S&C IntelliRupter PulseCloser Fault Interrupter

Outdoor Distribution (15.5 kV through 38 kV)

Specifications
Conditions of Sale
STANDARD: Sellers standard conditions of sale set
forth in Price Sheets 150 and 181 apply, except as modified
by the SPECIAL WARRANTY PROVISIONS and
WARRANTY QUALIFICATIONS on pages 6 and 7.

SPECIAL TO THIS PRODUCT AND


ASSOCIATED SERVICES:
INCLUSIONS: IntelliRupter PulseCloser Fault
Interrupter is a unitized package of fault-interrupting and
control components which provides fault isolation and
circuit restoration functions on an overhead distribution
system. It can operate as a stand-alone fault interrupter
or, with appropriate options, can be integrated into a
SCADA system and/or an S&C IntelliTeamSG Automatic
Restoration System.
IntelliRupter Fault Interrupter features PulseClosing
Technologya unique means for verifying that the line
is clear of faults before initiating a close operation.
Pulseclosing Technology is superior to conventional
reclosing techniques. It greatly reduces stress on system
components, as well as voltage sags experienced by
customers upstream of the fault.
IntelliRupter Fault Interrupter provides full liveswitching performance under all ice conditions
circuit making, circuit breaking, and the circuit testing
accomplished by S&Cs PulseClosing Technology are
accomplished within the interrupters; there are no external
moving parts.
Each IntelliRupter Fault Interrupter is factory-assembled
on a single stainless-steel base with:
Three-pole vacuum interrupters rated 630 amperes
continuous, 16,000 amperes interrupting for 15kV
models, and 12,500 amperes interrupting for 27kV
and 38kV models. A rating of 800 amperes continuous
applies with a 2 ft./sec. wind, similar to conductor
ratings.
Unique magnetic latching actuators that provide singlephase tripping/single-phase lockout, single-phase tripping/three-phase lockout, or three-phase tripping/threephase lockout of the interrupters. Interrupters can also
be manually tripped by means of a manual lever, operable
from the ground with an extendostick.
Sensors for three-phase monitoring of line current, and
three-phase monitoring of line voltage on both sides

March 16, 2015


S&C Electric Company 2006-2015, all rights reserved

of the interrupters, provides high accuracy sensing.


Total sensing system accuracy is 0.5% for steady-state
current, and 2% for fault current.
One or two integral power modules, which derive the
necessary energy directly from the distribution line.
Control power can alternately be derived from an
external power supply.
Open/close indicator for each phase.
External power supply connector. Permits pre installation uploading and downloading of configuration
settings, plus radio programming and battery charging,
as applicable, indoors in users service center or lab.
Manually-actuated open/close/ready lever, operable
from the ground with an extendostick.
Manually-actuated ground trip blocking lever, operable
from the ground with an extendostick.
Manually-actuated hot-line tag lever, also operable
from the ground with an extendostick, to enable or
disable a hot line tag or disable an electronically set
hot line tag.
Control group, featuring a hookstick-removable
protection and control module, and communication
module, mounted in the base. Its easily configured
and operated from the safety and security of a vehicle
parked near the base of the pole, by means of a secure
WiFi communication link to a laptop computer.
Unique multi-function status light which shows that the
control group is operating normally. Blink rate changes
if WiFi connection is made, control power is lost, or
position of open/close/ready lever has been changed.
Separate hot-line tag indicator shows a set tag.
Integrated Global Positioning System. Provides 1ms
accurate time-stamping of events to speed post-event
analysis, as well as IntelliRupter Fault Interrupter location data for entry in the users graphical information
system.
Provisions for three surge arresters on each side of
IntelliRupter Fault Interrupter. MacLean Power Systems Zforce Type ZHP (Heavy Duty) polymer-housed
metal-oxide surge arresters can be optionally factoryinstalled and wired.
Single-point lifting means, for convenient rigging
and hoisting of IntelliRupter Fault Interrupter during
installation.

Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter


Conditions of SaleContinued

Synchronization check,

IntelliRupter Fault Interrupter is available in the uprightcrossarm and compact-crossarm mounting configuration,
with or without integral, hookstick-operated disconnect
for visible air-gap isolation of switched-open circuits.
The disconnect is interlocked with the interrupters to
ensure that pole-units are open prior to opening or closing
the disconnect; a status point for remote monitoring
of disconnect position is included. Interrupters may be
operated with the disconnect in the open position.

Cold-load pickup modifier,

IntelliRupter Fault Interrupter may be mounted on


a utility pole or, in substation applications, on an S&C
Mounting Pedestal available separately.
IntelliRupter Fault Interrupter pole-units are molded
of S&C Cypoxy. The sensors are embedded, eliminating
the cost, clutter, and complexity associated with separately
mounted sensors. Sensing accuracy is 0.5% for both voltage
and current, and total system accuracy for fault detection
including sensing, control, and interrupting time is 2.0%.
IntelliRupter Fault Interrupters include on-site user
training on setup, configuration, and operation. These
services apply to first-time orders only; they can be provided
for subsequent orders as indicated in the table on page 17.

Control Groups
IntelliRupter Fault Interrupter is available with a variety
of control groups. Each features easy configuration and
operationand examination of waveforms and events
using secure wireless communication to a nearby laptop
computer.
The control group includes a base-mounted, hookstickremovable protection and control module, and communication module. This flexible, low-maintenance arrangement
offers excellent immunity to surges and noise induced
by normal power line events such as faults and lightning
strikes, and minimizes pole clutter. IntelliRupter Fault
Interrupter is powered from the distribution line, through
the integral power module(s) or the external power supply,
if furnished.
The protection and control module provides point-onwave closing to minimize asymmetric fault current and
inrush current. It features a complete set of protection and
control functions, including:
Simultaneous independent directional phase, ground,
negative-sequence, and sensitive-earth time-overcurrent,
instantaneous-overcurrent, and definite-time elements,
Directional blocking of overcurrent elements,
Over/under voltage elements,
Over/under frequency elements,
Phase unbalance detection,

2S&C Specification Bulletin 766-31

User-selectable single-phase or three-phase tripping


at any point in the test sequence, with single-phase or
three-phase lockout, and
Comprehensive diagnostics, including data and waveform capture.
The protection group is automatically selected in
response to the system configuration, for optimized
protection.
The protection and control module provides sophisticated RTU functionality, including remote reporting of
IntelliRupter Fault Interrupter status points and operations,
as well as current, voltage, watts, and VARs.
A 20channel Global Positioning System chip set in
the communication module provides 1ms accurate
time-stamping of events to speed post-event analysis, as
well as IntelliRupter Fault Interrupter location data to help
you maintain your graphical information system.
Select the control group that meets the needs of your
distribution system.

Standard Control Group


The Standard Control Group is suitable for the following
applications:
IntelliTeam SG Automatic Restoration System. Teams
utilize peer-to-peer communication, real-time data, and
distributed intelligence to make automatic operating
decisions. No central processing or SCADA is required,
though fully supported. Each IntelliRupter Fault Interrupter must be furnished with an S&C SpeedNet
Radio, S&C IntelliCom DA Mesh Radio, or other
approved communication device.
Automatic source transfer using two IntelliRupter
Fault Interrupters. The IntelliRupter Fault Interrupters ensure a high degree of critical-load continuity
by minimizing interruptions resulting from the loss of
one source. Each IntelliRupter Fault Interrupter must
be furnished with an S&C SpeedNet Radio, S&C IntelliCom DA Mesh Radio, or other approved communication device.
Automatic loop restoration using normally closed IntelliRupter Fault Interrupters or conventional reclosers,
with a normally open IntelliRupter Fault Interrupter
switching point. The feeder on either side of the
switching point can be fed from a different source. If
a fault occurs on either feeder, the normally closed
devices in that feeder open, then test the circuit using
PulseClosing Technology (or reclosing) sequentially to
sectionalize and isolate the fault. Service is automatically restored to unfaulted line segments by closing the
normally open IntelliRupter Fault Interrupter.

S&C IntelliRupter PulseCloser Fault Interrupter


Wide-area SCADA, when equipped with an S&C SpeedNet Radio, S&C IntelliCom DA Mesh Radio, or other
approved communication device.

Mesh Radio. One SpeedNet Repeater Radio or IntelliCom


WAN Mesh Radio is also included with the team.

Stand-alone (non-communicating) applications.

A communication site survey.

Approved communication devices permit configuration,


operation, interrogation, and software maintenance of
IntelliRupter Fault Interrupter from any location having
access to the communication system, using optional
IntelliLink Remote Setup Software.

Each package includes the following services:


IntelliTeam SG factory acceptance testing.
IntelliTeam SG training.
IntelliTeam SG commissioning.
IntelliRupter Fault Interrupter training.

No batteries are required for stand-alone applications


and applications with operating times of 30 seconds or
less; ac line voltage must be available on the side of the
IntelliRupter Fault Interrupter with the integral power
module or control power must be available from the
external power supply, if furnished.

Services-Only Packages

The Standard Control Group includes IntelliTeam SG


Bronze Level Software. When furnished with optional
IntelliTeam SG Silver Level Software, the Standard
Control Group is additionally suitable for basic closed-loop
applications. When furnished with optional IntelliTeamSG
Gold Level Software, the Standard Control Group is
additionally suitable for basic closed-loop applications
and applications on systems with three or more sources.
IntelliTeam Designer Configuration and License
Management Software is required to activate IntelliTeamSG
Software.

Overcurrent protective device coordination studies.

Standard Control Group with Battery Backup

Loop Restoration training.

This control group is identical to the Standard Control


Group and is suitable for the same applications. It
additionally includes batteries that support operation for a
minimum of four hours after loss of ac line voltage on both
sides of IntelliRupter Fault Interrupter, permitting extended
dead-line switching.

Universal Control Group


This control group is identical to the Standard Control Group
with Battery Backup but includes either IntelliTeamSG Gold
Level Software and IntelliTeam Designer Configuration
and License Management Software or an IntelliTeam II
Software License, as specified. When the former is specified,
the Universal Control Group is suitable for all applications
of the Standard Control Group with Battery Backup, as
well as basic closed-loop applications and applications
on systems with three or more sources. When the latter is
specified, the Universal Control Group is suitable for all
IntelliTeamII applications.

Equipment/Services Packages
Complete equipment/services packages are available
for three- through twelve-member IntelliRupter Fault
Interrupter teams, as listed in the table on page14. Each
team member includes the IntelliTeam SG Automatic
Restoration System and a SpeedNet Radio or IntelliCom DA

Services-only packages are also available for IntelliRupter


Fault Interrupter, as listed in the table on page 17. Offerings
include:
Communication site surveys.
IntelliTeam SG device settings determination.
IntelliRupter Fault Interrupter secondary injection
testing.
IntelliTeam SG factory acceptance testing.
IntelliTeam SG training.
IntelliTeam SG commissioning.
IntelliTeam SG SCADA integration.
IntelliTeam SG monitoring.
IntelliRupter Fault Interrupter training.
IntelliRupter Fault Interrupter maintenance.
IntelliRupter Fault Interrupter project and construction management.

Communication Site Surveys


A communication site survey is required for new
IntelliTeam SG applications and is critical to ensure
acceptable signal strength between the IntelliRupter Fault
Interrupters in the team and the head-end SCADA radio, if
applicable. A site survey includes:
An engineering review of selected team member sites
which considers distance, topological constraints, and
other factors that can affect signal strength.
An on-site survey of team member sites to confirm feasibilityand, if necessary, determination of alternative
sites that will provide better signal strength.
A detailed report defining the GPS coordinates of all
team and repeater radios.
Establishment of baseline communication statistics for
monitoring communication system performance.
Training on installation and configuration of SpeedNet
Radios, IntelliCom Mesh Radios, or UtiliNet Radios.

S&C Specification Bulletin 766-313

S&C IntelliRupter PulseCloser Fault Interrupter


The user will need to supply a line truck and the engineer/
technician responsible for the project.
The site survey ensures optimal communication when the
system is commissioned. However, building construction,
relocation of lines, vegetation growth, and other factors can
degrade communication over time. A subsequent tune-up
site survey may be desirable.

Overcurrent Protective Device


Coordination Studies
A coordination study is used to select appropriately rated
protective devices and their settings, including those of
IntelliRupter Fault Interrupters. Proper protective device
coordination minimizes the impact of short-circuits, by
isolating faults as quickly as possible, while maintaining
power to the rest of the system.

IntelliTeam SG Device Settings Determination


Appropriate device settings are essential to the successful
implementation of IntelliTeam SG. These settings must
be documented prior to factory acceptance testing and
commissioning of IntelliTeamSG.

IntelliRupter Fault Interrupter Secondary


Injection Testing
Secondary injection testing validates the settings, functions,
and logic of an IntelliRupter Fault Interrupter protection
and control module prior to installation, and helps ensure
successful commissioning. It can also be performed when
the users operating practices require periodic testing of
installed equipment to validate control and coordination
settings. The procedure utilizes Omicron testing equipment,
with a specially designed interface to the IntelliRupter Fault
Interrupter docking station.

is strongly recommended if there are any unusual system


characteristics or loading limitations. It provides significant
insight on how IntelliTeam SG will work on the users
systemwith the users specific system protection settings,
available fault currents, connected loads, etc. To perform
this testing, the user must furnish the following:
Substation breaker data, including overcurrent pickup
levels and relay timer settings.
Available fault current at each IntelliRupter Fault Interrupter location orif S&C is providing an overcurrent
protective device coordination study and/or determination of IntelliTeamSG device settingsinformation
which will allow S&C to calculate these values.
Any substation capacity limitations, conductor loading
limitations, or system operating rule limitations.
A written description of the desired system functionality.
A single-line diagram of the circuits on which IntelliTeamSG will be applied.
Completed IntelliTeam SG Settings Sheets. Determination of device settings is the customers responsibility,
or can be provided by S&C.
Factory acceptance testing is performed at S&Cs
IntelliLab facility in Chicago. S&C will provide a detailed
test plan. After testing has been completed, the user will
receive a CD-ROM containing the results of each simulation,
which they can use for training.

IntelliTeam SG Training
IntelliTeamSG training is conducted on-site and ensures
that users personnel fully understand IntelliTeam SG
functioning. Both operations and engineering sessions are
provided.

The user must provide the following, a minimum of two


weeks before commencement of this service:

Operations training is geared to persons who will


encounter the equipment in the field, dispatch personnel,
or create switching orders. A typical agenda includes:

Availability of the users designee, who will be the point


of contact for S&Cs field service specialist.

IntelliTeamSGwhat it is, how it works, and examples.

Proposed settings for each protection and control


module to be tested. Determination of these settings
is the responsibility of the users designee, or can be
provided by S&C.
A written description of the desired test plan.
Indoor access to each protection and control module
to be tested.
S&C will prepare a report detailing the results of the
testing for each protection and control module.

IntelliTeam SG Factory Acceptance Testing


Factory acceptance testing ensures that all information
required for a successful IntelliTeam SG implementation
is gathered and understood prior to commissioning, and

4S&C Specification Bulletin 766-31

Operation of IntelliRupter Fault Interrupters in an


IntelliTeam SG system.
Real-world examples of IntelliTeamSG operation using
IntelliTeam Designer in Instant Replay mode.
Engineering training is geared to engineers and
technicians who will configure the controls and radios. A
typical agenda includes:
A detailed look at how IntelliTeamSG works.
Explanation of all control settings.
Software screens useful for troubleshooting.
Configuration of the radios.
Creation of a DNP lookup table.

S&C IntelliRupter PulseCloser Fault Interrupter


IntelliTeam SG Commissioning
IntelliTeamSG commissioning ensures that the IntelliRupter
Fault Interrupters in the team have been set up correctly
and are ready to be put into service. These services include:

The scope and format of the reports can be customized


to meet specific user needs.

Loop Restoration Training

Verification of acceptable peer-to-peer communication.

This training is conducted on-site and ensures that the


users personnel know how to properly set up, configure,
and operate IntelliRupter Fault Interrupters in a loop
application comprised of normally closed IntelliRupter Fault
Interrupters or conventional reclosers, with a normally open
IntelliRupter Fault Interrupter switching point.

Verification of acceptable communication with the


SCADA system.

IntelliRupter Fault Interrupter Training

Assistance with configuring the IntelliRupter Fault


Interrupters. Determination of device settings is the
customers responsibility, or can be provided by S&C.

Checking each IntelliRupter Fault Interrupter for conformance with installation recommendations.
Verification that each team is capable of achieving
READY status. (Upon user request, the teams will be
disabled after verification.)

IntelliTeam SG SCADA Integration


If IntelliTeamSG is to communicate with a SCADA system,
integration services may be desirable. These services
include:
Working with the SCADA supplier.

This training is conducted on-site and ensures that the


users personnel know how to properly set up, configure,
and operate IntelliRupter Fault Interrupters. These services
include the following:
Training on use of IntelliLink Setup Software.
Configuring IntelliRupter Fault Interrupter for use in a
loop restoration system, if applicable.
Use of security keys.
IntelliRupter Fault Interrupter operation, including
PulseClosing Technology.
These services are included for first-time orders.

Designing and installing the communication infrastructure linking IntelliTeamSG with the users LAN.

IntelliRupter Fault Interrupter Maintenance

Developing the protocol conversion necessary to


change DNP into the native language of the SCADA
master.

IntelliRupter Fault Interrupter maintenance includes


periodic field inspection and testing on a three-year interval.
Services provided for each team member include:

Developing optimal SCADA settings and polling


sequence.

Visual inspection of the IntelliRupter Fault Interrupter,


antennas, grounding, arresters, and wiring connections.

IntelliTeam SG Monitoring

Verification of IntelliLink operation though secure WiFi


connection.

Ongoing remote system monitoring ensures that


IntelliTeamSG operation meets agreed-upon service levels.
It requires a SpeedGate Radio Interface or IntelliCom
WAN Mesh Radio with a wireless telephone modem. If
wireless telephone service is not available, a telephone
modem and user-supplied telephone line must be installed
at the SpeedGate Radio Interface or IntelliCom WAN Mesh
Radio.
System monitoring allows S&Cs engineers to assist with
any required troubleshooting, update configurations, and
provide weekly health reports on the status of the system.
Such reports can include:
Team READY status.
IntelliTeamSG operational status.
Battery system status.
Active trouble conditions or alarms.

Downloading of a full report from the IntelliRupter


Fault Interrupter, review of the data, and execution of
any corrective actions necessary.
Replacement of the battery.
Operation of the IntelliRupter Fault Interrupter (if it
can be bypassed): locally, manually, and from SCADA.
Inspection of the repeater radio and replacement of its
battery.
Monitoring of communication statistics and comparison against the initial baseline. Identification of recommended communication enhancements.
All system maintenance is coordinated with the users
designee. To facilitate the inspection process and ensure
consistent and accurate reporting, S&C will work with
the designee to develop an inspection checklist and train
inspection crews on its importance and use.

S&C Specification Bulletin 766-315

S&C IntelliRupter PulseCloser Fault Interrupter


IntelliRupter Fault Interrupter Project and
Construction Management
S&Cs highly trained, experienced staff will assist the users
automation team in the areas of project and construction
management, working closely with them to assure on-time
completion of the project. Services may include working
with the users contractor or crew to:
Ensure proper installation of the IntelliRupter Fault
Interrupters.
Supply the automation system as a complete turnkey or
Engineer-Procure-Construct (EPC) project.
EXCLUSIONS: IntelliRupter Fault Interrupters do not
include terminal-pad connectors. Various connectors are
available as listed in the Connectors table on page 14.
Equipment/services packages and services-only packages
do not include field installation or construction labor.
IntelliRupter Fault Interrupters furnished with Standard
Control Group or Standard Control Group with Battery
Backup do not include optional IntelliTeamSG Silver Level
Software, IntelliTeamSG Gold Level Software, or IntelliTeam
Designer Configuration and License Management Software.
For non-IntelliTeam SG applications, S&C may be able to
furnish and install in the communication module, or make
provision for, a customer-specified communication device
not listed in the table on page 13. S&C will need to evaluate
the physical and electrical requirements of the communication device and its performance characteristics, and
conduct qualification testing to verify its suitability for the
desired application. Refer to the nearest S&C Sales Office
for scheduling information. S&C cannot furnish or install
any communication device for which the supplier requires
S&C to offer Tier I (i.e., help desk) support.
If a licensed radio is required for a SCADA interface, the
frequency selection and FCC license application are to be
provided by others. S&C can provide a radio propagation
study as well as a general system review to ensure optimal
application of distribution automation components.
APPLICATION NOTES: The following factors should be
considered when applying IntelliRupter Fault Interrupters:
System voltage restrictions. For adequate power
to be available from the integral power module(s), an
IntelliRupter Fault Interrupter must be applied on a system
that is solidly grounded, uni-grounded, grounded through
a grounding transformer, or resonant-grounded through a
Peterson coil; the base of the IntelliRupter Fault Interrupter
must be grounded; and the line-to-line voltage must be in
the range shown in the table below.
Range, kV, at 60 Hz

Range, kV, at 50 Hz

11.43 through 15.5

9 through 19.2

18.81 through 27

20 through 24

23.8 through 38

29.7 through 38

6S&C Specification Bulletin 766-31

When furnished with the external power supply,


IntelliRupter Fault Interrupter may be applied at line-to-line
voltage as low as 4.13kV, 50/60 Hz.
For application on a completely ungrounded system,the
external power supply must be specified, less integral power
module(s). Integral power modules cannot be applied on
completely ungrounded systems.
Application of surge arresters. Surge arresters are
required on both sides of IntelliRupter Fault Interrupter
to protect it from surges beyond its ratings. IntelliRupter
Fault Interrupter includes provisions for mounting three
user-furnished surge arresters on each side of the device.
Alternately, IntelliRupter Fault Interrupter can be optionally
furnished with MacLean Power Systems Zforce Type ZHP
(Heavy Duty) polymer-housed metal-oxide surge arresters
factory-installed and wired.
SPECIAL WARRANTY PROVISIONS: The standard
warranty contained in sellers standard conditions of sale,
as set forth in Price Sheets 150 and 181, applies to the
IntelliRupter Fault Interrupter and its associated options
except for the control group as applicable. For these
devices the first and second paragraphs of said warranty
are replaced by the following:
(1) General: Seller warrants to immediate purchaser or
end user for a period of 10years from the date of shipment that the equipment delivered, with the exception
of S&C SpeedNet Radio and S&C IntelliCom DA
Mesh Radio, will be of the kind and quality specified
in the contract description and will be free of defects
of workmanship and material. S&C SpeedNet Radio
and S&C IntelliCom DA Mesh Radio are similarly
warranted for a period of two years from the date of
shipment. Should any failure to conform to this warranty appear under proper and normal use within ten
years after the date of shipment (two years for S&C
SpeedNet and S&C IntelliCom DA Mesh Radios)
the seller agrees, upon prompt notification thereof
and confirmation that the equipment has been stored,
installed, operated, and maintained in accordance
with recommendations of the seller and standard
industry practice, to correct the nonconformity either
by repairing any damaged or defective parts of the
equipment or (at sellers option) by shipment of necessary replacement parts. The sellers warranty does not
apply to any equipment that has been disassembled,
repaired, or altered by anyone other than the seller.
This limited warranty is granted only to the immediate
purchaser or, if the equipment is purchased by a third
party for installation in third-party equipment, the end
user of the equipment. The sellers duty to perform
under any warranty may be delayed, at the sellers
sole option, until the seller has been paid in full for
all goods purchased by the immediate purchaser. No
such delay shall extend the warranty period.

S&C IntelliRupter PulseCloser Fault Interrupter


Seller further warrants to the immediate purchaser
or end user that for a period of two years from the
date of shipment the Software will perform substantially in accordance with the then-current release of
specifications if properly used in accordance with the
procedures described in sellers instructions. Sellers
liability regarding any of the Software is expressly
limited to exercising its reasonable efforts in supplying or replacing any media found to be physically
defective or in correcting defects in the Software
during the warranty period. Seller does not warrant
the use of the Software will be uninterrupted or
error-free.
For equipment/services packages, seller warrants,
for a period of one year after commissioning, that the
IntelliRupter Fault Interrupters will provide automatic
fault isolation and system reconfiguration per agreed-upon
service levels. The remedy shall be additional system
analysis and reconfiguration of IntelliTeam SG until the
desired result is achieved.
WARRANTY QUALIFICATIONS: The standard warranty
contained in sellers standard conditions of sale, as set
forth in Price Sheets 150 and 181, does not apply to major
components not of S&C manufacture, such as batteries,
customer-specified remote terminal units and communication devices, as well as hardware, software, resolution
of protocol-related matters, and notification of upgrades
or fixes for those devices. Seller will assign to immediate
purchaser or end user all manufacturers warranties that
apply to such major components.

How to Order
1. Obtain the catalog number of the desired IntelliRupter
Fault Interrupter from the tables on pages 8 and9.
2. Add the suffix of the desired control power source option
from the table on page10.
3. Add the suffix of the desired control group option from
the table on page11.
4. Add the suffix(s) of desired optional features and
special optional features from the tables on page12.
5. If wide-area network capability is desired for the Standard Control Group, Standard Control Group with
Battery Backup, or Universal Control Group, add the suffix
of the desired communication device from the table on
page13.
6. If a mounting pedestal is desired for a substation application, obtain the catalog numbers of the desired mounting
pedestal and anchor bolts from the table on page 14.
Four anchor bolts are required per mounting pedestal.
7. Obtain the catalog number of the desired connectors
from the table on page14. Six connectors are required
per IntelliRupter Fault Interrupter.
8. Obtain the catalog numbers of desired accessories from
the table on page15.

Sellers standard warranty does not apply to any


components not of S&C manufacture that are supplied
and installed by the purchaser, or to the ability of sellers
equipment to work with such components.
Warranty of equipment/services packages is contingent
upon receipt of adequate information on the users distribution system, sufficiently detailed to prepare a technical
analysis. Seller is not liable if an act of nature or parties
beyond S&Cs control negatively impact performance
of equipment/services packages; for example, new
construction which impedes radio communication, or
changes to the distribution system that impact protection
systems, available fault currents, or system loading
characteristics.
END USER LICENSE AGREEMENT: End user is granted
a nontransferable, non-sublicensable, nonexclusive license
to use the LinkStart Connection Management Software,
IntelliLink Remote Setup Software, IntelliTeam
Automatic Restoration Software, Loop Restoration
Software, and/or other Software furnished with IntelliRupter
PulseCloser Fault Interrupter only upon acceptance of all
the terms and conditions of the sellers end user license
agreement set forth in Price Sheet 155.

S&C Specification Bulletin 766-317

S&C IntelliRupter PulseCloser Fault Interrupter


Non-Disconnect Style IntelliRupter PulseCloser Fault Interrupters
Mounting Configuration

Ratings

Standard
Mounting/
Operating
Arrangement

Max

BIL

15.5

110

27

125

ED-856

38

170

ED-855

15.5

110

ED-855

27

125

kV

Amperes, RMS
Cont.

Interr.

Catalog
Number

Upright-Crossarm

630

16 000

248112

12 500

248113

12 500

248114

16 000

248612

12 500

248613

Compact-Crossarm

630

For adequate power to be available from the integral power module(s),

Allowable continuous current capability: 800amperes with a minimum

When applied on a system that is not solidly grounded, uni-grounded,

Includes on-site user training on setup, configuration, and operation

the base of the IntelliRupter Fault Interrupter must be grounded.

grounded through a grounding transformer, or resonant-grounded


through a Peterson coil, total system phase-to-ground capacitance must
be sufficient to reduce the neutral-voltage shift produced by the integral
power module(s). Refer to the nearest S&C Sales Office.
The Standard Mounting arrangement is designated by the erection

drawing (ED) number shown.

8S&C Specification Bulletin 766-31

wind velocity of 2ft./sec.

of IntelliRupter Fault Interrupter. These services apply to first-time orders


only; they can be provided for subsequent orders as indicated in the table
on page 17.

Required External Power Supply, Catalog Number Suffix -P300 or

-P350.

ED-850 for pole mounting, ED-852 for pedestal mounting.

S&C IntelliRupter PulseCloser Fault Interrupter


Disconnect Style IntelliRupter PulseCloser Fault Interrupters
Mounting Configuration

Ratings

Standard
Mounting/
Operating
Arrangement

Max

BIL

15.5

110

27

125

38

170

kV

Amperes, RMS
Cont.

Interr.

Catalog
Number

Upright-Crossarm

ED-857

630

16 000

248122

12 500

248123

12 500

248124

For adequate power to be available from the integral power module(s),

Allowable continuous current capability: 800 amperes with a minimum

When applied on a system that is not solidly grounded, uni-grounded,

Includes on-site user training on setup, configuration, and operation

the base of the IntelliRupter Fault Interrupter must be grounded.

grounded through a grounding transformer, or resonant-grounded


through a Peterson coil, total system phase-to-ground capacitance must
be sufficient to reduce the neutral-voltage shift produced by the integral
power module(s). Refer to the nearest S&C Sales Office.
The Standard Mounting arrangement is designated by the erection

wind velocity of 2 ft./sec.

of IntelliRupter Fault Interrupter. These services apply to first-time orders


only; they can be provided for subsequent orders as indicated in the table
on page 17.

ED-851 for pole mounting, ED-853 for pedestal mounting.

drawing (ED) number shown.

S&C Specification Bulletin 766-319

S&C IntelliRupter PulseCloser Fault Interrupter


Control Power SourceOne Control Power Source Must Be Specified
Item

One Integral Power Module Fed from One Phase on


One Side

One Integral Power Module Fed from One Phase on


One Side Plus External Power Supply
Integral Power Modules for Use on
60-Hz Systems

Two Integral Power Modules Fed from a Different Phase


on Both Sides

Two Integral Power Modules Fed from a Different Phase


on Both Sides Plus External Power Supply
External Power Supply Only

One Integral Power Module Fed from One Phase on


One Side

One Integral Power Module Fed from One Phase on


One Side Plus External Power Supply

Integral Power Modules for Use on


50-Hz Systems
Two Integral Power Modules Fed from a Different Phase
on Both Sides

Two Integral Power Modules Fed from a Different Phase


on Both Sides Plus External Power Supply

External Power Supply Only


Accepts 90- to 259-Vac, 50/60-Hz primary source input; accepts

90- to 259-Vac, 50/60-Hz or 19- to 60-Vdc or 100- to 360-Vdc


secondary source input.

10S&C Specification Bulletin 766-31

Voltage Range, kV LL

Suffix to be Added
to Catalog Number

11.4315.5

-P162

18.8127

-P163

23.838.0

-P165

11.4315.5

-P362

18.8127

-P363

23.838.0

-P365

11.4315.5

-P262

18.8127

-P263

23.838.0

-P265

11.4315.5

-P462

18.8127

-P463

23.838.0

-P465

-P300

912

-P151

1419.2

-P152

2024

-P153

23.033.0

-P154

912

-P351

1419.2

-P352

2024

-P353

23.033.0

-P354

912

-P251

1419.2

-P252

2024

-P253

23.033.0

-P254

912

-P451

1419.2

-P452

2024

-P453

23.033.0

-P454

-P350

S&C IntelliRupter PulseCloser Fault Interrupter


Control GroupsOne Control Group Must Be Specified
Suffix to be Added
to Catalog Number

Item

Standard Control GroupFor IntelliTeamSG Automatic Restoration, automatic source transfer, automatic loop restoration,
SCADA, and stand-alone (non-communicating) applications. Includes IntelliTeamSG Bronze Level Software. Optional
IntelliTeamSG Silver Level Software provides suitability for basic closed-loop applications. Optional IntelliTeamSG Gold Level
Software provides suitability for basic closed-loop applications and applications on systems with three or more sources.
No batteries are required for stand-alone applications and application with operating times of 30 seconds or less; ac line
voltage must be available on the side of the IntelliRupter Fault Interrupter with the integral power module or control power must
be available from the external power supply, if furnished.

-C0

Specify communication device, if required for the application, from Communication Devices for IntelliTeamSG, IntelliTeamII,
Automatic Source Transfer, and SCADA Applications table on page13. All team devices must be furnished with the same type
of communication device.
IntelliTeam Designer Configuration and License Management Software is required to activate IntelliTeamSG Software
Standard Control Group with Battery BackupIdentical to the Standard Control Group but additionally includes batteries
that support operation for a minimum of four hours after loss of ac line voltage on both sides of IntelliRupter Fault Interrupter,
permitting extended dead-line switching.
Specify communication device, if required for the application, from Communication Devices for IntelliTeamSG, IntelliTeamII,
Automatic Source Transfer, and SCADA Applications table on page 13. All team devices must be furnished with the same type
of communication device.

-C1

IntelliTeam Designer Configuration and License Management Software is required to activate IntelliTeam SG Software
Universal Control GroupIdentical to the Standard Control Group with Battery Backup. Includes either IntelliTeam SG Gold
Level Software and IntelliTeam Designer Configuration and License Management Software or IntelliTeam II Software License,
as specified.
For IntelliTeam SG Automatic Restoration System specify one IntelliTeam Design Slot part number 008-007006-01 and one
IntelliRupter PulseCloser Fault Interrupter Gold License part number 008-007101-01. This license requires an IntelliTeam SG
qualified communication device from the communication device options listed on page 13.
For IntelliTeam II Automatic Restoration System specify one IntelliTeam Design Slot part number 008-007006-03 and
one IntelliRupter PulseCloser Fault Interrupter IntelliTeam II License part number 008-007106-01. This license requires an
IntelliTeam II qualified communication device from the communication device options listed on page 13.

-C7

When ordering enter the selected licenses as separate line items as included in the above and specify communication device,
if required for the application, from Communication Devices for IntelliTeam SG, IntelliTeam II, Automatic Source Transfer, and
SCADA Applications table on page 12. All team devices must be furnished with the same type of communication device

The 008-007106-01 license should not to be confused with IntelliTeam

SG Automatic Restoration System operating in IntelliTeam II Mode.


IntelliTeam SG Automatic Restoration System operating in IntelliTeam II
Mode requires an IntelliTeam SG qualified communication device.

S&C Specification Bulletin 766-3111

S&C IntelliRupter PulseCloser Fault Interrupter


Optional Features
Suffix to be Added
to Catalog Number

Item

Bracket-Mounted AntennaBracket extends


four feet (1219 mm) horizontally from the
bottom of IntelliRupter Fault Interrupter base.
Can be mounted on either side of the base

Includes 900-MHz, 3-dBd gain, omnidirectional 25-inch (635-mm) fiberglass


antenna with female N-Type connector, coax cable, and mounting hardware

-B1

Includes 900-MHz, 9-dBd gain, directional Yagi antenna with female N-Type
connector, coax cable, and mounting hardware

-B2

Bracket only, suitable for mounting a variety of user-furnished antennas.


Includes coax cable with male N-Type connector and mounting hardware

-B3

Includes OA-24-2, 2.4-GHz, 2-dBi Gain, Omnidirectional Antenna

-B12

Includes OA-24-10, 2.400- to 2.484-GHz, 10-dBi Gain, Omnidirectional


Antenna

-B13

Includes OA-50-10, 4.9- to 5.8-GHz, 10-dBi Gain, Omnidirectional Antenna

-B14

Includes PA-50-21, 4.9- to 5.8-GHz, 23-dBi Gain, Panel Antenna (21-dBi Gain
at 4.9 to 5.1 GHz), with Azimuth/Elevation Adjustable Mount

-B16

Includes PA-Dual-24-9, 2.24- to 2.483-GHz (9-dBi Gain), and 5.7- to 5.9-GHz


(14-dBi Gain), Two-Port Dual Band Panel Antenna

-B17

International CratingWood products used in packaging are either hardwood or certified by the wood supplier
as being heat treated (kiln dried) to a core temperature of 133F (56C) for a minimum of 30 minutes

MacLean Power Systems Zforce Type ZHP


(Heavy Duty) Polymer-Housed Metal-Oxide
Surge ArrestersFactory installed and wired
on one side of IntelliRupter Fault Interrupter.
Arresters include insulated mounting brackets
and integral ground-lead disconnects.
Arresters are solidly grounded to IntelliRupter
Fault Interrupter base; a separate ground
strap between arresters is not needed

MacLean Power Systems Zforce Type


ZHP (Heavy Duty) Polymer-Housed MetalOxide Surge ArrestersFactory installed
and wired on both sides of IntelliRupter
Fault Interrupter. Arresters include insulated
mounting brackets and integral ground-lead
disconnects. Arresters are solidly grounded
to IntelliRupter Fault Interrupter base; a
separate ground strap between arresters is
not needed

3 kV, 2.55 kV MCOV

-M9

6 kV, 5.1 kV MCOV

-M10

9 kV, 7.65 kV MCOV

-M1

10 kV, 8.4 kV MCOV

-M2

12 kV, 10.2 kV MCOV

-M3

15 kV, 12.7 kV MCOV

-M4

18 kV, 15.3 kV MCOV

-M5

21 kV, 17.0 kV MCOV

-M6

24 kV, 19.5 kV MCOV

-M7

27 kV, 22.0 kV MCOV

-M8

3 kV, 2.55 kV MCOV

-N9

6 kV, 5.1 kV MCOV

-N10

9 kV, 7.65 kV MCOV

-N1

10 kV, 8.4 kV MCOV

-N2

12 kV, 10.2 kV MCOV

-N3

15 kV, 12.7 kV MCOV

-N4

18 kV, 15.3 kV MCOV

-N5

21 kV, 17.0 kV MCOV

-N6

24 kV, 19.5 kV MCOV

-N7

27 kV, 22.0 kV MCOV

-N8

30 kV, 24.0 kV MCOV

-N11

36 kV, 29.0 kV MCOV

-N12

Ten-Year IntelliRupter Fault Interrupter WarrantyIn lieu of standard two-year warranty. Matches standard ten-year warranty
for control groups
Wildlife Protection

-L71

-T1

For Non-Disconnect Style IntelliRupter Fault Interrupter

-W1

For Disconnect Style IntelliRupter Fault Interrupter

-W2

15.5-kV IntelliRupter Fault Interrupter furnished with interrupters tested and certified to meet 27 kV
A whip antenna is not provided when this option is specified. If a whip

antenna is needed for testing or temporary use, specify Catalog Number


904-000071-00.

-Z3

Use only with Option Suffix -R201.


MCOV=Maximum Continuous Operating Voltage, RMS. MCOV must

1.2 actual line-to-ground voltage, RMS.

Special Optional Feature


Item

Reversed Colors for Interrupter Open/Closed Indicators and Open/Close/Ready Lever (green for closed, red for open)

12S&C Specification Bulletin 766-31

Suffix to be Added
to Catalog Number

-F2

S&C IntelliRupter PulseCloser Fault Interrupter


Communication Devices for IntelliTeam SG, IntelliTeam II, Automatic Source Transfer,
and SCADA Applications
Suffix to be Added
to Catalog Number

Item

Communication Devices Suitable for IntelliTeam SG, IntelliTeam II, Automatic Source Transfer, and SCADA Applications
Factory-Installed and Wired S&C SpeedNet Radio, providing high-speed network communication via DNP 3.0 protocol, and
900-MHz, 5-dBi gain antenna with male N-Type connector

-R80

Factory-Installed and Wired IntelliCom DA Mesh Radio

-R201

Provision Only for RuggedCom RS900 Single-Mode ST Connectors

-R139

Provision Only for RuggedCom RS900 Multi-Mode ST Connectors

-R140

Communication Device Suitable for IntelliTeam II, Automatic Source Transfer, and SCADA Applications Only
Factory-Installed and Wired UtiliNet Series IV IWR Radio, providing communication via DNP 3.0 protocol, and 900-MHz, 5-dBi
gain antenna with male N-Type connector

-R67

Communication Devices Suitable for Automatic Source Transfer and SCADA Applications Only
Factory-Installed and Wired Single-Mode Dymec 5843SHRT Fiber-Optic Modem

-R44

Factory-Installed and Wired Multi-Mode Dymec 5843HRT Fiber-Optic Modem

-R45

Provision Only for Single-Mode Dymec 5843SHRT Fiber-Optic Modem

-R42

Provision Only for Multi-Mode Dymec 5843HRT Fiber-Optic Modem

-R43

Factory-Installed and Wired MDS SD9 Radio

Factory-Installed and Wired MDS TransNET 900 Transceiver and 900-MHz, 5-dBi gain antenna with male N-Type
connector

-R18

Factory-Installed and Wired MDS TransNET 900 Transceiver with Diagnostics and 900-MHz, 5-dBi gain antenna with male
N-Type connector

-R19


These are the only wide-area network communication devices

approved for use with IntelliRupter Fault Interrupter. For other communication devices, refer to the nearest S&C Sales Office.

Antenna mounts directly to IntelliRupter Fault Interrupter base. If a

bracket-mounted antenna is desired instead, see the Optional Features


table on page12.

A female N-Type antenna connector, with integral surge suppressor, is

mounted to IntelliRupter Fault Interrupter base.

A Single-Mode Mating Connector and Termination Kit or a Single-

Mode Liquid-Tight Cable Assembly must be specified. See Fiber-Optic


Connection Accessories table on page 14.


A Multi-Mode Mating Connector and Termination Kit or a Multi-

Mode Liquid-Tight Cable Assembly must be specified. See Fiber-Optic


Connection Accessories table on page 14.

Specify the appropriate catalog number suffix based on the frequency

band range and application for the radio, from the following table. For
example, for a 928- to 960-MHz MDS SD9 Radio for Ethernet and serial
application, specify Catalog Number Suffix -R216CL.
Frequency Band Range, MHz

Application

Suffix to be Added
to Catalog Number

820 to 870

-R216AK

928 to 960

-R216CK

928 to 960, 50-kHz Channel

-R216DK

880 to 915
880 to 915, 50-kHz Channel

-R216EK
Serial

-R216FK

850 to 860 / 926 to 936,


Transmit Low

-R216GK

850 to 860 / 926 to 936,


Transmit High

-R216HK

Frequency Band Range, MHz

Application

Suffix to be Added
to Catalog Number

820 to 870

-R216AL

928 to 960

-R216CL

928 to 960, 50-kHz Channel

-R216DL

880 to 915
880 to 915, 50-kHz Channel

Ethernet
and Serial

-R216EL
-R216FL

850 to 860 / 926 to 936,


Transmit Low

-R216GL

850 to 860 / 926 to 936,


Transmit High

-R216HL

820 to 870

-R216AM

928 to 960

-R216CM

928 to 960, 50-kHz Channel

-R216DM

880 to 915
880 to 915, 50-kHz Channel

9710
Emulation

-R216EM
-R216FM

850 to 860 / 926 to 936,


Transmit Low

-R216GM

850 to 860 / 926 to 936,


Transmit High

-R216HM

S&C Specification Bulletin 766-3113

S&C IntelliRupter PulseCloser Fault Interrupter


Fiber-Optic Connection Accessories
Item

Catalog Number

Single-Mode Mating Connector and Termination KitIncludes connector hood, inserts, and fiber termination components

SD-6607

Multi-Mode Mating Connector and Termination KitIncludes connector hood, inserts, and fiber termination components

SD-6608

48-Foot Single-Mode Liquid-Tight Cable AssemblyIncludes pre-terminated mating connector on one end and ST connector
on other end

SD-6609

48-Foot Multi-Mode Liquid-Tight Cable AssemblyIncludes pre-terminated mating connector on one end and ST connector
on other end

SD-6610

Requires Harting Crimping Tool for Fiber-Optic Connector (glass fibre)

SW 6.5, 4.95, and 3.0 mm, Catalog Number 20 99 000 1033.


Custom-length cable assemblies can be furnished. Refer to the

nearest S&C Sales Office for more information.

Mounting Pedestals and Anchor BoltsFor Substation Applications


Item

Catalog Number

Mounting Pedestal88 (203 mm203 mm) galvanized steel tube construction

9.5 feet (2896 mm)

SDA-4813-1

12 feet (3658 mm)

SDA-4813-2
S-81365-1

Anchor Bolt138 (25 mm1118 mm). Four required per mounting pedestal
Galvanized steel. Furnished with two hex nuts and two flat washers to

facilitate leveling the mounting pedestal.

Connectors
Illustration

Description

Accommodating Conductor

Catalog Number

Bronze Body, Tin Plated, Single 132


Galvanized Steel Bolt

No. 2 solid (33.6 mm2) through 500 kc mil


(335 mm2) stranded copper or aluminum

4740R1

Aluminum-Alloy Body, Tin Plated,


Two 132 Galvanized Steel Bolts

No. 2 solid (33.6 mm2) through 500 kc mil


(335 mm2) stranded copper or aluminum

4741R2

Provision only for compression connectors. Includes two 132 Galvanized Steel Bolts

Connector suitable for hookstick handling.

Four-bolt compression connectors cannot be used with Wildlife


Protection, Catalog Number Suffix -W1 or -W2.

14S&C Specification Bulletin 766-31

4581

S&C IntelliRupter PulseCloser Fault Interrupter


Accessories
Description

Catalog Number

Battery Charger Output HarnessFor connecting battery pack to an 800-mA, current-limited 12-Vdc lead-acid
battery charger

007-001551-01

Module Handling FittingFor field installation and removal of protection and control module, and communication module,
in IntelliRupter Fault Interrupter base. Attaches to hookstick with universal fitting. Includes prong for operating IntelliRupter
Fault Interrupter levers

4450

Module Stub HandleFor installation and removal of protection and control module, and communication module, in
IntelliRupter Fault Interrupter basein users service center or lab. When permitted by utility operating practice, this handle
can be used by a gloved individual to install and remove modules in the field

4435

Pre-Configured Laptop Computer14-inch Dell computer with 2-MB RAM, 80-GB hard drive, and factory-loaded IntelliLink
Setup Software

7031-986

WiFi Tester. Simulates connection to communication module. Confirms users laptop computer is properly configured to
establish secure WiFi connection to IntelliRupter Fault Interrupter. Also demonstrates use of WiFi security keys. For indoor use
only, in users service center or lab

908-000961-01

Detailed Instruction ManualBinder containing printed copies of all IntelliRupter Fault Interrupter instruction sheets, erection
drawings, and reference drawings (detailing, for example, installation of optional features such as surge arresters and bracketmounted antennas)

RD-6949

Spare Protection and Control Module

SDA-4540

Spare Communication ModuleLess Battery Pack and Radio

SDA-4554-1

Spare 12-Vdc, 8-Ampere-Hour Battery Pack for Communication Module

SDA-4605

SEL AutoRANGER Model AR8-OH Faulted Circuit Indicators, Set of ThreeDetects and provides visible indication
of fault current passage. User-installed on each phase conductor. Eight-hour reset time

SDA-4625

Docking StationPowers protection and control module, and communication module, removed from IntelliRupter Fault
Interrupter base. Permits uploading and downloading of configuration settings, plus programming of radio and charging of radio
batteries, as applicable, in users service center or lab

SDA-4650R2

Indoor Power SupplyAttaches to external power supply connector in base. Powers protection and control module, and
communication module, for pre-installation uploading and downloading of configuration settings, plus radio programming
and battery charging, as applicable. For indoor use only, in users service center or lab. Input voltage range is 88264 Vac,
50/60 Hz

TA-3221

External Power SupplyFor use with a pedestal-mounted IntelliRupter Fault Interrupter in a substation. Enables use of
preferred and alternate control power sources, and can be installed in combination with integral power modules. Preferred
source input voltage range is 90159 Vac, 50/60 Hz, alternate source input voltage range is 90159 Vac, 50/60 Hz, 1960 Vdc,
or 100360 Vdc

SDA-4910

900-MHz 5-dBi Gain Antenna, N-Type Male Connector

904-000071-00

LinkStart Security Dongle

904-002216-01

S&C Specification Bulletin 766-3115

S&C IntelliRupter PulseCloser Fault Interrupter


IntelliRupter PulseCloser Fault Interrupter/Services Packages
Item

Three-Member Team
Four-Member Team
Five-Member Team
15.5-kV IntelliRupter PulseCloser Fault Interrupter/Services Packages
Each package includes Non-Disconnect Style IntelliRupter PulseCloser Fault Interrupters Catalog Number
248112P262C1N4R80W1 or 248112P262C1N4R201W1. Each IntelliRupter Fault Interrupter includes two Integral
Power Modules for use on 11.43kV to 15.5kV, 60Hz systems, Standard Control Group with Battery Backup, with
SpeedNet Radio or IntelliCom DA Mesh Radio, six 15kV Surge Arresters, and Wildlife Protection. One SpeedNet
Extension-Arm-Mounted Repeater Radio or IntelliCom WAN Mesh Radio is also included. Services furnished
include communication site survey, IntelliTeamSG factory acceptance testing, IntelliRupter Fault Interrupter training,
IntelliTeamSG training, and IntelliTeam SG commissioning

Six-Member Team
Seven-Member Team
Eight-Member Team
Nine-Member Team
Ten-Member Team
Eleven-Member Team
Twelve-Member Team
Three-Member Team
Four-Member Team
Five-Member Team

25-kV IntelliRupter PulseCloser Fault Interrupter/Service Packages


Each package includes Non-Disconnect Style IntelliRupter PulseCloser Fault Interrupters Catalog Number
248113P263C1N8R80W1 or 248113P263C1N8R201W1. Each IntelliRupter Fault Interrupter includes two
Integral Power Modules for use on 18.81kV to 27kV, 60Hz systems, Standard Control Group with Battery Backup,
with SpeedNet Radio or IntelliCom DA Mesh Radio, six 27kV Surge Arresters, and Wildlife Protection. One SpeedNet
Extension-Arm-Mounted Repeater Radio or IntelliCom WAN Mesh Radio is also included. Services furnished
include communication site survey, IntelliTeam SG factory acceptance testing, IntelliRupter Fault Interrupter training,
IntelliTeamSG training, and IntelliTeam SG commissioning

Six-Member Team
Seven-Member Team
Eight-Member Team
Nine-Member Team
Ten-Member Team
Eleven-Member Team
Twelve-Member Team
Three-Member Team
Four-Member Team
Five-Member Team

38-kV IntelliRupter PulseCloser Fault Interrupter/Service Packages


Each package includes Non-Disconnect Style IntelliRupter PulseCloser Fault Interrupters Catalog Number
248114P265C1N12R80W1 or 248114P265C1N12R201W1. Each IntelliRupter Fault Interrupter includes two
Integral Power Modules for use on 23.8-kV to 38-kV, 60Hz systems, Standard Control Group with Battery Backup,
with SpeedNet Radio or IntelliCom DA Mesh Radio, six 36kV Surge Arresters, and Wildlife Protection. One SpeedNet
Extension-Arm-Mounted Repeater Radio or IntelliCom WAN Mesh Radio is also included. Services furnished
include communication site survey, IntelliTeamSG factory acceptance testing, IntelliRupter Fault Interrupter training,
IntelliTeamSG training, and IntelliTeamSG commissioning

Six-Member Team
Seven-Member Team
Eight-Member Team
Nine-Member Team
Ten-Member Team
Eleven-Member Team
Twelve-Member Team

16S&C Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter


IntelliRupter Fault Interrupter Services Packages
Item

Catalog Number

Communication Site Survey. Field testing to confirm that user-proposed IntelliRupter Fault Interrupter locations will provide
acceptable communication between team members and head-end SCADA radio, if applicable. User should make available their
engineer/technician responsible for the project

AS100

IntelliTeam SG Training. On-site training on functioning of IntelliTeam SG. Includes operations and engineering training sessions

AS101

IntelliTeam SG Commissioning. Ensures that IntelliRupter Fault Interrupters have been set up correctly and IntelliTeamSG is
ready to be put into service

AS102

IntelliTeam SG SCADA Integration. Includes review of users SCADA system, development of DNP points lists, coordination with
the users SCADA supplier, and review of SCADA database

AS103

IntelliTeam SG Factory Acceptance Testing. Factory testing ensures that all information required for successful IntelliTeamSG
implementation is gathered and understood prior to commissioning. Provides insight on how IntelliTeamSG will work on the
users system. User must travel to Chicago to witness the testing

AS104

IntelliTeam SG Monitoring. Ongoing remote monitoring ensures that IntelliTeamSG operation meets agreed-upon service levels.
Minimum monitoring period is six months

AS105

IntelliRupter Fault Interrupter Maintenance. Includes inspection, testing, and battery replacement on a three-year interval

AS106

IntelliRupter Fault Interrupter Project and Construction Management. Includes IntelliRupter Fault Interrupter installation,
construction oversight, and EPC projects

AS107

Overcurrent Protective Device Coordination Study. Determination of appropriately rated protective devices and their settings,
including those of IntelliRupter Fault Interrupters. Proper coordination minimizes the impact of short-circuits, by isolating faults as
quickly as possible, while maintaining power to the rest of the system

AS108

IntelliTeam SG Device Settings Determination. Determination of these settings is essential to the successful implementation of
IntelliTeamSG, and must be documented prior to factory acceptance testing and commissioning

AS109

Loop Restoration Training. Covers setup, configuration, and operation of IntelliRupter Fault Interrupters in a loop application
comprised of normally-closed IntelliRupter Fault Interrupters or conventional reclosers, with a normally-open IntelliRupter Fault
Interrupter switching point

AS110

IntelliRupter Fault Interrupter Training. Covers IntelliLink Setup Software; configuring IntelliRupter Fault Interrupter for use in an
IntelliTeamSG, source-transfer, or loop restoration system, as appropriate; use of security keys; and operation

AS111

IntelliRupter Fault Interrupter Secondary Injection Testing. Validates settings, functions, and logic of IntelliRupter Fault
Interrupter protection and control module using Omicron testing equipment

AS112

S&C Specification Bulletin 766-3117

S&C IntelliRupter PulseCloser Fault Interrupter


IntelliRupter Fault Interrupter Ratings
Voltage Ratings
IntelliRupter Fault Interrupter Maximum Voltage Rating, kV

Voltage Rating

15.5

27

38

Lightning Impulse Withstand Voltage, kV

110

125

170

Power Frequency Withstand Voltage, Dry, kV

50

60

70

Power Frequency Withstand Voltage, Wet, kV

45

50

60

Current Ratings
IntelliRupter Fault Interrupter Maximum Voltage Rating, kV

Current Rating

15.5

27

38

Continuous Current, Amperes

630

630

630

Maximum Continuous Current with 2 ft./sec. Minimum Wind Velocity,


Amperes

800

800

800

Short-Circuit Current, Symmetrical, Amperes

16 000

12 500

12 500

Making Current, Amperes, Asymmetrical Peak

31 000

31 000

31 000

Making Current, Amperes, Asymmetrical, RMS

21 600

21 600

21 600

Loop Switching Current, Amperes

2 400

2 400

2 400

Cable Charging Current, Amperes

10

25

40

Number of Operations
IntelliRupter Fault Interrupter Maximum Voltage Rating, kV

Operations Rating

15.5

27

38

1520

44

44

44

4555

56

56

56

90100

16

16

16

Number of Load Switching Operations, C-O

10

10

10

Number of Line Charging Operations, C-O

20

20

20

Number of Cable Charging Operations, C-O

20

20

20

10 000

10 000

10 000

Number of Operations at Percent of Interrupting


Rating

Number of Mechanical Operations without Maintenance,


PulseClosing Technology Disabled

18S&C Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter


Other Ratings
IntelliRupter Fault Interrupter Maximum Voltage Rating, kV

Rating

15.5

27

38

-40 to +40

-40 to +40

-40 to +40

Voltage Sensor Accuracy, %

0.5

0.5

0.5

Current Sensor Accuracy, %

0.5

0.5

0.5

Time-Current Coordination Curve Accuracy, %

2.0

2.0

2.0

Ice Breaking Rating, Inch (mm)

.75 (19)

.75 (19)

.75 (19)

Radio Noise Limit, FCC Class

Operating Temperature Range, C

IntelliRupter Fault Interrupter Certified Test Abstracts and Engineering Test Reports
Description

Description

Standard

CERT-696

Temperature Rise

IEEE C37.60-2003, IEC 62271-111:2005

CERT-697

Dielectric Ratings, 15.5 and 27 kV

IEEE C37.60-2003, IEC 62271-111:2005,


IEEE C37.34-1994, IEEE 1291-1993,
ANSI C93.1-1999

CERT-698

Symmetrical Interrupting Ratings, 15.5 kV, without PulseClosing

IEEE C37.60-2003, IEC 62271-111:2005

CERT-699

Switching Current Ratings

IEEE C37.60-2003, IEC 62271-111:2005

CERT-700

Symmetrical Interrupting Ratings, 15.5 and 27 kV, with PulseClosing

IEEE C37.60-2003, IEC 62271-111:2005

CERT-701

Mechanical Endurance Ratings

IEEE C37.60-2003, IEC 62271-111:2005

CERT-705

Loop Switching Capability

IEEE C37.60-2003, IEC 62271-111:2005

CERT-706

Extreme Ambient Temperature

IEEE C37.60-2003

CERT-719

Surge Immunity Ratings

IEEE C37.60-2003, IEEE C37.90.1-1989,


IEEE C37.90.2-2004, IEC 61000-4-2, -4,
FCC Part 15, Subpart B, Section 15.109b

CERT-722

Lightning Arrester Grounding, 15 kV

IEEE C37.60-2003

CERT-766

Voltage and Current Metering Accuracy

IEEE C37.60-2003, IEEE C57.13

CERT-772

Symmetrical Interrupting Ratings, 15.5 kV, with PulseClosing

IEEE C37.60-2003, IEC 62271-111:2005

CERT-896

Symmetrical Interrupting Ratings, 38 kV

IEEE C37.60-2012, IEC 62271-111:2012-09

CERT-897

Temperature Rise Ratings, 38 kV

IEEE C37.60-2012, IEC 62271-111:2012-09

CERT-898

Dielectric Ratings, 38 kV

IEEE C37.60-2012, IEC 62271-111:2012-09

CERT-900

Mechanical Endurance Ratings, 38 kV

IEEE C37.60-2012, IEC 62271-111:2012-09

TR 13737-A1

Instantaneous Time-Current Curve Determination, 27 kV

IEEE C37.60-2003

TR 14893

Short Circuit/Short Time Withstand Current, 15 kV

IEEE 1247-2005

S&C Specification Bulletin 766-3119

S&C IntelliRupter PulseCloser Fault Interrupter


Terminal Pad Detail 15-kV and 27-kV Non-Disconnect Style IntelliRupter Fault Interrupter
(shown without optional Wildlife Protection, Catalog Number Suffix -W1)

Dimensions in inches (mm)


15
(387)

8
(213)

(16) TYP.

1 (38) TYP.
1 (44) TYP.

Terminal Pad Detail 38-kV Non-Disconnect Style IntelliRupter Fault Interrupter


(shown without optional Wildlife Protection, Catalog Number Suffix -W1)
15964 (385)
4716
(113)

1
(44)

(6)

3
(76)

(16)
1
(44)

20
(530)

(16)
3
(76)
1
(44)

20S&C Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter


Terminal Pad Detail 15-kV and 27-kV Disconnect Style IntelliRupter Fault Interrupter
(shown without optional Wildlife Protection, Catalog Number Suffix -W2)

Dimensions in inches (mm)


23
(591)

15
(387)

(19)

(16)

1 (38)
2 (51)

1 (44)
1 (44)

Terminal Pad Detail 38-kV Disconnect Style IntelliRupter Fault Interrupter


(shown without optional Wildlife Protection, Catalog Number Suffix -W2)

16
(406)

15
(381)

12
(305)

S&C Specification Bulletin 766-3121

S&C IntelliRupter PulseCloser Fault Interrupter


Non-Disconnect Style 15-kV and 27-kV IntelliRupter Fault Interrupter
Upright-Crossarm Mounting Configuration
ED-850, for pole mounting, is illustrated; ED-852, for pedestal mounting, is similar
(top and front views shown with optional Wildlife Protection, Catalog Number Suffix -W1)

Dimensions in inches (mm)


93
(2381)

22
(581)

11
(298)

49
(1254)

11
(298)
16
(410)

4 (102) TYP.

TOP VIEW

24
(610)
6116
(154)

24
(610)

32
(813)
8
(210)

8
(210)

2 (51) TYP.

FRONT VIEW

22S&C Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter

Ratings
kV
Max

15.5

Amperes, RMS
BIL

Continuous

Catalog Number

Interrupting

110

16 000

248112

12 500

248113

630
27

Net Wt.,
Assembled,
Lbs. (kg)

835 (378)

125

800 amperes with a minimum wind velocity of 2 ft./sec.

(6)
(6)
21
(543)

12
(308)

42
(1080)
29
(749)

SIDE VIEW

S&C Specification Bulletin 766-3123

S&C IntelliRupter PulseCloser Fault Interrupter


Non-Disconnect Style 38-kV IntelliRupter Fault Interrupter
Upright-Crossarm Mounting Configuration, ED-856
(top and front views shown with optional Wildlife Protection, Catalog Number Suffix -W1)

Dimensions in inches (mm)


94
94
(2388)
(2388)

2
(51)

.250
(6)
(6)

15
15
(381)
(381)

10
10
(254)
10
(254)

8
8
(203)
(203)

6116
(154)
9
(229)

24
(610)

TOP VIEW

32
(813)

48
(1219)
2
(51)

9
(229)

(6)

5
(127)

FRONT VIEW
24S&C Specification Bulletin 766-31

2
(51)

S&C IntelliRupter PulseCloser Fault Interrupter

Ratings
kV
Max

38

Amperes, RMS
BIL

Continuous

Interrupting

170

630

12 500

Catalog Number

Net Wt.,
Assembled,
Lbs. (kg)

248114

890 (403)

800 amperes with a minimum wind velocity of 2 ft./sec.

3
(76)
1
(44)

(16)

21
(533)

(16)
36
(914)

3
(76)

1
(44)

13
(330)

SIDE VIEW

S&C Specification Bulletin 766-3125

S&C IntelliRupter PulseCloser Fault Interrupter


Non-Disconnect Style 15-kV and 25-kV IntelliRupter Fault Interrupter
Compact-Crossarm Mounting Configuration, ED-855
(top and front views shown with optional Wildlife Protection, Catalog Number Suffix -W1)
Dimensions in inches (mm)
10
(260)

PEDESTAL ANGLES (2)


44
(9.5 102102)

PEDESTAL

TOP VIEW

51
(1314)

18
(457)

18
(457)

7
(200)
4716
(113)

2 (70)

FRONT VIEW

26S&C Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter

Ratings
kV
Max

Amperes, RMS
BIL

15.5

Continuous

Catalog Number

Interrupting

110

16 000

248612

12 500

248613

630
27

Net Wt.,
Assembled,
Lbs. (kg)

700 (317)

125

800 amperes with a minimum wind velocity of 2 ft./sec.

49
(1257)
221516
(582)

20
(520)

6
(156)

15
(387)

1
(29)

19
(482)

1
(44)

9
(248)

1
(35)

401316
(1036)

43
(1104)
14
(355)

531516
(1369)

20
(508)

SIDE VIEW

S&C Specification Bulletin 766-3127

S&C IntelliRupter PulseCloser Fault Interrupter


Disconnect Style 15-kV and 27-kV IntelliRupter Fault Interrupter
Upright-Crossarm Mounting Configuration
ED-851, for pole-mounting, is illustrated; ED-853, for pedestal mounting, is similar
(top and front views shown with optional Wildlife Protection, Catalog Number Suffix -W2)

Dimensions in inches (mm)


97
(2477)

22
(581)

11
(298)
66
(1689)

33
(841)

7 (191)

4 (102) TYP.

TOP VIEW

9
(251)

24
(610)

24
(610)

32
(813)

8
(210)

8
(210)

2 (51) TYP.

FRONT VIEW

28S&C Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter

Ratings
kV
Max

15.5

Amperes, RMS
BIL

Continuous

110

Catalog Number

Interrupting

16 000

248122

12 500

248123

630
27

Net Wt.,
Assembled,
Lbs. (kg)

1033 (467)

125

800 amperes with a minimum wind velocity of 2 ft./sec.

316 (5)

(6)

43
(1111)

12
(308)

20
(521)

29
(749)

SIDE VIEW

S&C Specification Bulletin 766-3129

S&C IntelliRupter PulseCloser Fault Interrupter


Disconnect Style 38-kV IntelliRupter Fault Interrupter
Upright-Crossarm Mounting Configuration, ED-857
(top and front views shown with optional Wildlife Protection, Catalog Number Suffix -W2)
Dimensions in inches (mm)
94
(2388)

2
(51)

(6)

10

(254)
12
(305)

27

(686)
14
(356)

2
(51)

(102)

TOP VIEW
48
24
6116
(154)

32
(813)

(1219)

(610)

(229)

(51)

18

(457)

FRONT VIEW
30S&C Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter

Ratings
kV
Max

38

Amperes, RMS
BIL

Continuous

Interrupting

170

630

12 500

Catalog Number

Net Wt.,
Assembled,
Lbs. (kg)

248124

1063 (482)

800 amperes with a minimum wind velocity of 2 ft./sec.

15
(381)

1
(44)
4
(76)

(16)

7
(178)

(16)
1
(44)

3
(76)

1 (44)

16
(406)

1
(44)
15
(381)

12
(305)

SIDE VIEW

S&C Specification Bulletin 766-3131

S&C IntelliRupter PulseCloser Fault Interrupter


Pole-Saddle

Dimensions in inches (mm)

10
(257)

(22)

2 DIA. (51)

25
(641)

22
(568)

1316 (21)

32S&C Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter


15-kV and 25-kV IntelliRupter Fault Interrupter

Dimension

Description

Dry Arcing
Distance, inches
(mm)

Leakage Distance,
inches (mm)

Leakage at 15 kV,
mm/kV

Leakage at 27 kV,
mm/kV

Integral Power Module

14 (359)

34 (864)

57

32

Interrupter

11 (292)

38 (965)

64

35

Insulator

18 (457)

37 (940)

62

34

Push Rod

15516 (389)

31 (795)

53

29

Dry arcing distance is the shortest distance between the metal sur-

faces separated by the insulator.

Leakage is the distance along the surface of the insulator.

S&C Specification Bulletin 766-3133

S&C IntelliRupter PulseCloser Fault Interrupter


38-kV IntelliRupter Fault Interrupter

Dimensions in inches (mm)

A 18

(457)

Dimension

16
(406)

Description

12
(305)

15
D
(381)

Dry Arcing
Distance, inches (mm)

Leakage Distance,
inches (mm)

Leakage at 38 kV,
mm/kV

Integral Power Module

18 (457)

46 (1178)

31

Interrupter

12 (305)

46 (1178)

31

Insulator

16 (406)

46 (1178)

30

Push Rod

18 (457)

47 (1207)

31


Dry arcing distance is the shortest distance between the metal

surfaces separated by the insulator.

Leakage is the distance along the surface of the insulator.

34S&C Specification Bulletin 766-31

S&C IntelliRupter PulseCloser Fault Interrupter


SDA-4540 Protection and Control Module
Weight 21 lbs.

SDA-4554 Communication Module


Weight 26 lbs. (with battery, less communication device)

Dimensions in inches (mm)

Requirements for Communication Device


Maximum size, including connectors:
9 inches deep, 6 inches wide, 3 inches high
Voltage: 10.515.9 Vdc
Maximum allowable average continuous power:
12 watts over a 10-second interval
Peak transient current: 2 amperes for 500 milliseconds

13
(337)

14
(356)

2364
(52)

132764
(341)

6
(152)

6
(171)

11
(292)

S&C Specification Bulletin 766-3135