Академический Документы
Профессиональный Документы
Культура Документы
PERFORMED AT
BUILDING 46,
ROOF ASSEMBLY AND LIGHTNING PROTECTION
BAY PINES REGIONAL VA
9500 BAY PINES BLVD.
ST. PETERSBURG, FL
PREPARED FOR
ESASOUTH,INC.
2727BNW43RDST.SUITE7C
GAINESVILLE, FL 32606
PREPARED BY
May 7, 2015
May 7, 2015
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
TABLE OF CONTENTS
1.0
INTRODUCTION..............................................................................................................2
1.1
2.0
2.2
2.3
3.0
RECOMMENDATIONS ...................................................................................................7
4.0
METHODS .......................................................................................................................10
4.1
4.2
4.4
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
1.0 INTRODUCTION
OHC Environmental Engineering, Inc., (OHC), was contracted by Mr. Phillip Burke
with ESA South, Inc., to perform an indoor air quality assessment at the Bay Pines VA
Medical Center, Building 46, located at 9500 Bay Pines Blvd. in St. Petersburg, Florida.
The purpose of this assessment was limited in scope to indoor air quality concerns
regarding the Roof Assembly and Lighting Protection project, partial third floor only.
Representatives from OHC Environmental Engineering Inc., Mr. James F. Rizk, CIH,
Florida Licensed Mold Assessor and Mr. Eric S. Mauritz, CIE, Florida Licensed Mold
Assessor, visited the area of Building 46 on April 28 and 29, 2015 to evaluate the area
environment for sources of indoor air quality contamination.
1.1
Executive Summary
Mr. Rizk and Mr. Mauritz performed a visual assessment within the area of
concern within building 46 in order to determine sources of potential indoor air
quality contamination. They also collected surface samples for biological agents
and collected comfort parameter testing which included: temperature, relative
humidity, Carbon Dioxide and Carbon Monoxide.
Based on the assessment water is believed to be infiltrating the area via the sky
light affecting all walls along the sky light. There is also evidence of water
infiltrating from along the exterior walls most likely from the roof or parapet wall.
Due to the extent of water damage and Visible Presumptive Fungal Growth
(VPFG) remediation is highly recommended. (Please refer to section 2.0
observations and assessments and section 3.0 recommendations).
Comfort parameter samples collected for temperature, relative humidity and
carbon monoxide were all within ASHERA recommended levels. These samples
were collected with minimum occupancy in the area so conditions may change
significantly once the area is fully occupied.
An Asbestos survey is required prior to any remediation or disturbance of any
building material. It is my understanding that the VA hospital has an Asbestos
survey of this facility.
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
Visual Observations
A visual inspection was completed on the on April 28 and 29, 2015. The findings of the
visual inspection indicated the following findings:
North Skylight Wall:
Along North Wall (skylight wall):
Water damage and deterioration located on drywall ceiling which
encompasses structural beam
Heavy rust and wet fire proofing associated with column *fire proofing =
100% moisture content
Bottom inch of drywall is wet around columns *drywall lower one inch =
100% moisture content
In the section that is covered with wallpaper; there is heavy Visible
Presumptive Fungal Growth (VPFG) on the drywall behind the wallpaper
Northeast Corner:
Water damage and deterioration located on drywall ceiling which
encompasses structural beam
Light Visible Presumptive Fungal Growth (VPFG) located behind vinyl
base molding below corner of the windows
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
Biological Samples
Surface Samples:
A total of three (3) biological surface samples were collected from the following
areas: Sample number one (1) was collected from within the North room, on the
backside of the water damaged drywall, which encompasses the structural ceiling
beam. Sample number two (2) was collected from the North wall, behind the
vinyl wall paper. Sample number three (3) was collected from the North wall in
the Northeast corner, behind the base molding, below the corner window. Sample
number one (1) yielded a Medium concentration of Aspergillus/Penicillium
species, Cladosporium Species, a high concentration of Stachybotrys and
Memnoniella and a Low concentration of Curvularia. Sample number two (2)
yielded a high concentrations of Aspergillus/Penicillium and a high count of
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
Cladosporium is a genus of fungi including some of the most common indoor and
outdoor molds. The many species of Cladosporium are commonly found on living
and dead plant material. Some species are plant pathogens, others parasitize other
fungi. Cladosporium spores are wind-dispersed and they are often extremely
abundant in outdoor air. Indoors Cladosporium species may grow on surfaces
when moisture is present. Cladosporium species are rarely pathogenic to humans,
but have been reported to cause infections of the skin and toenails, as well as
sinusitis and pulmonary infections. If left untreated, these infections could turn
into respiratory infections like pneumonia. The airborne spores of Cladosporium
species are significant allergens, and in large amounts they can severely affect
asthmatics and people with respiratory diseases. Cladosporium species produce
no major mycotoxins of concern, but do produce volatile organic compounds
(VOCs) associated with odors.
Aspergillus - This genus of fungi includes over 185 species. Members of this
genus are known as organisms that cause deterioration of materials. Among all
filamentous fungi, Aspergillus is the most commonly isolated in invasive and
opportunistic infections. Aspergillosis is the group of diseases caused by
Aspergillus. The most common subtype among paranasal sinus infections
associated with aspergillosis is A. fumigatus. The symptoms include fever,
cough, chest pain, or breathlessness, which also occur in many other illnesses, so
diagnosis can be difficult. Usually, only patients with already weakened immune
systems or who suffer other lung conditions are susceptible.
Penicillium is a very large group of fungi. They are commonly found in the soil, air
and on living vegetation. Some species are able to produce mycotoxins(1).
Curvularia sp. most species are pathogens of soil, plants, and cereal plants and is
found mostly in tropical or subtropical regions. It is commonly found on paper and
wood products. As well as being a contaminant, Curvularia may cause infections in
both humans and animals. It is reported to be an allergen causing Type I allergies
(i.e. asthma, hay fever) and is a relatively common cause of allergic fungal sinusitis.
Boss,MarthaJ.andDay,DennisW.2003,BiologicalRiskEngineeringHandbook.LewisPublishersWashington,
D.C.
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
Environmental Conditions
Dry bulb temperature (Tdb) and relative humidity (RH) measurements were
collected on April 29, 2015. Interior average temperature averaged 70.6F and
average Interior RH was 53.2%. American Society of Heating, Refrigerating, and
Air-conditioning Engineers, Inc. (ASHRAE) 55 criteria for thermal comfort were
met based for temperature and relative humidity on the day of the survey.
Observed environmental conditions are summarized in Table 1 below.
TABLE 1: ENVIRONMENTAL CONDITIONS
BUIILDING 46
APRIL 29, 2015
ENVIRONMENTAL TEST RESULTS
LOCATION NAME
Room 108
CARBON DIOXIDE
CO2
(ppm)
DRY BULB
TEMPERATURE
(F)
RELATIVE
HUMIDITY
(%)
807
70.6
53.2
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
3.0 RECOMMENDATIONS
Based on the findings of the air quality assessment remediation is highly recommended.
OHC recommends the following to be performed within containment, under negative air
pressure, with critical barriers sealed, utilizing HEPA vacuums, wet wipe or other
approved methods for cleaning, followed by dehumidification and/or drying.
Prior to build back the remediated areas should be inspected by a Florida Licensed
Mold Assessor. Any leaks associated with the roof or skylight should be identified and
repaired prior to build back or it is likely that any issues will be re-occurring. If
deemed more cost effective full sheets of drywall may be removed instead of localized
removal.
North Wall:
Due to the extent of water damage and Visible Presumptive Fungal Growth (VPFG)
found; all dry wall along the north wall (skylight wall) should be removed floor to
ceiling spanning the length of the wall. This includes any associated spray-on fire
proofing as well as any other type of insulation. The drywall ceiling should also be
removed starting at the north wall extending toward the south wall three (3) feet along
the north wall (skylight wall) spanning the length of the wall. Should any additional
water damage or VPFG be found then continue removal two (2) feet from the edge of
water damage or VPFG contaminated area. The wall and ceiling cavities should be
thoroughly cleaned and dried following current industry standards.
Due to the extent of water damage and Visible Presumptive Fungal Growth (VPFG)
detected; all dry wall along the north wall (skylight wall) should be removed floor to
ceiling spanning the length of the wall. This includes any associated spray-on fire
proofing as well as any other type of insulation. The drywall ceiling should also be
removed starting at the north wall extending toward the south wall three (3) feet along
the north wall (skylight wall) spanning the length of the wall. Any water damaged
ceiling tiles should be removed and disposed of. Should additional water damage or
VPFG be found then continue removal two (2) feet from the edge of water damage or
VPFG contaminated area. The wall and ceiling cavities should be thoroughly cleaned
and dried following current industry standards.
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
Columns: All vinyl wall coverings and drywall should be removed from all existing
columns floor to ceiling. This includes any associated spray-on fire proofing as well
as any other type of insulation. The drywall ceiling should be removed two (2) feet
from the edge of all columns radiating out in all directions. The wall and ceiling
cavities should be thoroughly cleaned and dried following current industry standards.
Should additional water damage or VPFG be found then continue removal two (2)
feet from the edge of water damage or VPFG contaminated area.
Windows: Drywall and any associated insulation should be removed two (2) feet
around all windows. Wall cavities should be thoroughly cleaned and dried following
current industry standards. Should additional water damage or VPFG be found then
continue removal two (2) feet from the edge of water damage or VPFG contaminated
area.
Along west wall: All remaining vinyl base molding should be removed spanning the
length of the wall. Should additional water damage or VPFG be found then continue
removal two (2) feet from the edge of water damage or VPFG contaminated area.
Near Southwest Column: Between the windows located below the water damaged
ceiling, drywall and any associated insulation should be removed from floor to
ceiling. The drywall ceiling should be removed two (2) feet starting at the edge of
water damage extending out in all directions. The wall and ceiling cavities should be
thoroughly cleaned and dried following current industry standards. Should additional
water damage or VPFG be found then continue removal two (2) feet from the edge of
water damage or VPFG contaminated area.
Southwest column: The vinyl wall covering and drywall should be removed from the
column floor to ceiling. This includes any associated spray-on fire proofing as well as
any other type of insulation. The drywall ceiling should be removed two (2) feet
from the edge of all columns radiating out in all directions. Wall and ceiling cavities
should be thoroughly cleaned and dried following current industry standards. Should
additional water damage or VPFG be found then continue removal two (2) feet from
the edge of water damage or VPFG contaminated area.
*Signs of animal activity were noted and precautions should be utilized upon removal
of drywall.
Southeast corner: drywall should be removed from floor to ceiling starting at the
Southeast corner spanning four (4) feet to the east and west. This includes any
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
associated spray-on fire proofing as well as any other type of insulation. The drywall
ceiling should be removed two (2) feet from the edge of all columns radiating out in
all directions. The wall and ceiling cavities should be thoroughly cleaned and dried
following current industry standards. Should additional water damage or VPFG be
found then continue removal two (2) feet from the edge of water damage or VPFG
contaminated area.
Windows: Drywall and any associated insulation should be removed two (2) feet
around all windows. The wall cavities should be thoroughly cleaned and dried
following current industry standards. Should additional water damage or VPFG be
found then continue removal two (2) feet from the edge of water damage or VPFG
contaminated area.
In the area where light water damage was noted on the ceiling; the drywall ceiling
should be removed two (2) feet from the edge of water damage radiating out in all
directions. The wall and ceiling cavities should be thoroughly cleaned and dried
following current industry standards. Should additional water damage or VPFG be
found then continue removal two (2) feet from the edge of water damage or VPFG
contaminated area.
Central Chase:
All vinyl wall coverings and drywall should be removed from floor to ceiling. This
includes any associated spray-on fire proofing as well as any other type of insulation.
The drywall ceiling should be removed two (2) feet from the edge of chase radiating
out in all directions. The wall and ceiling cavities should be thoroughly cleaned and
dried following current industry standards. Should additional water damage or VPFG
be found then continue removal two (2) feet from the edge of water damage or VPFG
contaminated area.
BAYPINESREGIONALVA
BUILDING46
ROOFASEMBLYANDLIGHTINGPROJECT
INDOORAIRQUALITYASSESSMENT
OHCPROJECTNO.:150074IA
Thermal Comfort
Temperature and relative humidity measurements are often collected as part of an IAQ
investigation because they affect the perception of comfort in an indoor environment.
The American Society of Heating and Refrigerating and Air-Conditioning Engineers, Inc.
(ASHRAE) guidance standard 55-2004 Thermal Environmental Conditions for Human
Occupancy (ASHRAE 55) specifies conditions or a comfort zone in which 80% of
occupants would be expected to find the environment thermally acceptable the comfort
zone is determined by temperature and humidity, and assumes clothing worn by and
activity levels of occupants to be typical of those in office spaces. For the purposes of
this investigation, dry bulb temperature is assumed to be the same as operative
temperature described in ASHRAE 55. In addition, ASHRAE recommends that relative
humidity be maintained below 65% to inhibit fungal growth on building surfaces.
Thermal comfort conditions for temperature and relative humidity was taken from a
central area within the affected area using a TSI Q-Trak Model 7565x during the
assessment.
10
APPENDIX I
LABORATORY ANALYTICAL RESULTS
APPENDIX II
SITE PHOTOGRAPHS
Photo #11: North room skylight wall VPFG and rust located
on drywall tape that fell from the area in picture 10.
10
11
Photo #15: west wall VPFG located on the drywall behind the
vinyl base cove
12
13
14
15
APPENDIX III
IR SITE PHOTOGRAPHS
16
17
18
19
20
21
APPENDIX IV
MOISTURE LOCATION MAP
22
23
APPENDIX V
CONSULTANT CREDENTIALS
24
25
26
27