Академический Документы
Профессиональный Документы
Культура Документы
1, JANUARY 2014
201
I. INTRODUCTION
HE output of small electromagnetic energy harvesters typically requires rectification and boosting in order to produce an output voltage that falls within the allowable operating
range of the load electronics. In some applications, there is also
a need to buffer energy in high capacity storage elements, such
as supercapacitors, in order to supply loads with a higher peak
demand than the harvester output [1]. Several circuit architectures have been reported in published literature, which meet
these requirements, including single-stage acdc switch-mode
power converters [2]. Efficiencies up to 75%80% at 500 W
Manuscript received October 11, 2012; revised December 21, 2012 and
January 23, 2013; accepted February 19, 2013. Date of current version July
18, 2013. Recommended for publication by Associate Editor S. Y. (Ron) Hui.
G. D. Szarka, P. P. Proynov, and B. H. Stark are with the Department of Electrical and Electronic Engineering, University of Bristol, Bristol,
BS2 8BB, U.K. (e-mail: G.Szarka.04@bristol.ac.uk; p.proynov@bristol.ac.uk;
Bernard.Stark@bristol.ac.uk).
S. G. Burrow is with the Department of Aerospace Engineering, University
of Bristol, Bristol, BS2 8BB, U.K. (e-mail: stephen.burrow@bristol.ac.uk).
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TPEL.2013.2251427
202
(1)
(2)
m 2 Y
(3)
(k 2 m)2 + c2 2
and the phase angle between the base and tip displacement is
given by
= tan1
c
.
k 2 m
(4)
SZARKA et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS
203
Fig. 3. Load resistance profiles with various gradients, resulting in linear load
resistance sweeps between 1000 and 100 in 0.5, 1 s, 2, 4, and 8 s. Both
(left) decreasing and (right) increasing resistance profiles are considered.
(2) simplifies to
mY
sin t
.
(6)
c
2
Depending on the application, both of the excitation frequency and amplitude Y can vary over time. Furthermore,
damping arising from the interfacing electronics affects the total damping given by [4]
z (t) =
c = cm +
Rcoil
2
+ Rload
(7)
where cm represents the mechanical damping, the electromagnetic coupling coefficient, and Rcoil is the parasitic resistance
of the coil. Rload is the load resistance, which is synthesized by
the input impedance of the power converter in a practical system. In typical small-scale electromagnetic energy harvesters,
the impedance of the parasitic coil inductance at the excitation
frequency is several orders of magnitude lower than the combined equivalent mechanical resistive output impedance and ac
coil resistance. Therefore, it is assumed that close to the theoretical, maximum power can be extracted using a purely resistive
load at resonance.
B. Illustration of Response to Dynamic Damping
The transient response of the mechanical system is related
to the energy stored in the oscillator and the total damping of
the system. To illustrate this experimentally, the load applied to
the harvester of Fig. 1 is swept from 100 to 1000 at differing
rates (see Fig. 3), while the excitation is kept constant. Prior to
Fig. 5. Measured generated power profiles of Fig. 4 mapped onto corresponding load resistance sweeps and compared against steady-state measurements.
204
mY
co
(9)
and after the step change, the oscillation should settle to the new
steady-state solution with a tip displacement amplitude of
Zs =
mY
.
cs
(10)
Fig. 6. (a) Generated rms current and voltage waveforms during the 4 s sweep
transients, and (b) current and voltage excursions mapped to the corresponding
load resistance.
co ,
cs ,
t0
.
t>0
(8)
c
=
.
2 mk
(12)
|z|
= Zs + (Zo Zs ) e(c s /2m )t
(14)
(15)
SZARKA et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS
205
m 2 Y
c (Rcoil + Rload2 )
(20)
(21)
2 m2 4 Y 2
Rload2
(Rcoil + Rload2 )2
1
1
A
1
(c s /2m )t
|I| =
+
e
Rload2 cs
co
cs
Fig. 7. Calculated, based on (13), and measured average output power during
the transient response of the system that occurred after a step change in the
load resistance. Initial load resistances are shown on the right; after the step
change, the resistance is constant at 400 . Excitation is a constant 3.75 ms2
acceleration at 43.8 Hz.
and
1
1
2
1
+
e(c s /2m )t
c2s
cs co
cs
2
1
1
(c s /m )t
+
e
.
co
cs
U (t)
Rcoil + Rload2
(18)
where Rload2 denotes the load resistance after the step change,
and during the settling time. During the settling time, the amplitude of the generated current will decay exponentially toward
the steady-state value
I (t) = Is + (Io Is ) e(c s /2m )t
(19)
(24)
(17)
(23)
|P | = A
(22)
(25)
e(c s /2m )t s
2 +
cs
cs co
cs
2
1
1
+
e(c s /m )t s = 0
(26)
co
cs
cs
co
cs co
x2 2x
=0
cs co
co
(27)
1+ 1+
(c s /2m )t s
(28)
=
e
co /(cs c0 )
Isolating the settling time ts gives
2m 1 + 1 +
ts =
ln
|cs co | .
cs
co
(29)
206
Fig. 8.
System-level block diagram showing the main power electronics blocks and the power definitions within the main power flow of the system.
SZARKA et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS
207
Fig. 10. Measured typical input current Iin and voltage V in waveforms. A period of 100 s at 5 ms point is shown on the right for increased resolution. The duty
ratio of the converter is 67% and the output voltage is 3.2 V. The energy harvester is excited with 43.8 Hz, 3 ms2 acceleration, producing a little over 450 W.
The printed circuit board implementation of the power conditioning system is shown in Fig. 12, corresponding to the block
diagram presented in Fig. 12.
IV. CURRENT-SHUNT-BASED MAXIMUM POWER
TRANSFER TRACKING
A. Operating Principles and Measurement
A typical low-power energy harvesting system requires large
capacity storage in order to be able to supply the high peak-tomean ratio power demand required by load electronics such as
wireless sensor nodes. The combination of low output power
and large storage capacitance results in slow charge up of the
supercapacitor. This enables the MPTT control to rely solely on
output current measurement. The reference signal that sets the
duty ratio of the boost rectifier is perturbed, and the effect of
this on the power transferred to the supercapacitor is observed
by measuring the output current while the output voltage is assumed to be near constant. This implementation requires the rate
of change of the output voltage to remain low enough to ensure
a near-constant voltage between successive measurements. In
the presented system, this limits the minimum capacitor size to
20 mF, when the worst-case voltage increase between measurements is 5 mV.
The measurement circuit is an operational amplifier based
circuit (see Fig. 13) that is designed to measure the voltage
drop across a 150 precision shunt resistor. The current ripple,
both at the switching and at the excitation frequency, must be
minimized to ensure correct measurement.
This is achieved by a combination of parallel capacitance
introduced before the shunt resistor in the circuit, and an active low-pass SallenKey [18] architecture employed in the design of the amplifier circuit. The 30 F capacitor smoothes the
switching frequency current ripple without adding any significant delay to the response of the system to the perturbation.
Fig. 11. Gate drive circuit generating 32.768 kHz output PWM signals. Pos,
Neg, and Blank are digital signals from the polarity detection circuit [6].
Reference is an analogue signal from the control circuit to set the duty ratio.
Fig. 12. Printed circuit board implementation of the main power conditioning
system blocks, corresponding to Fig. 12.
208
Fig. 15. Steady-state characterization of power conditioning system in openloop configuration. Voltage reference is stepped using an external signal at
>5 s intervals. Excitation is held at 3.75 ms2 and 43.8 Hz. Output voltage is
regulated using a shunt regulator circuit as a load (LM4041).
around 150 V [19], its low current consumption, and rail-torail input/output signal support. The gain of 30 V/V is selected,
in order to maintain a sufficient signal-to-noise ratio.
B. Digital Implementation of MPTT
The well-known perturb-and-observe algorithm is implemented on a MSP430F1132 microcontroller: the PWM duty
ratio of the boost converter is altered and the consequent change
in the output power is measured when the mechanical structure has settled. Based on the measured outcome, the direction
of the subsequent alteration is determined and the process repeated. The controllers CPU is clocked at 5 MHz frequency
in order to minimize the power hungry on-time. The 10-b onboard analogue-to-digital converter (ADC) converts the current
amplifiers output, and the reference voltage for the duty ratio is
set by an R2R ladder, shown in Fig. 14. The top two bits of the
ladder are connected to ground, while the remaining eight bits
are controlled via a full output port of the controller. This provides a 1.75 mV resolution with a maximum output of 450 mV.
A. Steady-State Performance
In order to evaluate the effectiveness of the MPTT circuitry,
the power Pstore as a function of the duty ratio is measured. This
is the useful output power after subtracting losses incurred due to
nonideal loading of the generator, during the power conversion
process, and the quiescent power overheads of the ancillary and
control circuits. In this test, the output voltage is kept constant
using a micropower shunt regulator (LM4041) and the reference
voltage is stepped using an external source in 5 s intervals to
create quasi-steady-state measurements. During all of the tests
presented in this section, a 68 mF supercapacitor is used as the
main energy storage element. The combined current consumption of the ancillary circuits and the leakage current drawn by
the start-up circuits is 19 A at 2 V output voltage and increases
to 22 A at 4.5 V output. The digital control circuit adds an
additional 3 A, amounting to a total of 44 W of minimum
quiescent power loss.
Fig. 15 presents the results measured at 3.75 ms2 excitation
magnitude, corresponding to a maximum extractable power of
SZARKA et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS
Fig. 16. Measured duty ratio samples and their modal values compared with
the range of duty ratios (shaded region) that correspond to over 99% of the
maximum useful output power based on the measurements of Fig. 15.
870 W under optimum load conditions. The maximum transferred power is 615 W at 2 V at the optimum duty ratio. This
corresponds to a power conversion efficiency of 78.5%, and an
overall system efficiency of 70.7%, where 100% is the maximum extractable power from the energy harvester. As the output
voltage is increased, the optimum duty ratio is also increased.
The maximum useful power is, however, reduced due to the
increased power overheads of the power conditioning circuits.
It is worth noting that a small dip in the power level can be
observed in the 4.5 V line around 80% duty ratio, creating two
local maxima that could result in the failure of a perturb-andobserve MPTT algorithm. During normal operation however,
this situation would not arise, as the output voltage rises slowly
across the large capacity storage element, allowing the algorithm
to track the correct peak. Starting the tracking at high duty ratios
would also reduce the risk of finding the wrong local maximum.
Fig. 16 shows duty ratio at discrete output voltages, held constant by the adjustable shunt regulator circuit. As the duty ratio is
constantly changing, even in these steady-state conditions, 100
recordings of the duty ratio are plotted, as dots, for each voltage,
showing a range of around 2.5%. The solid black line is fitted
over the statistical modal value of each group of 100 samples,
representing the most frequent duty ratio. The shaded region
in Fig. 16 represents the duty ratio range over which in excess
of 99% of the maximum transferred power is obtained. This
region widens toward the low output voltage levels, as can also
be seen in Fig. 15. The modes of the duty ratio measurements
fall within the 99% power region for most of the output voltage
points, which shows that the control circuit can effectively track
the optimum power point.
During the measurements of the duty ratio samples, the energy
harvesters generated power, the transferred power, and the quiescent power overhead of the power conditioning system were
also recorded. The 100 measurement points were averaged, to
take into account that the duty ratio ranges around an optimum
value. These values are plotted in Fig. 17 against output volt-
209
Fig. 17. Average power obtained from 100 measurements per output voltage.
Output voltage is regulated by an adjustable shunt regulator. Constant frame
acceleration of 3.75 ms2 at 43.8 Hz. P m a x is the maximum extractable
harvester power under optimum load conditions.
age, along with the maximum extractable power from the energy
harvester under optimum load conditions for comparison.
The difference between the measured generated power and
the transferred power are due to a combination of three major
loss mechanisms: 1) a nonideal power conversion process; 2)
quiescent power overheads of the control and ancillary circuits;
and 3) the conduction loss in the shunt resistor used for the
monitoring of the output current.
The ratio between the generated power of the nonideally
loaded harvester and the maximum potentially extractable
power under optimum load conditions is referred to as the utilization factor. The utilization of the energy harvester peaks
above 89% at 1.8 V output, and remains over 86% over the entire output voltage range. Less than 100% utilization is primarily
due to the increased conduction losses within the coil that result
from switching frequency current ripple. The power conversion
efficiency is calculated as the ratio of the useful output power
(Pstore ) of the converter to the generated power of the harvester,
while the overall system effectiveness is defined as the useful
output power normalized to the maximum extractable power
from the energy harvester under optimum load conditions. The
conversion efficiency is at its maximum of 76.5% at low voltage
levels where the quiescent power overhead is at its minimum,
dropping down to 66% at 4.5 V. The peak overall effectiveness reaches almost 70%, which when compared against the
maximum of 70.7% recorded under the steady-state characterization (see Fig. 15) shows a highly effective control.
B. Transient Response to Step Change in Excitation and
Output Voltage
The dynamic performance and stability is evaluated by
recording the transient behavior of the power conditioning circuit, monitored by the duty ratio of the converter, in response
to a step change in the frame excitation magnitude and in the
output voltage under the worst-case considerations.
210
Fig. 18. Output current and duty ratio in response to a step change in excitation
magnitude from 3 to 4 ms2 at a constant 2.5 V output. The frequency is
constant at 43.8 Hz. The current is inferred from the output of the current-sense
amplifier circuit.
SZARKA et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS
211
TABLE I
KEY SYSTEM METRICS
the duty ratio (inferred from the reference voltage of the control
circuit). The measured output voltage and useful output current
of the power converter are used to calculate the transferred
power. The ratio of this to the maximum extractable power under
optimum load conditions provides the overall system efficiency
over (see Fig. 20).
The passive quadrupler circuit provides zero-energy startup, charging the supercapacitor to 1.85 V at which point the
active boost rectifier circuit starts to operate. The duty ratio,
starting from a high initial value, quickly finds and tracks the
optimum power transfer point over the charging of the capacitor.
The overall efficiency is highest at low output voltages with an
average value of close to 70%, as presented in Section V-A.
The recorded instantaneous efficiency may exceed this due to
the inertial effects of the mechanical structure resulting in short
burst of power when the damping is increased.
Fig. 21 presents the transient accumulation of energy in the
68 mF supercapacitor when charged by differing power conditioning solutions: 1) passive voltage quadrupler; 2) the full-wave
nonsynchronous boost rectifier in open loop with a constant duty
ratio of = 0.67; and 3) full-wave boost rectifier with MPTT
control. The start-up phase is common for all approaches, provided by the passive voltage multiplier circuit, during which the
capacitor is charged from 0 to 1.85 V.
The results illustrate that the overall output power gain of the
system when MPTT control is employed: The total charge-up
time, corresponding to 0.5 J of energy stored, is reduced by
26.5% and by 8.6% as compared to the passive circuit and the
open-loop systems, respectively. A summary of the key system
metrics is presented in Table I.
VI. CONCLUSION
The work presented in this paper aimed to address the challenges that arise from implementing MPTT for low-power, kinetic electromagnetic energy harvesters. The transient response
of the single-degree-of-freedom mechanical system is presented
and discussed using experimental results and analytical derivations. A method that aids the design of perturb-and-observe
algorithm-based control with discrete perturbations of the control parameter is presented: the minimum time required between
perturbations in order to allow the mechanical structure to settle is calculated for highly underdamped massspringdamper
systems under the assumption of a constant, sinusoidal, nondirect excitation that occurs at the natural resonance frequency of
the mechanical structure.
A complete power conditioning circuit for a low voltage, submilliwatt electromagnetic energy harvester has been presented
that requires no external power and is capable of self-starting
from zero-energy conditions. In contrast with previous work,
the transferred power is maximized instead of the generated
power, thus accounting for the losses suffered during the power
conversion process and the due to the quiescent power overheads. Good peak power tracking effectiveness is demonstrated
despite of the lack of accurate regulation of the apparent input
impedance of the boost rectifier, thus allowing the use of a slow
feedback control, and consequently, a reduced quiescent power
implementation. The total power consumption of the power conditioning system is 44 W at 2 V output.
Steady-state and transient measurements show that the system
is stable and capable of tracking the maximum power transfer
point by optimizing the duty ratio of the PWM signals of the
boost converter over the entire output voltage range. A harvester
utilization of up to 89% is achieved. Overall system effectiveness up to 70% is recorded, corresponding to approximately
600 W of useful output power. The transient responses show
that the calculated settling time provides a reasonable choice for
the minimum time between perturbations. The power converter
topology used in this study can only synthesize resistive load
conditions, limiting the maximum achievable utilization when
the harvester is not in resonance as the optimum load required
212