Catalogue2014
Canalis KSA
100 - 1000 A
Busbar trunking systems
Aluminium
Canalis KSA
Contents
Index 4
Presentation 8
Straight components
15
47
Tap-off units
55
Characteristics 83
page 8
page 4
Straight components
DD230586.eps
page 16
Rising mains
DD230604.eps
DD230588.eps
page 20
page 23
page 48
DD206148.eps
DD230599.eps
page 51
page 52
Tap-off units
DD230603.eps
page 62
page 63
page 64
Characteristics
Design guide
page 84
Electrical characteristics
page 88
Specifications
page 90
Accessories
DD206151.eps
DD202082.eps
Fixing systems
DD210317.eps
Changing direction
page 26
page 42
page 38
Plaque 1.eps
Accessories
page 53
Accessories
DB414462.eps
For fuses
DD206150.eps
DD230603.eps
page 72
page 82
page 74
Coordinations
page 104
Maintenance
page 112
Canalis KS
Cat. no.
08000
Designation
Page
08903
82
08905
82
08907
82
13000
13136
71
13137
71
13940
82
81140
Household NF sockets
71
81141
71
81000
KFB
KFBCA81200
39, 41
KFBCA81300
39
39
KSA25
KSA25HD502
KSA40
KSA40HD502
KSA80
Cat. no.
Designation
Page
KSA250ABGD5
51
KSA250ABT4
50
53
KSA250ABZFL21
53
KSA250AE4
52
KSA250DLC4A
31
KSA250DLC4B
32
KSA250DLC4CF
34
29
KSA250DLC40
ELBOW 250 A
KSA250DLE4A
KSA250DLE4B
32
KSA250DLE4CF
34
29
KSA250DLE40
ELBOW 250 A
KSA250DLF4A
KSA250DLF4B
KSA250DLF4CF
34
KSA250DLF40
ELBOW 250 A
29
KSA250DMBK4A
32
79
KSA250DMCL4A
29
KSA250DXC40
30
KSA80EZ3
FIXING BRACKET
40
KSA250DZCG4A
33
KSA80EZ5
FIXING BRACKET
40
KSA250DZCG4CF
35
KSA80ZG20
FIXING BRACKET
40
KSA250DZCH4A
33
KSA250DZCH4CF
35
KSA250DZE4A
33
KSA250DZE4CF
35
KSA250ED4081
KSA250ED4156
KSA250ED4208
KSA250ED4306
KSA250ED43012
KSA250ED45010
KSA250ED45020
KSA100
KSA100AB4
KSA100ED4081
KSA100ED4306
KSA100ED43012
KSA100ED45010
KSA100ED45020
KSA100EV4203
KSA100EV4254
KSA125
KSA125HD5
KSA160
49
24
79
KSA160ED4306
KSA160ED43012
KSA160ED45010
KSA160ED45020
KSA250
KSA250AB4
KSA250ABCB4
KSA250ABDD4
51
KSA250ABDD5
51
KSA250ABGD4
51
49
17
KSA250ET4A
21
KSA250ET4AF
22
KSA250EV4AF
22
KSA250EV4203
24
KSA250EV4254
KSA250FA4
44
KSA250ZJ4
43
KSA400AB4
49
KSA400ABCB4
KSA400ABDD4
51
KSA400ABDD5
51
KSA400ABGD4
51
KSA400ABGD5
51
KSA400
Cat. no.
Designation
Page
Cat. no.
Designation
Page
KSA400ABT4
50
KSA500ET4AF
22
53
KSA500ET430
21
KSA400ABZFL21
53
KSA500ET450
21
KSA400AE4
52
KSA500EV4153
KSA400AF1
44
KSA500EV4203
KSA400DLC4A
31
KSA500EV4254
KSA400DLC4B
32
KSA500FA4
44
KSA400DLC4CF
34
KSA500FR425
44
29
KSA630
KSA630ABD4
49
KSA630ABG4
49
KSA630ABT4
50
KSA400DLC40
ELBOW 400 A
KSA400DLE4A
KSA400DLE4B
32
KSA400DLE4CF
34
KSA400DLE40
ELBOW 400 A
29
KSA400DLF4A
KSA400DLF4B
32
KSA400DLF4CF
34
KSA400DLF40
ELBOW 400 A
29
KSA400DMBK4A
29
KSA400DXC40
30
KSA400DZCG4A
33
KSA400DZCG4CF
35
KSA400DZCH4A
33
KSA400DZCH4CF
35
KSA400DZE4A
33
KSA400DZE4CF
35
KSA400ED4081
KSA400ED4156
17
KSA400ED4208
KSA400ED4306
KSA400ED33012
KSA400ED35020
KSA400ED43012
KSA400ED45010
KSA400ED45020
KSA400ET4A
21
KSA400ET4AF
22
KSA400ET430
21
KSA400ET450
21
KSA400EV4AF
22
24
KSA400EV4203
KSA400EV4254
KSA400FA4
44
KSA400ZJ4
43
KSA500
KSA500ED3306
KSA500ED4306
KSA500ED35010
KSA500ED43010
KSA500ED45010
KSA500ED45018
24
53
KSA630ABZFL21
53
KSA630AE4
52
KSA630DLC4A
31
KSA630DLC4B
32
KSA630DLC4CF
KSA630DLC40
ELBOW 630 A
KSA630DLE4A
29
KSA630DLE4B
KSA630DLE4CF
32
KSA630DLE40
ELBOW 630 A
KSA630DLF4A
29
KSA630DLF4B
KSA630DLF4CF
34
KSA630DLF40
ELBOW 630 A
29
KSA630DMBK4A
32
29
KSA630DXC40
30
KSA630DZCG4A
33
KSA630DZCG4CF
35
KSA630DZCH4A
33
KSA630DZCH4CF
35
KSA630DZE4A
33
KSA630DZE4CF
35
KSA630ED3306
KSA630ED4081
KSA630ED4154
KSA630ED4206
KSA630ED4306
KSA630ED35010
KSA630ED43010
KSA630ED45010
KSA630ED45018
17
KSA630ET4A
KSA630ET4AF
21
22
KSA630ET430
21
KSA630ET450
21
KSA630EV4AF
22
KSA630EV4153
Canalis KS
Cat. no.
Designation
Page
Cat. no.
Designation
Page
KSA630EV4203
24
KSA1000DZE4CF
35
KSA630EV4254
KSA1000ED4081
25
KSA630ZJ4
KSA1000ED4154
17
KSA1000ED4206
17
KSA1000ED4306
17
KSA1000ED45010
17
21
KSA800
43
KSA800ED3306
KSA800ED4306
KSA800ED35010
KSA800ED43010
KSA800ED45010
KSA800ED45018
KSA800ET4AF
22
KSA800ET430
21
KSA800ET450
21
KSA800EV4153
KSA1000ET4A
KSA1000ET4AF
22
KSA1000ET430
21
21
KSA1000ET450
KSA1000EV4AF
22
KSA1000EV4153
24
KSA800EV4203
KSA800EV4254
KSA1000EV4203
KSA800FA4
44
KSA1000EV4254
24
KSA1000ZJ4
43
76
78
KSA1000
24
KSA1000ABD4
49
KSA1000ABG4
49
KSA1000ABT4
50
53
KSB16
KSB16CN5
KSB20
53
KSA1000AE4
52
KSA1000AF1
44
KSA1000DLC4A
31
KSA1000DLC4B
32
KSA1000DLC4CF
34
KSA1000DLC40
ELBOW 1000 A
29
KSA1000DLE4A
31
KSA1000DLE4B
32
KSA1000DLE4CF
34
KSA1000DLE40
ELBOW 1000 A
29
KSA1000DLF4A
31
KSA1000DLF4B
32
KSB32CP35
KSA1000DLF4CF
34
KSB32SG4
KSA1000DLF40
ELBOW 1000 A
29
36
37
KSA1000DMBL4A
36
37
36
37
KSA1000DMCL4A
36
37
KSA1000DTC40
29
KSA1000DXC40
30
KSA1000DZCG4A
33
35
KSA1000DZCH4A
33
35
KSA1000DZE4A
33
KSB20CG5
KSB25
KSB25SD4
76
KSB25SD5
76
KSB32CF5
74
KSB32CM55
63
KSB32CP
KSB32
KSB32CP11D
KSB32CP11F
KSB32CP15D
KSB32CP15F
KSB50
78
KSB50SF4
74
KSB50SF5
74
KSB50SN4
76
KSB50SN5
76
KSB50SV4
62
KSB50SV5
62
KSB63EGP
62
KSB63PMP
62
KSB63
KSB63SD4
76
KSB63SD5
76
KSB63SM48
62, 63
KSB63SM58
62, 63
78
KSB80
KSB80SG4
Cat. no.
KSB100
KSB100SE4
Designation
TOU 100A FUSE T00
Page
75, 77
KSB100SE5
75, 77
KSB100SF4
74
Cat. no.
Designation
Page
KSB400ZF1
40
KSB400ZFKP1
39
KSB400ZV1
41
80
KSB630
KSB100SF5
74
KSB100SM412
63
KSB630SE4
KSB100SM512
63
KSB630SE5
80
KSB100SV4
62
KSB630ZV1
41
KSB100SV5
62
KSB160
KSB1000
KSB1000ZB1
43
KSB160DB412
66
KSB1000ZB2
43
KSB160DB512
66
KSB1000ZF1
40
KSB160DC4
65
KSB1000ZFKP1
39
KSB160DC5
65
KSB1000ZP1
43
KSB160DD411
67
KSB160SDF4
81
KSB1000ZP2
43
KSB160SDF5
81
KSB1000ZV1
41
KSB160SE4
75, 77
KSB160SE5
75, 77
KSB160SF4
75
KSB160SF5
75
KSB160SFZFL21
82
KSB160SG4
78
KSB160SM413
68
KSB160SM424
73
KSB160SM513
68
KSB160SM524
73
KSB160SV4
62
KSB160SV5
62
KSB250
KSB250DC4
65
KSB250DC4SP
KSB250DC4TRE
72
KSB250DC5
65
KSB250DC5TRE
72
KSB250DCZFL21
82
KSB250DD412
67
KSB250SDF4
81
KSB250SDF5
81
KSB250SE4
75, 77
KSB250SE5
75, 77
KSB250SM428
64
KSB250ZV1
41
KSB400
KSB1000ZV2
41
KSB1000ZV3
41
KSBQPF
70
KSBQPRD
70
KV
KV025YA4
tap-off joint
45
KV031AB40001
45
KV031AB70001
45
KV031AB40002
45
KV031AB70002
45
KV031YA4
tap-off joint
45
KV040CB71103E
45
KV040YA41
tap-off joint
45
KV040YA42
tap-off joint
45
KV063AB40001
45
KV063AB70001
45
KV063AB40002
45
KV063AB70002
45
KV063YA4
tap-off joint
45
KV080AB40001
45
KV080AB70001
45
KV080AB40002
45
KV080AB70002
45
KV080YA4
tap-off joint
45
PKY16F723
71
PKY16F725
71
PKY16F733
71
PKY16F735
71
PKY32F723
71
PKY32F725
71
PKY32F733
71
PKY32F735
71
PKY
KSB400DB412
66
KSB400DB512
66
KSB400DC4
65
KSB400DC4TRE
72
KSB400DC5
65
KSB400DC5TRE
72
KSB400DCZFL21
82
KSB400DD411
67
KSB400SDF4
81
KSB400SDF5
81
KSB400SE4
75, 77
KSB400SE5
75, 77
KSB400ZB1
43
KSB400ZB2
43
KSB400ZC1
DOOR MICROSWITCH
82
Advantages of the
Canalis...
is part of a comprehensive
offering of Schneider Electric
products designed to operate
together.
In particular, this offering
covers all low and medium
voltage electrical distribution
components.
PD202357_r2.eps
Tap-off units
b The Canalis tap-off units of the Schneider Electric system satisfy operator
needs in terms of:
v installation upgradeability without production downtime
v continuity of service
v safety.
PD202333_r1.eps
PD202332_r2.eps
PD202334_r1.eps
Distribution switchboards
Our protection switchgear optimises switchboard functions.
b Schneider Electric guarantees upstream device coordination:
v between Masterpact, Compact circuit breakers and between Compact and
Acti 9 circuit breakers
v between electrical distribution circuit breakers and industrial control circuit
breakers (motor circuit breaker, Integral, etc.) for industrial control application.
b Switch-disconnectors comply with the IEC 60947-3 standard and are
designed to ensure AC23 load breaking and isolation.
Their protection is guaranteed by coordination with the upstream circuit
breakers.
Canalis
Prefabricated busbar trunking
from 100 to 1000 A
10
11
Presentation
71427827_7_r.eps
dv1576116.eps
57284363_r.eps
12
DD202130_r.eps
DD202144_r.eps
DD202143_r.eps
DD202131_r.eps
An environmentally friendly
life cycle
Design
Recycling
Industrialization
Exploitation
PD202192_r.eps
Our performance...
your values
Excellent contact
Incomparable scalability
The electrical busbar trunking has a high density of tap-off points even in
rising mains, due to the absorption of differential expansion by the junctions.
The tap-off units are removable and can be handled live.
Because the available space in technical ducts is limited, Canalis KS gives the
advantage to use significantly less room compared to a centralised
distribution system using cables.
Installation is made easy due to the design of the jointing units that facilitate
alignment of the straight lengths.
Maintenance free
All sliding jointing contacts are lubricated for the life of the product.
Very flexible
PD202207_r1.eps
>> They monitor the installation to avoid overloads and ensure continuity of
service.
>> They can meter the energy consumed for precise management (cost
allocation for each consumer).
13
Canalis tools
Technical datasheets
p In exhibition center: KD0C00CTAFEEN
p In electronics factories: KD0C00CTAUEEN
p In tiles factories: DEBU005EN
p In automobile industry: KD0C98CTAAUEN
p Reduce electromagnetic emissions: DESWED113001EN
iBusway for
Data Center
Catalogue
2010
Lighting management
has never been so easy
and economical
Canalis
Dans les parkings
Fiche application
+
14
All these documents are available on Schneider Electric web site: www.schneider-electric.com
Canalis KS
Straights components
Contents
16
20
22
Rising mains
23
Changing direction
26
31
34
36
37
Fixing systems
38
39
41
Accessories
42
16
18
20
22
23
26
31
34
36
37
38
39
41
42
45
15
Description
DD210264.eps
The degree of protection of the busbar trunking is IP55 for indoor installations.
For the sprinkler protection, it is necessary to add a sealing kit (see page 43).
500 to 1000 A
DD230589.eps
100 to 400 A
Dimensions
DD230598.eps
Rating
height
width
length
146 mm
54 mm
146 mm
113 mm
Commercial numbers
and dimensions
Straight lengths 3L + N + PE
DD230597.eps
Rating
(A)
Length
(mm)
Standard components
100
5000
3000
160
5000
3000
250
5000
3000
DD230587.eps
400
DB403573.eps
5000
3000
500
5000
3000
630
5000
3000
800
5000
3000
1000
5000
3000
Special components
100 to 250
2000
1500
400
2000
1500
500 to 630
2000
1500
800 to 1000 2000
1500
Number of outlets
Cat. no.
Weight
(kg)
10
6
10
6
10
6
KSA100ED45010
KSA100ED4306
KSA160ED45010
KSA160ED4306
KSA250ED45010
KSA250ED4306
19.20
12.10
21.40
13.40
25.20
15.70
10
6
10
6
10
6
10
6
10
6
KSA400ED45010
KSA400ED4306
KSA500ED45010
KSA500ED4306
KSA630ED45010
KSA630ED4306
KSA800ED45010
KSA800ED4306
KSA1000ED45010
KSA1000ED4306
32.85
20.40
54.50
34.90
58.20
36.40
69.20
43.10
89.50
55.20
8
6
8
6
6
4
6
4
KSA250ED4208
KSA250ED4156
KSA400ED4208
KSA400ED4156
KSA630ED4206
KSA630ED4154
KSA1000ED4206
KSA1000ED4154
10.85
8.55
13.90
10.85
26.00
20.50
38.50
29.90
DD210290.eps
DD202023.eps
DD210291.eps
DD210292.eps
DD210293.eps
17
Commercial numbers
and dimensions
Rating
(A)
100
160
250
Straight length from 100 to 400 A.
DD230587.eps
400
500
630
800
Number of outlets
Cat. no.
Weight
(kg)
5000
3000
5000
3000
5000
3000
20
12
20
12
20
12
KSA100ED45020
KSA100ED43012
KSA160ED45020
KSA160ED43012
KSA250ED45020
KSA250ED43012
19.20
12.10
21.40
13.40
25.20
15.70
5000
3000
5000
3000
5000
3000
5000
3000
20
12
18
10
18
10
18
10
KSA400ED45020
KSA400ED43012
KSA500ED45018
KSA500ED43010
KSA630ED45018
KSA630ED43010
KSA800ED45018
KSA800ED43010
32.85
20.40
54.50
34.90
58.20
36.40
69.20
43.10
KSApppED45020 (100-400 A)
DD206152.eps
Length
(mm)
135
500
365
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
365
500
135
DB413611.eps
KSApppED45018 (500-800 A)
237
500
513
500
500
500
500
500
500
750
500
500
750
500
5000
DD230169.eps
KSApppED43012 (100-400 A)
135
365
500
500
500
500
500
500
500
365
500
500
500
135
3000
DB413612.eps
KSApppED43010
237
513
500
500
500
750
750
3000
18
513
500
500
500
237
500
500
500
500
513
237
Straight lengths 3L + PE
DD230597.eps
Rating
(A)
400
500
630
Straight length from 100 to 400 A.
Number of outlets
Cat. no.
Weight
(kg)
5000
3000
5000
3000
5000
3000
5000
3000
20
12
10
6
10
6
10
6
KSA400ED35020
KSA400ED33012
KSA500ED35010
KSA500ED3306
KSA630ED35010
KSA630ED3306
KSA800ED35010
KSA800ED3306
30.75
19.14
49.55
31.93
53.25
33.43
64.25
40.13
DD230587.eps
800
Length
(mm)
DD206154.eps
KSA400ED35020
135
500
365
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
365
500
135
DB403573.eps
5000
DD206155.eps
KSApppED35010 (500-800 A)
DD230576.eps
KSA400ED33012
135
365
500
500
500
500
500
500
500
365
500
500
500
135
DD230579.eps
KSApppED3306 (500-800 A)
19
Description
DD230594.eps
The degree of protection of the busbar trunking is IP55 for indoor installations.
For the sprinkler protection, it is necessary to add a sealing kit (see page 43).
20
Commercial numbers
and dimensions
Rating
(A)
400
500
630
800
1000
Length
(mm)
Cat. no.
Weight
(kg)
5000
3000
5000
3000
5000
3000
5000
3000
5000
3000
KSA400ET450
KSA400ET430
KSA500ET450
KSA500ET430
KSA630ET450
KSA630ET430
KSA800ET450
KSA800ET430
KSA1000ET450
KSA1000ET430
32.85
20.40
54.50
34.90
58.20
36.40
69.20
43.10
69.20
43.10
Length
(mm)
Cat. no.
Weight
(kg)
500 to 1995
500 to 1995
500 to 1995
500 to 1995
KSA250ET4A
KSA400ET4A
KSA630ET4A
KSA1000ET4A
2.50
3.25
12.00
15.00
DD230600.eps
KSApppET4p0 400 A.
DD230600.eps
DD202048.eps
Dimension l
500 to 1995 mm
21
Commercial numbers
and dimensions
Rating
(A)
100 to 250
400
500
Length
(mm)
Cat. no.
Weight
(kg)
900 to 2190
900 to 2190
900 to 2340
KSA250ET4AF
KSA400ET4AF
KSA500ET4AF
8.40
9.90
16.60
630
900 to 2340
KSA630ET4AF
18.00
800
1000
900 to 2340
900 to 2340
KSA800ET4AF
KSA1000ET4AF
19.50
24.20
DD230590.eps
DD230601.eps
DD202048.eps
Dimensions
Rating
(A)
Dimensions (mm)
l
900 to 2190
900 to 2340
100 to 400
500 to 1000
X
900 to 1740
900 to 1890
Rating
(A)
100 to 250
400
500 to 630
800 to 1000
Length
(mm)
1150
1150
1150
1150
Max. permissible
weight (kg)
680
680
1760
1760
Max. permissible
height (m)
40
30
50
40
Cat. no.
Weight
(kg)
KSA250EV4AF 10.00
KSA400EV4AF 12.00
KSA630EV4AF 25.00
KSA1000EV4AF 25.00
E
255
C
DB414039.eps
KSApppEV4AF
92
Dimensions
Rating
(A)
100 to 400
500 to 1000
22
Dimensions (mm)
A
B
750
67
700
124
C
166
169
D
1200
1151
E
223
293
Description
Rising mains
DD210675.eps
40 m
1760 kg
Max. height
150 m
Above 100 m, avoid the use of fixed components (e.g. elbows) and supply power
using cables wherever possible.
C Use custom-length fire barriers to block fire propagation between floors. They
also provide the means to adjust to the distance between floors (see page 22).
D Use standard straight lengths, 2 or 2.50 metres long. Lengths and fire barriers
can be combined to provide:
Solution 1: for a distance of 2900 mm to 4300 mm between floors, three tap-off
outlets with KSA pppEV4203 straight lengths,
Solution 2 : for a distance of 3400 mm to 4800 mm between floors, four tap-off
outlets with KSA pppEV4254 straight lengths,
E Use KSB1000ZV2 fixings to guide the riser on each floor.
Riser components
D Straight lengths for distribution
Specially designed for rising mains, they are available in two lengths (2 and 2.5
metres).
They have three or four tap-off outlets, all on the same side. The outlets are
positioned to enable connection of up to three 160 A tap-off units for Compact
NSX circuit breakers on the two-metre lengths and up to four on the 2.5-metre
lengths.
C Custom-length fire-barrier lengths (see page 22)
Installed at each floor level, these lengths eliminate any risk of fire propagation
from one floor to another via the trunking. These fire barriers have been tested in
a certified laboratory and comply with standard EN 1363-1. The laboratory report
lists the following results:
b thermal insulation: u120 minutes
b resistance to flames: u120 minutes
b stability: u120 minutes.
Provided in custom lengths, these barriers are used with the straight lengths to
adjust to the exact height of each floor.
23
Rising mains
Commercial numbers
and dimensions
Riser mains 3L + N + PE or 3L + PE
DB403573.eps
Rating
(A)
100
250
400
Connection of a tap-off unit onto a tap-off outlet.
500
630
800
1000
Length
(mm)
Number of outlets
Cat. no.
Weight
(kg)
2000
2500
2000
2500
2000
2500
1500
2000
2500
1500
2000
2500
1500
2000
2500
1500
2000
2500
3
4
3
4
3
4
3
3
4
3
3
4
3
3
4
3
3
4
KSA100EV4203
KSA100EV4254
KSA250EV4203
KSA250EV4254
KSA400EV4203
KSA400EV4254
KSA500EV4153
KSA500EV4203
KSA500EV4254
KSA630EV4153
KSA630EV4203
KSA630EV4254
KSA800EV4153
KSA800EV4203
KSA800EV4254
KSA1000EV4153
KSA1000EV4203
KSA1000EV4254
8.10
10.40
10.85
13.35
13.90
17.40
17.45
25.20
30.70
18.20
25.30
30.80
21.55
30.50
37.00
30.10
38.60
47.10
It is also possible to use standard 1.5 metre long straight lengths (KSA pppED4156).
Dimensions
A
B
C
400 A
150
485
865
KS1000EV4153
250
24
1500
500
500
DD230161.eps
264
DD230160.eps
KS500ED4051
DD202077.eps
DD202076.eps
100/250 A
135
500
865
250
DD202092.eps
DB414464.eps
Length
(mm)
Number of outlets
Cat. no.
Weight
(kg)
800
800
800
800
800
1
1
1
1
1
KSA100ED4081
KSA250ED4081
KSA400ED4081
KSA630ED4081
KSA1000ED4081
5.40
5.40
7.00
12.10
18.20
DB414463.eps
KSApppED4081
From 100 to 400 A
25
Changing direction
Description
All components for changing direction are supplied with a junction block.
The degree of protection of the busbar trunking is IP55 for indoor installations.
For the sprinkler protection, it is necessary to add a sealing kit (see page 43).
Elbows
DD230595r.eps
Standards
1 Edgewise: one model for turning right or left.
2 Flat : two models, one for turning up and the other for turning down.
Made-to-measure
bb Simple
3 Edgewise: one model for turning right or left.
4 Flat : two models, one for turning up and the other for turning down.
DD230500.eps
3
4
DD230574.eps
bb Made-to-measure angle
5 Edgewise: one model for turning right or left.
6 Flat : two models, one for turning up and the other for turning down.
5
6
DD230503.eps
26
Multiples
bb Simples
9 Edgewise: two models for turning down. One for turning right and the other for
turning left.
10 Flat: two models for turning up. One for turning right and the other for turning left.
DD230507.eps
10
DD230509.eps
11
12
Tee
DD230596.eps
27
Changing direction
Description
Cross
DD230573.eps
Zeds
The Z-connections allow you to get around obstacles.
Made-to-measure
bb Simples
15 Edgewise: two models for turning right or left.
16 Flat: one model for turning up or down.
DD230559.eps
16
15
DD230560.eps
17
18
28
Changing direction
Commercial numbers
and dimensions
Rating
(A)
DB404099.eps
DB404098.eps
Elbows 3L + N + PE or 3L + PE
100 to 250
400
500 to 630
Elbow to turn up or down
from 100 to 400 A.
Weight
(kg)
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
KSA250DLC40
KSA250DLE40
KSA250DLF40
KSA400DLC40
KSA400DLE40
KSA400DLF40
KSA630DLC40
KSA630DLE40
KSA630DLF40
KSA1000DLC40
KSA1000DLE40
KSA1000DLF40
3.15
5.00
5.00
3.80
5.60
5.60
13.40
12.10
12.10
19.00
16.70
16.70
KSApppDLC40
From 100 to 400 A
KSApppDLE40
From 100 to 400 A
KSApppDLF40
From 100 to 400 A
DD202058.eps
Cat. no.
DD210311.eps
DB404101.eps
DB404100.eps
800 to 1000
Direction (edgewise)
Tees 3L + N + PE or 3L + PE
DB404102.eps
Rating
(A)
Direction (edgewise)
100 to 250
Perpendicular
400
Perpendicular
500 to 630
Perpendicular
800 to 1000
Perpendicular
(1) Supplied without end cover.
Weight
(kg)
KSA250DTC40
KSA400DTC40
KSA630DTC40
KSA1000DTC40
4.30
5.20
15.80
22.60
KSApppDTC40
DB404103.eps
29
Changing direction
Commercial numbers
and dimensions
Cross 3L + N + PE or 3L + PE
DB404104.eps
Rating
(A)
100 to 250
400
500 to 630
800 to 1000
Direction (edgewise)
Cat. no.
Weight
(kg)
KSA250DXC40
KSA400DXC40
KSA630DXC40
KSA1000DXC40
4.50
7.00
11.00
11.50
DD230148.eps
DD230149.eps
165
KSApppDTC40
KSApppDTC40
Dimensions
Rating
(A)
100 to 400
500 to 1000
30
Dimensions (mm)
A
54
113
B
330
580
C
330
580
Made-to-measure changing
direction
From 100 to 1000 A
Cross 3L + N + PE or 3L + PE
DB404105.eps
Rating
(A)
100 to 250
400
500 to 630
Elbow to turn right or left.
DB404106.eps
800 to 1000
Direction
(edgewise)
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Cat. no.
KSA250DLC4A
KSA250DLE4A
KSA250DLF4A
KSA400DLC4A
KSA400DLE4A
KSA400DLF4A
KSA630DLC4A
KSA630DLE4A
KSA630DLF4A
KSA1000DLC4A
KSA1000DLE4A
KSA1000DLF4A
Weight
(kg/m)
4.00
4.00
4.00
6.80
6.80
6.80
12.20
12.20
12.20
14.40
14.40
14.40
KSApppDLC4A
147
46
DD413932.eps
DD230506.eps
KSApppDLE4A or KSApppDLF4A
From 100 to 400 A
Dimensions
Rating
(A)
100 to 400
500 to 1000
Direction
(edgewise)
Right or left
Upward or downward
Right or left
Upward or downward
Dimensions (mm)
A
B
200 to 695
200 to 695
250 to 745
250 to 745
290 to 785
290 to 785
290 to 785
290 to 785
31
Made-to-measure changing
direction
Commercial numbers
and dimensions
Rating
(A)
100 to 250
Direction
(edgewise)
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
400
500 to 630
Elbow with a made-to-measure angle
to turn right or left.
DB404108.eps
800 to 1000
Cat. no.
KSA250DLC4B
KSA250DLE4B
KSA250DLF4B
KSA400DLC4B
KSA400DLE4B
KSA400DLF4B
KSA630DLC4B
KSA630DLE4B
KSA630DLF4B
KSA1000DLC4B
KSA1000DLE4B
KSA1000DLF4B
Weight
(kg/m)
4.00
4.00
4.00
6.80
6.80
6.80
12.20
12.20
12.20
14.40
14.40
14.40
KSApppDLC4B
147
46
DD413932.eps
DD230505.eps
KSApppDLE4B or KSApppDLF4B
From 100 to 400 A
Dimensions
Rating
(A)
100 to 400
Direction
(edgewise)
Right or left
Upward ou Downward
500 to 1000 Right or left
Upward ou Downward
32
Dimensions (mm)
A
B
200 to 695
200 to 695
250 to 745
250 to 745
290 to 785
290 to 785
290 to 785
290 to 785
W (each 5)
90 to 180
90 to 180
90 to 180
90 to 180
Made-to-mesure zed 3L + N + PE or 3L + PE
DB404109.eps
Rating
(A)
Direction
(edgewise)
Cat. no.
Weight
(kg/m)
100 to 250
Right or left
400
Upward or downward
Right or left
500 to 630
Upward or downward
Right or left
800 to 1000
Upward or downward
Right or left
KSA250DZCH4A
KSA250DZCG4A
KSA250DZE4A
KSA400DZCH4A
KSA400DZCG4A
KSA400DZE4A
KSA630DZCH4A
KSA630DZCG4A
KSA630DZE4A
KSA1000DZCH4A
KSA1000DZCG4A
KSA1000DZE4A
4.00
4.00
4.00
6.80
6.80
6.80
12.20
12.20
12.20
14.40
14.40
14.40
DB404110.eps
Upward or downward
147
DD413934.eps
KSApppDZCH4A or KSApppDZCG4A
From 100 to 400 A
117
167
DD230562.eps
118
DD413936.eps
46
167
147
DD413937.eps
KSApppDZE4A
From 100 to 400 A
Dimensions
Rating
(A)
100 to 400
Direction (edgewise)
Right or left
Upward or downward
500 to 1000 Right or left
Upward or downward
Dimensions (mm)
A
B
200 to 695
200 to 395
250 to 745
200 to 395
290 to 785
200 to 575
290 to 785
200 to 575
C
200 to 695
250 to 745
290 to 785
290 to 785
33
Made-to-measure changing
direction with fire barrier
Commercial numbers
and dimensions
Rating
(A)
100 to 250
400
500 to 630
800 to 1000
DB404112.eps
Direction
(edgewise)
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Right or left
Upward
Downward
Cat. no.
KSA250DLC4CF
KSA250DLE4CF
KSA250DLF4CF
KSA400DLC4CF
KSA400DLE4CF
KSA400DLF4CF
KSA630DLC4CF
KSA630DLE4CF
KSA630DLF4CF
KSA1000DLC4CF
KSA1000DLE4CF
KSA1000DLF4CF
Weight
(kg/m)
8.40
8.40
8.40
9.90
9.90
9.90
18.00
18.00
18.00
24.20
24.20
24.20
KSApppDLC4CF
147
46
DD413933.eps
DD206217.eps
KSApppDLE4CF or KSApppDLF4CF
From 100 to 400 A
Dim.
A
900 to 1200
- with X > 450 mm
- with B - X > 450 mm
DD230583.eps
DD230582.eps
Rating
(A)
100 to 400
500 to 1000
34
Direction
(edgewise)
Right or left
Upward or downward
Right or left
Upward or downward
Dimensions (mm)
cote A
cote B
200 to 695
200 to 695
250 to 745
250 to 745
290 to 785
290 to 785
290 to 785
290 to 785
DB404113.eps
Direction
(edgewise)
Right or left
400
Upward or downward
Right or left
500 to 630
Upward or downward
Right or left
800 to 1000
Upward or downward
Right or left
Cat. no.
KSA250DZCH4CF
KSA250DZCG4CF
KSA250DZE4CF
KSA400DZCH4CF
KSA400DZCG4CF
KSA400DZE4CF
KSA630DZCH4CF
KSA630DZCG4CF
KSA630DZE4CF
KSA1000DZCH4CF
KSA1000DZCG4CF
KSA1000DZE4CF
Upward or downward
Zed with fire barrier to turn right or left.
Weight
(kg/m)
8.40
8.40
8.40
9.90
9.90
9.90
18.00
18.00
18.00
24.20
24.20
24.20
117
147
DD206218.eps
167
DB404114.eps
KSApppDZCH4CF or KSApppDZCG4CF
111
46
DD413938.eps
146
147
DD413935.eps
KSApppDZE4CF
From 100 to 400 A
DD230583.eps
DD230582.eps
Dimensions
Rating
(A)
100 to 400
Direction
(edgewise)
Right or left
Upward or downward
500 to 1000 Right or left
Upward or downward
Dimensions (mm)
A
B
250 to 745
200 to 395
200 to 695
200 to 395
290 to 785
200 to 575
290 to 785
200 to 575
C
250 to 745
200 to 695
290 to 785
290 to 785
900 to 1200
- with X > 450 mm
- with B - X > 450 mm
900 to 1200
- with X > 450 mm
- with C - X > 450 mm
35
Commercial numbers
and dimensions
Multiple elbows 3L + N + PE or 3L + PE
DB404115.eps
Rating
(A)
100 to 250
1st direction
(edgewise)
Downward
Upward
400
Downward
Upward
500 to 630
Downward
Upward
800 to 1000
Downward
Upward
2nd direction
(flat)
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Cat. no.
KSA250DMBK4A
KSA250DMCK4A
KSA250DMBL4A
KSA250DMCL4A
KSA400DMBK4A
KSA400DMCK4A
KSA400DMBL4A
KSA400DMCL4A
KSA630DMBK4A
KSA630DMCK4A
KSA630DMBL4A
KSA630DMCL4A
KSA1000DMBK4A
KSA1000DMCK4A
KSA1000DMBL4A
KSA1000DMCL4A
KSApppDMBK4A or KSApppDMCK4A
From 500 to 1000 A
KSApppDMBL4A or KSApppDMCL4A
From 100 to 400 A
DD230508.eps
DD230556.eps
DB404117.eps
DB404118.eps
Dimensions
Rating
(A)
100 to 400
500 to 1000
36
Dimensions (mm)
A
250 to 795
290 to 785
B
200 to 445
200 to 575
C
250 to 695
290 to 785
Weight
(kg/m)
4.00
4.00
4.00
4.00
6.80
6.80
6.80
6.80
12.20
12.20
12.20
12.20
14.40
14.40
14.40
14.40
Rating
(A)
100 to 250
1st direction
(edgewise)
Downward
Upward
400
Downward
Upward
500 to 630
Downward
Upward
DB404120.eps
Downward
Upward
2nd direction
(flat)
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Right
Left
Cat. no.
KSA250DMBK4CF
KSA250DMCK4CF
KSA250DMBL4CF
KSA250DMCL4CF
KSA400DMBK4CF
KSA400DMCK4CF
KSA400DMBL4CF
KSA400DMCL4CF
KSA630DMBK4CF
KSA630DMCK4CF
KSA630DMBL4CF
KSA630DMCL4CF
KSA1000DMBK4CF
KSA1000DMCK4CF
KSA1000DMBL4CF
KSA1000DMCL4CF
Weight
(kg/m)
8,40
8,40
8,40
8,40
9,90
9,90
9,90
9,90
18,00
18,00
18,00
18,00
24,20
24,20
24,20
24,20
KSApppDMBK4CF or KSApppDMCK4CF
From 500 to 1000 A
KSApppDMBL4CF or KSApppDMCL4CF
From 100 to 400 A
DD230558.eps
DD230557.eps
DB404121.eps
DD230583.eps
DD230582.eps
900 to 1200
- with X > 450 mm
- with B - X > 450 mm
900 to 1200
- with X > 450 mm
- with C - X > 450 mm
Dimensions
Rating
(A)
100 to 400
500 to 1000
Dimensions (mm)
A
250 to 745
290 to 785
B
200 to 445
200 to 575
C
250 to 695
290 to 785
37
Fixing systems
Description
DD230605.eps
DB403574.eps
38
Commercial numbers
and dimensions
Rating
(A)
100 to 400
500 to 1000
Max.
load (kg)
80
80
Mounting
Under ceiling or I-beam (1)
Under ceiling or I-beam (1)
Weight
(kg)
2.70
2.80
DB403871.eps
KSB400ZFKP1
Pendant kit.
328
428
Rating
(A)
100 to 400
Max. load
(kg)
Mounting
220
Wall or pendant
Max. load
(kg)
Mounting
200
Wall or pendant
KFBCA81200
Weight
(kg)
0.40
DD202193.eps
KFBCA81200
Rating
(A)
500 to 1000
KFBCA81300
Weight
(kg)
0.60
DD202199.eps
KFBCA81300
39
Commercial numbers
and dimensions
Rating
(A)
DD202296.eps
Max. load
(kg)
Mounting
100 to 400
70
500 to 1000
70
100 to 400
100 to 400
All
Wall or suspended on
threaded rod (1)
Wall or suspended on
threaded rod (1)
Wall or suspended on
threaded rod (1)
Wall or suspended on
threaded rod (1)
Floor
DD210301.eps
DD202297.eps
KSB1000ZF1
DD230686.eps
KSA80EZ5
40
0.30
10
KSB1000ZF1
0.40
10
KSA80EZ3
0.30
10
KSA80ZG20
0.30
KSA80EZ5
0.70
Weight
(kg)
Bottom support
Rating
(A)
250
400
500 to 630
800 to 1000
Cat. no.
Weight
(kg)
4.50
5.00
7.00
7.30
KSB250ZV1
KSB400ZV1
KSB630ZV1
KSB1000ZV1
KSBpppZV1
DB414465.eps
55 mm y Z y 105 mm
Floor guide
Used with the bottom support.
Rating
(A)
All
Cat. no.
Weight
(kg)
0.70
KSB1000ZV2
For floors higher than 3.5 metres, it is advised to use two guides per floor.
KSB1000ZV2
DD210643.eps
65 mm y A y 95 mm
Floor supports
Set of 2 floor supports.
Rating Max. permissible Mounting
(A)
weight (kg)
Set of 2 floor supports
Cat. no.
Order in
Weight
multiple of (kg)
All
440
Cantilever arm, 200 mm
1.80
All
Wall
KFBCA81200
0.40
220
For floors higher than 3.5 metres, it is advised to use a floor guide in addition to the support.
KFBCA81200
DD230606.eps
DB414469.eps
KSB1000ZV3
41
Description
Accessories
DD205043.eps
Lead-sealing system
This prohibits access to live parts. Two systems are available: one is installed either
on the power supply box or on the busbar connector, and the other on the tap-off
points.
Spare parts
Sprinkler kit
To comply with the sprinkler tests (guaranteeing operation under vertically and
horizontally sprayed water for 50 minutes), each electrical jointing system should be
fitted with a reinforced protection kit (the jointing sleeve).
Separate parts
Electrical and mechanical connecting plates
These are blocks fitted with elastic contacts in silver-plated copper.
They automatically provide electrical connection of all conductors.
IP55 plugs
These plugs protect the busbar trunking tap-off points.
Adapters
KSA1000ZJ4
KSA630ZJ4 or
KSA1000ZJ4
KSA500FR425
Beginning of line
End of line
Line power
100 A
160 A
100 A
100 A
250 A
100 A
160 A
100 A
100 A
250 A
100 A
100 A
160 A
250 A
160 A
250 A
160 A
160 A
1000 A
800 A
800 A
800 A
1000 A
800 A
500 A
630 A
500 A
500 A
800 A
500 A
500 A
1000 A
500 A
630 A
500 A
500 A
800 A
500 A
500 A
1000 A
500 A
500 A
630 A
800 A
630 A
630 A
1000 A
630 A
800 A
630 A
630 A
1000 A
630 A
630 A
400 A
500 A
400 A
500 A
400 A
400 A
630 A
400 A
400 A
800 A
400 A
400 A
1000 A
400 A
400 A
400 A
630 A
630 A
400 A
800 A
800 A
400 A
1000 A
1000 A
Reducer element
These part allow connection of KS busbar trunking of different sizes and ratings
(Size 1 = from 100 to 400 A; Size 3 = from 500 to 1000 A).
Protection end-pieces
The protection end-pieces insulate and protect the connectors at the end of busbar
trunking. They are installed on the last busbar trunking of the distribution line.
42
Accessories
Commercial numbers
and dimensions
Rating
(A)
All
For
Feed unit cover and jointing
screws
Tap-off outlets
Order in
multiple of
20
Cat. no.
KSB1000ZP1
Weight
(kg)
0.0035
20
KSB1000ZP2
0.002
Cat. no.
Weight
(kg)
KSA250ZJ4
KSA400ZJ4
KSA630ZJ4
KSA1000ZJ4
1.60
2.00
3.50
4.50
KSB400ZB1
KSB1000ZB1
0.015
0.020
KSB400ZB2
KSB1000ZB2
1.00
1.00
DB403578.eps
KSB1000ZP1
KSB1000ZP2
Rating
(A)
DD202020.eps
DD202019.eps
Spare parts
KSA400ZJ4
DD202060.eps
KSA250ZJ4
Order in
multiple of
DD202053.eps
DD202021.eps
DD202061.eps
KSA1000ZJ4
KSB400ZB1
KSB1000ZB1
KSB1000ZB2
KSB400ZB2
KSB1000ZB2
DD205042.eps
KSB400ZB2
DD205044.eps
DD205045.eps
DD205041.eps
DD202062.eps
KSA630ZJ4
43
Accessories
Commercial numbers
and dimensions
Adapters
DD202054.eps
DD202068.eps
Rating
(A)
100 to 250
250
400
500
630 to 800
KSA250FA4
KSA400FA4
Cat. no.
KSA250FA4
KSA250FA4
KSA400FA4
KSA500FA4
KSA800FA4
Weight
(kg)
1.35
1.35
2.90
3.65
4.00
DD202082.eps
DD202087.eps
KSA250FA4
For
KSA500FA4
DD206163.eps
DD202088.eps
KSA400FA4
KSA800FA4
DD202089.eps
Reducer element
Cat. no.
KSA500FR425
Weight
(kg)
1.60
DD230143.eps
KSA500FR425
DD230142.eps
DD230144.eps
Rating For
(A)
All
Connecting 400 A busbar trunking to 500 to 1000 A
trunking
KSA500FR425
76
142
Protection end-pieces
DD230040.eps
Rating
(A)
100 to 400
500 to 1000
For
Cat. no.
KSA400AF1
KSA1000AF1
44
Dimensions (mm)
A
B
DD206208.eps
186
KSApppAF1
DD206207.eps
KSApppAF1
KSA400AF1
KSA1000AF1
B
102
147
67
124
Weight
(kg)
0.25
0.40
Accessories
Rating
3L + N + PE
(A)
Cable-connection feed unit N1
200/315
KV031AB40001
400/630
KV063AB40001
800
KV080AB40001
Cable-connection feed unit N2
200/315
KV031AB40002
400/630
KV063AB40002
800
KV080AB40002
Single-feeder tap-off unit (1)
400
Standard joint kits
200/315
400/630
800
Joint/tap-off kits
200/315
400/630
800
KV0ppCB71103E
KV0ppYApp
3L + N + PER
Weight
(kg)
KV031AB70001
KV063AB70001
KV080AB70001
4.00
7.70
14.70
KV031AB70002
KV063AB70002
KV080AB70002
4.00
7.70
14.70
KV040CB71103E
7.00
KV031YA4
KV063YA4
KV080YA4
1.50
2.40
3.10
KV025YA4
KV040YA41
KV040YA42
1.50
2.40
3.10
20
10
30
20
70
20
67
10
DB414036.eps
20
DB414035.eps
8,5
DB414034.eps
Rating
200 and 315 A
40
15
h
60
60
50
H
44
71
114
Dimensions (mm)
A
B
200
650
200
700
200
700
C
300
400
450
D
450
500
500
Y
150
170
190
DB414037.eps
Configuration examples
DB414033.eps
45
46
Canalis KS
48
Feed units
49
50
51
52
53
48
49
50
51
52
Tap-off units
55
Characteristics 83
47
Description
DD206221.eps
Used to feed a KS line by cables or directly from the busbars in a switchboard. They can
be mounted at the end of a line (end feed, left or right) or in the middle (central feed).
Feed units with circuit breaker protection (not supplied) are also available.
Feed units
Commercial numbers
and dimensions
Rating Mounting
(A)
100
Connection
Right or left
Terminals
Weight
(kg)
1.85
DD210296.eps
KSA100AB4
KSA100AB4
Rating Mounting
(A)
100 to
250
400
Right
800 to
1000
Right
Left
Left
Lugs
(M10 screws)
Lugs
(M10 screws)
Lugs
(M12 screws)
Lugs
(M12 screws)
Lugs
(M12 screws)
Lugs
(M12 screws)
Cat. no.
Weight
(kg)
KSA250AB4
7.20
KSA400AB4
8.80
KSA630ABD4
18.50
KSA630ABG4
18.50
1 x 300
or 2 x 120
1 x 300
or 2 x 240
1 x 300
or 2 x 240
4 x 240
1 x 300
or 2 x 120
1 x 300
or 2 x 240
1 x 300
or 2 x 240
4 x 300
KSA1000ABD4 24.50
4 x 240
4 x 300
KSA1000ABG4 24.50
DD202028.eps
KSA630ABG4
KSA1000ABD4
DD202063.eps
KSA1000ABG4
DD202072.eps
KSA630ABD4
DD202070.eps
KSA400AB4
DD210642.eps
DD210297.eps
Right or left
500 to
630
KSAjjpppAB4
KSA250AB4
Right or left
Connection
Cable exit.
Rating
(A)
Designation
Cat. no.
KSA250ABCB4 4.8
KSA400ABCB4 5.3
350
DB405241.eps
DB405240.eps
250
Communication box for KS feeder 250 A
400
Communication box for KS feeder 400 A
KSA250ABCB4
KSA400ABCB4
Weight
(kg)
411,5
KSAABCB4
127
49
Commercial numbers
and dimensions
Rating Mounting
(A)
KSAjjpppABT4
From 100 to 400 A.
100 to
250
Central
400
Central
500 to
630
800 to
1000
Central
Central
DD202049.eps
DB416316.eps
KSA250ABT4
KSAjjpppABT4
From 500 to 1000 A.
DB416317.eps
KSA400ABT4
DD202051.eps
KSA630ABT4
DD202064.eps
KSA1000ABT4
Cable exit.
50
Connection
Lugs
(M10 screws)
Lugs
(M10 screws)
Lugs
(M10 screws)
Lugs
(M12 screws)
Cat. no.
Weight
(kg)
KSA250ABT4
12.90
2x 240
2x 240
KSA400ABT4
15.50
3 x 240
3 x 300
KSA630ABT4
30.50
4 x 240
4 x 300
KSA1000ABT4 41.50
400
NSX 250
Curve N. H or L
Rotary handle 29338
NSX 400
Curve N, H or L
Rotary handle 32598
Cat. no.
Right
Left
NSX
NSX
KSA250ABDD4 16.50
KSA250ABGD4 16.50
Right
NSX
KSA400ABDD4 22.00
Left
NSX
KSA400ABGD4 22.00
DD230542.eps
KSA250ABDG4
309
353
KSAjjpppABpD4
DD230541.eps
KSA250ABDD4
232
276
645
742
232
276
645
742
KSA400ABDG4
346
393
DD230540.eps
KSA400ABDD4
DD230539.eps
Weight
(kg)
353
309
250
Mounting Connection
232
276
764
860
393
346
DD230173.eps
232
276
764
860
Cable exit.
250
400
Mounting Connection
Cat. no.
Weight
(kg)
Right
Left
Right
Left
KSA250ABDD5
KSA250ABGD5
KSA400ABDD5
KSA400ABGD5
17.00
17.00
23.00
23.00
NSX
NSX
NSX
NSX
645
742
645
742
232
276
KSA400ABDG5
393
346
DD230548.eps
KSA400ABDD5
232
276
309
353
DD230550.eps
KSA250ABDG5
353
309
232
276
DD230549.eps
KSAjjpppABpD5
DD230551.eps
KSA250ABDD5
764
860
346
393
DD230173.eps
764
860
232
276
Cable exit.
51
Commercial numbers
and dimensions
Rating
(A)
100 to 250
400
500 to 630
800 to 1000
Mounting
Connection
Cat. no.
Right or left
Right or left
Right or left
Right or left
KSA250AE4
KSA400AE4
KSA630AE4
KSA1000AE4
DD202050.eps
KSAjjpppAE4
From 100 to 400 A.
DD230005.eps
Dimensions
A
B
C
D
E
KSAjj630AE4
From 630 to 1000 A.
DD202052.eps
52
100 to 250 A
243
261.5
108
278
294
400 A
261
279.50
117
318
334
Weight
(kg)
1.70
1.90
4.70
6.60
DB414710.eps
Designation
End
Central
End
Central
End
Central
End
Central
Dimensions Cat. no
KSA250ABZFL21
A
300
B
168.5
C
198
D
69
DB414711.eps
No. of
holes
of the
gland plate
KSA250AB4
1
KSA250ABT4 1
KSA400AB4
1
KSA400ABT4 1
KSA630AB4
2
KSA630ABT4 2
KSA1000AB4 2
KSA1000ABT4 2
KSA250ABTZFL21
391
168.5
198
69
Cat. no.
Weight
(kg)
KSA250ABZFL21
KSA250ABTZFL21
KSA400ABZFL21
KSA400ABTZFL21
KSA630ABZFL21
KSA630ABTZFL21
KSA1000ABZFL21
KSA1000ABTZFL21
0.30
0.45
0.50
0.75
0.78
0.72
1.08
0.91
KSA400ABZFL21
340
208.5
198
69
KSA400ABTZFL21
491
208
198
69
DB414712.eps
KSA250ABZFL21 - KSA250ABTZFL21
KSA400ABZFL21 - KSA400ABTZFL21
Dimensions Cat. no
KSA630ABZFL21
A
446
B
276
C
198
D
69
E
50
KSA1000ABZFL21
446
358
198
69
70
Dimensions Cat. no
KSA630ABTZFL21
A
502
B
227
C
198
D
69
E
30
KSA1000ABTZFL21
552
252
198
69
50
DB414713.eps
KSA630ABZFL21 - KSA1000ABZFL21
KSA630ABTZFL21 - KSA1000ABTZFL21
53
Commercial numbers
and dimensions
54
Canalis KS
Tap-off units
Contents
Tap-off units
56
60
62
63
64
65
68
70
71
72
73
74
75
76
77
78
79
80
81
82
56
81
Characteristics 83
55
Tap-off units
Description
Tap-off units
For rapid connection of loads or secondary lines, in compliance with installation standards IEC 60364 and regulations, whatever the system
earthing arrangement (TT, TNS, TNC or IT).
They can be handled and removed under off-load conditions with the trunking energised.
The tap-off outlets are automatically opened or closed when tap-off units are connected or removed.
With the cover open, no live parts are accessible.
The degree of protection is IPxxB (protected against access with a finger).
56
DD210278.eps
DD210280.eps
DD210279.eps
DD210281.eps
bb Colour: RAL 9001 white for the casing and the grip
zones and transparent green for the cover,The fixing
mechanisms are in RAL 7016.
bb Material: self-extinguishing, halogen free insulating
plastic (fire resistant and very high temperature
withstand).
bb Other characteristics: cable gland drilling zone,
stainless steel screws and the door can be lead sealed.
DD210461.eps
DD210277.eps
DD206164.eps
DD206165.eps
The degree of protection is IP55 for indoor installations as standard (noaccessories are required).
For tap-units with circuit breakers, a number of safety devices prevents from:
bb plugging and unplugging in the tap-off unit when the cover is closed
bb closing the cover before the tap-off unit is locked onto the trunking
bb having access to the electrical equipment and the terminals when energised
bb opening the cover in the position ON (tap-off units equipped with a Compact
NSX or NG circuit breaker)
bb the tap-off units accept modular devices in multiples of 18 mm wide modules.
These tap-off units can be equipped with certain accessories such as circuit-opening
contacts on the cover, lead seals, etc.
DD210283.eps
DD210284.eps
DB414226-40.eps
DD230656.eps
57
Description
Tap-off units
DD210459.eps
Rated current: 32 A
Capacity: 8 modules in multiples of 18 mm wide
Two versions are available:
b pre-equipped with a power sockets
b customisable:
v two 90 x 100 mm openings for PK-type (screw connections) or PratiKa (fast and
reliable connection without stripping) industrial or household sockets
v direct mounting for industrial IEC 16 A 5P or IEC 32
A 3, 4 or 5P sockets
v mounting on a 65 x 85 mm clip-on adapter plate for industrial IEC 16 A 3P or 5P
and household 10/16 A 2P + PE sockets.
DD210288.eps
58
DB403839.eps
Tap-off units (with and without isolators) equipped with a surge arrester
These tap-off units (with and without isolators) are pre-equipped with a modular Type
2 surge arrester, with integrated disconnection device.
2 versions of 3P+N protection are available, based on Quick PF10 or Quick PRD40r.
These units are ready for use, can be plugged directly into the busbar trunking and
do not require any additional wiring.
They should be positioned at least 30 m upstream of each load to be protected.
Tap-off unit covers can be lead sealed to prevent the surge arrester being tampered
with by unauthorised persons.
59
Description
The number of tap-off units presented below corresponds to an installation on a single side of the Canalis prefabricated busbar trunking
system.
This number is doubled for installations in which the tap-off units can be mounted on both sides.
KSB63SM8 (1)
8 modules
KSB100SM12 (1)
12 modules
KSB160SM24 (1)
24 modules
DD230630.eps
DD230629.eps
DB405627.eps
DD230627.eps
KSB32CM55 (1)
KSB160SM24 (1)
24 modules
DD230632.eps
DD230631.eps
KSB32CP (1)
(1) For more details on tap-off units, refer to the Canalis 20 to 1000 A prefabricated busbar trunking system catalogue (reference DEBU022EN).
: Outlets not usable for this type of tap-off.
60
DB416224.eps
61
Commercial numbers
and dimensions
Busbar trunking
Tap-off unit
DB414730.eps
Tap-off polarity
Tap-off diagram
(e.g. fuse protection)
TNC
TNC
3L + PEN
DB414731.eps
DD206168.eps
Earthing system
arrangement
KSBpppSVp
DD210472.eps
Rating
(A)
50
100
160
Cat. no.
Cat. no.
Weight
(kg)
KSB50SV4
KSB100SV4
KSB160SV4
KSB50SV5
KSB100SV5
KSB160SV5
2.20
4.80
8.00
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
KSB50SVp, KSB100SVp
50 A
356
153
167
309
103
202
100 A
444
178
202
397
128
220
32
182
KSB160SVp
300
X = 432.5 (KSB50SVp)
X = 545.5 (KSB100SVp)
X = 630.5 (KSB160SVp)
Dim.
A
B
C
D
E
F
DD230577.eps
DD2020081.eps
DD230553.eps
KSB160SVp
32
395
450
257
Cable exit
Centre line of tap-off outlets
(1) Protruding
Designation
For feed units
Rating (A)
Cat. no of
tap-off units
Mounting
50
KSB100SV4
KSB100SV5
KSB63SM48
KSB63SM58
63
KSB63PMP
62
Cat. no
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
Busbar trunking
Tap-off unit
DB414732.eps
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)
KSB32CM55
Rating
(A)
Number of
18 mm
modules (3)
Connection
32
Pre wired
Max. size
(mm)
Flexible Rigid
6
10
ISO 32 max.
Weight
(kg)
KSB32CM55
0.60
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Supplied with blanking plate (1 x 5 divisible).
(4) Maximum diameter for a multipolar cable.
KSB32CM55
DD210453.eps
Cable exit
Centre line of tap-off
outlets
Protruding
KSB63SM p8
KSB100SM p12
Rating
(A)
Number of
18 mm
modules (3)
63
100
12
Connection
Busbar trunking
Tap-off unit
Max. size
(mm)
Flexible Rigid
Copper cable 16
16
lugs
Copper cable 35
35
lugs
3L + N + PE (2)
3L + PEN
DD414772.eps
Earthing
system
arrangement
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)
DD414771.eps
DD210454.eps
Weight
(kg)
ISO 50 max.
KSB63SM48
KSB63SM58
ISO 63 max.
KSB100SM412
KSB100SM512 5.00
2.40
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed).
(3) Supplied with blanking plates: (1 x 5 divisible (8 modules) or 2 x 5 divisible (12 modules)).
(4) Maximum diameter for a multipolar cable.
(5) Not compatible with NG circuit breaker, see page 68.
Dim.
A
B
C
D
E
F
DD210455.eps
DD2020081.eps
X = 432.5 (KSB63SMp8)
X = 545.5 (KSB100SMp12)
Cable exit
Centre line of tap-off outlets
63A
357
158
167
309
108
202
100A
444
183
202
397
133
220
(5) Protruding
63
Commercial numbers
and dimensions
28-module tap-off unit for Compact NSX circuit breakers and modular devices
DD206166.eps
KSB250SM428
Rating
(A)
Type of circuit
breaker
250
NSX 250
Curve N, H or L
Connection
NSX
Rigid
150
DB414732.eps
Cat. no.
Weight
(kg)
ISO 32 max.
KSB250SM428
13.50
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
DB414409.eps
DD230164.eps
KSB250SM428
Cable exit
Centre line of tap-off outlets
64
(4) Protruding
(5) 6 modules
(6) 8 modules
Earthing system
arrangement
Busbar trunking
Tap-off unit
DB414732.eps
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)
DD414762.eps
DD210461.eps
The cover of the tap-off unit may be opened only when the circuit breaker is in the
On/Off position.
KSBpppDCp
Max. size
(mm2)
NSX
Flexible Rigid
70
70
ISO 32 max.
NSX
150
150
NSX
240
240
Connection
160
250
NSX 250
Curve N, H or L
Rotary handle 29338
NSX 400
Curve N, H or L
Rotary handle 32598
400
Cat. no.
Weight
(kg)
KSB160DC4
KSB160DC5
9.00
ISO 40 max.
KSB250DC4
KSB250DC5
12.50
ISO 50 max.
KSB400DC4
KSB400DC5
18.00
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
DD210462.eps
DD2020081.eps
KSB160DCp
X = 625.5 (KSB160DCp)
X = 726.5 (KSB250DCp)
X = 976.5 (KSB400DCp)
DD210463.eps
KSB250DCp
DD210464.eps
KSB400DCp
Cable exit
Centre line of tap-off outlets
(4) Protruding
65
Commercial numbers
and dimensions
Tap-off units for Compact NSX, fixed, circuit breakers with electrical handle
KSBpppDBp12
Type of circuit
breaker
160
NSX 160
Curve N, H or L
NSX 400
Curve N, H or L
400
DB414732.eps
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)
Rating
(A)
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
Busbar trunking
Tap-off unit
TNC
TNC
3L + PEN
DD414762.eps
DD413939.eps
Earthing system
arrangement
Max. size
(mm2)
NSX
Flexible Rigid
70
70
ISO 32 max.
KSB160DB412
KSB160DB512 13.50
NSX
240
ISO 50 max.
KSB400DB412
KSB400DB512 19.00
Connection
240
Cat. no.
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
532
500
DD413940.eps
DD2020081.eps
KSB160DBp12
73
X = 727.5 (KSB160DBp12)
X = 973.5 (KSB400DBp12)
303
250
532
500
DD413941.eps
KSB400DBp12
732
700
400
732
700
Cable exit
Centre line of tap-off outlets
66
(4) Protruding
Weight
(kg)
The cover of the tap-off unit may be opened only when the circuit breaker is in the
On/Off position. Tap-off units KSB250DD412 includes 2 opening for type FL21 cable
gland plate (not supplied) (see page 82).
Earthing system
arrangement
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
Busbar trunking
Tap-off unit
DB414732.eps
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)
KSB160DD411
Rating
(A)
Type of circuit
breaker
160
250
400
Connection
Max. size
(mm2)
Cat. no.
Weight
(kg)
NSX
Flexible
70
Rigid
70
ISO 32 max.
KSB160DD411
13.50
NSX
150
150
ISO 40 max.
KSB250DD412
16.00
NSX
240
240
ISO 50 max.
KSB400DD411
20.00
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
KSB250DD412
450
DD413943.eps
632
600
DD413944.eps
DD2020081.eps
KSB160DD411
73
X = 727 (KSB160DD)
X = 877 (KSB250DD)
X = 1073 (KSB400DD)
632
600
106
310
360
360
310
73
450
418
DD413945.eps
KSB400DD411
732
702.5
400
732
702.5
Cable exit
Centre line of tap-off outlets
(4) Protruding
67
Commercial numbers
and dimensions
Earthing system
arrangement
Busbar trunking
Tap-off unit
DB414732.eps
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
TNC
TNC
3L + PEN
DD414762.eps
DD202154.eps
The cover of the tap-off unit may be opened only when the circuit breaker is in the
On/Off position.
KSB160SMp13
Rating
(A)
160
Rotary handle
28060 - NG160
Max. size
(mm2)
Cat. no.
Weight
(kg)
Flexible Rigid
NG
Rotary handle
19088 - NG125
70
70
ISO 32 max.
KSB160SM413
KSB160SM513 8.50
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
DD202155.eps
DD2020081.eps
KSB160SMp13
X = 625.5
Cable exit
Centre line of tap-off outlets
68
(4) Protruding
Type of circuit
breaker
250
NSX 250
Curve N, H or L
Connection
NSX
Rigid
150
Cat. no.
Weight
(kg)
ISO 32 max.
KSB250DC4SP
13.50
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
KSB250DC4SP
DD230166.eps
Rating
(A)
DD230167.eps
KSB250DC4SP
DB414732.eps
Cable exit
Centre line of tap-off outlets
(4) Protruding
69
Commercial numbers
and dimensions
TT - TNS - TNC
Tap-off polarity
Diagram
3L + N + PE (1)
DD414763.eps
DD205753.eps
L1 L2 L3 N PE
KSBQPF
Protection Lightning arrester
type
cartridges
(supplied)
Permissible
short-circuit
Cat. no.
Max. discharge
current
Weight
(kg)
Isc (kA)
Imax (kA)
Pre-wired
6
10
KSBQPF
1.3
SPD (Surge Protection Device) installed: Quick PF10 SPD, 3P+N, cat. no. 16618 (Type 2
monoblock surge arrester, with fixed cartridges and integrated disconnection device, certified
IEC 81643-1, EN 61643-11).
(1) Also suitable for tap-off unit 3L + PE (N not distributed).
Fixed
DD511623.eps
Type 2
Connection
Busbar trunking
TT - TNS - TNC
DD414763.eps
3L + N + PE (1)
L1 L2 L3 N PE
KSBQPRD
Type 2
Removable
Connection
Permissible
short-circuit
309
357
Centre line of tap-off outlets
70
Cat. no.
Weight
(kg)
Isc (kA)
Imax (kA)
Pre-wired
25
40
KSBQPRD
3.40
Surge arrester installed: Quick PRD40r surge arrester, 3P+N, cat. no. 16294 (Type 2
monoblock surge arrester, with fixed cartridges and integrated disconnection device, certified
IEC 81643-1, EN 61643-11).
(1) Also suitable for tap-off unit 3L + PE (N not distributed).
167
DD202008.eps
X= 432.5
Max. discharge
current
202
Surge arrester
cartridges
(supplied)
DD511624.eps
Protection
type
108
158
(5) Side projection.
KSB32CPppp
Cat. no.
Weight
(kg)
2P + T
KSB32CP11D
2.90
230
2P + T
KSB32CP11F
2.90
230
2P + T
KSB32CP15F
3.00
Industrial socket
415
3P+N+T
230
2P + T
KSB32CP15D
3.00
Industrial socket
16
415
3P+N+T
Industrial socket
16
230
2P + T
KSB32CP35
3.10
Industrial socket
16
415
3P+N+T
KSB32CP
2.70
Equipment
Q. (3) Type
Tap-off
unit with
flushmounted
power
sockets
230
Empty
tap-off unit
32
32
TT-TNS-TNC (1)
TT-TNS-TNS (1)
3L + N + PE
Busbar trunking
Tap-off unit
DD414764.eps
DD210456.eps
Current
(A)
16
Voltage Polarity
(V)
To be equipped
DD210459.eps
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Supplied with blanking plate (1 x 5 divisible).
(3) Quantity.
DD210460.eps
KSB32CPppp
KSB32CP
(4) Protruding
Power sockets
PG149203.eps
Designation
Industrial sockets
Pratika
Rated current
(A)
16
Rated voltage
(V AC)
200-250
2P + T
3P + N + T
2P + T
3P + N + T
2P + T
3P + N + T
2P + T
3P + N + T
2P + T
2P + T
380-415
32 (5)
PKY16F723
200-250
380-415
Household NF sockets
Household Schuko sockets
Screw-on plate
10 to 16
250
10 to 16
250
For blanking of unused openings
For adapting 65 x 85 mm power-socket bases
65 x 85
90 x 100
65 x 85
90 x 100
90 x 100
90 x 100
90 x 100
90 x 100
65 x 85
65 x 85
PKY16F723
PKY16F725
PKY16F733
PKY16F735
PKY32F723
PKY32F725
PKY32F733
PKY32F735
81140
81141
13137
13136
Weight
(kg)
0.10
0.09
(5) The sum of currents in the 2 sockets installed on the tap-off unit y 32 A.
71
Commercial numbers
and dimensions
Earthing system
arrangement
Busbar trunking
Tap-off unit
DB414732.eps
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)
KSBpppDCpTRE
Rating
(A)
250
400
DD210465.eps
The cover of the tap-off unit may be opened only when the circuit breaker is in the
On/Off position.
Max. size
(mm2)
Cat. no.
Flexible Rigid
NSX CT block 150
150
ISO 40 max.
ISO 50 max.
240
DD2020081.eps
(1) The neutral must be protected or not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
DD202085.eps
KSB250DCpTRE
X = 726.5 (KSB250DCpTRE)
X = 976.5 (KSB400DCpTRE)
DD202086.eps
KSB400DCpTRE
Cable exit
Centre line of tap-off outlets
72
Weight
(kg)
(4) Protruding
Disconnector units
Earthing system
arrangement
Busbar trunking
TT-TNS-TNC-IT (1)
Tap-off
TT-TNS-TNS-IT (1)
TNC
3L + N + PE (2)
3L + PEN
KSB160SM424
Rating
(A)
Number
of 9mm
mod.
Number of
18mm (3)
mod.
160
48
24
Connection
Cable gland
(4) (not
supplied)
Cat. no.
Cat. no.
Weight
(kg)
Rigid
Not
ISO 50 max. KSB160SM424
KSB160SM524 10.69
used
(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system.
(2) Also suitable for 3L + PE tap-off (N not distributed).
(3) Supplied with blanking plate 1 x 5 divisible (8 modules) or 2 x 5 divisible (12 modules).
(4) Max. diameter for a multipole cable.
Lugs
Flexible
16
DD414765.eps
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker protection)
TNC
DD414766.eps
DD206222.eps
DD230652.eps
DD230657.eps
KSB160SM424
303
DD230847_r.eps
X = 650
32
395
450
494
177
230
308
Cable outlet
Tap-off outlet axis
73
Commercial numbers
and dimensions
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
Busbar trunking
Tap-off unit
DD414767.eps
Tap-off polarity
Tap-off diagram (e.g. fuse protection)
KSB32CF5
Rating
(A)
For fuses
(not supplied)
Connection
32
NF 10 x 38
Type gG: 25 A max.
Type aM: 32 A max.
Max. size
(mm2)
Flexible Rigid
6
10
ISO 32 max.
Weight
(kg)
KSB32CF5
0.60
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.
KSB32CF5
DD202011.eps
Cable exit
Centre line of tap-off outlets
(4) Protruding
Rating
(A)
For fuses
(not supplied)
Connection
50
NF 14 x 51
Type gG, 50 A max.
Type aM, 50 A max.
Cable clamp
terminals
100
NF 22 x 58
Type gG, 100 A max.
Type aM, 100 A max.
Copper cable
lugs
DD414768.eps
Tap-off polarity
Tap-off diagram (e.g. fuse
protection)
KSBpppSFp
Busbar trunking
Tap-off unit
DD414769.eps
DD210466.eps
Max. size
(mm2)
Flexible Rigid
25
25
ISO 50 max.
50
ISO 63 max.
50
Cat. no.
Weight
(kg)
KSB50SF4
KSB50SF5
2.40
KSB100SF4
KSB100SF5
5.00
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.
DD2020081.eps
DD210467.eps
KSB50SFp, KSB100SFp
X = 432.5 (KSB50SFp)
X = 545.5 (KSB100SFp)
74
Dim.
A
B
C
D
E
F
Cable exit
(4) Protruding
Centre line of tap-off outlets
50 A
356
153
167
309
103
202
100 A
444
178
202
397
128
220
Busbar trunking
Tap-off unit
KSB160SEp
KSB250SEp
KSB400SEp
DD414768.eps
Tap-off polarity
Tap-off diagram
(e.g. fuse protection)
DD414769.eps
DD210472.eps
Cat. no.
ISO 63 (3)
max.
KSB100SE4 (5)
70
ISO 32 (4)
max.
KSB160SE4
KSB160SE5
11.00
70
70
ISO 32 (4)
max.
KSB160SF4
KSB160SF5
11.00
Copper cable
lugs
150
150
ISO 40 (4)
max.
KSB250SE4
KSB250SE5
20.00
Copper cable
lugs
240
240
ISO 50 (4)
max.
KSB400SE4
KSB400SE5
29.20
Rating
(A)
For blade-type
fuses
(not supplied)
Connection
Max. size
(mm2)
100
Size 00
Type gG, 100 A max.
Type aM, 100 A max.
Copper cable
lugs
160
Size 00
Type gG, 160 A max.
Type aM, 160 A max.
Copper cable
lugs
70
Size 0
Type gG, 160 A max.
Type aM, 160 A max.
Copper cable
lugs
250
Size 1
Type gG, 250 A max.
Type aM, 250 A max.
400
Size 2
Type gG, 400 A max.
Type aM, 400 A max.
Flexible Rigid
35
50
Weight
(kg)
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100 A dimensions, see Tap-off units with insulators for cylindrical fuses, page 74,
cat. no. KSB100SFp.
Dim.
A
B
C
D
E
F
G
H
DD210473.eps
DD2020081.eps
KSB160Spp, KSB250SEp
X = 577.5 (KSB160Spp)
X = 777 (KSB250SEp)
X = 855 (KSB400SEp)
160 A
450
257
300
395
207
032
032
182
250 A
600
308
400
548
258
032
032
192
DD210474.eps
KSB400SEp
Cable exit
Centre line of tap-off outlets
(6) Protruding
75
16 to 63 A tap-off units
for DIN fuses
Commercial numbers
and dimensions
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
Busbar trunking
Tap-off unit
DD414767.eps
Tap-off polarity
Tap-off diagram (e.g. fuse
protection)
KSB16CN5
Rating
(A)
For fuses
(not supplied)
Connection
16
Neozed E14
Tunnel terminals
Max. size
(mm2)
Flexible
6
Rigid
10
Cat. no.
Weight
(kg)
ISO 32 max.
KSB16CN5
0.60
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.
KSB16CN5
DD202295.eps
Cable exit
Centre line of tap-off outlets
(4) Protruding
Rating
(A)
For fuses
(not supplied)
25
50
63
Diazed E27
Neozed E18
Diazed E33
Connection
DD414768.eps
Tap-off polarity
Tap-off diagram
(e.g. fuse protection)
KSBpppSpp
Busbar trunking
Tap-off unit
Max. size
(mm2)
Flexible
Tunnel terminals 25
Tunnel terminals 25
Tunnel terminals 25
Rigid
25
25
25
DD414769.eps
DD210466.eps
KSB25SD4
KSB50SN4
KSB63SD4
Cat. no.
Weight
(kg)
KSB25SD5
KSB50SN5
KSB63SD5
2.40
2.40
2.40
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.
Dim.
DD205037.eps
DD2020081.eps
KSBpppSpp
76
A
B
C
D
E
F
Cable exit
Centre line of tap-off outlets
(4) Protruding
25 and 50 A 63 A
356
153
167
309
103
202
444
178
202
397
128
220
Busbar trunking
Tap-off unit
Tap-off polarity
Tap-off diagram (e.g.
fuse protection)
DD414769.eps
DD210472.eps
KSB160SEp
KSB250SEp
Cable gland Cat. no.
(not supplied)
Cat. no.
ISO 63 (3)
max.
KSB100SE4 (5)
70
ISO 32 (4)
max.
KSB160SE4
KSB160SE5
11.00
150
150
ISO 40 (4)
max.
KSB250SE4
KSB250SE5
20.00
240
240
ISO 50 (4)
max.
KSB400SE4
KSB400SE5
29.20
Rating
(A)
For blade-type
fuses
(not supplied)
Connection
Max. size
(mm2)
100
Size 00
Type gG, 100 A max.
Type aM, 100 A max.
Copper cable
lugs
160
Size 00
Type gG, 160 A max.
Type aM, 160 A max.
Copper cable
lugs
70
250
Size 1
Type gG, 250 A max.
Type aM, 250 A max.
Copper cable
lugs
400
Size 2
Type gG, 400 A max.
Type aM, 250 A max.
Copper cable
lugs
Flexible Rigid
35
50
Weight
(kg)
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100 A dimensions, see Tap-off units with insulators for cylindrical fuses, page 74,
cat. no. KSB100SFp.
KSB160SEp, KSB250SEp
DD2020081.eps
DD210473.eps
Dim.
A
B
C
D
E
F
G
H
X = 577.5 (KSB160SEp)
X = 777 (KSB250SEp)
X = 855 (KSB400SEp)
160 A
450
257
300
395
207
032
032
182
250 A
600
308
400
548
258
032
032
192
DD210474.eps
KSB400SEp
Cable exit
Centre line of tap-off outlets
(6) Protruding
77
Commercial numbers
and dimensions
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
Busbar trunking
Tap-off unit
DD414767.eps
Tap-off polarity
Tap-off diagram (e.g. fuse
protection)
KSB20CG5
Rating
(A)
For fuses
(not supplied)
20
BS88 A1
Connection
Cable clamp terminals
Cat. no.
Weight
(kg)
KSB20CG5
0.60
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.
KSB20CG5
DD202295.eps
Cable exit
Centre line of tap-off outlets
(4) Protruding
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
Busbar trunking
Tap-off unit
DD202014.eps
KSB160SG4
DD414768.eps
Tap-off polarity
Tap-off diagram (e.g. fuse
protection)
Rating
(A)
For fuses
(not supplied)
Connection
32
80
BS88 A1
BS88 A1 ou A3
Max. size
Flexible or rigid
25
50
160
BS88 B1 ou B2
50
Cable gland
(not supplied)
Cat. no.
Weight
(kg)
ISO 50 max.(3)
ISO 63 max.(3) or
ISO 20 max.(4)
ISO 25 max.(4)
KSB32SG4
KSB80SG4
2.40
5.00
KSB160SG4
11.00
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed).
(3) Maximum diameter for a multipolar cable.
(4) Maximum diameter for a unipolar cable.
DD2020081.eps
DD202267.eps
KSB32SG4, KSB80SG4
KSBppSG4
X = 432.5 (KSB32SG4)
X = 545.5 (KSB80SG4)
X = 577.5 (KSB160SG4)
78
DD202015.eps
KSB160SG4
Dim.
A
B
C
D
E
F
32 A
356
153
167
309
103
202
80 A
444
178
202
397
128
220
Cable exit
Centre line of tap-off outlets
(5) Protruding
DD414767.eps
Tap-off polarity
Tap-off diagram
(e.g. fuse protection)
DD206167.eps
KSB125HD5
Rating
(A)
125
NHL 00 IN U5U5
Type 00
NHL 1 IN U5U5
Type 1
NHL 00 IN U5U5
Type 2
250
KSBppHD502
400
Connection
Cable clamp
terminals
Cable clamp
terminals
Cable clamp
terminals
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
Busbar trunking
Tap-off unit
Max. size
(mm2)
Cat. no.
Weight
(kg)
Flexible Rigid
50
50
ISO 63 max.
KSA125HD5
2.00
185
185
KSA25HD502
9,00
240
240
KSA40HD502
9,00
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a multipolar cable.
DD2020081.eps
DD230155.eps
KSB125HD5
DD230608.eps
X = 622.5 (KSB125HD5)
X = 763 (KSBppHD502)
DD230181.eps
KSBppHD502
Dim.
A
KSA25HD502
42
KSA40HD502
50
Cable exit
Centre line of tap-off outlets
79
Commercial numbers
and dimensions
Earthing system
arrangement
Busbar trunking
Tap-off unit
DD414768.eps
Tap-off polarity
Tap-off diagram
(e.g. fuse protection)
DD414769.eps
DD230607.eps
KSB630SEp
Rating
(A)
630 (4)
Size 3
Connection
Copper cable
lugs
Max. size
(mm2)
Flexible Rigid
2x240 2x240 ISO 40 (3)
max.
KSB630SE4
Cat. no.
Weight
(kg)
KSB630SE5
59,00
DD2020081.eps
(1) The neutral must be not distributed (3L + PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only
if N not distributed).
(3) Maximum diameter for a unipolar cable.
(4) Derating coefficient to apply: 0.9.
DD230552.eps
KSB630SEp
X = 1106.5
80
TT-TNS-TNC-IT (1)
TT-TNS-TNS-IT (1)
3L + N + PE (2)
Busbar trunking
Tap-off unit
DB413052.eps
Tap-off polarity
Tap-off diagram
(e.g. circuit-breaker
protection)
TNC
TNC
3L + PEN
DB413053.eps
DB413054.eps
The cover of the tap-off unit may be opened only when the INF is in the Off position.
KSB pppSDFp
Rating
(A)
Type of Fupact
(not supplied)
160
INFD160 or INFB250
with extended rotary
handle
INFD 250 or INFB 250
with extended rotary
handle 49619
INFD 400 or INFB 400
with extended rotary
handle LV480540
250
400
Connection
Max. size
(mm2)
Cable gland
(3)
Cat. no.
Cat. no.
Weight
(kg)
(not supplied)
INF
Flexible Rigid
70
70
ISO 32 max.
KSB160SDF4
KSB160SDF5
9,00
INF
70
150
ISO 32 max.
KSB250SDF4
KSB250SDF5
12.50
INF
150
240
ISO 40 max.
KSB400SDF4
KSB400SDF5
18.00
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
KSB250SDFp
DB413055.eps
X = 577.5 (KSB160SDFp)
X = 726.5 (KSB250SDFp)
X = 976.5 (KSB400SDFp)
KSB400SDFp
DB413056.eps
DD202008.eps
DB414227.eps
KSB160SDFp
Cable exit
Centre line of tap-off outlets
(4) Protruding.
81
Commercial numbers
and dimensions
Description
Divisible set of 10 x 5
Set of 12 label-holders (H = 24 mm - L = 180 mm)
Set of 12 labels-holders (H = 24 mm - L = 432 mm)
Set of 12 divisible labels-holders (H = 24 mm - L = 650 mm)
Cat. no.
unitaire
Weight
(kg)
13940
08905
08903
08907
0.08
0.50
0.50
0.50
(1) Self-adhevise support complete with transparent cover and paper label.
Designation
Cover contact
(break before opening)
Order in multiple of
Cat. no.
Weight
(kg)
KSB400ZC1
0.03
Rating
(A)
160
250
400
82
Cat. no. of
tap-off units
KSB160SFp
KSB160DCp
KSB160DDp
KSB250SFp
KSB250DCp
KSB250DDp
KSB400SFp
KSB400DCp
KSB400DDp
1
1
1
1
1
1
2
2
2
Cat. no.
KSB160SFZFL21
KSB250DCZFL21
KSB400DCZFL21
Weight
(kg)
0.20
0.20
0.20
0.30
0.30
0.30
0.40
0.40
0.40
Canalis KS
Characteristics
Contents
84
Electrical characteristics
88
Technical specifications
90
Harmonic currents
92
Direct current
94
Frequencies
96
Fire resistance
97
98
400 Hz
84
86
88
90
91
96
101
103
Trunking protection
104
107
103
104
106
107
108
110
112
83
Design guide
The procedure presented below describes the steps in creating a simple installation.
For a detailed design study, it is necessary to use the suitable tools, approved by
certification organisations and in compliance with local installation standards.
Ecodial software, published by Schneider Electric, is perfectly suited to the task.
Procedure
1
2
3
4
DD210067.eps
Layout of the distribution lines depends on load and source locations as well as
trunking fixing possibilities.
b A single distribution line can supply a zone four to six metres long.
b Load protection is located in the tap-off units, as close as possible to the loads.
b A single Canalis feeder can supply a set of loads with different power ratings.
DD414770.eps
33 - Power sum
Once the busbar trunking has been laid out, calculate the currents drawn by the
Canalis lines.
Calculation of the total operational current drawn by the line
(In) is equal to the sum of the currents drawn by the loads (Ib): In = Ib.
The loads do not all operate at the same time or continuously at full rated load, i.e. it
is necessary to calculate the diversity coefficient (KS): In = (Ib x KS).
Diversity coefficient as a function of the number of loads
Application
Lighting, heating
Distribution
(Mechanical workshop)
Number of loads
KS coefficient
1
2...3
0.9
4...5
0.8
6...9
0.7
10...40
0.6
40 or more
0.5
Caution. For industrial installations, remember to allow for changes in types and numbers of
machines. Similar to a switchboard, a margin of 20 % is recommended: In = Ib x KS x 1.2.
84
Busbar trunking
KNA40
KNA63
KNA100 or KSA100
KNA160 or KSA160
KSA250
KSA400
KSA500
KSA630
KSA800
KSA1000
Overload criterion
Ambient temperature
Canalis busbar trunking is sized for an ambient temperature of 35 C. For higher
temperatures, the trunking must be derated as per the data in the tables on the
technical characteristics.
Example: Canalis 400 A KSA at 45 C: In = 400 x 0.94 = 376 A.
Installation method
Canalis KN and KS trunking is designed to be installed edgewise.
In certain cases, it can also be installed flat (false floors) or vertically (KS rising
mains).
These installation methods do not require derating for the KN and KS trunking.
Protection against trunking overloads
To enable future extensions, protection for prefabricated busbar trunking is generally
sized for the rated current Inc (or the permissible current Iz if coefficient K1 is applied
as a function of the ambient temperature).
b Protection using gG (gI) flues:
v determine the standardised rated current In of the fuse such that In y Inc/1,1
(K1=1,1 for the fuses)
v select the standardised rating In equal to that value or just below.
Check that In u (Ib x KS). If that is not the case, select the busbar trunking with the
next highest rating.
Note: Protection using gI fuses results in a reduction of the permissible current in the trunking.
b Circuit-breaker protection: select the setting current Ir for the circuit breaker such
that (Ib x KS) y Ir y Inc.
Note: Circuit-breaker protection means Canalis busbar trunking can be used to the full rated
load.
Voltage-drop criterion
The voltage drop between the head and any other point in the installation must not
exceed the values in the table below:
Installation supplied by a distribution network
LV public system
High voltage
Lighting
3%
6%
Other application
5%
8%
For Canalis, voltage drops are indicated in V/100 m/A in the Characteristics
section.
U = (Ib x KS) x L / 100
For typical applications with power ratings up to 630 kVA, a Schneider Electric
solution including the low-voltage electrical switchboard, circuit breakers and
Canalis busbar trunking ensures an installation sized to handle all short-circuit levels
encountered.
To check the configuration of your installation (Isc up to 150 kA), refer to the
coordination tables on pages 110 and 111.
We also invite you to discover Ecodial, our complete design software for low-voltage
installations (selection of circuit breakers and cables, calculation of breaking
capacities, short-circuit currents and voltage drops, etc.), available from your
Schneider Electric representative.
85
Design guide
Degree of protection IP
Standard IEC 60529 (February 2001) indicates the degree of protection provided by
electrical equipment enclosures against accidental direct contact with live parts and
against the ingress of solid foreign objects or water.
This standard does not apply to protection against the risk of explosion or conditions
such as humidity, corrosive gases, fungi or vermin.
The IP code comprises 2 characteristic numerals and may include an additional letter
when the actual protection of persons against direct contact with live parts is better
than that indicated by the first numeral.
The first numeral characterises the protection of the equipment against penetration
of solid objects and the protection of people.
The second numeral characterises the protection of the equipment against
penetration of water with harmful effects.
Additional letter
Protection of persons against direct contact with live parts.
The additional letter is used only if the actual protection of persons is higher than that
indicated by the first characteristic numeral of the IP code.
If only the protection of persons is of interest, the two characteristic numerals are
replaced by the letter X, e.g. IPXXB.
Degree of protection IK
Standard IEC 62262 defines a coding system (IK code) indicating the degree of
protection provided by electrical equipment enclosures against external mechanical
impact.
Installation standard IEC 60364 provides a cross-reference between the various
degrees of protection and the environmental conditions classification, relating to the
selection of equipment according to external factors.
IKpp code
The IK code comprises 2 characteristic numerals (e.g. IK05).
Practical guide UTE C 15-103 shows, in the form of tables, the characteristics
required for electrical equipment (including minimum degrees of protection),
according to the locations in which they are installed.
86
Meaning of the numerals and letters representing the degree of protection IP.
5
6
Additional letter
Corresponds to protection of persons against direct contact
with live parts.
3
4
5
DB414739.eps
DB414740.eps
DB414741.eps
DB414742.eps
DB414743.eps
DB414744.eps
DB414745.eps
Dust tight.
DB414733.eps
DB414734.eps
DB414735.eps
DB414736.eps
Non-protected
DB414737.eps
Non-protected
DB414738.eps
Non-protected
DB414746.eps
A
B
C
D
DD210130.eps
DD210533.eps
00
01
02
03
04
05
06
07
08
09
10
Height
(cm)
Energy
(J)
7.50
0.15
10
0.20
17.50
0.35
25
0.50
Non-protected
0.20
35
0.70
0.50
20
40
1.70
30
20
10
40
20
87
Electrical characteristics
Electrical characteristics
From 100 to 1000 A
IP55
Ue = 230690 V
KS
100
250
400
500
630
800
1000
IP
IK
Inc
Ui
Ue
Uimp
f
A
V
V
kV
Hz
IEC/EN 61439-6
55
55
08
08
100
160
690
690
690
690
8
8
50/60 50/60
55
08
250
690
690
8
50/60
55
08
400
690
690
8
50/60
55
08
500
690
690
8
50/60
55
08
630
690
690
8
50/60
55
08
800
690
690
8
50/60
55
08
1000
690
690
8
50/60
R20
R1
X1
Z1
m/m
m/m
m/m
m/m
1.19
1.59
0.15
1.6
0.55
0.77
0.15
0.79
0.28
0.39
0.16
0.42
0.15
0.21
0.14
0.25
0.11
0.15
0.07
0.16
0.09
0.13
0.07
0.15
0.06
0.09
0.06
0.11
0.04
0.06
0.06
0.09
m/m
mm
0.42
4
0.42
4
0.35
22
0.19
50
0.07
222
0.07
222
0.07
222
0.06
252
R0 ph/N
X0 ph/N
Z0 ph/N
R0 ph/PE
X0 ph/PE
Z0 ph/PE
Rb0 ph/ph
Rb0 ph/N
Rb0 ph/PE
Rb1 ph/ph
Rb1 ph/N
Rb1 ph/PE
Xb ph/ph
Xb ph/N
Xb ph/PE
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
4.85
0.95
4.94
2.75
1.11
2.96
2.4
2.44
1.87
3.19
3.21
2.38
0.31
0.45
0.58
2.32
0.95
2.5
2.01
0.93
2.22
1.15
1.21
1.3
1.55
1.57
1.46
0.31
0.45
0.42
1.28
0.86
1.54
1.34
0.7
1.51
0.65
0.74
0.78
0.78
0.82
0.91
0.32
0.45
0.42
0.74
0.67
1
0.88
0.67
1.11
0.41
0.51
0.55
0.57
0.7
0.76
0.28
0.39
0.39
0.5
0.36
0.62
0.4
0.48
0.63
0.25
0.3
0.31
0.35
0.41
0.43
0.14
0.2
0.24
0.45
0.35
0.57
0.51
0.55
0.75
0.23
0.28
0.3
0.32
0.39
0.41
0.14
0.2
0.24
0.32
0.31
0.45
0.35
0.43
0.56
0.18
0.23
0.28
0.25
0.32
0.39
0.13
0.18
0.23
0.23
0.27
0.36
0.32
0.4
0.51
0.15
0.2
0.26
0.21
0.28
0.37
0.12
017
0.22
Ipk
kA
106 A2s
kA
15.7
6.8
2.6
22
20.2
4.45
28
100
10
49.2
354
18.8
55
733
26.2
67.5
1225
32.1
78.7
1758
37.4
78.7
1758
37.4
General characteristics
Compliance with standards
Degree of protection:
Mechanical impacts
Rated current at an ambient temperature of 35 C
Rated insulation voltage
Rated operational voltage
Rated impulse voltage
Rated frequency
Conductor characteristics
Phase conductors
Mean resistance at an ambient temperature of 20 C
Mean resistance at Inc and 35 C
Mean reactance at Inc, 35 C and 50 Hz
Mean impedance at Inc, 35 C and 50 Hz
Protective conductor (PE)
Mean resistance at an ambient temperature of 20 C
Copper cross-section
Symmetrical
components
method
Ph/N
at 20 C
Ph/PE
at 20 C
Impedance
method
At 20 C
For Inc at 35 C
For Inc at 35 C
and 50 Hz
Other characteristics
Mean resistance
Mean reactance
Mean impedance
Mean resistance
Mean reactance
Mean impedance
Mean
Ph/Ph
resistance
Ph/N
Ph/PE
Mean
Ph/Ph
resistance
Ph/N
Ph/PE
Mean
Ph/Ph
reactance
Ph/N
Ph/PE
Icw
160
Composite voltage drop (hot state) expressed in V/100 m/A (50 Hz) with the load
uniformly distributed over the run. If the load is concentrated at one end of the run,
the voltage drop is twice the value indicated in the table.
1
V/100 m/A 0.138 0.067 0.034 0.018 0.013 0.011
0.008 0.005
0.9
V/100 m/A 0.130 0.066 0.036 0.022 0.014 0.013 0.009 0.007
0.8
V/100 m/A 0.118
0.061 0.035 0.022 0.014 0.013 0.009 0.007
0.7
V/100 m/A 0.106 0.056 0.034 0.021 0.013 0.012 0.009 0.008
This calculation table applies to the three-phase system.
To obtain the single-phase voltage drop, the three-phase voltage drop shown above is divided by
1.732.
88
0.69
1.00
0.66
0.89
1.12
1.27
250
200
160
400
315
250
500
400
315
630
500
400
800
630
500
1000
800
630
40
0.97
45
0.94
50
0.91
55
0.87
IP
IK
Ui
Ue
Uimp
f
V
V
kV
Hz
55
08
400, 500 depending on protective device
400, 500 depending on protective device
6.8
50/60
100
10
1
B(T)
DB414131.eps
0,1
0,01
0,001
10
100
1000
Distance from the busbar (mm)
10000
KSA100
KSA160
KSA250
KSA400
KSA500
KSA630
KSA800
KSA1000
89
Specifications
Technical specifications
PD202340.eps
Horizontal trunking
Fire resistance:
b fire barriers as per standard ISO 834 (DIN 4102-part 9) for passages through
partitions.
b resistant to flame propagation in compliance with standard IEC 60332 - part 3.
b materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
All plastic components are halogen free.
b The enclosure (1), made of sheet steel, galvanised and pre-lacquered RAL 9001
white.
b The four aluminium conductors are mounted on fibreglass reinforced polyester
insulators. All electrical contacts are made of silver-plated copper.
b The straight lengths have a tap-off unit (2) every metre on both sides.
The tap-off outlets are equipped with automatic shutters that avoid accidental contact
with live parts. The protective conductor is electrically connected to the enclosure at
each jointing unit.
b Electrical contact between two components is ensured by flexible contacts
designed to adapt to the difference in expansion between the conductors and the enclosure.
It is possible to check visually that the electrical contact is effective.
The mechanical junction between two components is ensured by four captive screws.
The jointing unit (3) is maintenance free.
b The rigidity of the straight lengths is sufficient that fixing points (4) are required only
every three metres (excepting special conditions).
b Special components (5) are available to change direction or avoid obstacles.
b The tap-off units (6) have the following characteristics:
v connection and disconnection are possible only with the cover open
v the contact of the protective conductor ensures automatic opening of the shutters
and feeds the tap-off unit
v there is no access to live parts when the cover of the tap-off unit is open
(no finger access, IPxxD)
v when the tap-off unit is plugged in, the earthing contact connects first, followed by
the phases
v it is not possible to close the cover before the tap-off unit is mechanically locked on
the trunking, tap-off units can be equipped with fuses, modular devices or moulded
case circuit breakers.
90
PD202341_r.eps
Rising mains
Fire resistance:
b fire barriers as per standard ISO 834 (DIN 4102-part 9) for passages through
partitions (slabs for exemple).
b resistant to flame propagation in compliance with standard IEC 60332 - part 3.
b materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
All plastic components are halogen free.
b The enclosure (1), made of sheet steel, galvanised and pre-lacquered RAL 9001
white.
b The four aluminium conductors are mounted on fibreglass reinforced polyester
insulators. All electrical contacts are made of silver-plated copper.
b The straight lengths have a tap-off unit (2) every 0.5 metre on one side. There are
four tap-off units per floor for floor heights between 3.5 and 4.8 metres, or three
tap-off units per floor for floor heights less than 3.5 metres. The tap-off outlets are
equipped with automatic shutters that avoid accidental contact with live parts.
The protective conductor is electrically connected to the enclosure at each jointing
unit.
b Electrical contact between two components is ensured by flexible contacts
designed to adapt to the difference in expansion between the conductors and the
enclosure. It is possible to check visually that the electrical contact is effective.
The mechanical junction between two components is ensured by four captive screws.
The jointing unit (3) is maintenance free.
b A fire barrier (4) can be installed when the riser passes through a slab to avoid any
risk of fire propagation from one floor to another.
Two-hour fire resistance (A120) is provided in compliance with standard ISO834
(DIN 41-2-part 9).
b Special components (5) are available to change direction or avoid obstacles.
b The riser can be maintained by a special bottom support (6) or a spring-based
fixing device on each floor of the building (depending on the height of the building).
b The tap-off units (7) have the following characteristics:
v connection and disconnection are possible only with the cover open
v the contact of the protective conductor ensures automatic opening of the shutters
and feeds the tap-off unit
v there is no access to live parts when the cover of the tap-off unit is open
(no finger access, IPxxD)
v when the tap-off unit is plugged in, the earthing contact connects first, followed by
the phases
v it is not possible to close the cover before the tap-off unit is mechanically locked on
the trunking, tap-off units can be equipped with modular devices or moulded case
circuit breakers.
91
Harmonic currents
Recommendations
for special applications
Harmonic order
The order is the ratio
between the harmonic
frequency fn and the
fundamental frequency
(generally the power
frequency, 50 or 60 Hz):
n = fn / f1
By definition, the
fundamental f1 is order 1
(H1).
Third-order harmonics
(H3) have a frequency of
150 Hz (when f1 = 50 Hz).
92
PD202029_r.eps
PD202028_r.eps
Workshops
Mix of disturbing loads (computers,
UPSs, fluorescent lighting) and
non-disturbing loads (motors, pumps,
heating).
Offices
Numerous disturbing loads (computers,
UPSs, fluorescent lighting).
DD210680.eps
DD210682.eps
DD210680.eps
Fundamental frequency:
ih1 (50 Hz) and
33 % H3
DD210683.eps
Busbar-trunking selection
THD y 15 %
25
40
15 % < THD y 33 %
20
32
THD > 33 %
16
25
93
Recommendations
for special applications
Direct current
Thermal effect
Rule
The total power dissipated as heat must remain constant in the duct:
Pac = Pdc
Where:
bb the power dissipated as heat: Pac = 3 x R x Iac where:
vv R= resistance of a conductor
vv Iac = conductor rms current
bb the dissipated power for 4 conductors: Pdc = 4 x R x Idc where:
vv Idc = direct current.
Selection table
bb 1 source
Case of 2 conductors in parallel for the + and 2 conductor in parallel for the (only
1 circuit in the busbar trunking):
DD210893.eps
DD210894.eps
bb 2 sources
Case of 1 conductor for the + and 1 conductor for the (2 circuits possible in the
same busbar trunking):
Idc = 0,866 x Iac
Rating (A)
100
160
250
400
500
630
800
1000
94
1 source
173
277
433
693
866
1091
1386
1732
2 sources
87
139
217
346
433
546
693
866
Protection
With DC, there is no zero crossing point of the voltage and current to facilitate arc
extinction in the protective device.
The arcing time is longer and the energy that has to be absorbed is higher than for
AC.
The voltage of the DC arc must rise to the source voltage very quickly in order to
"put out" the short-circuit current.
"Shortened" electrical equation: U network = R x Isc + Uarc where:
bb Isc = U network - Uarc / R
bb Isc = 0 when Uarc = U network.
A quick rise in arcing voltage can be achieved by using series fuses, one fuse on
the + and one fuse on the of each circuit.
For some current rating and fuse characteristics, the placing of two fuses in series
on each polarity may be specified (highly inductive circuit).
In some cases, two fuses must be placed in parallel for each polarity.
95
Recommendations
for special applications
Frequencies
Values at 35 C.
Application of a derating coefficient at 400 Hz combined with that for temperature
derating.
400 Hz
Voltage drop
In (A)
92
146
221
342
403
514
621
745
Coefficient K at
400 Hz
0.92
0.91
0.88
0.85
0.81
0.82
0.78
0.74
3-phase voltage drop, in millivolts per metre and per amp 400 Hz with load spread
over the run.
For a concentration of load at the end of a run (transport), the voltage drops are
double those shown in the table below.
Voltage drop when frequency is 400 Hz in millivolts per meter and per ampere
KSA100 KSA160 KSA250 KSA400 KSA500 KSA630 KSA800 KSA1000
Conductor characteristics
Cos = 1.0
0.992
0.641
0.550
0.388
0.225
0.226
0.201
0.160
Cos = 0.9
0.975
0.627
0.546
0.388
0.223
0.225
0.200
0.159
Cos = 0.8
0.968
0.622
0.545
0.387
0.222
0.224
0.200
0.159
96
Average ohmic
1.564
resistance of
phase and neutral
conductors at In
Rb1ph (m/m)
0.687
0.320
0.249
0.120
0.118
0.113
0.110
Average
resistance at In
Xph (m/m)
1.207
1.264
0.942
0.535
0.551
0.506
0.405
1.203
Fire resistance
Definition of tests
Objective
To check a busbar trunking will not propagate a fire from one room to another by
crossing a fire barrier wall for 60, 120, 180, or 240 minutes.
As defined in standard EN 1366-3; EN 1363-1; ISO 834; DIN 4102 part 9.
Method
The fire barrier busbar trunking section to be tested is placed in an oven which
executes a standardised temperature-time curve.
Result criteria
The specimen is considered to have passed the test if:
bb there are no flames behind the fire barrier
bb there is no smoke or gas behind the fire barrier (not requested by the standard;
can appear as a remark in the test report)
bb the temperature rise of the casing behind the fire barrier does not exceed 180 C.
Objective
To check all the busbar trunkings electrical circuits are preserved in fire conditions.
As defined in standard DIN 4102 part 12.
Method
Its entire length inserted, the busbar trunking is taken as a specimen in an
insulating sheath.
Result criteria
The specimen is considered to have passed the test if:
bb conductor continuity is preserved
bb there is no short-circuit between conductors.
97
Recommendations
for special applications
Foreword
Prefabricated electrical trunking components expand and contract due to:
b changes in ambient temperature (e.g. summer and winter)
b current flowing in the conductors (e.g. 0 to In)
For example, consider a 30 metre long 800 A Canalis KS line equipped with ten
160 A tap-off units and installed under the roof of a building where the ambient
temperature varies by more than 30 C between summer and winter:
b just the change in the ambient temperature results in an expansion of 20 mm for
the conductors and the 10 mm for the casing
b at a constant ambient temperature, the temperature rise in the conductors every
morning when the installation is started (increase in current from 0 to In = 800 A)
results in an expansion of 55 mm for the conductors and 7 mm for the casing.
PD202309_r.eps
The lengths of the sheet steel (1) and the aluminium conductors (2) therefore vary as
a function of the changes in temperature and their specific thermal expansion
coefficients.
For this reason, Canalis components are designed so that these phenomena do not
affect their installation or operation.
How Canalis trunking components effectively compensate for the effects of conductor thermal expansion
DD202281.eps
Inside a trunking section, the conductors are fixed (1) at a single point in the casing
and, due to the change in temperature, expand (V) on either side of that point.
The zones affected by expansion and considered critical from the electrical
standpoint are the jointing system (2) and tap-off outlets (3).
98
How Canalis trunking components effectively compensate for the effects of conductor thermal expansion
DD202282.eps
1 Spring of clamps.
2 Copper area.
3 Silver plated copper.
DD202283.eps
Conclusion: at both the jointing system and the tap-off outlets, sliding contacts can
handle the expansion of the conductors.
These maintenance-free silver-plated contacts are guaranteed for life.
Only the expansion of the sheet steel must be taken into account for Canalis
installation, however the problem is minor because both trials and
calculations show that expansion is only approximately 1 mm for every
three-metre length under extreme operating conditions.
99
Recommendations
for special applications
Few precautionary measures used to compensate for the effects of thermal expansion in the casing,
depending on how the line is installed.
Horizontal line
For a trunking line made up exclusively of straight lengths, as noted above, the
effects of thermal expansion are not significant (only 1 mm for 3 m).
To avoid all risk of problems, Canalis trunking supports allow movement of the
casing, i.e. no fixed points.
For a fixed point caused by a blocked elbow, for example, the casings compensate
their expansion by slight lateral movement (0.7 mm maximum) on either side of the
longitudinal axis. This movement has no impact on the contact quality of the jointing
system or on the IP.
PD202310_r.eps
DD202285.eps
100
What is a sprinkler?
DD205065_r.eps
PD202443_r.eps
To provide you with all necessary safety guarantees, Schneider Electric has chosen
to go further still than the IP55 test by subjecting its busbar trunking to an extremely
severe sprinkler test.
101
Recommendations
for special applications
Chronology
In view of the absence of reference standard for sprinkler tests, we have chosen to
apply the following procedure:
b insulation resistance test (1000 V)
b dielectric properties test (2.5 kV, 5 s: IEC 60439-1 & 2
b water projection
b 5 min break
b insulation resistance test (1000 V)
b dielectric properties test (2.5 kV, 5 s: IEC 60439-1 & 2.
Water projection,
2 configurations, with or without energisation:
b horizontally installed busbar trunking:
v 15 min water projection with sprinkler type K-Wert 115, NF , 7.5 bar,
314 L/min
v 35 min water projection with sprinkler type K-Wert 115, NF , 1 bar,
115 L/min
b vertically installed busbar trunking:
v 15 min water projection with sprinkler type K-Wert 80, NF , 7.5 bar,
314 L/min
v 35 min water projection with sprinkler type K-Wert 80, NF , 1 bar,
80 L/min.
Mounting position
The distance between the sprinkler head and the busbar trunking is 500 mm.
DB414747.eps
1 Sprinkler
2 Pressure gauge
3 Closing valve
4 Tap-off unit.
5 Busbar trunking
DB414748.eps
Test configuration
Test results
Busbar trunkings KDP, KBA, KBB, KN and KS have undergone the sprinkler test.
This test, if successful, proves that our busbar trunkings can operate during and
immediately after sprinkling of a line by a sprinkler for a period of 50 min.
102
DB405625.eps
DB414424.eps
DB405620.eps
Functions available:
bb Protection of Canalis lines by Compact NSX circuit-breakers (100 A, 160 A, 250 A
or 400 A rating).
bb Protection of loads by circuit-breakers from the Acti 9 range (single-phase or
3-phase 16 A, 32 A or 63 A) with or without differential protection (30 mA).
bb Feed units are equipped with front panel-mounted sockets or wander sockets
(IEC 309).
bb For loads, measures power rate, phase balancing, THD, power factor, voltage,
current, active and reactive power and consumption.
Management
system
DB414425.eps
DB405543.eps
Architecture diagram:
Ethernet switch
PM
PM
EGX
PM
EGX
PM
EGX
EGX
Modbus RTU
Canalis
Modbus TCP
103
Coordination
Trunking protection
Overload protection
The busbar trunking rating can be optimised when the trunking is protected by circuit
breakers rather than fuses.
Example:
For a load current = 400 A with an ambient temperature of 35 C:
b Fuse protection:
In trunking = load current x f1 x k2 = 400 x 1 x 1.1 = 440 A
The recommended trunking is KSA500 (In trunking = 500 A).
b Circuit breaker protection:
In trunking = load current x f1 x k2 = 400 x 1 x 1 = 400 A
The recommended trunking is KSA400 (In trunking = 400 A).
Due to their design, circuit breaker thermal settings are more precise.
DD210601en.EPS
Explanations
b Calibration of thermal asymptotes:
v distribution fuses are calibrated to trip for overloads of between 1.25 and 1.6 times
their rated current
v circuit breakers are calibrated to trip for overloads of between 1.05 and 1.3
(1.2 for circuit breakers with electronic protection) times ther current setting.
104
Thermal-setting precision
b The fuse is assigned a fixed rating. A change in the current to be protected
requires fuse replacement. The difference between 2 fuse ratings is
approximately 25 %.
Standard ratings are given according to the series of characteristic numbers
of the Renard series.
For example: 40 - 50 - 63 - 80 - 100 - 125 - 160 - 200 - etc.
b the circuit breaker offers a setting precision of:
v 5 % for circuit breakers equipped with conventional thermal-magnetic trip units
v 3 % for circuit breakers equipped with electronic trip units.
For example, a circuit breaker with a nominal rating of 100 A can easily be set
to values of Ir = 100 A, 95 A, 90 A, 85 A, 80 A.
Example:
a circuit breaker with a nominal rating of 100 A set to 90 A will be used to protect
KSA100 busbar trunking (ln trunking = 100 A) which is used for an ambient
temperature of 50 C.
Extensive setting range of circuit breakers equipped with electronic trip units
Circuit breakers equipped with electronic trip units offer an extended range
of settings:
b thermal protection lr adjustable from 0.4 ln to ln
b short-circuit protection from 2 lr to 10 lr.
Example:
a 250 A circuit breaker (NSX250N equipped with an STR22SE) can easily
be set up for:
b thermal protection from 100 to 250 A
b short-circuit protection from 200 to 2500 A.
DD210603.EPS
Advantages:
105
Coordination
Trunking protection
Short-circuit protection
Trunking characteristics
Busbar trunking systems must meet all rules stipulated
in standards IEC 60439.1 and 60439.2.
b With respect to short-circuits, BTS sizing is determined by the following
characteristics:
v rated peak withstand current Ipk (k):
this characteristic expresses the instantaneous electrodynamic withstand limits
of the busbar trunking. The peak current value is often the most restrictive
instantaneous characteristic for the protective device
v maximum rms short-time withstand current Icw (kArms/...s):
this characteristic expresses the permissible temperature-rise limit of conductors
over a given period of time (0.1 to 1 s)
v thermal stress in A2s:
this characteristic expresses the instantaneous thermal stress withstand of the BTS.
Normally, if the short-circuit generates fault conditions that are compatible with
the first two characteristics, this constraint is automatically satisfied.
DD210613en.eps
106
Circuit breaker/trunking
coordination
Non-limiting or time-delayed
circuit breakers
v the permissible peak current, l peak, of the BTS must be greater than the peak
value of the prospective asymmetrical short-circuit current at point A.
The value of the asymmetrical short-circuit current is obtained from the value
of the symmetrical short-circuit current, Isc, multiplied by a standardised
asymmetry factor (k).
The value of the first short-circuit asymmetry peak in the transient state is taken
into account.
Standardised table for asymmetrical short-circuit calculations
kA (rms value)
4.5 y I y 6
6 < I y 10
10 < I y 20
20 < I y 50
50 < I
Asymmetry factor k
k
1.5
1.7
2.0
2.1
2.2
v the short-time withstand current lcw of the BTS must be greater than the current
Isc flowing through the installation for the duration of the short-circuit,
(duration T = total breaking time, including the time delay if applicable).
If one of these criteria is not satisfied, the rating of the busbar trunking to be used
must be increased.
107
Circuit breaker/trunking
coordination
Coordination
DD206178.eps
b In this case, the BTS must withstand the peak current limited by the protective
device and the corresponding thermal stress.
v The current limited (I peak) by the circuit breaker must be less than the peak
current permitted in the BTS.
v The thermal stress limited by the circuit breaker must be less than
the thermal stress permitted in the BTS.
DD206179.eps
108
BTS protection by
Compact NSX limiting
circuit breakers
Limiting capacity
Busbar trunking ratings can be optimised when circuit breakers rather than fuses are
sed for protection.
PB104166_SE.eps
The circuit breakers in the Compact NSX range are limiting circuit breakers
with a high current-limiting capacity.
A circuit breakers limiting capacity is its ability to let only a limited current IL,
lower than the prospective asymmetrical peak short-circuit current Isc through
in the event of a short-circuit.
The consequence is a considerable reduction in electrodynamic
and thermal stresses in the protected installation.
DD206182.eps
DD206181.eps
Current limiting.
Energy limiting.
109
Selection guide
Coordination
The selection guides below can be used to determine the circuit breaker required
to fully protect the trunking depending on the prospective short-circuit current
of the installation.
Example: in an installation with a prospective Isc of 15 kA, the circuit breaker
required to protect 25 A KBB trunking is a C60H (the rating depends on the rated
current of the circuit).
In bold, the most appropriate device to the rating of the busbar trunking.
25 kA
36 kA
NG125N 100
NG125H 100
NSX100B/F/N/H/S/L
25 kA
NSX100B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L
36 kA
NSX100F/N/H/S/L
NSX160F/N/H/S/L
NSX250F/N/H/S/L
50 kA
70 kA
NSX100N/H/S/L NSX100H/S/L
NSX160N/H/S/L NSX160H/S/L
NSX250N/H/S/L
90 kA
NSX100S/L
36 kA
NSX160F/N/H/S/L
NSX250F/N/H/S/L
NSX400F/N/H/S/L
50 kA
70 kA
NSX160N/H/S/L NSX160H/S/L
NSX250N/H/S/L NSX250H/S/L
NSX400N/H/S/L
100 kA
NSX160S/L
NSX250S/L
150 kA
NSX160L
NSX250L
36 kA
NSX250F/N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b L / LB
50 kA
NSX250N/H/S/L
NSX400N/H/S/L
NSX630N/H/S/L
NS630b L / LB
70 kA
NSX250H/S/L
NSX400H/S/L
NSX630H/S/L
NS630b LB
100 kA
NSX250S/L
NSX400S/L
NSX630S/L
150 kA
NSX250L
NSX400L
NSX630L
36 kA
NSX400F
NSX630F
NS630b N
50 kA
NSX400N
NSX630N
NS630b L / LB
70 kA
NSX400H
NSX630H
NS630b LB
100 kA
NSX400S
NSX630S
NS630b LB
150 kA
NSX400L
NSX630L
36 kA
NSX400F
NSX630F
NS630b L
NS800L
NT06L1
NT08L1
50 kA
NSX400N
NSX630N
NS630b L
NS800L
NT06L1
NT08L1
70 kA
NSX400H
NSX630H
NS630bL
NS800L
NT06L1
NT08L1
100 kA
NSX400S
NSX630S
NS630bL
NS800L
NT06L1
NT08L1
150 kA
NSX400L
NSX630L
NS630b LB
NS800LB
36 kA
NSX630F
NS630bN
NS800N
NS1000N
NT06H1
NT08H1
NT10H1
50 kA
NSX630N
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1
70 kA
NSX630H
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1
100 kA
NSX630S
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1
150 kA
NSX630L
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1
36 kA
NS800N
NS1000N
NS1250N
NT08H1
NT10H1
NT12H1
50 kA
NS800L
NS1000L
70 kA
NS800L
NS1000L
100 kA
NS800L
NS1000L
150 kA
NS800L
NS1000L
NT08L1
NT10L1
NT08L1
NT10L1
NT08L1
NT10L1
NT08L1
NT10L1
25 kA
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L
NSX400F/N/H/S/L
25 kA
NSX250B/F/N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b N/H/L/LB
25 kA
NSX400F
NSX630F
NS630b N
y 32 kA
NSX400F
NSX630F
NS630b N
NS800N
NT06H1
NT08H1
110
10 kA
NSX100N/H/S/L
NSX160N/H/S/L
NSX250N/H/S/L
15 kA
NSX100S/L
NSX160S/L
NSX250S/L
20 kA
NSX100L
15 kA
NSX100S/L
NSX160S/L
NSX250S/L
20 kA
NSX100L
NSX160L
NSX250L
15 kA
NSX160S/L
NSX250S/L
NSX400H/S/L
20 kA
NSX160L
NSX250L
NSX400/S/L
75 kA
NS100L
10 kA
NSX100N/H/S/L
NSX160N/H/S/L
NSX250N/H/S/L
75 kA
NS100L
10 kA
NSX160N/H/S/L
NSX250N/H/S/L
NSX400F/N/H/S/L
35 kA
NSX400L
75 kA
NS400L
10 kA
15 kA
NSX250N/H/S/L NSX250S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
20 kA
NSX250L
NSX400H/S/L
NSX630H/S/L
35 kA
NSX400L
NSX630L
NS630bN
75 kA
NS400L
NS630bLB
10 kA
15 kA
NSX400F/N/H/S/L
NSX630F/N/H/S/L
20 kA
NSX400H/S/L
NSX630H/S/L
25 kA
35 kA
NSX400L
NSX630L
75 kA
30 kA
35 kA
NSX400L
NSX630L
75 kA
NS630bN
NS800N
NS630bH
NS800H
NS400L
NS630bLB
NS800LB
30 kA
35 kA
75 kA
NS630bN
NS800N
NS1000N
NS630bH
NS800H
NS1000H
NS630bLB
NS800LB
30 kA
NS800N
NS1000N
NS1250N
35 kA
NS800H
NS1000H
NS1250H
NT08H1/H2
NT10H1/H2
NT12H1/H2
NW08N1
NW10N1
NW12N1
75 kA
NS800LB
NS630bN
NS800N
NS400L
NS630bLB
NS800LB
10 kA
15 kA
NSX400F/N/H/S/L NSX400H/S/L
NSX630F/N/H/S/L NSX630H/S/L
20 kA
NSX400/S/L
NSX630/S/L
10 kA
15 kA
NSX630F/N/H/S/L NSX630H/S/L
20 kA
NSX630/S/L
10 kA
15 kA
20 kA
111
Maintenance
Maintenance recommendations
for your installation
Feed units
They are equipped with terminals up to 100 A and lug connectors for higher ratings.
As for all screw-type connections, it is advised to check tightness one year after
installation and then run checks at longer intervals.
The feed units are jointed to the first run component of the line (see next paragraph).
This connection is maintenance free
DD202302.eps
Run components
They are interconnected by electrical jointing units ensuring automatic and
simultaneous connection of all live conductors.
The contacts are clamp + spring type and exert no forces on the plastic parts.
The electrical contacts of the jointing unit for the conductors are silver-plated copper.
This type of sliding connection is maintenance free.
Components can be dismantled and reused.
DD202303.eps
Tap-off units
Trunking contacts are flexible, made of silver-plated clamps providing optimum
contact quality. The contacts do not press or apply any forces on the plastic parts.
They connect to the live line conductors at the tap-off outlets. Conductors are made
of silver-plated copper at the point of contact.
These components are maintenance free.
The connections for outgoing cables are made to terminals or using lugs.
As for all screw-type connections, it is advised to check tightness one year after
installation and then run checks at longer intervals.
Other recommandations
Maintenance of devices
For all devices installed in Canalis tap-off units, follow the manufacturers instructions
(as for installation in a switchboard).
Visual check
Cleaning
It is advised to check annually that trunking is clean and to remove any dust, water,
oil or other conducting substances or objects from sensitive zones such as junctions,
tap-off outlets and tap-off units.
External appearance
Check the external appearance of the trunking to detect:
b signs of shocks, in which case it is necessary to check the degree of protection
to avoid any risk of insulation faults
b anomalies, i.e. incorrect implementation of the trunking (incorrect supports, etc.)
b traces of corrosion (in particular on supports).
112
DEBU026EN
10-31-1247
11-2013