapour captures a lot of energy from
the fire and extinguishes it quickly. Moreover, this increased volume prevents air
from flowing to the heart of the fire.
When a fire develops, ambient temperature rises to reach the calibration value.
Water then leaves the sprinkler opening and strikes a deflector that projects it onto
the fire in a certain form. Ground coverage ranges between 9 and 12 m according
to mounting height.
A sprinkler delivers between 60 and 120 l/min according to the hazard class.
On nuisance tripping lasting a few minutes, some hundreds of litres of water are
released. IPx5 approval as per standard
IEC 60529 does not guarantee non ingress of water in the busbar trunking in these
conditions, as the water volumes, test duration and projection distance vary (nozzle
22.5 mm in diameter, at a distance of 2.5-3 m, with a water volume of 12.5 l/min for
1 min/m for at least 3 min)

PD202443_r.eps

To provide you with all necessary safety guarantees, Schneider Electric has chosen
to go further still than the IP55 test by subjecting its busbar trunking to an extremely
severe sprinkler test.

Canalis KBA supplying luminaires nearby sprinklers.

101

Sprinkler test certification

Recommendations
for special applications

Sprinkler test procedure


PD202442.eps

Chronology
In view of the absence of reference standard for sprinkler tests, we have chosen to
apply the following procedure:
b insulation resistance test (1000 V)
b dielectric properties test (2.5 kV, 5 s: IEC 60439-1 & 2
b water projection
b 5 min break
b insulation resistance test (1000 V)
b dielectric properties test (2.5 kV, 5 s: IEC 60439-1 & 2.
Water projection,
2 configurations, with or without energisation:
b horizontally installed busbar trunking:
v 15 min water projection with sprinkler type K-Wert 115, NF , 7.5 bar,
314 L/min
v 35 min water projection with sprinkler type K-Wert 115, NF , 1 bar,
115 L/min
b vertically installed busbar trunking:
v 15 min water projection with sprinkler type K-Wert 80, NF , 7.5 bar,
314 L/min
v 35 min water projection with sprinkler type K-Wert 80, NF , 1 bar,
80 L/min.

Canalis KS and sprinkler.

Mounting position
The distance between the sprinkler head and the busbar trunking is 500 mm.
DB414747.eps

1 Sprinkler
2 Pressure gauge
3 Closing valve
4 Tap-off unit.
5 Busbar trunking

DB414748.eps

Test configuration

Test results
Busbar trunkings KDP, KBA, KBB, KN and KS have undergone the sprinkler test.
This test, if successful, proves that our busbar trunkings can operate during and
immediately after sprinkling of a line by a sprinkler for a period of 50 min.

102

Measurements and metering


Canalis part of StruxureWare

Loads monitored by a power meter in tap-off units

DB405625.eps

DB414424.eps

DB405620.eps

Line capacity is managed in real time.


Information is available on the monitoring system.

Functions available:
bb Protection of Canalis lines by Compact NSX circuit-breakers (100 A, 160 A, 250 A
or 400 A rating).
bb Protection of loads by circuit-breakers from the Acti 9 range (single-phase or
3-phase 16 A, 32 A or 63 A) with or without differential protection (30 mA).
bb Feed units are equipped with front panel-mounted sockets or wander sockets
(IEC 309).
bb For loads, measures power rate, phase balancing, THD, power factor, voltage,
current, active and reactive power and consumption.

Management
system

DB414425.eps

DB405543.eps

Architecture diagram:

Ethernet switch
PM

PM

EGX
PM

EGX

PM

EGX

EGX

Modbus RTU
Canalis
Modbus TCP

Compact NSX circuit-breakers can be fitted with


Micrologic power meter.

103

Coordination

Trunking protection
Overload protection

The busbar trunking rating can be optimised when the trunking is protected by circuit
breakers rather than fuses.

Selection of busbar trunking with respect to protective device ratings


To take into account busbar trunking thermal overload protection, the various
protection switchgear technologies and the currents under overload conditions
must be considered.
The sizing characteristics for the choice of busbar trunking and overload
protection are:
b In trunking = load current x f1 x k2
b f1: temperature coefficient
b k2: derating factor linked to the type of switchgear:
v fuse: k2 = 1.1
v circuit breaker: k2 = 1.
DD206183.eps

Example:
For a load current = 400 A with an ambient temperature of 35 C:
b Fuse protection:

In trunking = load current x f1 x k2 = 400 x 1 x 1.1 = 440 A

The recommended trunking is KSA500 (In trunking = 500 A).
b Circuit breaker protection:

In trunking = load current x f1 x k2 = 400 x 1 x 1 = 400 A

The recommended trunking is KSA400 (In trunking = 400 A).
Due to their design, circuit breaker thermal settings are more precise.

DD210601en.EPS

Explanations
b Calibration of thermal asymptotes:
v distribution fuses are calibrated to trip for overloads of between 1.25 and 1.6 times
their rated current
v circuit breakers are calibrated to trip for overloads of between 1.05 and 1.3
(1.2 for circuit breakers with electronic protection) times ther current setting.

104

Thermal-setting precision
b The fuse is assigned a fixed rating. A change in the current to be protected
requires fuse replacement. The difference between 2 fuse ratings is
approximately 25 %.
Standard ratings are given according to the series of characteristic numbers
of the Renard series.
For example: 40 - 50 - 63 - 80 - 100 - 125 - 160 - 200 - etc.
b the circuit breaker offers a setting precision of:
v 5 % for circuit breakers equipped with conventional thermal-magnetic trip units
v 3 % for circuit breakers equipped with electronic trip units.
For example, a circuit breaker with a nominal rating of 100 A can easily be set
to values of Ir = 100 A, 95 A, 90 A, 85 A, 80 A.
Example:
a circuit breaker with a nominal rating of 100 A set to 90 A will be used to protect
KSA100 busbar trunking (ln trunking = 100 A) which is used for an ambient
temperature of 50 C.

Extensive setting range of circuit breakers equipped with electronic trip units
Circuit breakers equipped with electronic trip units offer an extended range
of settings:
b thermal protection lr adjustable from 0.4 ln to ln
b short-circuit protection from 2 lr to 10 lr.
Example:
a 250 A circuit breaker (NSX250N equipped with an STR22SE) can easily
be set up for:
b thermal protection from 100 to 250 A
b short-circuit protection from 200 to 2500 A.

DD210603.EPS

Advantages:

b This ensures a high degree of flexibility with respect to:


v modifications (flexibility), extensions (upgradeability): protective devices
can be easily adapted to the application requiring protection and to the system
earthing arrangement used (protection of life and property)
v maintenance: use of this type of device considerably reduces maintenance
component stocks.
Example of setting possibilities

105

Coordination

Trunking protection
Short-circuit protection

Trunking characteristics
Busbar trunking systems must meet all rules stipulated
in standards IEC 60439.1 and 60439.2.
b With respect to short-circuits, BTS sizing is determined by the following
characteristics:
v rated peak withstand current Ipk (k):
this characteristic expresses the instantaneous electrodynamic withstand limits
of the busbar trunking. The peak current value is often the most restrictive
instantaneous characteristic for the protective device
v maximum rms short-time withstand current Icw (kArms/...s):
this characteristic expresses the permissible temperature-rise limit of conductors
over a given period of time (0.1 to 1 s)
v thermal stress in A2s:
this characteristic expresses the instantaneous thermal stress withstand of the BTS.
Normally, if the short-circuit generates fault conditions that are compatible with
the first two characteristics, this constraint is automatically satisfied.

Circuit breaker characteristics


A circuit breaker must meet the requirements of product construction standards
(IEC 60947-2, etc.) and installation standards (IEC 60364 or applicable country
standards), i.e. its breaking capacity lcu (1) must be greater than short-circuit current
Isc at the point where it is installed.
(1) Installation standard IEC 60364 and the construction standards specify that the breaking
capacity of a circuit breaker is:
- the ultimate breaking capacity, lcu, if it is not coordinated with an upstream protective device,
- the breaking capacity enhanced by cascading, if there is coordination with the upstream
protective device.

Characteristics of the circuit breaker/trunking combination


DD210604en.EPS

When the busbar trunking is directely protected, selection of the protective


device must take into account the following requirements:
b circuit breaker Icu u prospective Isc at point A
b BTS l peak u limited or asymmetrical prospective Isc at point A
b BTS thermal withstand at lcw u thermal stress passing through the BTS.

DD210613en.eps

When the busbar trunking is protected downstream of a cable, selection of


the protective device must take into account the following requirements:
b circuit-breaker lcu u prospective Isc at point A
b BTS l peak u limited or asymmetrical prospective Isc at point B
b BTS thermal withstand at lcw u thermal stress passing through the BTS.

106

Circuit breaker/trunking
coordination
Non-limiting or time-delayed
circuit breakers

Either non-limiting (instantaneous or time-delayed) or time-delayed limiting circuit


breakers can be used. They are mainly air-type power (= 800 A) circuit breakers.
This type of circuit breaker is used to implement time discrimination
and is often combined with KT type trunking.
b The busbar trunking must be capable of withstanding the peak fault current
to which it may be subjected as well as the thermal stress during any time delay:
DD206176.eps

v the permissible peak current, l peak, of the BTS must be greater than the peak
value of the prospective asymmetrical short-circuit current at point A.
The value of the asymmetrical short-circuit current is obtained from the value
of the symmetrical short-circuit current, Isc, multiplied by a standardised
asymmetry factor (k).
The value of the first short-circuit asymmetry peak in the transient state is taken
into account.
Standardised table for asymmetrical short-circuit calculations

Isc: prospective symmetrical short-circuit

Current value of the 1st. peak as a function of rms Isc.

kA (rms value)
4.5 y I y 6
6 < I y 10
10 < I y 20
20 < I y 50
50 < I

Asymmetry factor k

k
1.5
1.7
2.0
2.1
2.2

For example, for a circuit with a prospective short-circuit current of 50 kA rms,


the first peak reaches 105 kA (50 kA x 2.1). See the figure opposite.
DD206177.eps

v the short-time withstand current lcw of the BTS must be greater than the current
Isc flowing through the installation for the duration of the short-circuit,
(duration T = total breaking time, including the time delay if applicable).
If one of these criteria is not satisfied, the rating of the busbar trunking to be used
must be increased.

Transient and steady states of a short-time short-circuit.

107

Circuit breaker/trunking
coordination

Coordination

Limiting circuit breakers

This mainly concerns protection of BTSs by moulded-case circuit breakers


(y 1600 A).
This type of circuit breaker is used for energy discrimination and is therefore often
combined with Canalis KN and KS trunking.

DD206178.eps

b In this case, the BTS must withstand the peak current limited by the protective
device and the corresponding thermal stress.
v The current limited (I peak) by the circuit breaker must be less than the peak
current permitted in the BTS.
v The thermal stress limited by the circuit breaker must be less than
the thermal stress permitted in the BTS.

DD206179.eps

Checking the BTS withstand capacity in terms of peak current.

Checking the BTS withstand capacity in terms of thermal stress

108

BTS protection by
Compact NSX limiting
circuit breakers
Limiting capacity
Busbar trunking ratings can be optimised when circuit breakers rather than fuses are
sed for protection.

PB104166_SE.eps

The circuit breakers in the Compact NSX range are limiting circuit breakers
with a high current-limiting capacity.
A circuit breakers limiting capacity is its ability to let only a limited current IL,
lower than the prospective asymmetrical peak short-circuit current Isc through
in the event of a short-circuit.
The consequence is a considerable reduction in electrodynamic
and thermal stresses in the protected installation.

Example of a mid-sized installation (> 1000 kVA)


DD206180.eps

The diagram opposite shows the protection provided by an NSX400N limiting


circuit breaker for KSA400 trunking.
b Without taking into account the circuit breakers limiting capacity:
v the prospective Isc at point A would be 75.6 k
v KSA800 trunking would be required (Ipeak = 78.7 k > 75.6 k at point A).

DD206182.eps

DD206181.eps

b Taking into account the limiting capacity of the Compact NSX400N:


v the value of Ipeak limited by the circuit breaker is 30 k < 49.2 k of the KSA400
trunking
v the value of the limited thermal stress is 1.6 x 106 < 354 x 106 of the KSA400
trunking.

Current limiting.

Energy limiting.

Thanks to the high limiting capacity of Compact NSX400N circuit breakers,


KSA400 busbar trunking can be used for prospective Isc values up to 50 kA
(105 k) at point A.

109

Selection guide

Coordination

The selection guides below can be used to determine the circuit breaker required
to fully protect the trunking depending on the prospective short-circuit current
of the installation.
Example: in an installation with a prospective Isc of 15 kA, the circuit breaker
required to protect 25 A KBB trunking is a C60H (the rating depends on the rated
current of the circuit).
In bold, the most appropriate device to the rating of the busbar trunking.

Selection guide for 380/415 V


Type of Canalis busbar trunking KSA100
Isc max. in kA rms
Type of circuit breaker NG125
Compact NSX

25 kA
36 kA
NG125N 100
NG125H 100
NSX100B/F/N/H/S/L

Type of Canalis busbar trunking KSA160


Isc max. in kA rms
Type of circuit breaker Compact NSX

25 kA
NSX100B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L

36 kA
NSX100F/N/H/S/L
NSX160F/N/H/S/L
NSX250F/N/H/S/L

50 kA
70 kA
NSX100N/H/S/L NSX100H/S/L
NSX160N/H/S/L NSX160H/S/L
NSX250N/H/S/L

90 kA
NSX100S/L

36 kA
NSX160F/N/H/S/L
NSX250F/N/H/S/L
NSX400F/N/H/S/L

50 kA
70 kA
NSX160N/H/S/L NSX160H/S/L
NSX250N/H/S/L NSX250H/S/L
NSX400N/H/S/L

100 kA
NSX160S/L
NSX250S/L

150 kA
NSX160L
NSX250L

36 kA
NSX250F/N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b L / LB

50 kA
NSX250N/H/S/L
NSX400N/H/S/L
NSX630N/H/S/L
NS630b L / LB

70 kA
NSX250H/S/L
NSX400H/S/L
NSX630H/S/L
NS630b LB

100 kA
NSX250S/L
NSX400S/L
NSX630S/L

150 kA
NSX250L
NSX400L
NSX630L

36 kA
NSX400F
NSX630F
NS630b N

50 kA
NSX400N
NSX630N
NS630b L / LB

70 kA
NSX400H
NSX630H
NS630b LB

100 kA
NSX400S
NSX630S
NS630b LB

150 kA
NSX400L
NSX630L

36 kA
NSX400F
NSX630F
NS630b L
NS800L
NT06L1
NT08L1

50 kA
NSX400N
NSX630N
NS630b L
NS800L
NT06L1
NT08L1

70 kA
NSX400H
NSX630H
NS630bL
NS800L
NT06L1
NT08L1

100 kA
NSX400S
NSX630S
NS630bL
NS800L
NT06L1
NT08L1

150 kA
NSX400L
NSX630L
NS630b LB
NS800LB

36 kA
NSX630F
NS630bN
NS800N
NS1000N
NT06H1
NT08H1
NT10H1

50 kA
NSX630N
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1

70 kA
NSX630H
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1

100 kA
NSX630S
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1

150 kA
NSX630L
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1

36 kA
NS800N
NS1000N
NS1250N
NT08H1
NT10H1
NT12H1

50 kA
NS800L
NS1000L

70 kA
NS800L
NS1000L

100 kA
NS800L
NS1000L

150 kA
NS800L
NS1000L

NT08L1
NT10L1

NT08L1
NT10L1

NT08L1
NT10L1

NT08L1
NT10L1

Type of Canalis busbar trunking KSA250


Isc max. in kA rms
Type of circuit breaker Compact NSX

25 kA
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L
NSX400F/N/H/S/L

Type of Canalis busbar trunking KSA400


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS

25 kA
NSX250B/F/N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b N/H/L/LB

Type of Canalis busbar trunking KSA500


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS

25 kA
NSX400F
NSX630F
NS630b N

Type of Canalis busbar trunking KSA630


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS
Masterpact NT

y 32 kA
NSX400F
NSX630F
NS630b N
NS800N
NT06H1
NT08H1

Type of Canalis busbar trunking KSA800


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS
Masterpact NT

Type of Canalis busbar trunking KSA1000


Isc max. in kA rms
Type of circuit breaker Compact NS
Masterpact NT

110

Selection guide for 660/690 V


Type of Canalis busbar trunking KSA100
Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS

10 kA
NSX100N/H/S/L
NSX160N/H/S/L
NSX250N/H/S/L

15 kA
NSX100S/L
NSX160S/L
NSX250S/L

20 kA
NSX100L

15 kA
NSX100S/L
NSX160S/L
NSX250S/L

20 kA
NSX100L
NSX160L
NSX250L

15 kA
NSX160S/L
NSX250S/L
NSX400H/S/L

20 kA
NSX160L
NSX250L
NSX400/S/L

75 kA

NS100L

Type of Canalis busbar trunking KSA160


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS

10 kA
NSX100N/H/S/L
NSX160N/H/S/L
NSX250N/H/S/L

75 kA

NS100L

Type of Canalis busbar trunking KSA250


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS

10 kA
NSX160N/H/S/L
NSX250N/H/S/L
NSX400F/N/H/S/L

35 kA
NSX400L

75 kA

NS400L

Type of Canalis busbar trunking KSA400


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS

10 kA
15 kA
NSX250N/H/S/L NSX250S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L

20 kA
NSX250L
NSX400H/S/L
NSX630H/S/L

35 kA
NSX400L
NSX630L

NS630bN

75 kA

NS400L
NS630bLB

Type of Canalis busbar trunking KSA500


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS

10 kA
15 kA
NSX400F/N/H/S/L
NSX630F/N/H/S/L

20 kA
NSX400H/S/L
NSX630H/S/L

25 kA

35 kA
NSX400L
NSX630L

75 kA

30 kA

35 kA
NSX400L
NSX630L

75 kA

NS630bN
NS800N

NS630bH
NS800H

NS400L
NS630bLB
NS800LB

30 kA

35 kA

75 kA

NS630bN
NS800N
NS1000N

NS630bH
NS800H
NS1000H

NS630bLB
NS800LB

30 kA
NS800N
NS1000N
NS1250N

35 kA
NS800H
NS1000H
NS1250H
NT08H1/H2
NT10H1/H2
NT12H1/H2
NW08N1
NW10N1
NW12N1

75 kA
NS800LB

NS630bN
NS800N

NS400L
NS630bLB
NS800LB

Type of Canalis busbar trunking KSA630


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS

10 kA
15 kA
NSX400F/N/H/S/L NSX400H/S/L
NSX630F/N/H/S/L NSX630H/S/L

20 kA
NSX400/S/L
NSX630/S/L

Type of Canalis busbar trunking KSA800


Isc max. in kA rms
Type of circuit breaker Compact NSX
Compact NS

10 kA
15 kA
NSX630F/N/H/S/L NSX630H/S/L

20 kA
NSX630/S/L

Type of Canalis busbar trunking KSA1000


Isc max. in kA rms
Type of circuit breaker Compact NS
Masterpact NT
Masterpact NW

10 kA

15 kA

20 kA

111

Maintenance

Maintenance recommendations
for your installation

Maintenance on power-distribution lines


DD202301.eps

Feed units
They are equipped with terminals up to 100 A and lug connectors for higher ratings.
As for all screw-type connections, it is advised to check tightness one year after
installation and then run checks at longer intervals.
The feed units are jointed to the first run component of the line (see next paragraph).
This connection is maintenance free

DD202302.eps

Run components
They are interconnected by electrical jointing units ensuring automatic and
simultaneous connection of all live conductors.
The contacts are clamp + spring type and exert no forces on the plastic parts.
The electrical contacts of the jointing unit for the conductors are silver-plated copper.
This type of sliding connection is maintenance free.
Components can be dismantled and reused.

DD202303.eps

Tap-off units
Trunking contacts are flexible, made of silver-plated clamps providing optimum
contact quality. The contacts do not press or apply any forces on the plastic parts.
They connect to the live line conductors at the tap-off outlets. Conductors are made
of silver-plated copper at the point of contact.
These components are maintenance free.
The connections for outgoing cables are made to terminals or using lugs.
As for all screw-type connections, it is advised to check tightness one year after
installation and then run checks at longer intervals.

Other recommandations
Maintenance of devices
For all devices installed in Canalis tap-off units, follow the manufacturers instructions
(as for installation in a switchboard).

Visual check
Cleaning
It is advised to check annually that trunking is clean and to remove any dust, water,
oil or other conducting substances or objects from sensitive zones such as junctions,
tap-off outlets and tap-off units.
External appearance
Check the external appearance of the trunking to detect:
b signs of shocks, in which case it is necessary to check the degree of protection
to avoid any risk of insulation faults
b anomalies, i.e. incorrect implementation of the trunking (incorrect supports, etc.)
b traces of corrosion (in particular on supports).

Reuse after exposure to water


If a Canalis line is exposed to water during installation, it is necessary
to measure the insulation resistance of the line by isolating the supply and the loads.
b If R < 0.69 M, the installation must not be energised:
v cut the line in two by removing the jointing unit in the middle
v locate the faulty zone
v remove all jointing covers and dry the parts using compressed air
v continue until the insulation resistance is greater than 0.69 M
v the system can then be energised.

112

35, rue Joseph Monier


CS 30323
92506 Rueil Malmaison Cedex
France

As standards, specifications and designs change from


time to time, please ask for confirmation of the
information given in this publication.

RCS Nanterre 954 503 439


Capital social 896 313 776
www.schneider-electric.com

Publication: Schneider Electric Industries SAS


Photos: Schneider Electric
Publishing: Altavia St Etienne

DEBU026EN

10-31-1247

 his document has been


T
printed on ecological paper.

11-2013

ART960387 2013 - Schneider Electric - All rights reserved