TypicalLimitingValuesofSubStationEquipments.
MARCH31,2011 12COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2011/03/31/TYPICALLIMITING
VALUESOFSUBSTATIONEQUIPMENTS/#COMMENTS)
TypicalLimitingValuesofSubStationElectricalEquipments.
1.Transformer/Reactor:
Sr.No.
Equipment/testdata
Permissiblelimits
Reference
Transformeroil
a)BDV
Atthetimeoffirstcharging
600kV(Gap2.5mm)
Minimum
IS1866
DuringO&M
50kV(Gap2.5mm)
Minimum
IS1867
b)Moisturecontent
IS1868
Atthetimeoffirstcharging
15PPM(Max.)
IS1869
DuringO&M
25PPM(Max.)
IS1870
c)Resistivityat90degreeC
0.11012OhmCM(Min.)
IS1871
d)Acidity
0.2mgKOH/gm(Max.)
IS1872
e)IFTat27degreeC
0.018N/M(Min.)
IS1873
f)Tandeltaat90degreeC
0.20(Max.)
IS1874
g)Flashpoint
126Deg.C(Min.)
IS1875
Vibrationlevelforreactors
200Microns(PeaktoPeak)
IS1876
60Microns(Average)
IS1877
C)
Tandeltaforbushingat20Deg.
C
0.007*
IEC137
D)
Capacitanceforbushing
+5%variation
IEC138
E)
IRvalueforwinding
1000MOhmBy5.0/10.0kV
Megger
IEC139
F)
Tandeltaforwindingsat20
Deg.C
0.007*
IEEE/C57.12.90.1980
G)
Contactresistanceofbushing
terminalconnectors
10M.Ohm/Connector
NGC.UK
Recommendations
H)
TurretNeutralCTratioerrors
39
IS2705
A)
B)
2.CircuitBreakers
https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/
1/7
7/13/2015
TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles
Sr.No.
Equipment/testdata
Permissiblelimits
Reference
A)
DewpointofSF6gas
Dewpointvaluesasper
AnnexureII
B)
Dewpointofoperatingair
45Deg.CatATM.Pressure
CBOperatingtimings
400kV220KV
a)Closingtime(Max.)
150MS200MS
b)Triptime(Max.)
25MS35MS
c)Close/triptime,Pole
discrepancy
PhasetoPhase(Max.)
3.33MS3.33MS
Breaktobreak(Max.)ofsame
phase
2.5MS2.5MS
PIRtime
1216MS
Manufacturers
Recommendations
812MS
Manufacturers
Recommendations
812MS
Manufacturers
Recommendations
812MS
Manufacturers
Recommendations
812MS
Manufacturers
Recommendations
812MS
Manufacturers
Recommendations
C)
BHELmake
ABBmake
D)
NGEFmake
M&Gmake
TELKmake
ABBmake(HVDC)
E)
PIRopeningtimepriorto
openingofmaincontacts(ABB,
CGL,NGEFmakeCBs)
5MS(Min.)atratedpressure
Manufacturers
Recommendations
F)
Pirandmaincontactsoverlap
time[BHEL,M&G,ABB
(imported)makeCBs]
6MS(Min.)atratedpressure
Manufacturers
Recommendations
G)
Tandeltaofgradingcapacitors
0.007at20Deg.C
H)
Capacitanceofgrading
capacitors
Within+10%/5%oftherated
value
IEC359
I)
ContactresistanceofCB
150M.Ohm
J)
ContactresistanceofCB
terminalconnector
10M.Ohmperconnector
NGC,UK
recommendations
IRvalue:
1.Phaseearth
1000MOhm(Min.)by5.0/10.0
kVMegger
2.Acrossopencontacts
1000MOhm(Min.)by5.0/10.0
kVMegger
3.Controlcables
50MOhm(Min.)by0.5kV
Megger
Pressureswitchsettings
SF6gaspressureswitches
Within+0.1Barofsetvalue
Operatingairpr.Switches
Within+0.1Barofsetvalue
Operatingoilpr.Switches
Within+0.1Barofsetvalue
BDVofoilusedforMOCB
Atthetimeoffilling
40kVat2.5mmGap(Min.)
Mfgs.Recommendation
DuringO&M
20kVat2.5mmGap.(Min.)
Mfgs.Recommendation
K)
L)
M)
https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/
2/7
7/13/2015
TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles
3.CurrentTransformer
Sr.No.
Equipment/testdata
Permissiblelimits
Reference
IRvalue
1.Primaryearth
1000MOhm(Min.)by5.0/10.0
kVMegger
2.Secondaryearth
50MOhm(Min.)by0.5kV
Megger
3.Controlcables
50MOhm(Min.)by0.5kV
Megger
B)
Tandeltavalue
0.007*at20Deg.C
C)
TerminalConnector
10MOhmperconnector
NGC,UK
Recommendations
D)
CTratioerrors
+3%Protectioncores
IS2705
D)
CTratioerrors
+1%Meteringcores
IS2706
A)
4.CapacitiveVoltage
Sr.No.
Equipment/testdata
Permissiblelimits
Reference
A)
TanDelta
0.007*at20Deg.C
B)
Capacitance
Within+10%/5%oftherated
value
IEC358
Contactresistanceofterminal
connector
10MOhmperconnector
NGC,UK
Recommendations
IRValue
IRValue
1.Primaryearth
1000MOhm(Min.)by5.0/10.0
kVMegger
2.Secondaryearth
50MOhm(Min.)by0.5kV
Megger
3.Controlcables
50MOhm(Min.)by0.5kV
Megger
EMUtankoilparameters
EMUtankoilparameters
a)BDV(Min.)
30kV(Gap.2.5mm)
IS1866
b)Moisturecontent(Max.)
35ppm
do
c)Resistivityat90Deg.C
0.11012Ohm.CM
do
d)Acidity
0.5mgkOH/gm(Max.)
do
e)IFTat27Deg.C
0.018N/M(Min.)
do
f)Tandeltaat90Deg.C
1.0Max.
do
g)Flashpoint
125Deg.C(Min.)
do
F)
CVTvoltageratioerrors
+5%protectioncores
IEEE/C93.1.1990
F)
CVTvoltageratioerrors
+0.5%meteringcores
IEC186
D)
E)
5.Isolators
Sr.No.
Equipment/testdata
Permissiblelimits
Reference
A)
Contactresistance
300MOhm.(Max.)
https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/
3/7
7/13/2015
B)
C)
TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles
Contactresistanceofterminal
connector
10MOhmperconnector
NGC,UK
Recommendations
IRvalue
1.Phaseearth
1000MOhm(Min.)by5.0/10.0
kVMegger
NGC,UK
Recommendations
2.Acrossopencontacts
1000MOhm(Min.)by5.0/10.0
kVMegger
NGC,UK
Recommendations
3.Controlcables
50MOhm(Min.)by0.5kV
Megger
6.SurgeArrester
Sr.No.
Equipment/testdata
Permissiblelimits
Reference
A)
Leakagecurrent
500MAmp.(Resistive)
Hitachi,JapanRecom.
B)
IRvalue
1000MOhm.(Min.)
Hitachi,JapanRecom.
7.Miscellaneous
Sr.No.
Equipment/testdata
Permissiblelimits
Reference
A)
Stationearthresistance
1.0Ohm(Max.)
Thermovisionscanning
Temp.upto15Deg.C(above
ambient)
Normal
Temp.above1550Deg.C
(aboveambient)
Alert
Temp.above50Deg.C(above
ambient)
Tobeimmediatelyattended
TerminalconnectorsContact
resistance
10MOhmperconnector
HGC,UK
Recommendations
IRvalues
1.Allelectricalmotors
50MOhm(Min.)by0.5kV
Megger
2.Controlcables
50MOhm(Min)by0.5kV
Megger
3.Lt.Transformers
100M.Ohm(Min.)byMegger
4.Lt.Switchgears
100MOhm(Min.)by0.5kV
Megger
B)
C)
D)
8.Batteries
Sr.No.
Equipment/testdata
Permissiblelimits
Reference
A)
Terminalconnectorresistance
10MOhm+20%
ANSI/IEEE4501989
B)
Specificgravity
1200+5GM/Lat27Deg.C
TemperatureCorrectionFactorforTanDeltaMeasurement
Sr.No.
OiltemperatureDeg.C
Correctionfactor(K)
https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/
4/7
7/13/2015
TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles
10
0.8
15
0.9
20
1.0
25
1.12
30
1.25
35
1.40
40
1.55
45
1.75
50
1.95
10
55
2.18
11
60
2.42
12
65
2.70
13
70
3.00
IfTanDeltaofbushing/winding/CVT/CTismeasuredatoiltemperatureTDeg.C.ThenTanDeltaat20Deg.Cshallbeasgiven
below:
TanDeltaat20Deg.C=TanDeltaatTempTDeg.C/FactorK.
DewPointLimitsforSF6GasinEHVCircuitBreakers
Sr.No
MakeofC.B
BHEL
M&G
CGL
ABB
NGEF
Dewpointat
ratedPr.Deg.C
Correspondingdewpoint
atAtmospheric.Pr.
Remarks
15
36
Atthetimeof
commissioning
29
DuringO&M
27
Critical
39
Atthetimeof
commissioning
32
DuringO&M
15
35
Atthetimeof
commissioning
10
31
DuringO&M
15
35
Atthetimeof
commissioning
26
DuringO&M
15
36
Atthetimeof
commissioning
29
DuringO&M
Note:DewpointofSF6gasvarieswithpressureatwhichmeasurementiscarriedout.Soitistobeensuredthatifmeasurementis
doneatpressureotherthanatmosphericpressure,itneedstobeconvertedtotheatmosphericpressure.
https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/
5/7
7/13/2015
TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles
About these ads (https://wordpress.com/about-these-ads/)
FILEDUNDERUNCATEGORIZED
AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan13years
experienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectrical
Projects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputy
ManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectrical
EngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeand
helptechnicalenthusiaststofindsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.
12ResponsestoTypicalLimitingValuesofSubStationEquipments.
S.Krishnamurthysays:
July25,2011at6:44am
Veryusefulinformationforallsubstationoperating&maintenancepersonnel.Allequipmentsdataisindicatedinoneplace.Best
wishes.
S.K.MURTHY
Reply
VVNRaosays:
December17,2011at5:13am
Happytoseetheusefulinformation.Ifpossiblepleaseaddrangeandcriticalityoftandeltavaluesandalsotheinternational
standaredsofclearancesinasubstationaswellasinlines.
Reply
vighneshsays:
January3,2012at11:20am
iamunabletolocateIEC139pertainingtoIRvaluesofwindings.WhatshallbercommendedvaluesofIR?
Reply
SsatishShindesays:
May25,2012at5:50am
Thanxforprovidinginstantimportantinformation.
Reply
masoomkhansays:
July4,2012at10:09am
cananyoneprovide380EHVSurgearresterpowerfactor10KVTESTpermissibilelimits
Reply
Tikaramwaghadesays:
July19,2012at1:04pm
Thisparametersisexcellencetoimpruvecomfidenceinequptesting
Reply
DineshSinghsays:
July31,2012at11:04am
Thanksforprovidingimportantlimitinginformation.
Reply
vinodrathodsays:
June10,2013at2:42pm
thanksbosscontinuewithstudy
https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/
6/7
7/13/2015
TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles
Reply
kirankumarGudlasays:
July17,2013at7:25am
Atthetimeoffirstcharging
600kV(Gap2.5mm)Minimum
Correctedis
60kV(Gap2.5mm)Minimum
Reply
siptrunkingprovidersays:
July29,2013at7:12pm
Hi,ithinkthatisawyouvisitedmysitethusicametoreturnthefavor.
Imattemptingtofindthingstoenhancemywebsite!Isupposeitsoktousesomeofyourideas!!
Reply
AnilPrajapatisays:
October8,2013at4:49pm
Itswonderfulandyouhaveexplainedeverythinginverysimplebutinpowerfulandeffectiveway
Er.AnilPrajapati,Jodhpur
Reply
AAAXXXsays:
February4,2015at1:50am
WhenIwillgofortestingof100MVAtransformerturretcttesting,whattestsIhavetotake?andminimumandmaximumvalues
ofthetestswithunit.