Вы находитесь на странице: 1из 21

It seems that fuel oil does not have the same meaning in Europe and USA.

In USA fuel oil can mean any fuel from diesel (No 1) to heavy residues. In
Greece and Europe fuel oil (mazout) means No 5 or 6 per ASTM D-396,
called heavy fuel oils in USA. For instance, diesel oil in Europe is not
.included in fuel oils
:Please could someone explain the difference between the following
Internal reflux .1
Circulating reflux .2
Pumparound .3
Answers
Ralph Ragsdale, Ragsdale Refining Courses,
ralph.ragsdale@att.net

A:

Internal reflux is the flow rate inside the column of the liquid from one tray
to the tray below. The other two terms are interchangeable and represent
the flow rate in the external piping of the liquid drawn the column, through
heat exchangers, and back into the column either above or below the
.draw-off location/elevation
During Crude distillation unit start up activities, water travels from crude
storage tank to crude tower when furnace outlet temperature was 172C. It
caused crude tower trays to dislodge. What if level of crude tower remains
high then flash zone, does level of crude tower have significant effect on
.tray dislodge? Our system is furnace operated crude tower

The sudden large water vaporization increase the vapor


flowrate thru column internals creating an uplift force that dislodge the
trays above the flash zone. Trays above flash zone are specified to hold 1
psi of uplift (some designers may prefer 2 psi, or 1/2 psi), this apply only
.to 3-5 trays located above the flash zone
If bottom crude level is high (above the flash zone), and water gets into
the column, then large water bubbles rising thru the liquid will dislodge
the trays

What quantity of steam is required in distillation column and side strippers


.per barrel of crude/products

:Very sorry. I should have stated


Column bottoms 0.2 lbs/gal bottoms
side strippers 0.1 lbs/gal stripper bottoms, not per barrel
.Stripping steam have an important influence over the yields
A general rule of thumb is around 10 -15 lb/barrel of product, but that
ratio, which could be lower or higher than the previous range, should be
optimized at the field and will depend of product nature. During field
tuning, it should be considered the condenser capacity and hydraulic
.capacity of main tower or sidestripper
Related to atmospheric residue stripping , the main objective is to recover
light fractions as diesel or AGO. The bad performance or poor design of
atmospheric residue stripping section could be a problem for downstream
vacuum tower. There are many cases where atmospheric residue stripping
section has poor design, then poor performance at any steam/residue
.ratio
For the case of side products the objectives could be as flash point control
.and to recover light material
If you are executing a new design, 10 lb/barrel could be used and then
optimized based on products spec, condenser duty and percent of stripped
.product
Also it is very important to consider that stripping steam rate will impact
.the sourwater production
Column bottoms 0.2 lbs/bbl bottoms
side strippers 0.1 lbs/bbl stripper bottoms
If there is a good reason to sharpen the cut between Atm Gas Oil and Atm.
Bottoms, the bottoms stripping steam rate can be a part of the
optimization calculations. But the reason must be valid considering the
overall refinery marg
When water travels with crude, through furnaces into the crude tower,
?what process indications reflects on process parameters/tower profile
Furnace feed control valves will get open for lots of water with crude and
.in extreme case the furnace will trip for low flow
If you know you have water passing through with your crude in addition to
the answers already provided you would need to make sure your tower top
temperature is kept higher otherwise you will experience sever corrosion
in you top trays and overhead system. Calcium Chloride common in most
crude combines with heat and water to form chloride salts and hydrolyze
.to form HCl (dew point ~220F)

In addition to what Sam indicated you would also see an increase in the
valve opening on the overhead water from the accumulator. With a lot of
water carryover to the crude column you might also see an increase in
delta P across the trays due to the increased volume of vapor flow that
occurs when all the water flashes. The amount of firing in the furnace to
maintain outlet temperature would also increase with a lot of water carry
over due to the high latent heat of the water and the increased
vaporization that would occur when the steam formed reduces
.hydrocarbon partial pressure
f it is only a little bit of water you may see addition water going overhead
of the crude tower or preflash tower,if it is a lot of water the preheat circuit
could exhibit high pressures reducing flow rates, or the crude tower ovhd
will over pressure , potentially lifting its safeties, or dislodging the trays
The presence of water vapor reduces the temperature at which a
hydrocarbon vaporizes. Therefore, if the water in the crude is removed,
and if the furnace outlet and column draw temperatures are maintained,
directionally the overhead and side product End Points will decrease. The
quantity of vacuum column feed will increase. To offset those changes
.when the water is kept out of the crude, increase the temperatures
Can you please advise some literature sources or design guidelines for
.Naphtha Stabiliser design
The purpose of the column is to reduce the vapor pressure such that the
naphtha can be stored in an API tank in lieu of a bullet or sphere. Using the
target maximum vapor pressure allowed in the region, specify the quantity
of butane and lighter to remain in the product. Allowing some pentanes
and heavier to go to the gas plant is O.K. as they will be recovered there.
That means that it is difficult to justify an intense fractionation in this
column. Thus, the reflux ratio in the column need not be high. With that
.goal, use the simulation to produce the heat and material balance data
Some refineries do not have this column. The unstabilized naphtha is
routed directly to the naphtha splitter (without tankage) which separates
the Isomerization unit feed from the Catalytic Reformer feed. The
specifications for that column depend on whether benzene is to be
.destroyed or recovered for sale
In the crude distillation unit, we face problem with Gas Oil colour. Any one
have any idea to solve this problem or any one have seen like this in any
!?refinery
:The Color deterioration is due to the following reasons
Crude processed containing more Nitrogen content. Mostly it will be .1
reflecting up to Kerosene section. In worst case Naphtha section too will be
.affected

Flooding in the section beneath your Gas oil section. This may be .2
reflected in the pressure drop measurement. Reason shall be, more partial
pressure of Gas oil in the flash zone which is a reflection of improper crude
blending containing higher gas oil content or stretching the throughput
.beyond the design
Very high sensitive Crudes which can crack in the Crude Heaters can .3
.contribute to this cause
Heavy cut of gas oil at considerably lower temperature of Draw off may .4
.absorb moisture and it may turn bright(not black)
In all cases, we need to scrutinize the position and try to solve it as soon
as possible. The best safe solution would be change the successful crude
.blend composition and run to retrieve the position
Brown/Black coloration of gas oil is a problem frequently observed in CDU
and can be resolved easily with proper efforts. Such coloration may be
accompanied with increase in metal contents too like V or Ni in the gas oil.
Care may be taken for the reason that the contaminated stream with
increased metals may have adverse effect on downstream Hydrotreating
.or conversion catalysts
The coloration may be due to poor fractionation with improper split of the
cuts. The reasons for poor fractionation may be flooding, dumping at
specific locations particularly wash zone region. The problem could crop
up due to mal-operation, improper design of internals leading to residue
.entrainment in gas oil
The tests like delta P survey in the zone, gamma scanning can throw light
on the roots of the problem. I agree with other respondents stating the
probable causes like bottom stripping steam rate, damage to wash zone,
distributor issues for wash bed, wash bed coking etc. I know of published
case where the coloration was caused due to an issue in the downcomer
.clearance after a revamp
As mentioned it is a common problem due to residue entrainment with the
Gas Oil, it can be caused ether by low liquid rate going to the wash section
or high vapor coming from the feed, also flooding in the stripping section
or damage in the wash zone internals (cause by operational upset) can
deteriorate the color of Gas Oil
You will need to performed a series of tests to determine what is affecting
:the Gas oil color, some tests are
Reduce Gas Oil draw
Reduce bottom stripping steam rate
Reduce Fired Heater outlet temperature

Based on your unit configuration you may try other tests that will help you
to improve the Gas Oil color
Is this colour issue due to haze? Steam stripping of AGO saturates AGO
and can then can form haze due to condensation of water after the cooler
on the rundown. Its a pretty stable emulsion with an IFT usually lower than
10 dynes/cm however a high efficiency Liquid Liquid coalescer can break
the emulsion and prevent the need for tank settling. It's possible to get <
15 ppmv free water after the coalescer which will be C&B provided the
.rundown temperature is not too high
Gas oil colouration is normally due to entrainment of residue from the
wash bed which may be malfunctioning or the stages provided in the bed
are insufficient or the distributor (normally spray type) is maldistributing. If
the column loads and internals details are available better analysis of the
causes can be made. In fact we have carried out gamma ray scanning of
.the wash bed and the distributor to find out exact cause
It is likely either entrainment or a leaking gas oil vs crude heat exchanger
that is leaking crude oil into the gas oil stream. A number of things can
cause entrainment - increasing rate, change in feed stock to one with a
higher gas oil yield, an increase in vacuum, coking of the wash bed or
.inadequate wash oil rate
It may be either poor distillation internals allowing entrainment of jet
spraying OR it may be a leaking heat exchanger. Check the heat
.exchangers first
Very common problem due to entrainment. Did you increase the cut point?
The tray efficiency? If the gas oil is fed to hydrotreater, you may see
.quicker catalyst deactivation
I'm working on a study to design a new control schematics for Crude
Distillation Column Pressure Control. Any ideas for CDU pressure control
?strategies
Crude unit pressure control is to be done by using Fuel gas in the over
head reflux drums. Generally second reflux drum will be used for this
pressure control. Fuel gas is injected to second reflux drum and pressure
.reliving is to be done by taking out excess vapors to flare
I am trying to build a model to optimize the operation of Crude Desalter
.and study its effect on Crude Column Overhead Corrosion
The major salts present in Crude are NaCl, MgCl2 & CaCl2; but in our
laboratory we measure only Total Salt Content of Crude (before and after
.Desalter); we do not measure individual salt
:My queries are

How the individual salt affect Desalter performance and Crude (1


Overhead corrosion
?Is it required to measure the individual salt's content in Crude (2
Can I assume some typical break-up of individual salt (Note that the (3
.type of crude we process changes very often)
Typically the relative concentrations of chloride salts in crude oil mimic
that of sea water. My rule of thumb is that 70% of the chlorides are in the
form of NaCl, 20% MgCl2 and 10% CaCl2. I don't believe there is a
significant difference in the desaltability of the different salts, although I
have never seen data to prove or disprove this. MgCl2 is the primary
contributor to overhead corrosion because it almost all hydrolyzes to form
HCl. CaCl2 hydrolyzes but to a much lesser extent than Mg. NaCl does not
hydrolyze to any appreciable extent. If you look at some old hydrolysis vs.
temperature curves available in the literature, you will find that at typical
crude unit conditions that about 20% of the salts in the desalted crude
could be expected to hydrolyze in the absence of caustic. Some literature
indicates that besides temperature, nap acid can increase the %
.hydrolysis
While there can be differences in the salt composition for crudes, the effort
to try and figure it out is probably not worth it. From a practical stand point
you can't speciate the salts present in crude oil. You can do elemental
analysis or ion chromatography, but in any case you have to make
.assumptions about what the actual salts present are
One handy thing you can do is track the % hydrolysis of the salts leaving
your desalter. Calculate the lb/d of chlorides in the overhead system from
the chloride concentration and the total water. Divide this by the lb/d of
chlorides in the desalted crude to get the fraction of the salts that
.hydrolyzed
CDU overhead system
To provide a CDU with top reflux there are several configurations. The two
main ones are as follows
Configuration 1: Double condensation
Configuration 2: Top pumparound
In configuration 1, total overhead vapors are condensed in two condensers
in series. In the first condenser part of vapor equal to the required top
reflux is condensed, water is separated and hydrocarbon liquid is returned
to column as top reflux. The remained vapors (this includes the top
.product plus non condensable vapors) is routed to the second condenser
In configuration 2, the top reflux is provided by a top pumparound and the
overhead vapors ( (this includes ONLY the top product plus non

condensable vapors) are condensed in a condenser and no liquid is


.returned to the CDU
For a refinery with capacity above 100,000 bpd what configuration is
recommended? Considering in both case energy is used in top/feed
exchangers network. Can Heat Integration cause to use one of these
configurations? We know in configuration 2 some more stages are needed
!as we have added one more pumparound

:Additional
Thank you for the answers! Don't you think, the double condensation
configuration results in lower flowrate in top section? When I can remove
water in the first condenser, why not to return the reflux in lower
temperature! furthermore I think thermodynamically, configuration 1 is
better than configuration 2. As Ralph stated, the latter also needs at least
two/three more trays for top pumparound! What I am not sure is energy
saving! it is believed that configuration 2 results in a better heat
.integration
The first configuration that you mention is used to reduce water
condensation inside the column, which will lead to corrosion, also it
reduces the probability of water condensation in the overhead, all this
allow to use less expensive metallurgy in the mentioned areas. You have
to make sure that water condensation happens at the outlet of the first
.condenser so chlorides can be removed
For the second configuration, pumparound return temperature will be
lower, which could lead to corrosion, specially that pumparound return will
probably have free water (due to water solubility being reduce as
temperature is drop in the exchangers)
Both designs are effective in reducing corrosion in the top section of the
column, compared with a design that uses a single overhead accumulator.
In any of the 3 cases, resist the desire to yield light naphtha overhead and
heavy naphtha as the first side draw product. In other words, in any case,
the overhead vapor temperature needs to be well above the temperature
.at which water is a liquid
An advantage of the top pumparound (PAR) only design is that the crude
exchanger does not need to be elevated for free draining. This savings
can directionally offset the cost of additional trays and column height
.associated with the top PAR only design
One thing to compare: For the general power failure case, and using the
hot firebox, tube boilout criterion, there can be a significant difference in
the size of the relief system. It has to do with the Cox Chart effect on

LMTD of the air and water cooling portion of the heat removal
.configuration when calculated at relieving pressure
To what extent can we blend fuel oil into gas oil without affecting the
viscosity characteristics and maintaining the flash point specifications for
?gas oil or to keep them within the allowed limits

:Additional info
First of all we don't have neither FCC, Hydrocracker nor VDU...we only run
a conventional CDU
the objective here is to maximize the yield of gas oil...(we call it solar in
our national markets) by extra stripping out from fuel oil or residue...the
question is; Is there any equations or experimental methods to calculate
or estimate the resulting viscosity and flash point of either the gas oil or
?fuel oil
.Thanks a lot
Gas oil is quality is governed by the 90% or 95% (T90 - T 95) recovery
temperature (whatever is the applicable case for the refinery) as well as
the cold properties viz., Pour point and cloud point. One blends the Fuel oil
to the extent that both their recovery temperature and the cold properties
.are not violated
From your query, it looks that you want to blend Fuel Oil (i.e. long residue
or atm bottom in your case) into gas oil - Solar oil which I guess is diesel.
The answer is pl do not do as metals and other CCR components in fuel oil
will get added into diesel which is no desirable for high efficiency diesel
automobiles. Further, the heavy boling distillates in fuel oil will generate
substantial smoke while driving and end up in engine deposits too. The
best way to lift the front end of long residue into diesel is to operate the
Crude tower at the possible lowest pressure and higher furnace outlet
.temperature within possible lowest overflash
To clear every one's doubt about the question, please spell out clearly
whether it is GO to fuel oil or fuel oil to GO. This will help to give more
.appropriate answer for the question
If you are referring to gas oil as conventional feed to the FCCU, many
refiners increase the cut point of vacuum unit bottoms until the maximum
.coke burning capacity of the FCCU is reached
If the gas oil is hydrocracker feed, increasing the End Point is not
.recommended due to the affect on run length
If you mean gasoil, aka diesel fuel, the amount of resid shifted to the
gasoil can be determined in the lab. Distill the front end of the resid under

vacuum as done in a crude assay, collecting small cut samples. Make a


series of blends of gasoil and these cuts until the blend no longer meets
.the gasoil specifications when tested
If you mean dropping diesel fuel into FCCU feed, some refineries have had
to do this when the diesel fuel market is depressed. If you do it
incrementally by cut point, lab test blending will tell you when the diesel
fuel will still meet specifications. Otherwise, dump full range diesel into
FCCU feed until you reach a capacity limitation in the FCCU, or until your
.LP model tells you that it is a mistake to run that operation
Can you please advice what type of corrosion inhibitor, biocide, antifoulant
?and polyelectrolyte polymer can be used in Desalter effluent
We have had success with merus rings to solve various problems including
biofouling and corrosion. The ring is fitted to feed pipe. For info:
www.merusaustralia.com.au
Quality of Desalter effluent Brine (pH, Oil content) is very important as
brine joins the inlet streams of Waste water treatment. Brine pH could be
lower while processing opportunity crudes. In such cases to protect the
brine piping from the Desalter to WWTF corrosion inhibitors (simple pH
boosters) shall be used. However, before dosing any chemical in Desalter
effluent brine impact on the downstream sections must be thoroughly
.validated
A chemical injection into the desalter effluent is not very common.
Sometimes a cationic charged polymer is dosed into the desalter effluent
.to separate oil from the water at the API
Beside the injection of emulsion breakers it is more common to inject
metals removal additives and corrosion inhibitors into the wash water in
front of the desalter. In that case the effluent water will contain most of
these metals. Antifoulants like asphaltene dispersants are often dosed into
.the crude oil after electrical desalting
If the desalter is performing properly you should not need all of the
? mentioned chemicals. What is the fate of Desalter effluent
We have a very strange problem, it's that the desalter outlet crude has
greater salt content than that of the inlet... the lab examinations proved
that more than once...this always happens when the injection water is cut
?off-while switching from a tank to another. What could explain this

:Additional info/response
We cut off water while switching between tanks because of the existing .1
water accompanied with the crude from the new tank; I mean the first 30

minutes after switching to a tank, the crude has too much water to inject
.more
?How could the NaOH type could affect this situation .2
At the outset, I congratulate the person for asking a very good question
:which received such good response. My observations are as follows
Some of the refiners temporarily stop make up wash water when they .1
switch over the crude tank. It is to prevent water shot in the desalter and
.subsequently to CDU due to large amount of water coming with the crude
Under such situations it becomes important to increase the dose of .2
demulsifier appreciably very high. Monitoring and controlling of the
interface layer and water drain valve becomes very important parameters
to follow and act
Agar Corporation have invented very good design for such situation and .3
control of desalter operation. It can be read at their site namely
http://www.agarcorp.com/Animation/Desalter.html
Number of experts have expressed their opinion on use of caustic pre / .4
post desalter. It is useful to overcome the issue of naphthenic acid. Sodium
.naphthenate formed in desalter make emulsion very tough to break
Well, for a stable desalter operation, its better to have continous injection
of water. The reason is 1. if teh inlet water content is low, injection water
will actually improve the dehydration to certain extent and thus will have
better desalting as well. when injection water is cut off with low inlet
water, dehyration/desalting may not be as efficient as it should be and
also at this point of time the actual water carry over should be checked as
it could be higher as well. The reason for having higher outlet salt than
inlet could be because of doing the test method wrongly. for instance, if
the inlet BS&W is 0.3% taken at 15.6C aand outlet sample is taken at 120C
and cooeld it to 100C and not 15.6C will surely result in high water content
.& high salt content as water will be more soluble at higher temp
The solution is to drain the water from crude tank and then only to send it
for desalting, without cutting the wash water. This will ensure that the
.desalter functions properly
When you feed crude without draining the water, you are loading your
desalter with crude containing brine which is already saturated with salts
.and therefore desaled crude will have same salt contents as feed crude
Adding caustic will not solve the problem,use of caustic in desalter is
resortedfor high acid crudes and is done after a thorough analysis of the
.effects on down stream processing

Also please check the quality of water you are using for desalting, clean
and low TDS preferred if using Stripped sour water ensure proper pH as
.per recommendation of Desalter supplier
If problem pesists consult desalter vendors
Just cool the crude sample before you put in the sample bottle. What is
happening when the crude is hot and not enough cooling it vaporize and
you are concentrating the salt in the bottle. you think that you collect a
litter for example to fill in the bottle but actually, you collect 2 litters , one
vaporize and one remain in liquid phase , at this moment the salt in the
bottle is not for one litter it is doubled and finally you find the salt content
.. in the outlet is higher than inlet
I experienced this issue myself and solved it by the proper cooling the
.sample before you put in the bottle
Cutting off water as part of preparing for the Crude tank switch can be
avoided by proper mixing, settling and draining of Crude tank before the
tank is lined up for unit feeding. Opportunity / heavy crudes call for longer
times of mixing as the water at times remain as pockets in the startified
layers of crude blends. To avoid this stratification one can store neat
crudes in separate tanks (an expensive option) and carry out inline
blending if the Refinery needs to process a blend of opportunity crudes so
.as to maximise profits
NaOH injection will only help in improving the pH of Crudes when the pH is
lower than the recommended range of 6.5 to 7.5. It can help in
neutralising chlorides such as Mg Cl2, Na Cl2 that can lead to high
Chloride corrosion. One needs to be very careful with NaOH injection as it
can lead to a variety of extremely difficult to handle, downstream issues
viz., poor desalting and poor dehydration when the crude pH goes beyond
7.5, preheat fouling due to poor dehydration, Catalyst poisoning in FCCs,
.Premature coking Cokers etc
First I would like to ask about NaOH injection point up stream or down
stream the desalter
injection of NaOH up stream the desalter cause formation of Na Napthenes
especially if you processed high napthenes crude which act as emulsion
stablizer and this may be the cause of the problem
your problem also may be due to over mixing across the mixing valve so
try to establish optimum pressure drop across mixing valve (as if pressure
drop is higher than optimum it will cause water carry over and higher salt
outlet)
No situation will warrant to cut off desalting water while changing the feed
tank. Once you are sure that the tank farm operations are taken care to
prepare the feed tank well, that is makiing the tank free of water before

feeding the unit, then you need not cut the desalting water. Even you feel
water carryover in crude after feed tank is changing, you can cut off water
after you realise water in crude. The trick is in preparing the feed tank.
.Once you cut off water it is obvious that salt carry over is natural
NaOH may not affect the desalting process adversly, it helps only to
maintain the pH of brine (desalter drain). But it will contribute to increase
the metal content in VGO and this will be poison for the down stream units
.lile FCCu/HCU
Another possible source of the problem could be the sludge carry-over,
with related emulsion (which is far tighter than the rag layer at the
interface). You could evaluate online cleaning the desalter. ITW has
developed and patented a technology for doing the job in as low as 24
.hours on a oil-to-oil basis
If you inject NaOH that could contribute to the result you see. Are you
?using D3230 for analysing the salt
Why do you cut the wash water, as I understand, completely, why not
.reduce it 40-50%
If you could analyse the constituents by AAS/ICP I would assume this could
help guiding you to what is contributing to your higher values
I guess my first question is why are you cutting off the desalter wash
water when you switch tanks... this is not a common practice and probably
contributing to your problem... one possible cause for what you are seeing
is that when you cut the washwater off the desalting process is stopped
and you may be losing some of the desalter emulsion into the outlet which
could then increase the amount of salt coming in
?What is the best way of judging the efficiency of a desalter
Desalters are the Key equipment in CDUs and does the functions of
Desalting as well as Dehdyration. There are a few parameters that indicate
the efficienty of Desalters, viz., Desalting efficiency, Dehydration
efficiency, Brine quality, desalting water consumption, chemical
consumption. While desalting helps minimising corrosion, dehydration
helps in preventing fouling of down stream preheat exchangers (improve
preheat recovery and hence minimise the Fuel consumption) and Brine
quality helps in ensuring effluent quality in Waste water treatment facility
at a low expense. Desalting is said to be efficient when 90% of Desalting is
done in each stage (target of <1.0 PTB salt and <500 PPM of Oil in Brine).
NO water carry over into Desalted Crude is the other parameter that
judges the desalter performance. All the above need to be achieved with
lowest Desalting water and Chemical consumption. Remember water is
not cheap. High oil carry over with Desalter Brine increases slops
.production and hence increase recycling costs

The foremost objective of the desalter is to remove inorganic salt such as


chlorides of sodium and magnesium from the crude oil. Also it acts as a
surge drum to give sufficient residence time to help settling of suspended
particles. It should remove all water including micro size particles of water
.using the high electric field
Efficiency is calculated as follows: (Quantity of salt removed/Total salt in
.crude before desalter)*100
The expected removal percentage is 95 to 98%. Removal of water can be
identified by closely observing the variation in sour water make from
.atmospheric column overhead product drum or reflux drum
Efficiency of desalter can be improved by adding correct quantity of water
(3 to 5% of feed), maintaining differential pressure across the mix valve
(approx 1.0kg/cm2), desalter temperature to improve solubility and
desalter operating pressure to give proper residence time for settling of
water. Desalter temperature also plays a role for settling of water by
reducing the viscosity of crude oil. As the settling velocity is inversely
.proportional to viscosity, it helps to settle water
Very good indicators for the desalting performance are the desalting
efficiency (%) and dehydration efficiency (%). A single stage desalter
system should give a desalting efficiency >90%. With a double stage
desalter system a desalting efficiency >98% is expected. The inorganic
.salts of NaCl, MgCl2 and CaCl2 are typically expressed as ppm NaCl
The desalting efficiency is calculated with this formula: Desalting
efficiency = ((ppm NaCl in crude oil before desalter ppm NaCl in crude oil
after desalter) / ppm NaCl NaCl in crude oil before desalter) * 100
To calculate the dehydration efficiency the amount of wash water must be
included: Dehydration efficiency =((%water in crude oil before desalter +
%wash water to desalter - %water in crude oil after desalter) / (%water in
crude oil before desalter + %wash water to desalter)) * 100
In order to best judge the 'efficiency' of a desalting unit (whatever
efficiency means) one compares the quality of the product with the feed,
and estimates that improvement compared to the maximum theoretically
possible. In the practical world, one measures the un-removed
contaminants in the de-salter product stream and the oil lost in the desalter water product. Salt content in pounds (kilograms) per thousand
barrels is a commonly used metric. Also important is the BS&W to
determine how much dispersed water is not being removed. Then a KarlFischer water analysis (ppm) to determine the dissolved water remaining
.in the processed crude is helpful
:The process objective of 'de-salting' is to

a) remove water soluble chlorides and sulfates and any other 'salts' so
they do not cause corrosion as they decompose and form mineral acids in
the distillation equipment
b) remove any particulates such as sand, iron oxides, clays, and any other
'sediment' that would accumulate on the distillation trays or packing and
.cause both plugging and corrosion under the deposits
The goal is a perfectly 'clean' feed to the distillation equipment. 'Efficiency'
can be considered as a calculation of just how far short of perfection the
.unit and operations achieved
One might also be concerned about the quantity of chemicals used,
electricity consumed, pumping horsepower, water use versus theoretical
minimum for the measured performance, hydrocarbon loss in the water
effluent, total treating cost per barrel, etc. The BIG MONEY savings are in
reducing residual salts and sediments as much as reasonably possible to
.reduce corrosion and fouling of the equipment
KW per Barrel
salt removal per stage %
oil in brine
Required transformer size varies with crude source, so care is required in
.comparing with other desalters
The simplest way is to measure the residual salt, i.e. 'Salt = ~ 1 pound per
thousand barrels is good target for single stage desalting of conventional
crude oils, while 'Salt' = ~0.5 ptb is good target for recommended two
.stage desalter system
:Other aspects to consider are
Residual water in crude oil [should be down in the few tenth weight (a)
percent via BS&W testing]
Residual dirt and rust and any carbonaceous materials in crude oil (b)
[Most of these should have collected in the bottom of the desalter vessels
and been blown down to suitable external decanting and transfer receiver
'via well engineered 'mud drain system
whether emulsions have been mostly 'broken' such that there is only a (c)
small 'rag' layer inside the desalter vessels [with reasonable expenditures
on demulsification chemicals]
Ensuring that desalting is at optimal crude oil outlet temperature year (d)
around [regardless of whether crude oil in tankage is cold and encon
.exchanger network is clean or fouled]

What makes outside shapes of distillation columns differ from one


?another? i.e. shape of pre-flash differs from CDU, CDU differs from VDU
.I concur with the responses by Keith and Ralph
The key drivers for cross-sectional area are the ACFS,vapors or Am3/sec,
vapors and the feasible / comfortable capacity factors of the internals
[trays or structured packing or grid packing] and the design margins.
Vessel cost and structural considerations favor only a limited number of
diameters in any given tower. Sometimes the bottom swage down below
.the flash zone is internal in crude atmospheric towers
Best practice designs for crude atmospheric towers often favor high liquid
wetting flux pump-arounds using structured packings [as Lesson Learned
from complex distillation tower theory / computer modeling]. In these
instances, the hot gpm per ft2 or hot Am3/hr-m2 can become an important
factor in determining cross-sectional area in conjunction with ACFS, vapors
.or Am3/sec, vapours
Distillation column cross sectional area necessary to meet design thruput
is determined by the volume of vapor and liquid that must be processed
.'on that 'tray
A preflash column is sized to allow sufficient disengaging space for the
'.light ends so 'flashed
A flashed crude column will typically have a larger mid-section since much
of the 'work' of distillation is done in that section of the column. The top
end may be either smaller, or larger, depending on operating pressure and
the light-ends yield of the design crude. The bottom of the so-called
Atmospheric column will be sized to accommodate the work necessary to
.separate the gas-oil from the reduced crude
A vacuum distillation column is similarly designed but has a much larger
cross section because of the low density of the vapor due to the very low
absolute pressure. Often the very bottom section is much smaller because
both the vapor content and liquid rate are so much lower that the reduced
crude feed and residence time at the typical high temperature must be
minimized to avoid thermal degradation that will form deposits in the
. column and plug it
Sometime the physical strength requirements are such the very bottom
section is too small to support the column and, and a 'skirt' must be added
around the bottom section to provide necessary strength
Usually due to vapor rates being much lower in some sections, such as
below the flash zone of the atmospheric column and the vacuum column.
Save the cost if a smaller diameter is needed in that section. Another
example: In a reboiled absorber, the vapor rate in the absorber section,
.above the feed, is much lower and can have a smaller diameter

if the column pressure increases, will the separation increase, and vice
?versa
Increasing pressure makes the separation worse directionally. That's
.because k values of adjacent components converge as pressure increases
We want to by-pass our de-salters in order to check the consequences with
and without desalters on CDU. Moreover we have stopped de-emusifier
dosing prior to desalters. What impacts are anticipated in your opinion and
what parameters to be monitored in case when there is no desalter in
?crude preheat trains
A desalter de-salts; that is eliminates part of the CaCl2 and MgCl2 .1
occluded in the crude. If you do not do this, well, both of this salts (none
the NaCl) decomposes with the water and heat (120 - 370 C) to HCL,
hydrochloric acid, which is "mortal" to the walls of the CDU mainly at the
head - coolest - zone (water condensation). In the other hand, a desalter
helps to decrease the water and solids/dirt content in the crude. If you do
not do so, you will get troubles on the heated zones of the furnace and the
CDU (fouling, over boiling, erosion and corrosion)
A demulsifier de-emulsify; that is to break the emulsion crude-water. If .2
you do not do this you will increase dramatically the water content in the
crude; the result: instability in the CDU operation (over boiling)
Consequences of bypassing desalter are already well known. What
prompts you to do so? Demulsifiers do great job in water separation
Answer to question lies in why desalting is done. Crude coming to the
refinery contains water, some free and some as emulsion. The water also
has dissolved salts in it and possibly suspended solids, depending on
source of crude. In desalter the water along with salts are knocked out.
Not using desalter is not a good practice and cannot be recommended.
.Literature deals in detail about it and should be consulted
In case non-desalted crude is used as feed in CDU, serious problems can
be encountered depending on quantity and quality water coming with the
:crude. Anticipated major problems are
Process upsets .1
Fouling of exchanger train, erosion of heater tubes and transfer line by .2
dissolved / suspended salts
Upset and lack of consistency in the O/H corrosion control .3
All these in long run would damage equipment and result in loss of
.production and high cost of maintenance
Answer to what parameters to be monitored in case when there is no
:desalter in crude preheat trains are

By-pass desalter only if it is required for maintenance .1


Ensure max. drainage of water from the feed crude tank bottom before .2
,it is used as feed
Monitor out let and inlet temperatures of feed at critical locations in the .3
feed exchanger train to see if desired degree of temperature rise is
achieved or not. This would indicate extent of fouling, if any, and also
.identify affected exchangers
Operation would have to be vigilant to avoid upsets in distillation .4
.column in case of entry of large quantity of water
As there would be large variations (fluctuations) in HCl going in the O/H, .5
the O/H corrosion control system cannot be manually operated and
.advanced automatic system will have to be installed
Any increase in erosion / corrosion of heater tube and transfer lines .6
.should be monitored
Perhaps the crude you process is extremely light, clean, and does not have
.significant chloride salts
However, the industry trend is toward significantly increasing the
.performance of their de-salter operations
Dirt (fine particles from the producing formation), water-usually a complex
brine, rust particles, and other miscellaneous deleterious matter normally
MUST be removed from the crude oil before being heated to above about
200C. This is the approximate temperature at which the chloride salts
dissolved in the inevitable brine in the crude begin to decompose into
insoluble deposits and chlorine -which immediately turns into hydrochloric
.acid--which has a ferocious appetite for steel and its alloys
The entrained dirt and rust particles will drop out of suspension, depositing
in all the quiet regions on the trays, packing, horizontal surfaces,etc.
plugging them up You may easily calculate the volume and mass of these
potential deposits from the BS&W analysis of the crude. If those are not
removed by the desalter, they WILL remain inside the heat exchangers
.and distillation tower
IF the crude you process is similar to MOST, and you cease desalting, I
would expect to find much more rapid decline in heat transfer coefficients
on the pre-heat exchangers, requiring more severe firing of the furnace-resulting in more coke formation and higher pressure drop there, greatly
increased corrosion rates on all the metals in the top section of the tower
and all the associated equipment (HCL is not picky about what it eats up),
and within a few weeks/months, the fractionation performance of the
tower itself will have noticeable decline, requiring higher reflux ratios to

maintain product distillation specifications. All of these effects significantly


.lower the operating efficiency of the unit
Excellent answers, in my opinion. I would add the obvious: If the salt in the
crude is 1 lb/1000 bbls or less, the desalter is needed only to remove
BS&W, which in itself can cause fouling, but is not as critical as the
.corrosive effect of higher salt levels
If you bypass desalters, salt,sediments and water content can't be .1
separated from crude.You can't add wash water to crude if desalter is
bypassed and salts will carryover to preheat train and foul the exchangers.
Caustic and magneesium salts will decompose above 200 C forms
Hydrochloric Acid in Column overhead system which in turn increases
.corrion in overhead system
If you stop de-emulsifier, water in emulsion phase will not be separated .2
even with Electric field. De-emulsifier reduces the surface tension between
.crude and water and helps to separate water from crude
If Desalter bypassed, post desalter preheat train fouling will increase .3
and pressdrop across each exchanger increases which can be observed at
last exchangers (>200 C). CDU colum overhead system pH will drastically
drop to 3 to 4 because of HCl in aqueous form and rate of corrosion will be
increased. Overhead chlorides will be increased which is a direct indicates
.of salts carryover in crude to preheat train and heater
:you should verify the following parameters
Chlorides content in overhead water draw
Iron content in overhead water draw (to try to measure an increase in
corrosion)
Sodium in the residium (If sodium if above 20 ppm it will speed up the
coke formation in the fired heater of the vacuum column)
monitored the fouling on the heat exchangers downstream (this will
change within a long period of time)
If you have a coker or visbreaker unit, also monitored the sodium in the
.feed to these units
Bypassing Desalters is a BAD idea within the context of CDU+VDU
operations. This will cause accelerated fouling of the hotter crude preheat
exchangers plus salt fouling and accelerated coking within the Crude
Heater plus accelerated deposition + fouling + corrosion of the top trays
[assuming that CDU is not best practice with "double overhead drum
system" or "high recirculation warm TTPA and single overhead drum
."system

Desalters are intended to water wash the crude oil to remove dirt and rust
and particulates and as well as lower the salt levels [both in emulsified
.brine form and micro-particulates]
The only plausible reason to bypass a desalter---except temporarily to fix
or upgrade its internals or to retrofit a second stage desalter---is that the
API Gravity of the crude mix is less than 19 degrees. Even then, best
practice calls for recycling overhead naphtha or TTPA naphtha to bring the
.API Gravity seen by the desalter to 22 degrees or higher
this is not a very wise move in my opinion, besides the potential increase
in fouling of not only your preheat train but also your furnace due to salts
and solids you can count on increase in corrosion concerns in the top of
your cdu tower... suggest that you review your operations and ask
:yourself
what am I trying to achieve, by shutting down the desalter, are the (1
financial gains from shutting down the desalter at the CDU offset from all
?of the other downstream cost impacts
?is the desalter working to its fullest potential, has it been optimized (2
Besides the immediate impact on preheat, furnace and tower over
corrosion you will see much larger losses in energy and due to the impact
anticipated on downstream processes (if they exist), for example a slight
increase in water can increase the energy loss by >$500 K USD/per year;
increases in salt can result in FCCU catalyst impacts that can be >$1 M
.USD; there are similar impacts on thermal conversion units also
What is the relationship between smoke point and ASTM D-86 of kerosene?
Does an increase in IBP increase the smoke point or is it the increase in
?final boiling that increases the smoke point
Just to fix ideas in case the OP wonders why more aromatics means lower
...smoke point
Aromatics (contains unsaturated benzene rings) have higher carbon-tohydrogen ratio. And this is that deficiency of hydrogen that can cause
.unburned HC (smoke) during combustion in a Jet engine
.More aromatics means lower smoke point (low is bad)
Highest the FBP, poorest the Smoke Point but that depends on the
molecularity of the FBP. Remember that the ASTM D 1655 09 establish a
minimum Smoke point of 25 mm, or a minimum of 18 mm and a
Naphthalene content of 3.0 vol, % maximum. Naphthalene is located at
.the FBP tail
Smoke point is directly related to the Aromatic, if you done more aromatic
.saturation, then the smoke point will increase

A good simple correlation to estimate smoke point from TBP and gravity
data is probably that published by (Albahri, T. A., Riazi, M. R., Alqattan, A.
A., "Analysis of Quality of the Petroleum Fuel," Energy & Fuels, 2003, Vol.
17, pp. 689-693.). The relationship therein is that increasing API gravity
and Mean Average Boiling Point increase the smoke point. So increasing
your IBP or FBP may reduce API gravity more than the benefit of adjusting
.the MeABP, which might reduce the smoke point
Mr. Ragsdale is correct that increasing the FBP is more likely to increase
.the aromatics content, which is bad for smoke point
I'm new to the refining field. We have eletrostatic desalter with three
:transformers (each of 22KV). and I have questions about this
?Why is a single heavier transformer is not used instead of three .1
?We have 2 PSVs on desalter. What is the reason for two PSVs .2
Why the water injection before desalter is maintained 4.5% of crude .3
?charging
?What is the function of grills (grids) inside the desalter .4
Three phase supply - three transformers , one on each phase balances (1
.the load. Also if one breaks, you still have some treatment
Not sure - what are the set points and design pressure? Are there two (2
separate PSVs with different set points? Are you sure its a PSV andnot
?something else
Ensures the dilution is sufficient to reduce the salt content to spec (3
The grids are connected to the high voltage outlets of the transformers, (4
the oil passes between them, the water droplets become polarised,
coalesce and travel towards the grids and are removed. Try google books
.for a longer explanation
Desalter manufacturer will have to answer the first question. My guess .1
.is that it's so that if a transformer fails, you don't lose all the electric field
I don't believe that there is a fundamental reason why a desalter would .2
need 2 PSVs. If it's a large vessel, you might have a very large fire load so
that the required load exceeds the capacity of a single PSV or there could
be a large blocked in liquid relief load if the vessel is not designed for the
.blocked in head of the charge pump
Wash water is added to enhance the desalting by improving contacting .3
of salts with water, diluting chlorides in water, and enhancing water
coalescing (more water means water droplets are closer together, which
makes it easier for them to coalesce & settle). 4-5% is a common amount

of water for lighter crudes. If you are processing a heavy crude you might
.need 7-10% wash water to help with the desalting
The grids create the electrical field used to coalesce the water droplets. .4
The size of the transformer and the spacing between the grids set how
.strong of electric field can be generated for coalescing the water
One of the observations pertaining to 2 stage desalters is that 2nd stage
efficiency remains poor as compare to 1st stage (50 to 60 % in 2nd stage
as compare to 91 % in 1st stage) despite trying all necessary parameter
adjustments such as Delta P, Fresh water flow, interface level, emulsion
.checking etc
?Is there a means of remedying this discrepancy
The question I would have is what is the actual salt number going to the
2nd stage? if it is low then the relative removal percentage may not be
90%, but something lower. If the salt going to the 2nd stage is >10 % then
it would be reasonable to expect >90%. There are ways to calculate if it
has reached the ideal level by determining the mixing efficiency (function
of dehydration and salt removal) as well as determining the optimal salt
content (function of the dehydration and inlet salt conc.)

Вам также может понравиться