Академический Документы
Профессиональный Документы
Культура Документы
d
Tank, P1
S2
S1
Pu
mp
c
Fig 1: Pumping System Schematic
Head,
m
C
B
D
A
System static head, Fixed head
losses = (S2-S1) + (H2-H1) see fig
1.
Qc
Qb
Q, m3/s
AB represents the system friction losses. The solid curves represent the head loss under
the condition of fully open valve. The valve can be controlled to apply head losses to
reach duty point C. Therefore the system maximum and minimum flow must lie within
the flow range.
Problem services
Only flow rate defers, temperature and composition remains the same
Flow is turbulent throughout
Friction factor remains constant over the range of flow rate.
Frictional drop in equipment treated the same manner as in piping.
Darcy Equation delP2=delP1*(V2/V1) ^2
A piping section from which piping branches off is referred to as a common.
Calculation Procedure:
For each operating case, determine the flow rates in each branch, the commons, and at the
pump to correct the frictional delP.
Rate Flow Rate, Qr = Qn*(Qb*sp.gv)
Calculate the rated-case pump suction pressure, using the LLL level as the suction static
height.
Calculate the NPSH
Calculate the discharge. The designer must allow a minimal control-valve differential for
each branch. Typically, this differential is based on a percentage of the frictional pressure
drop (ie, 10-20%) or an absolute minimum (5-10psi).
Pump discharge piping is generally one size larger than the pump discharge nozzle size.
When pumping saturated liquid, if vaporization occurs after equipment, the friction
resistance in the pipe would increase and this potion of pipe should be calculated as twophase flow. If two-phase flow is expected between two equipments, they should be
placed side by side to keep the piping short.
Flow sensing controls provide the most stable control. Pressure control can have very
large swing when operating in flat area of the pump curve. Both temperature and level
sensing control can lead to pump running at end-of-curve condition during failure modes.
Selection of mechanical seals
Selection of an unbalanced or balanced seal is determined by pressure in seal chamber. If
b (the ratio of hydraulic closing area to seal face area) is > 100%, it is unbalanced.
Selection of rotating or stationary seal is determined by speed of pump shaft. If shaft
speed is >25.4 m/s, use stationary seal. Higher speed applications require a rotating
mating ring. Stationary seal should be considered for all split case pumps.
Selection of single or multiple spring seal head construction is determined by the space
limits and the liquid sealed. Single spring seals are often used with bellow seals to load
the seal faces. Multiple spring seals require a shorter axial space. Most multiple spring
designs are used with O-rings or hedges as secondary seals.
Pusher-type seals apply to seals that use an O-ring, wedge, or V-ring. Nonpusher applies
to seals that use half-, full-, and multiple-convolution bellows as a secondary seal.
Compressor
Compressor can be designed quite accurately. It is one the most expensive equipment in
the plant and has long delivery time. The flows shown on the compressor schedule are
normal flows. The compressor shall be rated for 105% of these normal flows. The
maximum efficiency should be at normal flow.
Safety Valve
In a process component with liquid & gas section, PSV or vent should be installed to
relieve pressure from the gas section.
Critical line:
for process, normally those PSV, BDV inlet outlet line are critical (depend)
for piping... normally line size >6" they consider critical.(depend)
high pressure, toxic,where any process upset can trip the whole process or plant.
Valve Selection
Ball Valve Suitable for most manual on-off hydrocarbon or utilities service when
operating temperatures are between -20F and 180F.
Gate valves Suitable for most on-off, non-vibrating hydrocarbon or utilities service
for all temperature range. Gate vales have better torque characteristics than ball or
plug valves but do not have the easy operability of quarter turn action. Reverse
acting slab gate valves are suitable for automatic shutdown service.
Plug valves Similar to ball valves. It is based on lubricated or non-lubricated
designs.
Butterfly valves Suitable for coarse throttling and other applications where a tight
shutoff is not required. They are not suitable for primary block valve for vessels.
Globe valves Suitable when good throttling control is required (e.g. in bypass
service around control valves)
Diaphragm (Bladder) Valves Primarily used for low pressure water (200psig or less)
service. They are suitable for systems containing appreciable sand or other solids
Needle Valves Miniature globe valves. Used for instrument lines. The small
passageways through needle valves are easily plugged, and this should be
considered in their use.
Check Valves A full opening swing check is suitable for most non-pulsating
applications and it can be used for vertical run pipe (upward & not downward)