Вы находитесь на странице: 1из 2

MOUNTING HARDWARE

WHERE FREQUENT WASH DOWNS


OCCUR SUPPLIED WITH SUB-122
ENVIRO KIT
06297T EXTERNAL
MOUNTING TABS
INSERT TABS INTO FRAME
SLOTS AS SHOWN

Safety Technology International, Inc.


2306 Airport Road Waterford, Michigan 48327-1209
Phone: 248-673-9898 Fax: 248-673-1246
Toll Free: 800-888-4784 E-mail: info@sti-usa.com
Web: www.sti-usa.com
OPTIONAL CONDUIT HUB
SUB-6297B20
(ACCEPTS 3/4 in. RIGID
CONDUIT FITTINGS)
19033
ANCHOR
INCLUDES
GASKET AND
(4) PROVIDED
MOUNTING
HARDWARE

Safety Technology International (Europe) Ltd.

Unit 49G Pipers Road Park Farm Industrial Estate Redditch


Worcestershire B98 0HU England Tel: 44 (0) 1527 520 999
19013 SCREW #10 x 1 1/2 in. Fax: 44 (0) 1527 501 999 Freephone: 0800 085 1678 (UK only)
(4) PROVIDED
E-mail: info@sti-europe.com Web: www.sti-europe.com

BACK OF FRAME ASSY.


MAY BE DRILLED TO
ALLOW WIRE ACCESS
AS SHOWN

IF ADDED PROTECTION IS
NEEDED DUE TO ENVIROMENTAL
CONDITIONS ORDER SUB-122
ENVIRO KIT

TYPICAL NOTIFICATION
APPLIANCE
629763 STANDOFF BLOCKS
(4) MUST BE USED IN AREAS
WHERE FREQUENT WASH DOWNS
OCCUR SUPPLIED WITH SUB-122
ENVIRO KIT

19013 SCREW #10 x 1 1/2 in.


(4) PROVIDED
01210 COVER ONLY
BACK OF FRAME ASSY.
MAY BE DRILLED TO
ALLOW WIRE ACCESS
AS SHOWN

LOCATED IN THIS AREA


DRILL A 1/4 in.(6.3mm) DIA. HOLE

1. To minimize strobe light loss, regardless of the type of horn/strobe appliance used, the
clear section (NOT the section containing the cutout slots), must be centered over the
strobe light lens. Failure to follow these instructions may lead to light loss transmission.
2. Damage Stopper must be installed to comply with applicable NEC, NFPA and local codes.
1 in.(25mm)
3. In areas where frequent
wash downs occur, standoff blocks must be used.
4. In applications where wash downs, rainfall or condensation occur, it is recommended
APPROX
that a drain or weep hole be provided. Refer to weep hole installation diagram.
CENTER LINE
5. OF
Damage
Stopper
may be installed outdoors when appliance carries an outdoor rating.
UNDERSIDE
OF
LOCATED IN THIS AREA

INSTALL CLAMP IN NOTCH 2 AS SHOWN

IF ADDED PROTECTION IS
01210 COUVERCLE SEULEMENT
NEEDED DUE TO ENVIROMENTAL
CONDITIONS ORDER SUB-122
ENVIRO KIT

TYPICAL NOTIFICATION
APPLIANCE

HEIGHT
8.5 in.(216mm)

19047 #8-32 x 3/8 in. SOCKET


HEAD CAP SCREW (4) PROVIDED

19033 AN
(4) PRO
DEPTH
3.5 in.(89mm)

CLEAR
SECTION

06297B FRAME ASSY.

INSTALLATION NOTES

COVER

629764 CLAMP
(4) PROVIDED

OPTIONAL COND
SUB(ACCEPTS 3/4
CONDUIT F
INCLUDES GAS
MOUNTING HA

06297T EXTERNAL
MOUNTING TABS
CLEAR
INSERT TABS INTO FRAME
SECTION
SLOTS AS SHOWN

06297B FRAME ASSY.

19033 ANCHOR
(4) PROVIDED

01210 COVER ONLY

WIDTH
6.5 in.(165mm)

01210 COUVERCLE SEULEMENT


06297A BACKBOX
06297T MOUNTING
TABS (4) PROVIDED

629764 CLAMP
(4) PROVIDED

DRILL FOR CONDUIT ENTRY


3 3/8 in.
(86mm)

19047 #8-32 x 3/8 in. SOCKET


HEAD CAP SCREW (4) PROVIDED

3/4 in.(44mm)
HEIGHT
8.5 in.(216mm)
PRODUCT DIMENSIONS
INTERNAL
DIMENSIONS

REMARQUES SUR
DRILLLINSTALLATION
A 1/4 in.(6.3mm) DIA. HOLE

1. Afin de minimiser la perte de lumire stroboscopique, quel que soit le type dalarme sonore/de stroboscope utilis, la section
dgage (et NON la section contenant les fentes de dcoupe), doit tre centre sur lobjectif stroboscopique. Le fait domettre
ces instructions risque dentraner la perte de diffusion de la lumire.
2. Le Stopper de dgts doit tre install de sorte tre conforme avec les normes NEC, NFPA applicables et les codes locaux.
3. Dans les zones o des jets deau frquents surviennent, des blocs de dtection distance doivent tre utiliss.
4. Dans les applications o des jets deau, des prcipitations ou de la condensation se produisent, il est recommand de prvoir
un trou de vidange ou une barbacane. Reportez-vous schma dinstallation dune barbacane.
5. Il est possible dinstaller un Stopper de dgts lextrieur lorsque lappareil est homologu pour utilisation lextrieur.
1 in.(25mm)

INSTALLATION INSTRUCTIONS - REFER TO EXPLODED VIEW


1.
2.
3.
4.
5.
6.
7.
8.
9.

Insert
the (4) 06297T external mounting tabs into the frame assembly slots.
APPROX
Using
backLINE
box assembly as a template, place against mounting surface at proper location according to NFPA 72.
CENTER
Mark
drill (4)
OF and
UNDERSIDE
OFholes 1/4 in. (6.3mm) diameter, 1 1/4 in. (32mm) deep.
COVER
Insert
the (4) anchors into the wall.
Mount back box to wall with screws.
Install electrical fittings as needed.
Install horn/strobe appliance.
Install cover with clips and screws.
Test appliance according to appliance manufacturers instructions.

LOCATED IN THIS AREA


DEPTH
DRILL A 1/4 in.(6.3mm) DIA. HOLE
3.5 in.(89mm)

629763 STANDOFF BLOCKS


(4) PROVIDED

19033 ANCHOR
(4) PROVIDED

CLEANING INSTRUCTIONS

WIDTH
6.5 in.(165mm)

19013 SCREW
#10 x 1 1/2 in.
(4) PROVIDED

Rinse with water to remove abrasive dust and


dirt. Wash with
629764 RETAINING CLIPS
soap or mild detergent, using a soft cloth (do not scrub).
Rinse
(4) PROVIDED
once more then dry with a soft cloth or chamois. To remove
19047with
#8-32 x 3/8 in. SOCKET
grease or wet paint, rub gently with a cloth wetted
naphtha. Then wash and rinse. DO NOT USE RAZOR BLADES.HEAD
(DOCAP SCREWS
(4) PROVIDED
NOT USE RAZOR BLADES.)

629762
DRAIN
SCREEN

WEEP HOLE INSTALLATION

Electronic warranty form at www.sti-usa.com/wc14

INSTALLATION OF STI-1210B SPEAKER HORN/STROBE


DAMAGE STOPPER
A 1-1/16 in. DIAMETER CONDUIT

1-3/4

1 in.(25mm)

APPROX PRODUCT DIMENSIONS


CENTER LINE
OF UNDERSIDE OF
COVER

629761 NEOPRENE GASKET

All specifications and information shown were current as of publication and are
subject
without notice.
ENTRY
HOLE MUSTto
BE change
FIELD INSTALLED

CLEAR
SECTION

A 1-1/16 in.
1210BIS APRIL2006
DIAMETER CONDUIT
ENTRY HOLE MUST
BE FIELD INSTALLED

0121

0121

UL INSTALLATION REQUIREMENTS
STI-1210 / STI-1221 SERIES
CAUTION

Attention

This enclosure is rated to protect signaling appliances indoors and in areas of indirect weather exposure.
The cover may be used outdoors only with devices also suitable for outdoor use.
When covering fire-signaling appliances with this enclosure, some light and sound loss occurs. Please
follow these guidelines listed during installation.
Voice speaker appliance: No spacing adjustment is required for 0.5W, 1.0W and 2.0W appliances.
Refer to the appliance manufacturer's candela rating. Multiply this number by the light loss value from the
chart below to determine the new candela rating. Use this number and refer to the notification layout
table of NFPA 72 for proper device locations.
The use of this cover on audible devices decreases the sound output by 6dB(A). Actual sound level output
should be checked after installation to determine if adequate sound levels exist. Refer to the notification
layout table of NFPA 72 for proper device locations.

Ce botier est homologu pour protger les appareils de signalisation dincendie lintrieur et dans les zones
dexposition indirecte aux intempries. Le couvercle ne peut tre utilis lextrieur quavec les appareils
appropris pour une utilisation lextrieur aussi.
Le fait de couvrir les appareils de signalisation dincendie au moyen de ce botier risque dentraner une certaine
perte lumineuse et sonore. Veuillez vous conformer ces directives lors de linstallation.
Haut-parleur: Aucun ajustement de distance nest ncessaire pour les appareils tension de 0,5 W, 1,0 W et 2,0 W.
Reportez-vous la cote candla du fabricant de lappareil. Multipliez cette valeur par la valeur de la perte de
lumire du tableau ci-dessous pour dterminer la nouvelle cote candla. Utilisez cette nouvelle valeur et
reportez-vous au tableau de disposition des alertes de la norme NFPA 72 pour les emplacements appropris de
lappareil.
Lutilisation de ce couvercle sur les dispositifs sonores diminue la puissance sonore de 6 dB(A). Le niveau rel de
la sortie sonore doit tre vrifi aprs linstallation pour dterminer le maintien de niveaux sonores adquats.
Reportez-vous au tableau de disposition des alertes de la norme NFPA 72 pour les emplacements appropris de
lappareil.

Performance Review - LIGHT DERATING FACTOR


MANUFACTURER
ADT SECURITY
AMSECO

SERIES

STI-1210

STI-1221/1221A4X

MANUFACTURER

ADTG1-V SERIES

40%

34%

HONEYWELL

SERIES

STI-1210

STI-1221/1221A4X

XLS202 SERIES

40%

34%

SL24W-153075

22%

37%

HONEYWELL

XLSG1-HV SERIES

40%

34%

AMSECO COLORED LENSES

SL24W-153075 A, B, G, OR R

47%

26%

HONEYWELL

XLSG1-HOV SERIES

40%

34%

AMSECO COLORED LENSES

SL24C-3075110 A, B, G, OR R

47%

26%

MIRCOM

FS-240

47%

26%

AMSECO COLORED LENSES

CSL24W-A, B, G, OR R

47%

26%

MIRCOM

MS SERIES

43%

45%

AMSECO COLORED LENSES

CSL24C-A, B, G, OR R

47%

26%

MIRCOM

MG1-V SERIES

40%

34%

GES24 SERIES

31%

MIRCOM

MG1-HV SERIES

40%

34%

DETECTION SYSTEMS
DETECTION SYSTEMS

GES24-15/75

MIRCOM

MG1-HOV SERIES

40%

34%

EST / EDWARDS

2440S SERIES

43%

45%

MIRTONE

MG1-V SERIES

43%

45%
31%

EST / EDWARDS

202 SERIES

43%

45%

NATIONAL TIME & SIGNAL

GES24 SERIES

EST / EDWARDS

G1-V SERIES

40%

34%

NATIONAL TIME & SIGNAL

GES24-15/75

EST / EDWARDS

G1-HV SERIES

40%

34%

POTTER ELECTRIC

AS-24-153075R

47%

26%

EST / EDWARDS

G1-HOV SERIES

40%

34%

POTTER ELECTRIC

AS-24-153075W

47%

26%

EST / EDWARDS

EG1-V SERIES

40%

34%

SECUTRON

GES24 SERIES

31%

EST / EDWARDS

EG1-HV SERIES

40%

34%

SECUTRON

GES24-15/75

EST / EDWARDS

EG1-HOV SERIES

40%

34%

SIEMENS

202- SERIES

43%

45%
34%

FARADAY LLC

2700

57%

SIEMENS

G1-V SERIES

40%

GENTEX

GES24 SERIES

31%

SIEMENS

U-MCS SERIES

GENTEX

GES24-15/75

SYSTEM SENSOR

SS24110ADA

46%

37%

SYSTEM SENSOR

61%

HARRINGTON SIGNAL

GES24 SERIES

31%

HARRINGTON SIGNAL

GES24-15/75

XLSG1-V SERIES

43%

45%

HONEYWELL

P2, PC2, P4, PC4, SX, SC

53%

WHEELOCK

RSS-24MCW

ZITON PTY LTD

ZG1-V SERIES

40%

34%

STI-1210 Series Sound Derating Factor: System Sensor P2, PC2, P4, PC4, SX, SC series models: 6.7 dBA, General: 6 dBA
STI Generic Light Loss Value: STI-1210 Series: 53%; STI-1221 Series: 61%
SAFETY TECHNOLOGY INTERNATIONAL, INC. 2306 AIRPORT ROAD WATERFORD MICHIGAN 48327-1209 PHONE: 248-673-9898 FAX: 248-673-1246 www.sti-usa.com