Challenge - Interpretation
Which Devices are Required to be Selectively
Coordinated?
700.27 states, Emergency system(s) overcurrent
devices shall be selectively coordinated with all
supply side overcurrent protective devices.
Similarly, 701.27 states, Legally required standby
system(s) overcurrent devices shall be selectively
coordinated with all supply side overcurrent
protective devices.
U T I L IT Y B
MAIN A
GE N #1
GE N #2
M A IN B
G EN # 1 M A I N
M S G -T I E
M SG -A
G EN # 2 M A I N
M S G -B
C H IL L E R F D R
C BL - C H IL L E R
D IS T R P N L FD R
C BL - D IST R P N L
A T S -E Q N O RM
A T S-C R N O RM
C B L -A T S E Q N
GE N SW GR
A T S- L S N O R M
C BL -A T S C R N
A T S- E Q E M E R
C BL -A T S L S N
A T S -C R E M E R
C BL -0 00 5
C B L -0 0 06
A T S -L S E M E R
C BL - 00 0 7
C H ILL E R
3. Normal
source to the
line side of the
ATS???
D IS T R P N L
N
4 80 V L R G S T
4 80 V L T G P N L F D R
A T S- E Q
C BL - 48 0V LT G P N L
C B L -E Q 4 80 V P N L
A T S -C R
C BL -C R 4 8 0V PN L
A T S -L S
2. Emergency
source to the
line side ATS
C BL -L S 4 80 V P N L
E Q 4 80 V P N L
C R 4 8 0V PN L
L S 4 80 V P N L
EQ X F M R P R I
C R X FM R P R I
L S X FM R P R I
48 0 V LT G P N L
L T G BR A N C H
C B L -E Q X F M R P R I
C BL -C R X F M R P R I
E Q XFMR
S
C R X FM R
S
C B L -E Q 2 08 V P N L
C BL -L S X F M R PR I
LS X F M R
S
C BL -C R 2 0 8V PN L
C BL -L S 2 08 V P N L
E Q 2 0 8V P N L M A IN
C R 20 8 V P N L M AIN
L S 2 0 8V PN L M A IN
E Q 2 08 V P N L
C R 2 0 8V PN L
L S 2 08 V P N L
E Q 2 0 8V B R A N CH
C R 20 8 V BR A N C H
L S 2 0 8V BR A N C H
U T I L IT Y B
MAIN A
GE N #1
GE N #2
M A IN B
G EN # 1 M A I N
M S G -T I E
M SG -A
G EN # 2 M A I N
M S G -B
C H IL L E R F D R
C BL - C H IL L E R
D IS T R P N L FD R
C BL - D IST R P N L
A T S -E Q N O RM
C B L -A T S E Q N
A T S-C R N O RM
GE N SW GR
A T S- L S N O R M
C BL -A T S C R N
A T S- E Q E M E R
C BL -A T S L S N
A T S -C R E M E R
C BL -0 00 5
C B L -0 0 06
A T S -L S E M E R
C BL - 00 0 7
C H ILL E R
3. Normal
source to the
line side of the
ATS???
D IS T R P N L
N
4 80 V L R G S T
4 80 V L T G P N L F D R
A T S- E Q
C BL - 48 0V LT G P N L
C B L -E Q 4 80 V P N L
A T S -C R
C BL -C R 4 8 0V PN L
A T S -L S
C BL -L S 4 80 V P N L
E Q 4 80 V P N L
C R 4 8 0V PN L
L S 4 80 V P N L
EQ X F M R P R I
C R X FM R P R I
L S X FM R P R I
48 0 V LT G P N L
L T G BR A N C H
C B L -E Q X F M R P R I
C BL -C R X F M R P R I
E Q XFMR
S
C R X FM R
S
C B L -E Q 2 08 V P N L
C BL -L S X F M R PR I
LS X F M R
S
C BL -C R 2 0 8V PN L
C BL -L S 2 08 V P N L
E Q 2 0 8V P N L M A IN
C R 20 8 V P N L M AIN
L S 2 0 8V PN L M A IN
E Q 2 08 V P N L
C R 2 0 8V PN L
L S 2 08 V P N L
E Q 2 0 8V B R A N CH
C R 20 8 V BR A N C H
L S 2 0 8V BR A N C H
10
10
Challenge - Interpretation
What level of Selective Coordination is
required?
Total Selective Coordination
0.01 seconds
0.1 seconds
11
11
12
12
13
13
14
14
15
15
16
16
17
17
Challenge - Design
How Do I Design a System that can be
Coordinated?
18
18
Selective Coordination
Design Tips
1. Flatten the system
19
19
Selective Coordination
2. Transformer Breakers
20
20
Simplified One-Line
Utility
800A
MSB
3000A
750kW
ESB
400A
400A
12,105A
52kA
ATS
400A
HE1
125A
75kVA
XE1
225A
LE1
60A
LE2
20A
2009 Eaton Corporation. All rights reserved.
21
21
800A
MSB
3000A
750kW
ESB
400A
400A
12,105A
52kA
ATS
400A
HE1
125A
52kA
75kVA
XE1
225A
60A
LE1
3187A
LE2
20A
2516A
22
22
800A
MSB
3000A
750kW
ESB
400A
400A
$6K
52kA
12,105A
ATS
400A
HE1
125A
52kA
$4K
75kVA
225A
$1K
$11.5K
XE1
60A
LE1
3187A
LE2
20A
$0.5K
2516A
23
23
800A
MSB
3000A
750kW
ESB
400A
400A
12,105A
52kA
ATS
400A
HE1
125A
52kA
75kVA
TE1
225A
60A
LE1
3187A
LE2
20A
1874A
24
24
25
25
800A
MSB
3000A
750kW
ESB
400A
400A
12,105A
52kA
ATS
400A
HE1
125A
52kA
75kVA
TE1
LE1
225A
3187A
LE2
20A BAB
1874A
26
800A
MSB
3000A
750kW
ESB
400A
400A
12,105A
52kA
ATS
400A
HE1
125A
52kA
75kVA
TE1
LE1
225A
100A FDE
3187A
LE2
20A BAB
1874A
27
27
28
28
800A
MSB
3000A
750kW
ESB
400A
400A
12,105A
52kA
ATS
400A
HE1
125A KD
52kA
75kVA
TE1
LE1
225A KD
100A FDE
3187A
LE2
20A BAB
1874A
29
29
800A
MSB
3000A
750kW
ESB
400A
400A
12,105A
52kA
ATS
400A
HE1
125A KD
10,721A 52kA
75kVA
TE1
LE1
225A KD
100A FDE
3187A
LE2
20A BAB
1874A
30
30
31
31
800A
MSB
3000A
750kW
ESB
400A
400A ND
12,105 A
52kA
ATS
400A
HE1
125A KD
10,721A 52kA
75kVA
TE1
LE1
225A KD
100A FDE
3187A
LE2
20A BAB
1874A
32
32
33
33
800A RD
MSB
3000A
750kW
ESB
400A
400A ND
12,105 A
52kA
ATS
400A
HE1
125A KD
10,721A 52kA
75kVA
TE1
LE1
225A KD
100A FDE
3187A
LE2
20A BAB
1874A
34
34
800A RD
MSB
3000A
750kW
ESB
400A
400A ND
$7.5K
52kA
12,105 A
ATS
400A
HE1
125A KD
10,721A 52kA
$5K
75kVA
TE1
LE1
225A KD
$2K
100A FDE
30% Increase
LE2
20A BAB
$0.5K
1874A
35
35
800A RD
MSB
3000A
750kW
ESB
400A
400A ND
$7.5K
52kA
12,105 A
ATS
400A
HE1
125A KD
10,721A 52kA
$5K
75kVA
TE1
225A KD T/MLE1
$1K
TFL
3187A
Upgrade panel
22% Increase
LE2
20A BAB
to 225A MLO
$0.6K
1874A
36
36
37
37
38
38
39
39
Do we coordinate at the
0.01 level?
40
40
41
41
42
42
To achieve coordination to
0.01 seconds above the ATS
on the generator side, we
have to:
Provide an 800AF/400AT
electronic trip breaker to
feed the ATS
Use a Power Circuit Breaker
on the Generator
43
43
Challenge - Enforcement
How is Selective Coordination Evaluated?
Some jurisdictions are looking at curves
Some jurisdictions require a stamped letter from the
engineer of record
In some jurisdictions, it has yet to be defined
44
44
Challenge - Enforcement
Breaker Curves
No standardized
method for
representing time
current curves
45
45
.01 Sec
46
46
10K
ATS CR
1000
CBL -HC2
PANEL HC2
ATS CR FDR E
CUT LER-HA MMER
ND, RMS 310
Trip 800 A
Plug 40 0 A
Settings Ph ase
LTPU (1.0 x P) Fixed (40 0A)
LTD (Fixed) Fixed
STPU ( 2-8 x P) 5 (20 00A)
STD (Inst-3 00 ms) 1 00 ms(I^2 T Out)
INST (14000 A) Fixed (14000 A)
XFMR LC2
XFMR LC2 SE C
CBL -LC2
LC2 MF
100
PANEL L C2
LC1 FDR
10
CBL -LC1
PANEL LC1
L C1 BRANCH
XFMR LC2
75.0 kV A
10
LC2 MF
CUT LER-HA MMER
EDB
Trip 225 A
Settings Ph ase
Fi xed
TX Inrush
LC1 BRANCH
CUT LER-HA MMER
BA B, 1-Po le
Trip 20 A
Settings Ph ase
Fi xed
0.01
0.5
0.10
0.01
1
10
Current Scale x 10
Oneline:
LC1 BRANCH
August 1, 2007 4:10 PM
10K
0.10
LC1 FDR
CUT LER-HA MMER
BA B, 3-Po le
Trip 60 A
Settings Ph ase
Fi xed
1K
TIME IN SECONDS
1000
100
10
CBL-ATS CR E
1K
100
100
ATS CR FDR E
CURRENT IN AMPERES
47
47
Challenge - Design
What about Arc Flash?
Arc Flash Energy is dependent upon:
Actual magnitude of the fault energy
Time that the arc is allowed to propagate
48
48
800A RD
MSB
3000A
750kW
ESB
400A
400A ND
12,105 A
52kA
ATS
400A
HE1
125A KD
10,721A 52kA
75kVA
TE1
LE1
225A KD
100A FDE
3187A
LE2
20A BAB
1874A
49
49
50
50