Академический Документы
Профессиональный Документы
Культура Документы
SVE712
Product Information
2/6
SVE712
Excellent price/performance ratio
Rugged and service-friendly design
Reliability through use of latest technology
Delivered in ready-to-connect condition
Convenient and safe to configure
Can be monitored from a remote point
Cost-effective, space-saving,
adaptable to specific needs, well
thought out in every detail and
perfected, these products of our
series 700 are competitive everywhere on the world market.
Our compact system SVE712 is
an ideal solution both from a
technological as well as an economic point of view.
Reliable
The rectifiers of this system are
designed using the latest switch
mode technology.
Two battery fuses are installed
as standard, allowing the connection of any type of battery.
The direct connection between
batteries and loads offers
maximum system reliability,
specifically when redundant
rectifiers are used, and thus
ensures uninterruptible supply
of power.
3/6
Basic equipment:
Before leaving the factory, the systems are ready for
operation, equipped with the following components:
Control SVS-SM7
Two rectifiers GR70 (750 W each)
Two battery fuses
DC / AC distribution
Temperature sensor
Deep discharge protection
System description
This compact system complies
with the ETSI standard as far as
its basic dimensions and design
are concerned. The front is fitted with a door; the paint finish
is Ergo grey.
The cables are brought in from
the top. This is where the battery fuses, load output assemblies and load fuses are situated. The rectifiers are accommodated in the bottom section
of the cabinet.
All components are clearly arranged and readily accessible.
System SVE712 is suitable for
wall mounting, but can also be
installed as a free-standing unit.
The use of a suitable battery
cabinet is possible to optimise
the system.
Rectifiers
Rectifiers convert the AC from
the public system to a constant
DC and supply the loads with
DC power and the batteries
with float current.
The rectifers used in our power
supply systems always operate
in standby parallel mode, with
loads, batteries and rectifiers
connected in parallel. If the
SVE712
public power line fails, the batteries take over without interruption.
The rectifiers GR70 (750 W)
used here employ the latest
switch mode technology.
Power density, efficiency and
electromagnetic compatibility
meet the most stringent requirements.
Safety devices
The system can additionally be
equipped with lightning and
overvoltage protective devices.
A temperature sensor is installed as standard. It ensures
that the battery float charge is
regulated as a function of temperature.
Batteries
As an addition to the SVE712 a
battery cabinet is on offer.
Each of the compact systems
contains two battery fuses
HCR-type which ensure safe
electrical isolation in the event
of a short circuit even in cases
where large battery capacities
are involved.
4/6
Features
75 A at 48 V / 24 V
60 A at 60 V
Up to 6 rectifiers GR70 (750 W each)
Wall mounting possible
Battery cabinet as additional unit
SVE712
Technical data
Input voltage/ current
48 V / 60 V
24 V
3/N AC 400 V
1/N AC 230 V
Output voltage / current
6,6 A
19,8 A
3,3 A
9,9 A
48 V / 24 V
60 V
75 A
60 A
3 x 16 A or 2 x 50 A (Tripping characteristic C)
10 mm2 (solid) or 16 mm2 (stranded)
System overview
Ordering number
SVE712
Battery cabinet
Up to 6 rectifiers GR70 (750 W each)
Spare parts package
Contactor for conversion to 24 V
S30050-G6301-X100
S30050-B6310-X140
S30050-K6302-X212
S30050-K6301-P700
S30050-K6301-P724
43 kg*
24 kg*
4 kg
5/6
S30050-K6302-X212
Rectifier
GR70 750 W
Technical data
24 V
48 V
60 V
1.7 A
12.5 A
> 0.83
3.4 A
12.5 A
0.89
3.4 A
10 A
> 0.90
Input voltage
Input voltage range
Nominal frequency
Power factor ()
1/N AC 230 V
184 V .....264 V
47 Hz ..... 63 Hz
1
< 1.0 mV frequency weighted
( ITU-T A filter curve)
< 10 mV RMS
24 V
48 V
60 V
(default setting: 48 V)
The GR70 is designed as a slidein module for use in the power
supply unit SVE712 and is constructed using the latest switch
mode technology.
It is extremely compact and
light; at the same time it has an
excellent power density
For us, sinusoidal line input
current is a must. And so a
circuit breaker provides
protection against overloading
and short circuits.
Noise voltage
Superimposed AC voltage
Electromagnetic compatibility
Interference emission
Interference immunity
Type of enclosure acc. to EN 60529
(IEC 529, VDE 0470 Part 1)
Ambient temperature
Dimensions ( H x W x D )
Weight
EN 55022 Class B,
DIN VDE 0878 Class B
EN 61000-6-2
IP 20
-10 C to +45 C
262 x 71 x 300 mm
4 kg