Testing of the Limiters in offline (i.e.

When the Machine


is at stand still).
1. Field Current Maximum Limiter :

a. Preliminary in order to ensure that the value displayed in the microterminal for Ifac is correct, measure the milli-volt drop across the FB Shunt
& compute the same for rated value in terms of percentage. This
computed value should match the value displayed in micro-terminal for
Ifac. In case the values are different then calibration for Ifac has to be
done.
b. Please note down the Following parameters
c. With Generator Terminal voltage at rated value (Uref= 100 %), Note down
all the parameters of DVR as per table.
d. Gradually increase terminal voltage by varying the reference value from
local panel to a higher value i.e. in Micro-terminal Uref= 105%.
e. With Generator Terminal voltage at 105% of rated value ( Uref= 105 %) ,
Note down all the parameters of DVR as per following table.
f. Bring back the terminal voltage to rated value i.e. Uref=100%.
g. Note down Field current variation from the above reading at 100 & 105 %.
In order to check the intervention/operation of limiter, field current
value shall be adjusted within the above two values recorded.
h. After adjusting limiter value (F400) to new value, give step input to
Generator voltage from 100 % to 105 %.
i. Check operation / intervention of Field current maximum limiter.
j. With the help of dual channel recorder record the limiter intervention. Also
check the operation of output relay at digital output Module.
k. With limiter in operated condition, note down all the parameters as per
table.
l. Restore the limiter values to original as per factory test report or as per
site requirement.
Parameter

U reference Uref
Generator Voltage
Ugen
Field Current Ifac
Generator Current
Igac
Power P
Control Voltage Uc

Before operation
of Limiter

After
operation
of Limiter

Remarks

Reactive Power Q
Parameters to be recorded from micro terminal.
Ref. Module: 50%

2. Inductive Stator Current Limiter:


a. Check and ensure that the value in micro-terminal for Igac and the generator
current meter reading in the control desk display the same value.
b. With Generator Terminal voltage at rated value ( Uref= 100 %) , Note down
all the parameters of DVR as per table.
c. Gradually increase terminal voltage by varying the reference value from
Micro-terminal. I.e adjust ref. Value Uref= 105%.
d. With Generator Terminal voltage at 105% of rated value (Uref= 105 %), Note
down all the parameters of DVR as per following table.
e. Bring back the terminal voltage to rated value i.e. Uref=100%.
f.

Note down Generator stator current variation zone hence obtained from
reading at 100 & 105 %. In order to check the intervention/operation of
limiter, Inductive stator current value shall be adjusted within the above two
values recorded.

g. After adjusting limiter value (F430) to new value, give step input to Generator
voltage from 100 % to 105 %.
h. Check operation / intervention of Inductive stator current limiter.
i.

With the help of dual channel recorder record the intervention. Also check the
operation of output relay at digital output Module.

j.

With limiter in operated condition, note down all the parameters as per table.

m. Restore the limiter values to original as per factory test report or as per site
requirement.
Parameter

U reference Uref
Generator Voltage
Ugen
Field Current Ifac

Before
operation
of Limiter

After
operation of
Limiter

Remarks

Generator Current Igac


Control Voltage Uc
Power P
Reactive Power Q
Power Factor Cos
2

6. Capacitive Stator Current Limiter


a. With Generator Terminal voltage at rated value ( Uref= 100 %) , Note down all the
parameters of DVR as per table.
b. Gradually reduce terminal voltage by varying the reference value from Micro-terminal. I.e
adjust ref. Value Uref= 90%.( Voltages shall be varied as per system conditions)
c. With Generator Terminal voltage at 105% of rated value ( Uref= 90 %) , Note down all
the parameters of DVR as per following table.
d. Bring back the terminal voltage to rated value i.e. Uref=100%.
e. Note down Generator stator current variation zone hence obtained from reading at 100 &
90 %. Hence to check the intervention/operation of limiter, capacitive stator current
value shall be adjusted within this zone.
f.

After adjusting limiter value (F460) to new value, give step input to Generator voltage
from 100 % to 90 %.

g. Check operation / intervention of Capacitive stator current limiter.


h. With the help of dual channel recorder record the intervention. Also check the operation
of output relay at digital output card.
i.

At limiter operated condition, note down all the parameters as per table.

j.

Restore the limiter values to original as per factory test report.

Parameter

Before
operation
of Limiter

After
operation of
Limiter

Remarks

U Reference Uref
Generator
Voltage Ugen
Field Current Ifac
Generator
Current Igac
Control Voltage
Uc
Power P
Reactive Power
Q
Power Factor
Cos
F 460
Ind
3

7. Load Angle Limiter


a. The value of Xq & Xe has to be entered in DVR.
Xq (C4A4) =
(164.19%) = Pu
Xe (C4A6) =
Pu
= pu
Procedure for Calculations of Xe & Xd
1. Please refer calculations details for " External Network Reactance Xe P.U."
Xe= (change in vol. Ug/ Ugn) / (change in MVAR/ S)
Where,
Ug = Generator terminal Voltage
Ugn= rated generator terminal voltage.
S= Rated MVA capacity of generator.
For reference, the data of BPCL DVR is enclosed.

Take machine to inductive zone and note down readings as.( all
measurements are taken from microterminal)
Power factor=

Lag; Ug= 110.00 V AC ( PT volts)

Reactive power Q =
Delta act.( Dact) =

deg.

Take machine to capacitive zone and note down readings as.( all
measurements are taken from microterminal )
power factor= Lead; Ug=
V AC;
Reactive power Q =
%( MVAR lead )
Delta act.( Dact) =
deg.

Calculations
Change in Ug/ Ugn = (U lag - U lead)/ Ugn
=
Change in MVAR = (MVAR lag - MVAR lead)
=
Xe

= (change in vol. Ug/ Ugn) / (change in MVAR/ S)


=
=

2 Xd and Xe Values.
a. For this, refer to the DVR factory test report document, page titled "
synchronous machine data & specification of excitation equipment". This
sheet gives details about machine synchronous reactance (direct axis
4

unsaturated / quadrature axis). In case the Quadrature axis reactance is not


mentioned then the value as given for direct axis unsaturated in the
generator data sheet or DVR test report for e.g. 192.26% (1.92 p.u.) then this
value of Xd can be assumed.
b. With Generator Terminal voltage at rated value ( Uref= 100 %) , Note down
all the parameters of DVR as per following table.
c. Gradually reduce terminal voltage by varying the reference value from Microterminal. I.e adjust ref. Value Uref= 90%.( Voltages shall be varied as per
system conditions)
d. With Generator Terminal voltage at 105% of rated value ( Uref= 90 %) , Note
down all the parameters of DVR as per table.
e. Bring back the terminal voltage to rated value i.e. Uref=100%.
f.

Note down Generator stator current variation zone hence obtained from
reading at 100 & 90 %. Hence to check the intervention/operation of limiter,
capacitive stator current value shall be adjusted within this zone.

g. After adjusting limiter value (F4A0) to new value, reduce terminal voltage
gradually from 100 % to 90 %.
h. Check operation / intervention of load angle limiter at set value.
i.

With the help of dual channel recorder record the intervention. Also check the
operation of output relay at digital output card.

j.

At limiter operated condition, note down all the parameters as per table.

k. Restore the limiter values to original as per factory test report.


Parameter
U reference Uref
Generator Voltage
Ugen
Field Current Ifac

Before
operation
of Limiter

After
operation
of Limiter

Remarks
is enclosed

Generator Current Igac


Control Voltage Uc
Power P
Reactive Power Q
Power Factor Cos