Technical Manual
Version
Revision date
BOM

V1.0
2008-07-17
31020737

Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.

Copyright 2008 by Emerson Network Power Co., Ltd.


All rights reserved. The contents in this document are subject to change without notice.

Emerson Network Power Co., Ltd.


Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
E-mail: support@emersonnetwork.com.cn

Contents
Chapter 1 Overview ............................................................................................................................................................ 1
1.1 Classification And Model....................................................................................................................................... 1
1.2 Model Description ................................................................................................................................................. 1
1.3 Appearance And Structure.................................................................................................................................... 1
Chapter 2 Techanical Parameters....................................................................................................................................... 3
2.1 Environmental Parameters ................................................................................................................................... 3
2.1.1 Paramters Of Storage Environment........................................................................................................... 3
2.1.2 Paramters Of Operation Environment ....................................................................................................... 3
2.2 Mechanical Parameters ........................................................................................................................................ 4
2.2.1 Mechanical Parameters Of Condenser...................................................................................................... 4
2.2.2 Mounting Base Parameters ....................................................................................................................... 4
2.3 Performance Parameters ...................................................................................................................................... 5
2.3.1 Fan Design Parameters............................................................................................................................. 5
2.3.2 Heat Exchanging Capacity ........................................................................................................................ 6
2.3.3 Noise Parameters ...................................................................................................................................... 6
2.3.4 Configuration Parameters.......................................................................................................................... 7
Chapter 3 Fan Speed Controller ......................................................................................................................................... 8
3.1 Control Logic......................................................................................................................................................... 8
3.2 Wiring Terminals ................................................................................................................................................... 9
3.3 HMI ..................................................................................................................................................................... 10
3.4 Operation Description Of HMI ............................................................................................................................. 11
3.5 Protection Function ............................................................................................................................................. 14
3.6 Alarm Protection ................................................................................................................................................. 14
Chapter 4 Maintenance And Troubleshooting ................................................................................................................... 15
4.1 Maintenance ....................................................................................................................................................... 15
4.2 Troubleshooting .................................................................................................................................................. 16
Appendix 1 Condenser Matching Table ............................................................................................................................ 18
1. R22 Matching Table.............................................................................................................................................. 18
2. R407C Matching Table ......................................................................................................................................... 19
Appendix 2 Circuit Diagram............................................................................................................................................... 20
Appendix 3 Lifting Figure................................................................................................................................................... 22

Liebert.PEX Condenser Technical Manual

Chapter 1 Overview

Chapter 1 Overview
This chapter introduces the classification, model, model description, appearance and structure of the Liebert.PEX
condenser (condenser for short).

1.1 Classification And Model


The condenser can be classified into two types: single system and double system with 13 models. See Table 1-1 for
detailed models.
Table 1-1

Models

Type

Model

Single system

LSF24, LSF32, LSF38, LSF42, LSF52, LSF62, LSF70, LSF76, LSF85

Double system

LDF42, LDF52, LDF62, LDF70

1.2 Model Description


Taking LSF62 for example, the model description of the condenser is shown in Figure 1-1.

L SF 62
Model code
SF: single system with fan speed controller
DF: double system with fan speed controller
Liebert
Figure 1-1

Model description

1.3 Appearance And Structure


The condenser consists of heat exchanger, fan, fan speed controller and pressure sensor. The heat exchanger is
inside the condenser, other components are shown in Figure 1-2. Note that if the side copper pipes are collided, they
will be deformed easily to result in the system leakage. So you must use a correct method to move the condenser.
For detailed movement, refer to Chapter 2 Installation in Liebert.PEX Condenser User Manual and Appendix 3
Lifting Figure in this manual.
Fan

Electrical control box (there is


a fan speed controller inside)

Pressure sensor

Single fan

Liebert.PEX Condenser Technical Manual

Chapter 1 Overview
Fans

Electrical control box (there is


a fan speed controller inside)
Pressure sensors

Double fans
Figure 1-2

Condenser

Liebert.PEX Condenser Technical Manual

Chapter 2 Technical Parameters

Chapter 2 Techanical Parameters


This chapter expounds the environmental parameters, mechanical parameters and performance parameters of the
condenser.

2.1 Environmental Parameters


2.1.1 Paramters Of Storage Environment
See Table 2-1 for storage environment of the condenser.
Table 2-1

Item
Storage environment
Environmental temperature
Environmental humidity
Storage time

Parameters of storage environment

Requirement
Clean indoor environment with good ventilation and no dust
-40C ~ +70C
5%RH ~ 85%RH
The total storage time should not exceed 6 months. Otherwise, the performance needs to be
re-calibrated

2.1.2 Paramters Of Operation Environment


See Table 2-2 for the operation environment of the condenser.
Table 2-2

Item
Installation position

Parameters of operation environment

Requirement
The standard equivalent distance between the indoor unit and condenser is 30m. The vertical
difference* H is from -5m to 20m. The installation mode includes horizontal mode and vertical mode

Environmental
Outdoor temperature: -20C ~ +45C. Low temperature accessories are required if the temperature is
temperature
-35C ~ -20C
Environmental humidity Outdoor: 5%RH ~ 95%RH
Operation power
380V10%, 50Hz
Altitude
1000m. Derating is required if the altitude exceeds 1000m
Protection level
Electrical control box: IP55; unit: IP20
Note*:
The value is positive if the condenser is installed higher than indoor unit; and negative if the indoor unit is installed higher than
the condenser

Note

When the equivalent distance between the indoor unit and condenser exceeds 30m, see 5.1 Refrigerant Tubing System in
Liebert.PEX Series Air Conditioner Technical Manual for the detailed requirement for the line equivalent distance.

Liebert.PEX Condenser Technical Manual

Chapter 2 Technical Parameters

2.2 Mechanical Parameters


2.2.1 Mechanical Parameters Of Condenser
The condenser appearance and structure with vertical placement is shown Figure 2-1 and the detailed mechanical
parameters are listed in Table 2-3.
LL

Front view
Figure 2-1

Table 2-3

Model

Weight
(kg)

LSF24
LSF32
LSF38
LSF42
LSF52
LSF62
LSF70
LSF76
LSF85
LDF42
LDF52
LDF62
LDF70

105
110
120
130
140
150
150
220
230
130
140
160
160

L
1410
1410
1410
1610
1610
1910
1910
2410
2410
1610
1610
2110
2110

Side view

Appearance and structure (double fans)

Dimension (mm)
H
980
980
980
1280
1280
1280
1280
1280
1280
1280
1280
1280
1280

Structure parameters

W
679
679
686
686
686
679
679
686
686
686
686
679
679

Liquid pipe dimension (mm)

Discharge pipe dimension (mm)

16
16
16
16
22
22
22
22
22
16
16
22
22

22
22
22
22
28
28
28
28
28
22
22
28
28

2.2.2 Mounting Base Parameters


The condenser can be installed in horizontal and vertical modes. The mounting base is shown in Figure 2-2 during
horizontal installation and the detailed mounting base dimensions of each model are listed in Table 2-4.
L'
D

D
D

Part amplified figure


Installtion holes
(8 holes in total )
H'

D
Figure 2-2

Mounting base dimensions

Liebert.PEX Condenser Technical Manual

D
D

Chapter 2 Technical Parameters


Table 2-4

Mounting base dimensions

Model

Dimension (L' H' D)

Model

Dimension (L' H' D)

LSF24

1126 837 53

LSF76

2126 1120 53

LSF32

1126 837 53

LSF85

2126 1120 53

LSF38

1126 837 53

LDF42

1326 1120 53

LSF42

1326 1120 53

LDF52

1326 1120 53

LSF52

1326 1120 53

LDF62

1826 1120 53

LSF62

1626 1120 53

LDF70

1826 1120 53

LSF70

1626 1120 53

Note

The installation holes are long and flat holes. It is recommended to use M10 20 bolts to fix the mounting base.

2.3 Performance Parameters


The performance parameters of the condenser include the fan design parameters, heat exchanging capacity, noise
parameters and configuration parameters.

2.3.1 Fan Design Parameters


The fan design parameters of the condenser are listed in Table 2-5.
Table 2-5

Model

Fan No.

LSF24
LSF32
LSF38
LSF42
LSF52
LSF62
LSF70
LSF76
LSF85
LDF42
LDF52
LDF62
LDF70

1
1
1
1
1
2
2
2
2
1
1
2
2

Diameter
(mm)
710
710
800
800
800
710
710
800
800
800
800
710
710

Fan design parameters

Rated air flow


3
(m /h)
13600
8150
15800
15800
14000
25600
25600
31600
28000
15800
14000
25600
25600

Rated speed (rpm)

Rated current (A)

Rated power (W)

900
690
650
650
650
900
900
650
650
650
650
900
900

1.65
1.05
2.4
2.4
2.4
3.3
3.3
4.8
4.8
2.4
2.4
3.3
3.3

0.88
0.62
1.05
1.05
1.05
1.76
1.76
2.1
2.1
1.05
1.05
1.76
1.76

Note

1. The rated air flow, rated speed, rated current and rated power are the operating parameters supplied by the fan in 400V voltage.
2. The condenser unit power supply is provided in site and its specification is selected following the rated current in Table 2-5.
3. The specification 20AWG (0.52mm2) is recommended for the condenser startup/stop signal cable.

Liebert.PEX Condenser Technical Manual

Chapter 2 Technical Parameters

2.3.2 Heat Exchanging Capacity


The heat exchanging capacity (unit: kW) of all condenser models are listed in Table 2-6 and Table 2-7.
Table 2-6

Heat exchanging capacity table (R22)


*

Model

10
12
LSF24
15.3
19.8
LSF32
18.0
23.1
LSF38
24.9
31.8
LSF42
28.6
36.2
LSF52
35.3
44.8
LSF62
43.1
54.6
LDF42
30.0
38.0
LDF52
34.2
43.3
LDF62
45.5
57.6
Note*:
TD is the heat exchanging temperature difference of the condenser
Table 2-7

TD (C)
15
26.3
30.5
41.5
47.6
58.9
71.8
50.0
57.0
75.8

18
32.3
36.6
50.7
58.1
71.9
87.6
61.0
69.5
92.5

20
35.9
41.0
56.6
64.7
80.1
97.6
68.0
77.5
103.1

Heat exchanging capacity table (R407C)


*

Model
LSF24
LSF32
LSF38
LSF42
LSF52
LSF62
LSF70
LSF76
LSF85
LDF42
LDF52
LDF62
LDF70

10
11.6
14.2
19.2
21.7
26.7
32.8
34.9
39.8
45.9
22.6
27.7
35.2
37.2

TD (C)
15
22.8
27.8
37.6
42.5
52.4
64.4
68.4
78.0
90.0
44.4
54.4
69.0
73.0

12
14.4
18.6
25.1
28.5
35.1
43.1
45.8
52.3
60.3
29.7
36.4
46.2
48.9

18
29.1
35.1
48.2
54.4
67.1
82.4
87.6
99.8
115.2
56.8
69.6
88.3
93.4

20
33.6
39.8
54.8
62.1
76.5
94.0
99.9
113.9
131.4
64.8
79.4
100.7
106.6

Note*:
TD is the heat exchange temperature difference of the condenser

2.3.3 Noise Parameters


Place the condenser vertically and test the noise of the outdoor fan separately following JB/T 4330-1999. The fan
testing voltage is the output voltage of the condenser fan speed controller in noise testing condition. See Table 2-8 for
noise testing condition and refer to Figure 2-3 and Figure 2-4 for noise test unit place mode. The noise parameters of
all models are listed in Table 2-9.
Table 2-8

Noise test condition (unit: C)

Internal cycle air condition


Dry bulb temperature
Wet bulb temperature
23
17

External cycle air condition


Dry bulb temperature
Wet bulb temperature
35
-

Liebert.PEX Condenser Technical Manual

Chapter 2 Technical Parameters

E
Condener
C
(vertical mode)
B

Testing point 4

Testing point 3

Testing point 1

Testing point 2
Air flow

Horizontal difference: the difference between the testing point and the unit shell is 1m
Vertical difference: the vertical difference from the earth is 1/2 (the unit height +1m)
ECB: electrical control box
Figure 2-3

Single fan noise test figure with vertical placement

Condener
(vertical mode)

Testing point 4

Testing point 3

E
C
B

Testing point 1

Testing point 2
Air flow

Horizontal difference: the difference between the testing point and the unit shell is 1m
Vertical difference: the vertical difference from the earth is 1/2 (the unit height +1m)
ECB: electrical control box
Figure 2-4

Double fan noise test figure with vertical placement


Table 2-9

Model
LSF24
LSF32
LSF38
LSF42
LSF52
LSF62
LSF70
LSF76
LSF85
LDF42
LDF52
LDF62
LDF70

Noise parameters (unit: dB (A))

Actual measured noise


64
64
66
66
68
68
68
68
68
68
68
68
68

GB/T 19413-2003
68
71
71
71
73
73
73
73
73
71
73
73
73

2.3.4 Configuration Parameters


The condenser uses the fan speed controller to control the fan full load voltage according to the designed loads of all
models and decrease the fan noise in the condition of meeting the designed load. The defaulted full load voltage
Vmax percentages at factory of all models are listed in Table 2-10.
Table 2-10

full load voltage Vmax percentages at factory

Condenser model
LSF32, LSF70, LDF52, LDF70
LSF52, LSF76, LSF85, LDF42
LSF38, LSF42, LSF62, LDF62
LSF24

Vmax percentage at factory (%)


100
89
73
65

Liebert.PEX Condenser Technical Manual

Chapter 3 Fan Speed Controller

Chapter 3 Fan Speed Controller


This chapter expounds the application of the fan speed controller, including control logic, wiring terminals, pressure
sensor selection, Human-Machine Interface (HMI), HMI operation, protection function and alarm function.

3.1 Control Logic


The control logic of the fan speed controller is shown in Figure 3-1.
V
F

100Vin
B

Vmax

E
C

2bar
A

Vx
Vmin

1bar
I
Poff

Pset

Figure 3-1

Pband
Px

5bar
Pv max Pv100

Control logic figure

The control logic is described as follows:


z Startup control: if the startup condensing pressure is within the set range (Pset, Pset + Pband), the fan speed
controller will output Vx; if the startup condensing pressure exceeds the set range (Pset, Pset + Pband), the fan
speed controller will output Vmax.
z Operation control: the control logic during operation follows A -> B -> C -> D -> E -> F -> C -> B -> A -> G -> H ->
I. The A point is the corresponding point of condensing pressure from B to G.
z Shut down control: when the condensing pressure is less than Poff ( = Pset - 1), the fan speed controller stops
supplying power with fan.
z Max. output voltage control: when the condensing pressure exceeds Pv100 ( = Pset + Pband + 5), the fan speed
controller supplies 100% input voltage Vin with fan; when the condensing pressure is down to Pvmax ( = Pv100 - 2),
the fan speed controller supplies the max. setting voltage Vmax with fan.

Note

1. The boosting pressure process of the system follows the control logic of black line: G -> A -> B -> C -> D -> E and the
releasing pressure process follows the control logic of red line: E -> F -> C -> B -> A -> G -> H -> I. The difference between the
two processes is the return difference: Pv100 - Pvmax = 2bar and Pset - Poff = 1bar.
2. Pv100 - (Pset + Pband) = 5bar.
The definitions, default values and setting ranges of the relative configuration parameters about the control logic are
listed in Table 3-1.
Table 3-1

SN
1
2
3
4
5
6

Configuration parameters of control logic

Name
Startup pressure Pset
Pressure control range Pband
Min. setting voltage Vmin
Max. setting voltage Vmax
Fan configuration number

Default
13bar
5bar
30%
See Table 2-10
1

Sensor type

2: current type

Liebert.PEX Condenser Technical Manual

Setting range
11bar ~ 15bar
4bar ~ 6bar
30% ~ 50%
60% ~ 100%
1~2
1: voltage type
2: current type

Chapter 3 Fan Speed Controller


Note

1. The configured fan number must be the actual fan number, otherwise the alarm will be generated.
2. The configured pressure sensor type must be the same as the used type, otherwise the pressure will not be measured accurately
and the deviation will be increased during the control process.

3.2 Wiring Terminals


The wiring terminals are on the fan speed controller board. Their distributions are shown in Figure 3-2 and the
definitions are listed in Table 3-2. Refer to Appendix 2 Circuit Diagram for detailed connections.
J8(SCRTemp) LCD and keys D15

J9

W
V

J3(HP1)
J4(HP2)

U
J1

J17
J18

L3
L2
L1

J14(HP2)
J15HP1
J5(Out Temp)
J11(RS232)
J7(Fan1Sta)
J10(Fan2Sta)

PE

J6(CompSta)

D16
Figure 3-2
Table 3-2

Silk print

Layout of wiring terminals


Definitions of wiring terminals

Definition

J1

AC I/O terminal

J9

Passive dry contactor relay output (for the


power switch of fan power supply contactor)

J3 (HP1)
J4 (HP2)
J15 (HP1)
J14 (HP2)

Input terminal of voltage pressure sensor 1


(spare)
Input terminal of voltage pressure sensor 2
(spare)
Input terminal of current pressure sensor 1
Input terminal of current pressure sensor 2

J17, J18

Shorting jumpers of current pressure sensor

J5 (Out Temp)

Input terminal of environment temperature


sensor (spare)

J11 (RS232)

Serial communication interface (used for


maintenance)

J7 (Fan1Sta)
J10 (Fan2Sta)

D22

Detecting terminal of fan 1 over temperature


state
Detecting terminal of fan 2 over temperature
state

Definition of pins
PE: protection earth
L1, L2, L3: three-phase AC input
U, V, W: three-phase AC output, which connects with the
power supply terminals
The middle terminal pin without logo is reserved
Pin 1: normally closed terminal of relay, which is reserved
Pin 2: common terminal of relay, which is used for AC input
Pin 3: normally open terminal of relay, which is used for AC
output
Pin 1: positive terminal of 5V power
Pin 2: input terminal of 0.5V ~ 4.5V pressure voltage signal
Pin 3: negative terminal of 5V power
Pin 1: positive terminal of 12V power
Pin 2: input terminal of 4mA ~ 20mA pressure current signal
Current prssure sensor: the short circuit ring must be installed
on the shorting jumpers
Voltage pressure sensor: the open state of short jumpers must
be kept
Pin 1: input terminal of temperature signal
Pin 2: signal groud
Pin 1: communication ground
Pin 2: reception terminal of communication
Pin 3: transmission terminal of communication
Pin 1: output terminal of 19V AC signal
Pin 2: return terminal of 19V AC signal

Liebert.PEX Condenser Technical Manual

10

Chapter 3 Fan Speed Controller


Silk print
Definition
Definition of pins
J6 (CompSta)
Detecting terminal of compressor state
Note :
J8 (SCRTemp) in Figure 3-2 is the interface of fan speed controller board, and not to be used by users

Note

1. If the phase sequence of three-phase AC input (L1, L2 and L3) is connected reversely, the fan speed controller will generate
the phase loss alarm A00 and cannot supply the AC output.
2. If the phase sequence of three-phase AC output (U, V and W) is connected reversely, the fan will operate in reverse.
3. If he over temperature detecting terminals (J7, J10) of fan1 and 2, and the compressor detecting terminal (J6) are not connected,
you can short them by short cables to make sure the fan speed controller can operate normally. If the terminals are disconnected,
the fan speed controller cannot supply the AC output.

3.3 HMI
The fan speed controller can realize the HMI function through indicators, RS232 serial communication port, keys and
LCD.
Indicators
There are three indicators (see Figure 3-2) on the fan speed controller board. See Table 3-3 for the functions of
indicators.
Table 3-3

Silk
print
D16

Definition

Color

Power indicator

Green

D22

Run indicator

Green

D15

Power switch controlling


indicator of AC contactor

Indicator functions

State
On
Off
On or off
Blinking at 1Hz (slowly)
Blinking at 5Hz (quickly)
On

Red
Off

Function
There is 5V power supply on the CPU circuit of
fan speed controller board
There is a faulty on fan speed controller board
There is a faulty on fan speed controller board
The system is running normally without alarm
There is an alarm or the compressor is shut down
The control switch which supplies the AC contactor
with the driving power is open
The control switch which supplies the AC contactor
with the driving power is closed

RS232 serial communication port


RS232 serial communication port (see J11 in Figure 3-2) provides a port to interface the computer using
factory-defined protocol. It is used in factory commissioning and maintenance.
Keys and LCD
The keys and LCD, which can realize the functions in Table 3-4, provide the HMIs for maintenance personnel. Refer
to 3.4 Operation Description Of HMI for the detailed operations of keys and LCD HMI.
Table 3-4

NO.
1

Function
Inquiry the acquisition
data in real time

Function descriptions of keys and LCD

Description
The inquiried acquisition data includes condensing pressure, environment temperature, SCR
temperature, output percentage
The inquiried current alarm data includes phase loss alarm, SCR over temperature, fan 1
over temperature, fan 2 over temperature, pressure sensor failure, EEPROM read fault
alram, SCR temperature sensor failure and abnormal frequency

Inquiry
the
current
alarm data in real time

Inquiry the historical


alarm data in real time

The present 100 historical alarms saved can be inquiried

Change the configured


parameters in real time

The changed configured parameters include running pressure, pressure controlling range,
minimum voltage, maximum voltage, fan number, pressure sensor type; or resume the
default values

Liebert.PEX Condenser Technical Manual

Chapter 3 Fan Speed Controller


The keys and LCD are located on the upper right corner of the fan speed controller, as shown in Figure 3-2. Their
appearance is shown in Figure 3-3.

LCD

ENT key

ESC key
UP key DOWN key

Figure 3-3

Keys and LCD

3.4 Operation Description Of HMI


Initial Interface
The LCD will display alternately F01 (the max. pressure logo) and the bigger one of condensing pressure 1 and
condensing pressure 2 when the fan speed controller is powered on initially. The key function on initial interface is
listed in Table 3-5. The show order is shown in Figure 3-4 (the 16.1 is only an example, and the actual value is
determined by the sampling result).
Table 3-5

Key on initail interface

Key
ESC

Function
Used to enter the main menu interface

F01

16.1

F01

Figure 3-4

16.1

Initial interface

Note

The pressure value will be displayed as 88.8 on the LCD upon the following occasions:
1. The pressure sensor is not installed.
2. The short jumper caps of terminals J17, J18 used to configure the current pressure sensor is not installed correctly.
3. The pressure sensor is disabled.
Main Menu Interface
The main menu interface includes the analog main menu interface F--, current alarm main interface A--, historical
alarm main menu interface H-- and configuration main menu interface C--. The key functions of main menu
interface are listed in Table 3-6. The switching operation processes and orders are shown in Figure 3-5.
Table 3-6

Key functions of main menu interface

Key
UP, DOWN
ENT

Function
Used to switch between the main menu interfaces
Used to enter the submenu interface

DOWN key

DOWN key

F-Analog main
menu interface

A-UP
key

DOWN key

H--

Current alarm
main interface

DOWN key
UP key
Figure 3-5

C--

UP
UP
Configuration main
key Historical alarm main key
menu interface
menu interface

Switch figure of main menu interfaces

Liebert.PEX Condenser Technical Manual

11

12

Chapter 3 Fan Speed Controller


Analog main menu interface
The key functions of analog main menu interface are listed in Table 3-7. The switching operation processes and
orders are shown in Figure 3-6.
Table 3-7

Key functions of analog main menu interface

Key
UP, DOWN
ESC

Function
Used to switch between ID
Used to return the analog main menu interface F--

Analog main menu

F- -

ENT key

Analog submenu shows


the ID and values circulary

DOWN key F01

16.1

F02

16.1

F03

.0

F04

-15

F05

60

F06

88

ESC key

Initial interface
Analog ID definitions
F01: the maximum pressure between the
pressure 1 and pressure 2; 88.8 will be
shown when the pressure sensor is disable
F02: pressure 1
F03: pressure 2
F04: environment temperature
F05: SCR temperature
F06: output voltage percentage
UP key

Figure 3-6

Switch figure of analog main menu interface

Current alarm main interface


The key functions of the current alarm main interface are listed in Table 3-8. The switching operation processes and
orders of the current alarm submenu are shown in Figure 3-7.
Table 3-8

Key functions of the current alarm main interface

Key
UP, DOWN
ESC

Function
Used to switch between ID
Used to return the analog main menu interface F-Current alarm
main interface

When there is alarm, the XX


of alram ID is number from 00

ENT key

A- -

DOWN key
- - ESC key

No alarm

or

AXX
AXX
AXX

F- -

AXX
UP key

Current alarm ID definitions


A00: Phase loss alarm
A01: SCR over temperature
A02: Fan 1 over temperature
A03: Fan 2 over temperature
A04: Pressure sensor failure
A05: EEPROM read fault
A06: SCR temperature sensor failure
A07: Abnormal frequency

Figure 3-7 Switch figure of current alarm main interface

Note

The alarm generating conditions and troubleshooting are listed in Table 4-2.

Liebert.PEX Condenser Technical Manual

Chapter 3 Fan Speed Controller

13

Historical alarm main menu interface


The key functions of historical alarm main menu interface are listed in Table 3-9. The switching operation processes
and orders of the historical main menu are shown in Figure 3-8.
Table 3-9

Key functions of historical alarm main menu interface

Key
UP, DOWN
ESC

Function
Used to switch between ID
Used to return the analog main menu interface F--

Historical alarm main


The radix point is the space mark between the number order and
menu interface
alarm ID. The number is the alarm number and from1 whcih is
ENT key the present historical alarm. 0 is the 100th historical alarm. X is
the hiatorical alarm ID. when there is no alarm, '-' will be shown
H- DOWN key
1.X
2.X

ESC key

99.X

F- -

0.X

Historical alarm ID definitions


0: Phase loss alarm
1: SCR over temperature
2: Fan 1 over temperature
3: Fan 2 over temperature
4: Pressure sensor failure
5: EEPROM read fault
6: SCR temperature sensor failure
7: Abnormal frequency
UP key -: No alarm

Analog main menu


Figure 3-8

Switch figure of historical alarm main menu interface

Configuration data main menu interface


Note

The configuration data main menu interface is designed only for maintenance personnel to set parameters, others are prohibited
to operate it.
The key functions of configuration data main menu interface are listed in Table 3-10. The switching operation
processes and orders of the configuration data main menu are shown in Figure 3-9.
Table 3-10

Key
UP, DOWN
ENT

ESC

Key functions of configuration data main menu interface

Function
1. Used to switch between ID
2. Used to change the ID value
1. Used to enter the changing interface of ID value
2. Used to ensure the changed ID value
1. Used to return the configuration main menu interface C-2. Used to return the configuration value change submenu interface from the configuration
ID selected submenu interface
3. Used to return the configuration value change submenu interface from the prompt
interface of successful change

Liebert.PEX Condenser Technical Manual

14

Chapter 3 Fan Speed Controller


Configuration main
menu interface
ENT key

ESC key

C- -

Configuration value
Configuration ID
selected submenu changed submenu (using
UP key
DOWN and UP keys)
C01
13
C02
ESC key

C03
C04

4
ESC key
ENT key

C05

30
100
1

C06

888

Prompt interface of
successful change

Configuration ID definitions
ENT key C01: Pressure set Pset
C02: Pressure band Pband
C03: Minimum voltage Vmin
C04: Maximum voltage Vmax
C05: Fan number
C06: Sensor type
C99: Resume the default

C99
DOWN key

Figure 3-9 Switch figure of configuration data main menu interface

3.5 Protection Function


The fan speed controller can provide the protection function according to the acquired information. The detailed
protection functions are as follows:
z Compressor operation synchronization protection
When the compressor operates normally, the fan speed controller can provide the output control according to the
condensing pressure measured value. Otherwise, the fan power supply will be shut off.
z Fan power protection 1
Before starting the fan power output, if the AC abnormal frequency alarm (the normal range of AC frequency is 45Hz
~ 65Hz) is detected, the fan power output will be stopped until the AC frequency is back to be normal.
z Fan power protection 2
If fan over temperature, phase loss alarm and SCR over temperature are generated during single fan configuration,
the fan power output will be stopped until there are not the alarms. When the temperature is up to 100C, the SCR
cuts the power from the fan; when the temperature is down to 70C, the power to fan is restored.
z Fan power protection 3
When the single fan is configured, if the interval time between two consecutive over temperature alarms of fan 1 is
less than 24 hours, the power of fan contactor coil will be cut off and the fan power output will be stopped. After the
maintenance personnel resolve the faulty and restart the fan speed controller, the fan re-works.
When the double fans are configured, if the interval time between two consecutive over temperature alarms of both
fan 1 and fan 2 is less than 24 hours, the power of fan contactor coil will be cut off and the fan power output will be
stopped. After the maintenance personnel resolve the faulty and restart the fan speed controller, the fans re-work.

3.6 Alarm Protection


The fan speed controller can handle the corresponding alarms according to the acquired alarm information. The
detailed alarms include:
1. Phase loss alarm
4. Fan 2 over temperature,
7. SCR temperature sensor failure

2. SCR over temperature


5. Pressure sensor failure
8. Abnormal frequency

See Figure 4-2 for the generating conditions and troubleshooting.

Liebert.PEX Condenser Technical Manual

3. Fan 1 over temperature,


6. EEPROM read fault

Appendix 1

Condenser Matching Table

15

Chapter 4 Maintenance And Troubleshooting


This chapter gives an introduction to the maintenance and troubleshooting of the condenser. You should check the
condenser regularly and solve the problems in time

4.1 Maintenance
Refrigeration system
1. Check that the refrigeration pipes are firmly fixed. The refrigeration pipes shall not shake with the vibration of wall,
earth or equipment frame. Otherwise reinforce the refrigeration pipes with fastening objects.
2. Check that there is no oil on the accessories of all refrigeration pipes, and make sure that the pipes does not leak.
Heat exchanger
1. Clean the fin of heat exchanger regularly.
2. Clean the fin of heat exchanger with compressed air or fin detergent (weakly alkaline) if the condenser airflow is
blocked. The direction of inverse airflow is good when the compressed air is used.
3. Check for damaged fins and maintain them in time.
4. Avoid snow accumulation around the condenser in winter.
Fan
Check that the fan runs normally, check it for problems such as abnormal noise, vibration and bearing failure. If the
fan should be replaced, refer to Table 4-1 for selecting the fan models.
Table 4-1

Model

Fan selected model parameters

Fan model

Fan number

Wiring type of fan

LSF24

FE071-SDK.6F.V7

LSF32*

FE071-SDK.6F.V7

LSF62, LSF70, LDF62, LDF70

FE071-SDK.6F.V7

LSF38, LSF42, LSF52, LDF42, LDF52

FE080-ADK.6N.V7

LSF76, LSF85

FE080-ADK.6N.V7

Note*: when the LSF32 fan should be replaced, you should change the wiring of fan motor from the angle wiring to star wiring
Y

Fan speed controller


Check that the fan speed controller board operates normally. If not, replace it in time. The board is installed inside the
electrical control box. Refer to Figure 4-1 for assembling.
Heat
sink

Bolt 1
Fan speed controller board
Bolt 2

Figure 4-1

Removing the fan speed controller board

Liebert.PEX Condenser Technical Manual

16

Appendix 1 Condenser Matching Table


Note

1. Seven M4 10 bolts are used to fix the fan speed controller board. The bolt 1 and bolt 2 are used to fix the heat sink.
2. Except for the seven bolts in Table 4-1, other bolts are prohibited to be removed.
3. While installing the fan speed controller board, the bolt 1 and bolt 2, used to fix the heat sink, must be fastened firstly. The heat
sink must cling to the floor of the electrical control box. After installing the heat sink, use the other five bolts to fix the fan speed
controller board.
Pressure sensor
If the standard-configurable pressure sensor fails, follow below to select the model and install.
z Selecting the model of pressure sensor
To make sure the precision of the condensing pressure measured value, the pressure sensor should be selected as
follows:
1. The same fan speed controller must select the same type of pressure sensors.
2. The configuration of pressure sensor type (see Figure 3-9) must be the same as the used type.
3. The current type pressure sensor must meet: 4mA ~ 20mA corresponds to 0 ~ 30bar; the voltage type pressure
sensor must meet: 0.5V ~ 4.5V corresponds to 0 ~ 34bar.
4. Except for the type configuration, all parameters of pressure sensor should be amended by factory to use.
z Installing the pressure sensor
The condenser is configured with current type pressure sensor in factory. If the pressure senor should be replaced,
the current type pressure sensor is recommended. If the voltage pressure sensor has to be used because of especial
condition, refer to the following steps:
1. Remove the current type pressure sensors on J14 and J15 terminals and the jumper caps of the current type
pressure sensors on J17 and J18 terminals.
2. Connect the voltage type pressure sensor to J3 and J4 terminals. For the type configuration of pressure sensor,
refer to Configuration data main menu interface in 3.4 Operation Description Of HMI.

4.2 Troubleshooting
The troubleshooting of the condenser is listed in Table 4-2.
For alarms, refer to Current alarm main interface in 3.4 Operation Description Of HMI.
Table 4-2

Alarm
number ID

Alarm name

A00

Phase loss
alarm

A01

SCR
over
temperature

A02A03

Fan 1 over
temperature,
Fan 2 over
temperature

Table of alarm troubleshooting

Cause
1. One phase or two phase of
three-phase voltage is lost
2. The input connection is reversed
3. The fan speed controller board has
hardware fault
1. The fan cannot run normally
2. The fan speed controller board has
hardware fault
1. The fan cannot run normally
2. The AC contactor supplying power
for fan has fault or its wire cuts off
3. Fan speed controller board has
hardware fault (the detecting circuit or
SCR power supplying circuit has fault)

Troubleshooting
1. Measure that the three-phase voltage is correct
2. Check the input order of wire
3. Replace the fan speed controller board and
compare
1. Check that the fan runs normally
2. Replace the fan speed controller board and
compare
1. Check that the fan runs normally
2. Check the wiring of AC contactor; detect the
auxiliary contact state of AC contactor
3. Replace the fan speed controller board and
compare

Liebert.PEX Condenser Technical Manual

Appendix 1
Alarm
number ID

A04

Alarm name

Pressure
sensor
failure

A05

EEPROM
read fault

A06

SCR
temperature
sensor
failure

A07

Abnormal
frequency

Cause
1. The pressure sensor is not installed
or its terminal connection is poor
2. Jumper caps are not used at
shorting terminals J17 and J18 of
current pressure sensor
3. The pressure sensor failed
4. The fan speed controller board has
hardware fault
The fan speed controller board has
hardware fault
1. The SCR temperature sensor is not
installed or its terminal connection is
poor
2. The SCR temperature sensor failed
3. The fan speed controller has
hardware fault
1. The frequency of power supply
voltage is wrong
2. The fan speed controller has
hardware fault

Condenser Matching Table

17

Troubleshooting
1. Check the wiring of pressure sensor
2. Install the jumper cap when the current pressure
sensor is configured
3. Replace the pressure sensor and compare
4. Replace the fan speed controller board and
compare
Replace the fan speed controller board and compare
1. Check the wiring of SCR temperature sensors (J8
SCRTemp, see Figure 3-1 for whose position )
2. Replace the SCR temperature sensor and compare
3. Replace the fan speed controller board and
compare

Replace the fan speed controller board and compare

Liebert.PEX Condenser Technical Manual

18

Appendix 1 Condenser Matching Table

Appendix 1 Condenser Matching Table


1. R22 Matching Table
See Table 1 for single system condenser matching relationships.
Table 1 Matching table of single system condensers

Model of indoor unit

The matched condensers under different temperatures


35C

40C

45C

P1020

LSF24

LSF24

LSF32

P1025

LSF32

LSF32

LSF32

P1030

LSF38

LSF38

LSF42

P1035

LSF42

LSF42

LSF52

P2045

LSF52

LSF52

LSF62

P2055

LSF62

LSF62

LSF62

P2040

LSF24 2

LSF24 2

LSF32 2

P2050

LSF32 2

LSF32 2

LSF32 2

P2060

LSF38 2

LSF38 2

LSF42 2

P2070

LSF42 2

LSF42 2

LSF52 2

P3080

LSF52 2

LSF52 2

LSF52 2

P3090

LSF52 2

LSF52 2

LSF62 2

P3100

LSF62 2

LSF62 2

LSF62 2

See Table 2 for double system condenser matching relationships.


Table 2 Matching table of double system condensers

Model of indoor unit

The matched condensers under different temperatures


35C

40C

45C

P2040

LDF42

LDF52

LDF52

P2050

LDF52

LDF62

LDF62

P2060

LDF62

P2070

P3080

P3090

P3100

Liebert.PEX Condenser Technical Manual

Appendix 1

Condenser Matching Table

2. R407C Matching Table


See Table 3 for single system condenser matching relationships.
Table 3 Matching table of single system condensers

Model of indoor unit

The matched condensers under different temperatures


35C

40C

45C

P1020

LSF32

LSF32

LSF38

P1025

LSF38

LSF38

LSF38

P1030

LSF42

LSF42

LSF52

P1035

LSF52

LSF52

LSF52

P2045

LSF62

LSF62

LSF76

P2055

LSF70

LSF76

LSF85

P2040

LSF32 2

LSF32 2

LSF38 2

P2050

LSF38 2

LSF38 2

LSF38 2

P2060

LSF42 2

LSF42 2

LSF52 2

P2070

LSF52 2

LSF52 2

LSF62 2

P3080

LSF52 2

LSF62 2

LSF62 2

P3090

LSF62 2

LSF62 2

LSF76 2

P3100

LSF70 2

LSF76 2

LSF85 2

See Table 4 for double system condenser matching relationships.


Table 4 Matching table of double system condensers

Model of indoor unit

The matched condensers under different temperatures


35C

40C

45C

P2040

LDF52

LDF52

LDF62

P2050

LDF62

LDF62

LDF70

P2060

P2070

P3080

P3090

P3100

Liebert.PEX Condenser Technical Manual

19

20

Appendix 2 Circuit Diagram

Appendix 2 Circuit Diagram

02

L1
Yellow

04

Pressure sensor 1

Pressure sensor 2

J9 3

04

Whitle

Yellow

J3 HP1

J4 HP2

J14 HP2

Compressor signal

Orange

J15 HP1 J5 OutTemp J11 RS232 J7 Fan1Sta

L3

J10 Fan2Sta J6 CompSta

L2

L1

PE

Shell connecting
to the earth
03

03

Black

Blue

04

L1

03

Brown Yellow

04

White Orange

Blue Olivine

02

Blue

Red

05

02

02

02

Green Yellow Olivine

7
Air circuit
breaker

Wiring terminal block


8

10

Black

Blue

06

06

11

Brown Yellow
06

12

14

13

White Orange White Olivine

07

08

09

01

01
N

1L1

3L2

5L3

A1

4T2

6T3

01

01

01

Black

Blue

Brown

L2

L1

PE

NO

Contacotor 1
2T1

L3

External power
A2

01

NO
09

White Orange

Remark:
1. Connect the pressure sensor 1 only, when PEX condenser is single system.
V1

2. Connect the pressure sensor 1 and 2 with the pipeline of PEX condenser, when PEX condenser is double system.

U1

W1

Fan

TB
TB
PE

3. The system adjacent the bottom connects with the pressure sensor 1 and the system
adjacent the top connects the pressure sensor 2, when PEX condenser is located vertically.
4. Both external power and compressor signal are wired in field.
5. The compressor signal lines should be in parallel and then connected

01

01

Olivine

White

into the electrical controlling board, when the indoor unit is double system.

Figure 1 Circuit diagram of the condenser with single fan

Liebert.PEX Condenser Technical Manual

Appendix 2

J3 HP1

J14 HP2

J15 HP1

J5 OutTemp

J11 RS232

J7 Fan1Sta

04

06

Blue Brown Yellow

White

Compressor signal

11
Orange

J10 Fan2Sta

J6 CompSta

L3

L1

J4 HP2

10
Brown

04

Black

Wiring
terminal
block

04

06
Whitle

Yellow

J9 3

Pressure sensor 1

Pressure sensor 2

03

L1
Yellow

Circuit Diagram

10

11

N
Blue

Brown Orange

05

Shell connecting
to the earth
N

Olivine

Blue

03

L2

03

L1

PE

03

03

Red Green Yellow Olivine

9
Air circuit
breaker

11

10
Black

12

13

Blue Brown Yellow

07

07

07

15

14

White

08

16

Brown Orange
09

09

09

17

18

White

White

02

01

Olivine Olivine
02

01
N

1L1

3L2

5L3

A1

NO

1L1

3L2

Contacotor 1
2T1
Black
01

4T2

6T3

A2

W1

01

V1

01

NO

2T1 4T2
Black
02

09

U1

6T3 A2

01
Olivine

01
White

L1

PE

NO

NO

Blue Brown White Orange


02

W1

02

V1

TB
PE TB

A1

L2

Contacotor 2

Blue Brown White Orange


01

5L3

L3

02

09

U1
TB

Fan 1 (remote )
PE
01
Olivine

TB

Fan 1 (proximal)

01
White

Remark:
1. Connect the pressure sensor 1 only, when PEX condenser is single system.
2. Connect the pressure sensor 1 and 2 with the pipeline of PEX condenser, when PEX condenser is double system.
3. The system adjacent the bottom connects with the pressure sensor 1 and the system
adjacent the top connects the pressure sensor 2, when PEX condenser is located vertically.
4. Both external power and compressor signal are wired in field.
5. The compressor signal lines should be in parallel and then connected
into the electrical controlling board, when the indoor unit is double system.

Figure 2 Circuit diagram of the condenser with double fan

Liebert.PEX Condenser Technical Manual

External power

21

22

Appendix 3

Lifting Figure

Appendix 3 Lifting Figure


See Figure 3 for lifting the condenser package (taking double fan for example).

Note

When lifting the package, fix the cable by leading it through the slot at the bottom of the pallet. Otherwise, the cable may slide
during the lifting process, and the package may fall to the ground, damaging the pipes within and resulting in system leakage.

Figure 3

lifting figure

Liebert.PEX Condenser Technical Manual