GUARANTEED TECHNICAL PARTICULARS

I. CONTROL AND RELAY PANELS


1 Dimensions of the C & R panels
i) Depth
ii) Overall height
iii) Width
2
4

Dimensions of supporting channel


Thickness of the sheet Plates
proposed for use of panels
a) Front (mm)
b) Other sides (mm)

800mm
2250mm
800mm or depending on the
requirement
102mm

3mm
2mm

II. CONTROL SWITCHES FOR CIRCUIT BREAKERS


1 Make
Multimode
2 Type
Descripency type
III. SELECTOR SWITCHES
1 Make
2 Type
3 Type of handle provided
4 No. of positions
5 No. of contacts in each position
i)
Open
ii)
Close
6 Making capacity of contacts. (Amp)
7 Breaking capacity of contacts. (Amp)
IV. INDICATING LAMPS
1 Make
2 Type
3 Operating Voltage
4 Size of lens
5 Wattage of the lamp
6 Colour of lamp
VI. SWITCH BOARD WIRING
1 Insulation of wiring
2 Size of wiring conductor for the
following:
i) C.T. Circuits
ii) P.T. Circuits
iii) D.C. Supply Circuits
iv) A.C. Supply Circuits
v) Other Circuits

Switron
Stay put
Knob
Four

NA
10A @ 440V AC
10A @ 440V AC

JVS
Cluster LED
110 or 220V
30mm
< 0.5W
As per requirement

1100V
2.5sq.mm.
2.5sq.mm.
2.5sq.mm.
2.5sq.mm.
2.5sq.mm.
Contd..2

Page..2
4
5
6

Size of earthing bar for safety


earthing
Type of terminals used in wiring the
panel
Wiring conductor aluminium / copper

25x6mm
Crimped lugs
Copper

VII. INDICATING INSTRUMENTS

1
2
3
4
5
6
7
8

Type of instrument
Applicable IS
Size
Whether magnetically shielded or not
Limits of error in the effective range
Maximum scale length
Whether tropicalised
VA burden :
a) Current coil
b) Potential coil
9 Short time overload capacity
i)
Current coil (VA)
ii)
Potential coil (VA)
1 Power consumption :
0 a) Current coil
b) Potential coil
11 Temperature at which the
instruments are calibrated (C)
1 Description of leaflet reference Nos.
2 submitted
1 Makers name and country
3
9
Type of selector switch
1
2
3
4

Make
Type
Size
VA burden :
a) Current coil
b) Potential coil
Power consumption :
a) Current coil
b) Potential coil

AMMETER & VOLTMETER


Digital
IS 1248
144x144mm
YES
As per IS 1248
Digital
Yes
1VA
2VA
2 times the rated current continuous
2 times the rated voltage continuous
0.5W
1.0W

Submitted
Switron
Stayput type
Energy meter
Secure/L&T
Static
96 sq.mm
0.2VA/Ph.
3VA on aux. Supply
Same as above

Contd..3

Page..3
6
7
8
9

10

I.S. Standard grade of accuracy


Range of dial
Limits of error in effective range
Calibration for :
a) CT ratio
b) PT ratio
Finish
VIII.

IS 13779
6 digit impulse counter
As per IS 13779
1A or 5A
-/110V
Black

ANNUNCIATORS

1
2
3
4
5
6

Make
Type
Particulars of window
Rated voltage (volts)
Power consumption (Watts)
Instantaneous making capacity of
contacts

7
8
9

Breaking Capacity
Overall dimensions of annunciator
Descriptive leaflet number submitted

JVS/Alan
JAV 014
LED type
110/220V DC
Less than 1 Watt per window
5A, 240V, 50Hz. AC; contacts are
provided with 1A glass fuse in series
for protection.
As above
12 window 216(W)x144(H)x 125(D)
Submitted

IX TRANSFORMER DIFFERENTIAL RELAY


1
2
3
4
5
6
7
8
9

10
11
12

Makers Name
Type
Current coil base
Amount of Base
Details of Harmonic Restraint Features
provided
No of steps for Current setting on
operating & Restraining Coils
Range of current setting

GE
T60
1A or 5A

Provided with second and fifth harmonic


restraint feature.
Settable from 20,25,35 or 50% of rated
current
Reconnectible: 8,13 and 20 times the
rated current
Range of time setting
30ms typical
Burden(VA)for 50cycle operating & Operating ckt.:
Restraining/Coils under Normal & fault 0.02VA per ph. (at rated 1A),
condition
0.14VA per ph. (at rated 5A)
Restraining ckt.
0.003VA per ph. (at rated 1A),
0.02VA per ph. (at rated 5A)
Mechanical stability Class index
IP51, Flush mounting or rack mounting
Whether flag are Mechanical or Electrical
Electrical
Continuous and short time rating of the 4 times rated continuos
Relay at different times
100 times rated for 1s

Contd..4

Page..4
13
14
15
16
17

Whether Instantaneous Over Current Yes


Protections is provided or not?
Tripping Characteristics
Current differential element. : typical
30ms
High set O/C element.: typical 20ms
Restraining arrangement if any for Provided
abnormal High System Voltage
Knee Point Voltage requirement of CTS
Please refer catalogue
Descriptive leaflet number submitted
Yes

DISTANCE PROTECTION SCHEME

Name of Manufacturer

GE

Type Designation of the offered relay

D60

Typical operating time of relay

20ms

Re-setting time of the relay

Typical 30ms

The offered relay shall have


polygonal characteristics with
adjustable resistive and reactive
reach Bidders may confirm
Number of phase and ground
distance zones of protection
Reach of the relay ini) Zone I
ii) Zone II
iii) Zone III
iv) Zone IV

Confirmed

7
8

Timings
i) Zone II
ii) Zone III
iii) Zone IV

10

Zero sequence compensation factor

12

Suitability of the offered relay for


i) Power swing blocking
ii) Detection of VT fuse failure
iii) SOTF condition
iv) Trip Circuit Supervision
v) Protection against broken wire
(line)
vi) Stuck breaker condition (LBB
feature)

4 x Forward, 2 x Reverse a
i)
ii)
iii)
iv)

0.10 to 250.00 in 0.01 steps


0.10 to 250.00 in 0.01 steps
0.10 to 500.00 in 0.01 steps
0.1 to 500.0 in 0.1 steps

i) 0.00 to 10.00s in 0.01s steps


ii) 0.00 to 10.00s in 0.01s steps
iii) 0.00 to 10.00s in 0.01s steps
Yes
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)

Confirmed
Confirmed
Confirmed
Not available
Confirmed
Confirmed
Confirmed
Confirmed

13

15

22
23
24

25

26

27

vii) Single pole tripping and reclosing


viii) Thermal imaging / over load
detection
(All these points are to be
commented
upon / confirmed by the bidders)
A) Suitability of the offered relay
for negative phase sequence
imbalance condition following
one of the phases of the line
becoming faulty
B) Bidders may confirm if the
protection provided in A above
shall not operate for the two
phase traction loads.
Suitability of the offered relay for
Permissive under / over reach
Zone-I extension
Event sequence recording
Disturbance recording
Distance to fault to location
Maximum permissible continuous
current in the offered relay
Maximum permissible over voltage
which the relay can sustain
Human machine interface facility in
the offered relay. Bidders may
confirm if front panel display with
facility to scroll through settings given
in the relay and to view the
measurements, is available in the
offered relay
Suitability of the offered relay for
auxiliary DC supply. Bidders may
confirm if both, 110 & 220 Volts DC
supplies can be had in the offered
relay or two separated relays are
required for 110V & 220V
Provision of serial ports type RS232
& RS485 in the offered relay for
downloading of the data and remote
communication in-line with IEC
Communication protocol Bidders
may confirm.
Provision of port type IRIG for time
synchronization of the relay. Bidders
may confirm

No

N/A

Yes
Yes
Yes
Yes
Yes
4 times rated current.
100 times rated current for 1 sec.
Confirmed

Model is separate for 110V and


220V.
Offered suitable model as per
specification requirement.
Confirmed

Confirmed. BNC Type connector for


IRIG-B

XI. DIRECTIONAL OVER CURRENT RELAYS & EARTH FAULT RELAY


1
2
3

4
5
6
7

8
9

Makers name
Type
Polarization
i)
Current
ii)
Potential
Current coil rating
Potential coil rating
Tap range

GE
F650
30,45 & 60 deg. Lead
1A
110V AC
50-200% in steps of 10%
200 to 3200% in steps of 200%

VA burden:
a) Highest tap
Less than 1 VA constant at all
b) Lowest tap
settings
Power Consumption
10W
D.C. Current carrying capacity of Make & carry 1000W with current max.
of 5A & voltage max. of 250 VDC
tripping Contacts

Break
200W
(resistive)
100W(inductive) with max. current max.
of 10A & voltage max. of 250 VDC

10
11

12
13
14
15

Whether Relay is hand or self


resetting
Whether extra contacts provided for
actuating Alarm Bell in the relay
itself
Whether
Test
Links
are
incorporated in the Relay or not?
Insulation Test Voltage (kV)
Whether seal in contacts provided
Descriptive
leaflet
number
submitted

Self reset contacts


Yes. Provided

NO.
2kV RMS 50Hz. For 1 Minute
NA
Enclosed

XII. AUXILIARY RELAYS FOR TRANSFORMER TROUBLE


1
2

Make
Type & Designation

Nominal voltage and % variation

Contacts, hand reset/self reset

No. of pairs of contacts


i) Make contacts
ii) Break contacts
Speed operation of relay
Pick up / drop off ratio

6
7

JVS
JRV 151 / JRV 161 (S/R or H/R
contacts as per requirement)
110V or 220V DC (75 to 120% of
rated voltage)
S/R or H/R contacts as per
requirement
4 pairs of change over contacts can
be used in any combination of N/O or
N/C
Typically 20 millisecods
Reset value: above 10% of the rated
voltage

8
9

Burden of relay VA
i) Contact rating
ii) Voltage

4W 9at rated voltage

iii) Making current and duration

iv) Breaking current

10
11
XIII.
1
2
3
4

5
6

a) Resistive
b) Inductive 0.3 PF
c) Inductive L/R 10m sec
40m sec
Detailed literature furnished
Standard

Yes
IEC / IS3231

HIGH SPEED TRIPPING RELAYS


Make
Type designation
Rating
i) Operating principal
ii) Literature write up enclosed

JVS
JRV 181
110V or 220V DC
Attracted armature

Operating time at rated voltage.


No. of Tripping Contact and rating

Typical 10 millisecond
4 NO + 1 NC per element

i) Voltage

ii) Making current and duration

iii) Breaking current

a) Resistive
b) Inductive 0.3 PF
c) Inductive L/R 10m sec
40m sec
Hand reset/self reset contacts
i) No. of NO & NC contacts
ii) Rating of contacts.

As above

(XIV) TRIP CIRCUIT SUPERVISION RELAY


1
2
3
4
5
6
7

10
11
12
13

Make
Type designation
Rating
i) Operating principal
ii) Literature write-up enclosed.
Minimum voltage for satisfactory
operation.
Burden
Monitoring of breaker trip coil in
both open and close position
provided.
Safety resistor provided to limit the
current if the relay coil is short
circuited.
Output contacts
i) No. of NO/NC contacts
ii) Rating of contacts
Time delay on drop off
Type of indication
Standard
Any other relevant details.

JVS
JRV 911
110V or 220V DC per requirement
Enclosed
70% of the rated voltage
10W max.
Yes.

Yes.

2NO+1NC
5A
400msec. appx.
LED
IEC 60255
-

for VENSON ELECTRIC PRIVATE LIMITED