PAG HSS SNAGR REPORT

ID

Type
HIGH PRIORITY ITEMS
AA - Placeholder for unknowns

Drawing

Location

Description

General view

Building - General/Building - General

address-Level 3 East : ii. Level 3 East Concourse l. Water pools away from floor drain
along Grid N7

Ext - Substantial - Sanitary Sewer

Site Services Drawing

Site Services/Site Services

Not to specification/drawings-sag in sanitary line from San MH4A to San MH 5A.

Arch - Substantial - Door Hardware

A 00104 A3 Corridor 3

4W-AC3/4W-AC3

Not to specification/drawings-Astragal missing

Arch - Substantial - Masonry Units

A 00103 B3 PC 9 10

3W-BAD/3W-BAD

Not to specification/drawings-Diagonal crack

A 00101 B3 Main Electrical


Room
A 00103 C3 lift

1W-703/1W-703

address-Concrete finish has dips and divots

3E-CL/3E-CL

Arch - Substantial - Grandstands Pedestrian


Coating System
Arch - Substantial - Grandstands Pedestrian
Coating System
Arch - Substantial - Grandstands Pedestrian
Coating System
Arch - Substantial - Grandstands Pedestrian
Coating System
Arch - Substantial - Grandstands Pedestrian
Coating System
AA - Placeholder for unknowns

A 00103 C3 gradin 2

3E-CG2/3E-CG2

address-Significant wear slab cracking parallel to installed saw cuts was observed in
the area of SE elevator 5.
Not to specification/drawings-Surface defects.

A 00103 C3 gradin 1

3E-CG1/3E-CG1

A 00103 C3 gradin 4

3E-CG4/3E-CG4

Not to specification/drawings-Surface defects. Row 13, seat 5 south of 1st VOM on


south end
Not to specification/drawings-Footprints in coating

A 00103 C3 gradin 4

3E-CG4/3E-CG4

Not to specification/drawings-Bubbles in coating

A 00103 C3 gradin 4

3E-CG4/3E-CG4

Not to specification/drawings-Footprints in coating

AA - Placeholder for unknowns

A 00103 B3 Stair F

3W-106/3W-106

address-Cracks observed at landings and in treads, along long axis of stair. Cracks
also generating at lowest landing at joint between structural steel support and concrete
foundation support. (Cannon SVR 022)

AA - Placeholder for unknowns

A 00103 D3 stairs

3E-104/3E-104

AA - Placeholder for unknowns


Arch - Substantial - Fixed Audience Seating

A 00102 B3 Mechanical service 2W-707/2W-707


room
A 00104 A3 gradin 3
4W-AG3/4W-AG3

address-Significant cracks in inner curbs noted at landing between L2-L3. (Cannon


SVR 022)
address-Slope in mechanical room. 2W-707 between north exterior.

Arch - Substantial - Acoustic Tile Ceilings

A 00105 A3 corridor 2

5W-201/5W-201

AA - Placeholder for unknowns

A 00101 A3 Exercise
STORAGE

1W-303/1W-303

2302
2739
2817
5876
MEDIUM PRIORITY ITEMS
AA - Placeholder for unknowns
491
AA - Placeholder for unknowns
509
540
542
561
562
563

A 00103 A3 Stairs A

address-Cracks observed at landings and in treads, along long axis of stair. Cracks
also generating at lowest landing at joint between structural steel support and concrete
foundation support. (Cannon SVR 022)

587

588
591
677
682
694
711

Not to specification/drawings-Concern regarding clearance between accessible seats


and glazing facade.
Ceiling not installed to correct level-Ceiling height to be confirmed or a variance
submitted.
address-Fill and finish hole.

PAG HSS SNAGR REPORT

ID
712
790
794
817
819
820

Type
Arch - Substantial - Door Hardware
Arch - Substantial - Design issues
AA - Placeholder for unknowns
AA - Placeholder for unknowns
AA - Placeholder for unknowns
AA - Placeholder for unknowns
Arch - Occupancy - Gypsum Board

823
825 Arch - Substantial - Painting
826 Mech - Substantial - Sheet Metal
Elec - Substantial - Building Automation
827 System
Elec - Substantial - Audio Visual & Sound
829 Systems
831 Arch - Substantial - Painting
AA - Placeholder for unknowns
833
835 AA - Placeholder for unknowns
836 AA - Placeholder for unknowns
850 Arch - Substantial - Masonry Units
853 General - Substantial - Final Clean
Arch - Substantial - Design issues
919
922 AA - Placeholder for unknowns
972 AA - Placeholder for unknowns
AA - Placeholder for unknowns
1349
1379 Elec - Substantial - AV System
Arch - Substantial - Architectural Woodwork

Drawing
A 00101 A3 Exercise
STORAGE
A 00103 A3 gradin 1
A 00103 B3 Mech
A 00103 B3 Prepa area
A 00103 A3 First aid
A 00103 B3 Prepa area
A 00103 B3 Prepa area

Location

3W-G1/3W-G1
3W-409/3W-409
3W-407/3W-407
3W-405/3W-405
3W-407/3W-407
3W-407/3W-407

Design Issue-Seat alignment due to bowl curve to be confirmed.


address-Hole in concrete block upper wall requires fill.
address-Paint required on plywood.
address-Fill holes.
address-SS Countertop not sized properly for the slanted bottle coolers
Not to specification/drawings-Typical all concessions - Seal all openings in ceilings.

A 00103 A3 Hawkers Room


A 00103 A3 Hawkers Room
A 00103 A3 Hawkers Room

3W-404/3W-404
3W-404/3W-404
3W-404/3W-404

Make good damage-Finish door frame


Not to specification/drawings-Sleeve masonry for ductwork
Not to specification/drawings-Incomplete work

A 00103 A3 Queue Area

Description
Not to specification/drawings-Latch plate missing - non-rated door

Not to specification/drawings-Conduit left proud of wall. To be cut flush

A 00103 A3 TR
A 00103 A3 Prepa area

3W-302/3W-302
3W-403/3W-403

Make good damage-Paint touch up


address-caulk between brace and wall. Is this to be caulking? Who is doing the work?

A 00103 A3 Prepa area


A 00103 A3 Prepa area
A 00103 A3 Merchandise
A 00103 A3 PCX
A 00101 B3 Media truck

3W-403/3W-403
3W-403/3W-403
3W-401/3W-401
3W-PCX1/3W-PCX1
1W-602/1W-602

address-Fire-rated paint patch needed on plywood.


address-Seal openings in ceiling. Install access doors.
Not to specification/drawings-Hole needs filled.
Not to standards-Lots of concrete staining.
Design Issue-Typical all columns - column protection in loading dock to be reviewed.

General view
A 00102 C3 Stairs
A 00103 C3 spectator
concourse
A 00103 C3 Food prep
General view

FOP/FOP
2E-20X/2E-20X
3E-CQA/3E-CQA

address-Date for installation of soccer equipment sleeves requested


address-Cracked wear slab
address-Wear slab cracked

Arch - Substantial - Design issues

General view

Building - General/Building - General

Arch - Substantial - Design issues

General view

Building - General/Building - General

Design Issue-13) 1) bottom stair on exterior club stairs is extremely short. Please have
Cannon and PDC verify. Concrete was cast to raise the railing, S and N stairs Level 4.

Arch - Substantial - Design issues

General view

Building - General/Building - General

Design Issue-13) 8) the information/email re: glazing requires a response. Labels on


the glazing are inside or outside? To be reviewed by Cannon, inside SVR of Cannon,
Level 7 stickers inside of glazing.

1453

Not to specification/drawings-Data cover missing


Not to specification/drawings-14) 7) Millwork as to be MDF but does not look MDF on
site. Specifications do not say MDF. Use MDF instead of particle board. Please
confirm MDF was not used.
Design Issue-14) 8) Group sales MDF to be mobile but are fixed on site. Drawings
have always shown fixed millwork as millwork cannot move with a sink in it.

1454

1460

1461

PAG HSS SNAGR REPORT

ID

Type
AA - Placeholder for unknowns

Drawing
General view

Location
Building - General/Building - General

Description
address-12.) 11) wiring mesh for the speaker to be submitted

AA - Placeholder for unknowns

Level 6.1

6.1W/Level 6.1

address-11.) 1) Guard rails Level 6.1 : CoH requests a review of safety standards for
cleaning purposes ONSS to provide mesh to prevent people climbing.

Arch - Substantial - Design issues

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

Arch - Substantial - Design issues

General view

Building - General/Building - General

Elec - Substantial - Other

General view

Building - General/Building - General

Design Issue-11.) 8) List of obstructed view seats to be sent to the CoH 24 on the
lower East.
address-2.)7) Column Level 3 West issue with the vertical pipe to be closed?
Fastening to be reviewed
Design Issue-17.) 5) visiting coaches change room, not as per drawing: Millwork to be
reviewed.
Not to specification/drawings-17.) 6) Electrical/ smart boards in TC Offices...was this
fixed as per layout provided by TiCats? Quote for plug modification to be sent to IOS.

Arch - Substantial - Design issues

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

Design Issue-17.) 8) Seat count/ obstructed views- currently, TiCats have sat in each
seat and counted more than 700 obstructed seats (count continues). Cannon to
review.
address-17.) 14) n/s power- understanding the variation was not submitted however
understand that there are power and data capabilities in the existing light standardsplease confirm. No power/ data provision. VD required.
address-General Notes of Sept 30/14 , 2) Letter from AHU Factory to confirm the
warranty to AHU after smoke fire.
address-16.3 Upper East VOM area- stair depth (safety issue?)

AA - Placeholder for unknowns

General view

Building - General/Building - General

address-16.7 Suites -glass slider/ transition to be flush? Code/PSOS compliance.

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

address-16.17) Washroom accessories (including hand dryer) - shop drawings to be


forwarded / reviewed (by sponsors) / approved- noted.
address-16.23) west storage doors are not compliant with variation.

AA - Placeholder for unknowns

General view

Building - General/Building - General

address-15.2) TV level 7 position to be clarified

FF&E - Substantial - Kitchen Equipment

FF&E - Substantial - Kitchen Equipment

A 00102 C3 Concessions prepa 2E-404/2E-404


area
A 00102 C3 Concessions prepa 2E-404/2E-404
area
A 00102 D3 Concessions areas 2E-405/2E-405

FF&E - Substantial - Kitchen Equipment

A 00102 D3 Concessions areas 2E-405/2E-405

FF&E - Substantial - Kitchen Equipment

A 00102 D3 Concessions areas 2E-405/2E-405

1469

1470
1471
1474
1480

1481

1482

1483
1494
1498
1499
1507
1510
1520
1527
FF&E - Substantial - Kitchen Equipment
1531
1535
1536
1537

Not to specification/drawings-Cup dispensers are missing


Not to specification/drawings-Pop and ice machine not operational at time of
inspection
Not to specification/drawings-Pop and ice machine not operational at time of
inspection
Not to specification/drawings-Pop and ice machine not operational at time of
inspection
Not to specification/drawings-Pop and ice machine not operational at time of
inspection

PAG HSS SNAGR REPORT

ID

Type
FF&E - Substantial - Kitchen Equipment

Drawing
Location
A 00102 D3 Concessions areas 2E-406/2E-406

FF&E - Substantial - Kitchen Equipment

A 00102 D3 Concessions areas 2E-406/2E-406

FF&E - Substantial - Kitchen Equipment


1544
1551 AA - Placeholder for unknowns
FF&E - Substantial - Kitchen Equipment
1556
FF&E - Substantial - Kitchen Equipment
1559
FF&E - Substantial - Kitchen Equipment
1568
FF&E - Substantial - Kitchen Equipment
1569
1570 FF&E - Substantial - Kitchen Equipment
FF&E - Substantial - Kitchen Equipment
1579
1581 FF&E - Substantial - Kitchen Equipment
FF&E - Substantial - Kitchen Equipment
1582
1583 FF&E - Substantial - Kitchen Equipment
1584 FF&E - Substantial - Kitchen Equipment
1586 FF&E - Substantial - Kitchen Equipment
1605 FF&E - Substantial - Kitchen Equipment
AA - Placeholder for unknowns
1645
AA - Placeholder for unknowns

A 00102 D3 Concessions areas 2E-406/2E-406

1538
1543

A 00102 D3 Hawkers room


A 00102 C3 Concession prepa
area
A 00102 C3 Concession prepa
area
A 00103 C3 Food prep

2E-403/2E-403
2E-400/2E-400

A 00103 C3 Food prep

3E-400/3E-400

A 00103 C3 Food prep


A 00103 D3 prep area

3E-400/3E-400
3E-405/3E-405

A 00103 D3 prep area


A 00103 D3 prep area

3E-405/3E-405
3E-405/3E-405

A 00103 D3 prep area


A 00103 D3 prep area
A 00103 D3 prep area
A 00103 B3 Prepa area
A 00101 A3 Stairs

3E-405/3E-405
3E-405/3E-405
3E-405/3E-405
3W-407/3W-407
Building - General/Building - General

General view

Building - General/Building - General

AA - Placeholder for unknowns

A 00104 A3 stairs H

4W-105/4W-105

AA - Placeholder for unknowns

A 00104 A3 stairs H

4W-105/4W-105

AA - Placeholder for unknowns

A 00104 A3 stairs H

4W-105/4W-105

AA - Placeholder for unknowns

A 00104 A3 Stairs G

4W-102/4W-102

AA - Placeholder for unknowns

A 00104 A3 Stairs G

4W-102/4W-102

2E-400/2E-400
3E-400/3E-400

Description
Not to specification/drawings-Pop and ice machine not operational at time of
inspection
Not to specification/drawings-Stainless steel trims missing on concession side for pop
lines
Not to specification/drawings-Stainless steel chase for pop lines missing
address-Hot heated drawers to be commissioned
Not to specification/drawings-Pop and ice machine not operational at time of
inspection
Not to specification/drawings-Stainless steel chase for pop lines missing
Not to specification/drawings-Pop and ice machine not operational at time of
inspection
Not to specification/drawings-Stainless steel trims missing on concession side for pop
lines
Not to specification/drawings-Stainless steel chase for pop lines missing
Not to specification/drawings-Pop and ice machine not operational at time of
inspection
Not to specification/drawings-One (1) popcorn holder broken
Not to specification/drawings-Stainless steel trims missing on concession side for pop
lines
Not to specification/drawings-Stainless steel chase for pop lines missing
Not to specification/drawings-Stainless steel chase for pop lines missing
Not to specification/drawings-Warmer 708 is not set in place as per drawing
Not to specification/drawings-Cup dispensers are missing
review-Level one East: 1.1 SE Stair J North concrete guard has through-wall cracks in
several locations. Pin and take a picture
review-Level One East: 3. SE Stair J crack across first landing, aligned with transition
from steel to concrete support structure below no relief cut or movement joint as per
NW Stair J and NE Stair M radiates. Pin and take a picture

1684
1845
1847
1848
1862
1863

address-Cracking of concrete seams in stairwell. Wearing slab affected only - not a


waterproofing or structural issueC
address-Lots of cracking and chipping of concrete on stair edges. Wearing slab
affected only - not a waterproofing or structural issue
address-Lots of cracking and chipping of stair treads. Wearing slab affected only - not
a waterproofing or structural issue
address-Rough seam between concrete pads, lots of chipping and nearby cracks.
Wearing slab affected only - not a waterproofing or structural issue
address-Stair pan infill concrete cracking between club and suite level, south end.
Wearing slab affected only - not a waterproofing or structural issue

PAG HSS SNAGR REPORT

ID

Type
AA - Placeholder for unknowns

Drawing
A 00105 A3 Stairs G

Location
5W-102/5W-102

A 00105 A3 private suite WC


female
A 00105 A3 B stairs H
A 00105 A3 B stairs H

5W-332/5W-332

General view

Building - General/Building - General

General view

Building - General/Building - General

General view

Building - General/Building - General

General view

Building - General/Building - General

Arch - Substantial - Aluminum Grandstands

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

address-2. Level 2 East iv. a. Remove oversized sealant infill between door frame and
concrete curb, infill with concrete and seal to door frame. confirm work is complete

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

Arch - Substantial - Acoustic Tile Ceilings

General view

Building - General/Building - General

Arch - Substantial - Masonry Units

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

address-Level 3 East : I. General: a. Fill all CMU wall inside corners and movement
joints flush with sealant c/w backer rod as required by width/depth
address-Level 3 East : ii. Level 3 East Concourse e. Repair cracks in wear slab
radiating from Elevator 6 shaft
address-Level 3 East : ii. Level 3 East Concourse k. Repair cracks in wear slab
including at heads of seating access aisles adjacent to Grid N1, Grid N7, Grid S2 to
Stair N2 three cracks at North corner and door of Elevator 5. Lobby
address-Level 3 East : ii. Level 3 East Concourse n. At Stair N1, JM has left his/ her
initials in the concrete repair
Not to specification/drawings-2.3 West Building 1 Level 1 West xvi. 1W-325 Vestibule
b. Seal the t-bar along the East corridor
Not to specification/drawings-2.3 West Building 1 Level 1 West xvi. 1W-325 Vestibule
c. Fill the concrete block wall where it meets the floor. Confirm required work is
complete.
address-2.4 East Building 1. Level 1 East: Stair J: a. At least one crack in concrete
running up the bottom flight
address-2.4 East Building 1. Level 1 East: Stair J: b. Crack across lower landing where
concrete aligned with concrete support wall below
address-2.4 East Building 1. Level 1 East: Stair J: h. Seal joint flush at transition from
stair concrete to wear slab concrete

1864
Arch - Substantial - Washroom Accessories
1962
2110 AA - Placeholder for unknowns
AA - Placeholder for unknowns
2111
General - Substantial - Final Clean
2156
AA - Placeholder for unknowns
2159
AA - Placeholder for unknowns
2249
AA - Placeholder for unknowns

5W-105/5W-105
5W-105/5W-105

2251

Description
address-Hole in corner of pad, cracking and rough finish. Wearing slab affected only not a waterproofing or structural issue
Not to specification/drawings-Replace scratched stall door.
address-Rough patches around column
address-Pad seams rough and cracked. Wearing slab affected only - not a
waterproofing or structural issue
Not to standards-Bldg General: 2.1 xiv: remove rust stains, oil, weld scorches, and
other foreign material stains on finished concrete floors
address-Bldg General: 2.1 xvii: install backer rod and sealant at joints between tops of
CMU walls and concrete /precast slabs
address-2. Level 2 East ii : South East Accessible Seating Platform: f. At front slab
edge metal panels, seal all edges typical
address-Level 2 East: South East Accessible Seating Platform h. Crack in concrete
wear slab from bottom of Stair R7 to infill wall below Stair J. Wearing slab affected only
- not a waterproofing or structural issue
Not to specification/drawings-2. Level 2 East ii : South East Accessible Seating
Platform I. Install sealant at tops and sides of refinished metal infill panels throughout

2252

2265
2292
2295

2301
2304
2330

2331
2344
2345
2349

PAG HSS SNAGR REPORT

ID

Type
AA - Placeholder for unknowns

Drawing
General view

Location
Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

Arch - Substantial - TPO Roofing

General view

Building - General/Building - General

General view

Building - General/Building - General

A 00106 A3 stair G

6W-102/6W-102

A 00106 A3 corridor 2

6W-AC2/6W-AC2

A 00102 C3 Guest service


A 00102 C3 Queue areas
A 00102 C3 parking

2E-201A/2E-201A
2E-205/2E-205
2E-QA/2E-QA

A 00102 D3 Queue area

2E-208/2E-208

2352
2353
2354

Description
address-2.4 East Building 1. Level 1 East: Stair M : d. Seal joints in concrete curbs at
mid- landing repair cracks in curbs
address-2.4 East Building 1. Level 1 East: Stair M : e. Patch concrete around column
base L2 head of lower flight
address-2.4 East Building 1. Level 1 East: Stair M : f. Repair cracks in L2 concrete
wear slab at floor drain adjacent to head of lower flight
Not to specification/drawings-2.4 East Building 1. Level 1 East: Stair M : h. Install
flashing against side wall of Elevator 6 shaft, at upper flight concrete block wall

2355
Struc - Substantial - Metal Stairs and
2357 Balustrades
AA - Placeholder for unknowns
2358
AA - Placeholder for unknowns
2360
2490 AA - Placeholder for unknowns
2497 AA - Placeholder for unknowns
Elec - Substantial - AV System
2508
Arch - Substantial - Signage and Graphics
2516
2541 AA - Placeholder for unknowns
2560 AA - Placeholder for unknowns
AA - Placeholder for unknowns
2667
AA - Placeholder for unknowns
2669
AA - Placeholder for unknowns
2733
2828 FF&E - Substantial - Kitchen Equipment
Arch - Substantial - Design issues
2842
Mech - Substantial - Air Handling Units
2869
2876 AA - Placeholder for unknowns
Elec - Substantial - Other
2888
3021 AA - Placeholder for unknowns
Arch - Substantial - Gypsum Board
3039
Arch - Substantial - Gypsum Board
3042

A 00103 A3 PCX
3W-PCX1/3W-PCX1
A 00106 A3 corridor 2
6W-AC2/6W-AC2
A 00106 A3 B elevator vestibule 6W-202/6W-202

Not to specification/drawings-2.4 East Building 1. Level 1 East: Stair M : j. Repair bent


guard pickets at North side of upper mid- landing
address-36.2. 6 Level 6 West ii. Stair G : a. Stair no sings , guards, and handrails
rusting: grind, clean, and recoat. Confirm work is complete
address-36.2 6 Level 6 West: iii Level 6 West Concourse : a. Cracks in wear slab:
outside Mens Washroom6W-302 at head of Stair G
address-Concrete slab incomplete behind column. Typical of columns on Level.
address-Concrete slab behind column incomplete
Not to specification/drawings-Conflict between sign and TV. TV to be moved to center
of wall.
Not to specification/drawings-Conflict between sign and TV. Move sign to adjacent wall
(north).
address- crack in pad.
address-Concrete staining and rust marks, typical 6 west.
address-Crumbling seal between curb and concrete pad

A 00106 A3 B elevator vestibule 6W-202/6W-202

address-Large crack in pad between concession and column

Site Services Drawing

address-OSG-1 change 1 lid that has no holes to holes. Confirm work has been
complete
Not to specification/drawings-Pop lines incomplete
Design Issue-Sound attenuation - confirm with BKL if this is a concern.

Site Services/Site Services

A 00104 A3 Bar
4W-309/4W-309
A 00104 A3 Group sales suite B 4W-315/4W-315
A 00101 B3 Uniform laundry
storage
A 00103 C3 spectator WR
A 00106 A3 hawkers room

1W-401/1W-401

A 00102 D3 Stairs
A 00102 D3 Spectator WR
male
A 00102 D3 Spectator WR
female

2E-104/2E-104
2E-307/2E-307

Not to specification/drawings-West side L1 Security Operations 1W-401: coordinate


location of rad heater with system furniture
address-Unfinished around structural brace. Confirm work is complete
Not to specification/drawings-Hard wiring being changed to plug in to be consistent
with other combi ovens
address-Masonry cap required.
Not to specification/drawings-Mud/sand trim. Both ends of washroom.

2E-306/2E-306

Not to specification/drawings-Mud/sand trim. Both ends of washroom.

3E-304/3E-304
Exterior of West Stands

PAG HSS SNAGR REPORT

ID

Type
Arch - Substantial - Gypsum Board

3049
Mech - Substantial - Gas Fired Units

Drawing
Location
A 00102 C3 Spectators WR
2E-302/2E-302
female
A 00102 D3 Concessions areas 2E-406/2E-406

3073
AA - Placeholder for unknowns

5W-30X/5W-30X

Fire - Substantial - Sprinkler System

A 00105 A3 Premium guest


services
A 00105 A3 private suite WC
female
General view

Mech - Substantial - Piping

A 00101 A3 Suite 1 washroom

1W-323/1W-323

Mech - Substantial - Piping

A 00101 B3 Suite 3 washroom

1W-375/1W-375

AA - Placeholder for unknowns

General view

Exterior of West Stands

AA - Placeholder for unknowns


Mech - Substantial - Piping

A 00106 A3 B elevator vestibule 6W-206/6W-206


2
A 00101 C3 Vestibule
1E-201/1E-201

AA - Placeholder for unknowns

General view

3105
Arch - Substantial - Tiling
3111

5W-332/5W-332
Building - General/Building - General

3146

3167

3168
3176
3203
3215
Exterior East Stands/Exterior East
Stands

3222
Arch - Substantial - Sheet Metal Flashing and A 00101 D3 elevators
3227 Trim
AA - Placeholder for unknowns
A 00101 D3 elevators

1E-205/1E-205
1E-205/1E-205

3228
AA - Placeholder for unknowns
3229
AA - Placeholder for unknowns
3230
AA - Placeholder for unknowns
3232
AA - Placeholder for unknowns
3236
Arch - Substantial - Masonry Units
3239
3240 AA - Placeholder for unknowns

General view

Exterior East Stands/Exterior East


Stands
General view
Exterior East Stands/Exterior East
Stands
A 00106 A3 B elevator vestibule 6W-206/6W-206
2
General view
Exterior East Stands/Exterior East
Stands
General view
Exterior of West Stands
General view

Exterior of West Stands

Description
Not to specification/drawings-Mud trim. Both sides of washroom.
Not to specification/drawings-L 2 NE Concession- gas regulator needs to be minimum
1m away from electrical equipment, currently it is about 850mm from future light
fixture.
address-Door hardware complete per code. Additional hardware requested through
Change Order.
grout missing / inadequate-Grouting required
Not to specification/drawings-East Side: sprinkler exit from East side to West side,
labelling still required.
Not to specification/drawings-West SIde: TMV-1 for showers for visitors 1W-322 and
1W-332 will need temperature gauge provided for discharge supply (for visual
temperature delivery)*
Not to specification/drawings-West SIde: TMV-1 for shower rms 1W-375, 1W-382, 1W391, 1W-395 will need temperature gauge provided for discharge supply (for visual
temperature delivery)*
address-West Building: 1. Building Exterior: I. Stair A and South facade: a. Prefinished
metal flashing over masonry veneer not installed slab edge.
address-Level 6 West: ii. Concrete exterior floor cracks adjacent to Elevator 4
Brackets loose/missing-2.4 East Building: III. Elevator 5 and vestibule 1E-201: b.
Attach standpipe plate to wall
address-2.4 East Building: iv. West wall of East parking: a. Veneer block not installed
to underside of slab deck above, c/w exposed spray insulation detail for closure
required
Not to specification/drawings-2.4 East Building 1. Building Exterior V. D. Seal to
underside of slab edge at Stair M install prefinished metal flashing.
address-2.4 East Building 1. Building Exterior v. e. Above door E1E-205, the thermal
barrier continuity appears incomplete , with veneer block as cold bridge. Jog in wall
east of door not as per drawings.
address-2.4 East Building 1. Building Exterior vi. North facade: a. Resolve stair M open
block air space at east end
address-2.4 East Building 1. Building Exterior vi. North facade: b. Overhead door H1E200 requires soffit, and vapor/thermal/air barrier continuity.
address-L6W Elevator 4 lobby , slab crack
address-East Bldg Exterior L1E exposed interior block partition
Not to specification/drawings-West Bldg Exterior: Door 1W-202 repair block work.
Confirm required work is complete.
address-West Bldg Exterior: Door 1W-202 requires soffit, insulation continuity

PAG HSS SNAGR REPORT

ID

Type
AA - Placeholder for unknowns

Drawing
General view

3246
Mech - Substantial - Diffusers, Registers,
3291 Grilles, Louvers, Vents
Arch - Substantial - Glass and Glazing

Location
Exterior East Stands/Exterior East
Stands

A 00101 B3 BIN cleaning RM

Description
address-19. 7 Gas Valve at North East to be protected: issue of code for access to be
clarified.
Not to specification/drawings-West Side L1 : Compactor Bay 1W-513 : Damper
actuator not installed. Remove cover on transfer grille on opposite wall.
Not to specification/drawings-East Level 1: Players Equipment Storage windows to be
transaction type as scheduled. Installed window to be changed out for transaction
window.
address-General : East head wall cracks to be monitored and repaired. Dirt and
equipment marks to be cleaned. East head wall repairs required at mis- aligned rail
fasteners and other locations
address-West Stands : level 4 head wall, precast repairs required due to damage
during construction activities, four locations. Coordinate repair
address-Grandstand coating at east stands between N6 and N7 (Stair R6 aisle) shows
irregular surface texture and coverage, footprints, and other deformations in the
coating. Area shall be resurfaced.
address-2West finish trim and window closures required atLevel 2 offices , Area A
Confirm work is complete
Not to specification/drawings-2E-309 Fire hose cabinet outside of 309 , contractor
review and correct angle of fire hose connection for proper operation and clearance.

A 00101 A3 Laundry

1W-306/1W-306

AA - Placeholder for unknowns

General view

FOP/FOP

AA - Placeholder for unknowns

General view

Exterior of West Stands

AA - Placeholder for unknowns

General view

Exterior East Stands/Exterior East


Stands

AA - Placeholder for unknowns

General view

Exterior of West Stands

Fire - Substantial - Standpipe and Hose


System

A 00102 D3 FIRST AID

2E-309/2E-309

AA - Placeholder for unknowns

General view

FOP/FOP

address-FOP : manhole covers have domed tops, covers should be replaced with flat
tops that are flush with players walking surface. Confirm work is complete

A 00103 A3 Merchandise
A 00103 A3 PCX
A 00103 B3 PC 9 10
A 00103 B3 PC 9 10

3W-400/3W-400
3W-PCX1/3W-PCX1
3W-BAD/3W-BAD
3W-BAD/3W-BAD

address-3West 3W-400 Merch Outlet: steel deck dents.


Not to specification/drawings-3West Exterior: repainting, IMP markings
address-3West , Concourse: anchor bolts rusted
address-3West , Concourse: spray on water proofing -finished product/workmanship??

A 00103 B3 PC 9 10
General view

3W-BAD/3W-BAD
North Plaza

General view

Exterior East Stands/Exterior East


Stands

Struc - Substantial - Metal Stairs and


Balustrades

General view

Building - General/Building - General

AA - Placeholder for unknowns

A 00102 D3 Stairs

2E-104/2E-104

address-3West , Concourse: speakers too low.


Not to specification/drawings-SVR 013 : Level 1 West: North hosting patio receptacle
not yet relocated to wall
Not to specification/drawings-A-SVR # 29: 2.4.6.East Upper Seating Bowl: I. 28th
Seating installed: some seating showing rust at hinges some seats don't return to
vertical.
Not to specification/drawings-Cannon Design Field architects Report # 31:
Observations of Work in Progress:2.1 General: As per previous ASVRs the guard as
installed at the lowest tiers of seating, east and west buildings, has a gap between the
bottom bar of the guard and the edg
address-Cannon Design Architects Field Report #31: 2.4 East Building 4 Level 2 East
Concourse: ii. Correct poor saw cuts at Stair M middle column, Grids E15z/N14v

3307

3312
3313

3342
3343

3344

3346
3442 AA - Placeholder for unknowns
3469 Arch - Substantial - Painting
3477 AA - Placeholder for unknowns
AA - Placeholder for unknowns
3479
3481 AA - Placeholder for unknowns
Elec - Substantial - Other
3490
Arch - Substantial - Fixed Audience Seating
3529

3532

3537

PAG HSS SNAGR REPORT

ID

Type
Ext - Substantial - Security Fences

Drawing
General view

Location
Exterior East Stands/Exterior East
Stands

AA - Placeholder for unknowns

General view

South Plaza/South Plaza

AA - Placeholder for unknowns

A 00101 D3 elevators

1E-205/1E-205

Arch - Substantial - Signage and Graphics

A 00103 B3 Prepa area

3W-407/3W-407

Plumb - Substantial - Fixtures

A 00106 A3 spectator WR
female
A 00105 A3 Stairs G

6W-301/6W-301

A 00101 C3 Janitors
A 00101 C3 FOP Storage
Community
A 00101 D3 For Equip Storage
Events
A 00101 D3 End zone
A 00103 C3 spectator WR

1E-509/1E-509
1E-502

address-Cannon Design Architects Field Report # 37: 4. Level 5 West III. Stairs G and
H: a. Repair cracks in many treads at 1/3 points
address-Fill gap between wall and access cover. who is doing this work?
review-Repair broken slabs at base of column. Confirm repair is complete.

G1E-500/G1E-500

address-Seal conduit return above/ near 1E-604 doors. Who is to do this work?

1E-305/1E-305
3E-400/3E-400

Make good damage-Paint return filler


Not to specification/drawings-Trim around opening around heating water lines

A 00104 A3 Group sales suite

4W-300/4W-300

Not to specification/drawings-G&P to provide a price to replace scratched countertop.

A 00107 A3 Media WG unisex

7W-301/7W-301

grout missing / inadequate-

A 00107 A3 broadcast
A 00101 B3 Suite 3 washroom

7W-602/7W-602
1W-374/1W-374

3W-303
A 00103 A3 First aid
A 00103 A3 Prepa area
A 00107 A3 Security spotters
booth
A 00103 C3 spectator WR
A 00103 C3 Food prep
A 00103 C3 lift
A 00103 C3 lift
A 00103 C3 lift

3W-303/3W-303
3W-405A/3W-405A
3W-403/3W-403
7W-500/7W-500

Not to specification/drawings-Latch plate missing on non-rated door


address-caulk corner between walls, fill mortar seam and remove writing above door.
Who is doing the masonry caulking on the west side?
Lack of filling-fill and paint holes above toilet
Tile cracked / damaged-broken missing tile in corner behind toilet
Not to specification/drawings-Access hatch missing
Not to specification/drawings-millwork is chipped

3E-304/3E-304
3E-402/3E-402
3E-CL/3E-CL
3E-CL/3E-CL
3E-CL/3E-CL

address-repair damage to wall adjacent to access panel below sink.


address-repair hole in masonry, and paint.
address-Is this pipe to be insulated
address-fill floor gap behind column. Determine what work is required here.
address-transome frame not installed. Confirm work is complete.

3547
3631

Description
Not to specification/drawings-Cannon Design Architects Field Report #32:
Observations of work in progress 2.1 General: East Side: I. Perimeter security fencing
post at North parking entrance is damaged and bent.
address-the City rejected the green- stained concrete paving at the south end of the
plaza
address-Cannon Design Architects Report # 34: 35.2. East Building: General : 2. Level
2 Elevator 5 Lobby : a remove oversized sealant infill between door frame and
concrete curb infill with concrete and seal to door frame. Confirm work is complete

3674

3708
3741
AA - Placeholder for unknowns
3789
3829 AA - Placeholder for unknowns
AA - Placeholder for unknowns
3864
AA - Placeholder for unknowns
3871
3899 Arch - Substantial - Painting
Mech - Substantial - Hydronic Piping Systems
3900
Arch - Substantial - Architectural Woodwork
3956
Arch - Substantial - Tiling
3960
3969 Arch - Substantial - Door Hardware
AA - Placeholder for unknowns
4053
4214 Arch - Substantial - Painting
4218 Arch - Substantial - Tiling
4237 Elec - Substantial - Other
Arch - Substantial - Architectural Woodwork
4523
4566 AA - Placeholder for unknowns
4581 AA - Placeholder for unknowns
4599 AA - Placeholder for unknowns
4600 AA - Placeholder for unknowns
4601 AA - Placeholder for unknowns

5W-102/5W-102

Not to specification/drawings-Cannon Design Architects Field Report # 37 Level 3


West: ii. Prep 3W-407: a. As installed, room identification signage is hidden when door
is open
Not to specification/drawings-access panel in wrong place.

PAG HSS SNAGR REPORT

ID

Type
AA - Placeholder for unknowns

Drawing
Location
A 00102 D3 Concessions areas 2E-405/2E-405

Description
address-Trim temporary conduit flush to wall and patch.

AA - Placeholder for unknowns

A 00102 D3 Concessions areas 2E-405/2E-405

address-seal pipe cuts at wall. Confirm what work, if any, is required here.

A 00102 D3 Concessions areas 2E-405/2E-405

Make good damage-repaint door and frame

A 00101 A3 Players lounge


General view

Building Signage

General view

Building Signage

address-wall finish around device Plan pic # 10360


Not to specification/drawings-Banner-G-C-F_FR-CA EXT 8.0-G2 Change 'Porte' to
'Portes'
Not to specification/drawings-EXT-8.1_FR-CA to add Tribunes (for East and Ouest)

General view
General view
General view

Building Signage
Building Signage
Building Signage

General view

Building Signage

General view

Building Signage

General view

Building Signage

General view

Building Signage

General view
General view
General view

Building Signage
Building Signage
Building Signage

General view

Building Signage

General view

Building Signage

General view

Building Signage

Arch - Substantial - Signage and Graphics

General view

Building Signage

Not to specification/drawings-INT-1.5 G2-C2 TYPE 01_FR-CA Stockage pour le sport


communautaire instead of Stockage d'equipement de sport de communaute

Arch - Substantial - Signage and Graphics


5266
5267 Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
5268

General view

Building Signage

General view
General view

Building Signage
Building Signage

Not to specification/drawings-INT-1.5 G2-C2 TYPE 01_FR-CA Stockage de la loge du


club instead of loge du club stockage
Not to specification/drawings-INT-3.2 G3_FR-CA SIGES
Not to specification/drawings-INT-4.0 G2_FR-CA change all SIEGES" into "SIGES""

4627
4628
Arch - Substantial - Painting
4630
4713 AA - Placeholder for unknowns
Arch - Substantial - Signage and Graphics
5244
Arch - Substantial - Signage and Graphics
5245
5246 Arch - Substantial - Signage and Graphics
5247 Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
5248
Arch - Substantial - Signage and Graphics
5249
Arch - Substantial - Signage and Graphics
5250
Arch - Substantial - Signage and Graphics
5251
Arch - Substantial - Signage and Graphics
5254
5256 Arch - Substantial - Signage and Graphics
5257 Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
5258
Arch - Substantial - Signage and Graphics
5260
Arch - Substantial - Signage and Graphics
5261
Arch - Substantial - Signage and Graphics

Not to specification/drawings-EXT-8.1_FR-CA Change 'Media' to 'Medias'


Not to specification/drawings-EXT-14.1_FR-CA Change the accent
Not to specification/drawings-EXT-15.1_FR-CA debarcadaire/embarcadaire instead of
quai de chargement/dechargement
Not to specification/drawings-EXT-16.0 G1_FR-CA EQUIPEMENT instead of
EQUIPMENT
Not to specification/drawings-INT-1.2 G-C2 Type 01_FR-CA Change 'add
HYDROTHRAPIE' to 'add HYDROTHRAPIE'
Not to specification/drawings-INT-1.2 G-C2 Type 01_FR-CA Change '1W-33' to '1W332'
Not to specification/drawings-INT-1.2 G-C2 Type 02_FR-CA STAGING AREA is ZONE
DE TRANSIT
Not to specification/drawings-INT-1.4 G1_FR-CA Trainer is Entraneur""
Not to specification/drawings-INT-1.5 G2 Type 03_FR-CA TRASH = ORDURES
Not to specification/drawings-INT-1.5 G2-C1 Type 02-FR-CA 'Salle d'audiovisuel'
instead of 'salle de conference'
Not to specification/drawings-INT-1.5 G2-C2 Type 01_FR-CA Stockage de
poussettes/fauteuils roulants
Not to specification/drawings-INT-1.5 G2-C2 TYPE 01_FR-CA Placard de l'ascenseur
instead of Acsenceur WC
Not to specification/drawings-INT-1.5 G2-C2 TYPE 01_FR-CA Stockage pour le sport
communautaire instead of Stockage d'equipement de sport de communaute

5263

5264

PAG HSS SNAGR REPORT

ID

Type
Arch - Substantial - Signage and Graphics

Drawing
General view

Location
Building Signage

Arch - Substantial - Signage and Graphics

General view

Building Signage

Arch - Substantial - Signage and Graphics


Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics

General view
General view
General view
General view
General view
General view
General view
General view
General view
General view
General view
General view
General view
General view
General view

Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage

Arch - Substantial - Signage and Graphics


Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
Arch - Substantial - Signage and Graphics
AA - Placeholder for unknowns

General view
General view
General view
General view
General view
General view
General view
Site Services Drawing

Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Building Signage
Site Services/Site Services

AA - Placeholder for unknowns

Site Services Drawing

Site Services/Site Services

AA - Placeholder for unknowns

A 00101 A3 Athletic trainers


private
A 00107 A3 Broadcast booth
camera
A 00101 B3 Suite 3 washroom

1W-310/1W-310

5269
5270
5271
5273
5274
5276
5277
5278
5279
5281
5282
5284
5285
5286
5287
5288
5289
5292
5293
5294
5295
5296
5297
5298

7W-303/7W-303

Not to specification/drawings-INT-12.1 G1_FR-CA Promenade suprieure


Not to specification/drawings-INT-12.1 G1_FR-CA Terrain
Not to specification/drawings-INT-12.1 G1_FR-CA Quai de chargement
Not to specification/drawings-INT 3.0 G2 SIGES
Not to specification/drawings-INT 12.0 PROMENADE SUPRIEURE
Not to specification/drawings-INT 5.0 G1 SIGES
Not to specification/drawings-INT 5.1 SIGES
address-PDC report Nov 2014 - Provide consultant Test Certificate for each manhole
passing the test.
address-PDC Report Nov 2014 - reports of the Television and Photographic
inspections
address-PDC Report Nov 2014 - Privacy curtain between office and examination areas
to be installed
Not to specification/drawings-PDC Report Nov 2014 - Cue lights not observed

1W-375/1W-375

Design Issue-Area deficiency - Locker numbers

General view

Building - General/Building - General

General view

Building - General/Building - General

Not to specification/drawings-Suspected thermal bridge at Local joints on Level 07


East Elevation
Not to specification/drawings-Suspected thermal bridge at local joints on Level 07 East
Elevator, North End

5301
5303
5306
Elec - Substantial - Other
5313
Arch - Substantial - Design issues

Description
Not to specification/drawings-INT-6.0 G1_FR-CA Change Service Client to Services
clients
Not to specification/drawings-INT-6.2 G3_FR-CA promenade suprieure instead of
Promanade
Not to specification/drawings-INT-7.0 G1_FR-CA Ascenseur
Not to specification/drawings-INT-7.1 G1_FR-CA Ascenseur
Not to specification/drawings-INT-7.1 G1_FR-CA Salon des joueurs
Not to specification/drawings-INT-7.1 G1_FR-CA Stockage de vlos
Not to specification/drawings-INT-9.0 G2_FR-CA SORTIE instead of sortie
Not to specification/drawings-INT-9.0 G2_FR-CA Vestiaires
Not to specification/drawings-INT-10.0 G2_FR-CA Tribune de la presse
Not to specification/drawings-INT-10.0 G2_FR-CA promenade
Not to specification/drawings-INT-10.0 G2_FR-CA Niveau suite
Not to specification/drawings-INT-10.0 G2_FR-CA Niveau suite
Not to specification/drawings-INT-10.0 G2_FR-CA Salle du club
Not to specification/drawings-INT-10.0 G2_FR-CA Promenade infrieure
Not to specification/drawings-INT-10.0 G2_FR-CA salle de presse
Not to specification/drawings-INT-10.0 G2_FR-CA Vestiaires d'quipe
Not to specification/drawings-INT-10.0 G2_FR-CA PROMENADE SUPRIEURE

5877
Arch - Substantial - Preformed Metal Wall
6223 System
Arch - Substantial - Preformed Metal Wall
6224 System

PAG HSS SNAGR REPORT

ID
6225
6226
6227
6228

Type
Arch - Substantial - Preformed Metal Wall
System
Arch - Substantial - Preformed Metal Wall
System
Arch - Substantial - Preformed Metal Wall
System
Arch - Substantial - Preformed Metal Wall
System
Elec - Substantial - Communications

Drawing
General view

Location
Building - General/Building - General

General view

Building - General/Building - General

General view

Building - General/Building - General

General view

Building - General/Building - General

A 00102 A3 Director US
scouting office
A 00106 A3 spectator
concourse
A 00105 A3 B private suite 12

2W-324/2W-324

Description
Not to specification/drawings-Suspected thermal bridge at local joints on Level 07 East
Elevation, South end
Not to specification/drawings-Suspected thermal bridge at east Stands, north Elevator
Tower (north elevation shown)
Not to specification/drawings-Suspected thermal bridge at local joints on Level 07 East
Elevation, North End
Not to specification/drawings-Suspected thermal bridge at southeast corner of
southwest elevator tower
Not to specification/drawings-Placement of data outlets is unacceptable to tenant.

6W-201/6W-201

address-Signage is overlapping. Determine new location/layout

5W-327/5W-327

Not to specification/drawings-Pot Light (2 relamp)

7W-303/7W-303

address-Green Screens required in both TV Camera booths

Arch - Substantial - Design issues

A 00107 A3 Broadcast booth


camera
A 00105 A3 B VIP lobbies

5W-202/5W-202

AA - Placeholder for unknowns

A 00102 B3 Studio 2W 601

2W-601/2W-601

AA - Placeholder for unknowns


AA - Placeholder for unknowns

A 00101 A3 Security Operation 1W-207/1W-207


Center
General view
Exterior of West Stands

Design Issue-Head room issue with brace on south wall of elevator lobby. Levels 4, 5,
& 6?
address-Studio rooms 2W-601, 2W-602, 2W-603 per room data sheet to have
multilevel and dimmer light switching. Switching requires programming.
address-Door to exterior is not accessible - threshold too high, width insufficient.

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

General view

Building - General/Building - General

AA - Placeholder for unknowns

A 00102 C3 Portable
concession
A 00102 D3 empty 2

2E-204/2E-204

6234
AA - Placeholder for unknowns
6240
Elec - Substantial - Other
6250
AA - Placeholder for unknowns
6255
6258
6262
6263
6264
6265
6266
6272
AA - Placeholder for unknowns

2E-20E/2E-20E

address-Grade at entrance approximately 8% from sidewalk. Does this meet


accessibility/OBC?
address-Showers (all Accessible showers): Pressure equalizing / thermostatic mixing
valve lever required (currently it is a spring loaded shower head)
address-Washrooms: Sink pipes should be insulated (even with temp controlled
faucet).
address-concourse, repair concrete curb fracture at one guard post near Grid S8b
/E15 ensure guard still meets structural requirements.
address-concourse, water pooling away from drains at North accessible platform

6274
AA - Placeholder for unknowns
6279
AA - Placeholder for unknowns
6280
Arch - Substantial - Design issues
6281
6282 AA - Placeholder for unknowns
AA - Placeholder for unknowns
6286
AA - Placeholder for unknowns
6290

A 00102 C3 Spectators WR
2E-301/2E-301
male
A 00102 C3 Concessions prepa 2E-407/2E-407
area
A 00107 A3 stairs D
7W-400/7W-400

address-2E 301 washroom, install concrete grout between curbs and door frames

A 00103 C3 PC X
A 00103 D3 stairs

3E-PCX/3E-PCX
3E-104/3E-104

A 00101 A3 Exercise
STORAGE

1W-303/1W-303

address-3E Concourse, remove rust stains including along field side curb
address-Level 1E stair M remove staining of concrete, including mid landings and
apparent paint at movement joint at lowest mid landing
address-Level 1W Stair A and south facade, holes in masonry joints

address-2E 407/404 Concession and Prep, seal CMU knee joints.


Design Issue-Glazing to be installed between CFL Statistician and Written Press Both

PAG HSS SNAGR REPORT

ID

Type
AA - Placeholder for unknowns

Drawing
A 00107 A3 broadcast

Location
7W-602/7W-602

A 00103 A3 PCX 2
A 00101 B3 Main Electrical
Room
General view

3W-PCX2/3W-PCX2
1W-703/1W-703

A 00105 A3 Private suite 2

5W-303/5W-303

A 00101 D3 LV elec room


A 00106 A3 B universal WC

1E-604/1E-604
6W-304/6W-304

A 00103 A3 Queue Area

3W-QA/3W-QA

A 00107 A3 Broadcast booth


camera
A 00104 A3 TR

7W-303/7W-303

A 00101 B3 Telecom area

1W-706/1W-706

A 00101 B3 Internal Media


Production

1W-601/1W-601

A 00101 B3 Internal Media


Production
A 00101 B3 Internal Media
Production
A 00101 B3 Telecom area

1W-601/1W-601

A 00101 B3 Uniform laundry


storage
A 00101 B3 Uniform laundry
storage
A 00101 B3 Uniform laundry
storage

1W-702/1W-702

Elec - Substantial - Communications

A 00101 B3 Uniform laundry


storage

1W-702/1W-702

Elec - Substantial - Communications

A 00101 B3 Uniform laundry


storage

1W-702/1W-702

6291
6292 AA - Placeholder for unknowns
Elec - Substantial - Other
6297
Elec - Substantial - Other
6300
Elec - Substantial - Other
6301
6311 Elec - Substantial - Other
AA - Placeholder for unknowns
6368
AA - Placeholder for unknowns
6370
Elec - Substantial - Other
6373
Elec - Substantial - Other
6375
Elec - Substantial - Communications
6417
Elec - Substantial - Communications

Building - General/Building - General

4W-501

Description
address-PDC Report - Level 6 W, broadcast room, work counter supports are not
casework panels
address-Level 3 W exterior, repainting, IMP marks.
Not to specification/drawings-Any missing arc flash hazard labels shall be installed as
indicated in final arc flash study. SVR 017
Not to specification/drawings-SVR 017-Contractor to ensure panel schedules are
typed.
Not to specification/drawings-SVR 017-Circuit labelling is not in the correct format in
Suite S3.
Not to specification/drawings-Lighting control panel wiring ongoing in 1E-604
address-Accessibility Report 2.13 - 6W-304 Universal Toilet Room is provided with a
vending machine that is mounted too high and is not cane detectable.
address-Accessibility Report 2.17 - Concession stands have protrusions on either end
that extend into the path of travel
Not to specification/drawings-SVR-15 Booths in general: Pot Lights have not been
installed in a straight line
Not to specification/drawings-SVR-15 Some panel directories are hand-written. Panel
directory shall be neat and type-written
Not to specification/drawings-SVR-001 1W-706 BIX IDC blocks shall be clearly
labelled per specification
Not to specification/drawings-SVR-001 (1W-601) Empty patch panel positions are not
closed. Contractor shall place blank plates where connectors have not been installed.

6420
Elec - Occupancy - Communications
6421
Elec - Substantial - Communications
6424
Elec - Substantial - Communications

1W-601/1W-601
1W-707/1W-707

6425
Elec - Substantial - Communications
6430
Elec - Substantial - Communications
6431
Elec - Substantial - Communications

1W-702/1W-702
1W-702/1W-702

6432

6433

6434

Not to specification/drawings-SVR-001 (1W-601) Contractor shall bond ground/


common lead on audio cables to patch panel.
Not to specification/drawings-SVR-001 (1W-601) Cable drop bends (waterfalls) from
cable tray shall be provided as per specification.
Not to specification/drawings-SVR-001 (1W-707) BIX IDC blocks shall be located as
per specification.
Not to specification/drawings-SVR-001 1W 702: All optical fibre patch panels shall be
labeled and unused ports shall be capped.
Not to specification/drawings-SVR-001 1W-702 ; Every copper BIX patch panel shall
be lablled as per specification
Not to specification/drawings-SVR-011 1W-702 : Multipair cabling from MER stops on
level 1, room 1W-700 before travelling to above floors. Contractor shall install cabling
continuously from MER to each TR.
Not to specification/drawings-SVR-001 1W-702 ; Multipair cabling from MER stops on
level 1 room 1W702 before travelling to above floors. Contractor shall install cabling
continuously from MER to each TR.
Not to specification/drawings-SVR-001 1W-702: multipair cabling stops on level 1
room &02 before travelling to above floors. Contractor shall install cabling continuously
from MER to each TR.

PAG HSS SNAGR REPORT

ID

Type
Elec - Substantial - Communications

Drawing
A 00101 A3 Warm up area

Location
1W-360/1W-360

Elec - Substantial - Communications

A 00101 A3 Warm up area

1W-361/1W-361

Elec - Substantial - Communications

A 00101 A3 Warm up area

1W-360/1W-360

Elec - Substantial - Communications

A 00101 A3 Warm up area

1W-360/1W-360

Elec - Substantial - Communications

A 00101 A3 Warm up area

1W-360/1W-360

Elec - Substantial - Communications

A 00102 B3 TR

2W-705/2W-705

Elec - Substantial - Communications

A 00102 A3 2W701

2W-701/2W-701

Elec - Substantial - Communications

A 00103 A3 Spectators WC

3W-300/3W-300

Elec - Substantial - Communications

A 00104 A3 EL

4W-502/4W-502

Elec - Substantial - Communications

A 00104 A3 TR

4W-500

Elec - Substantial - Communications

A 00105 A3 TR

5W-500/5W-500

Elec - Substantial - Communications

A 00105 A3 B corridor TR EL

5W-502/5W-502

Elec - Substantial - Communications

A 00107 A3 TR

7W-603/7W-603

Elec - Substantial - Communications

A 00107 A3 TR

7W-603/7W-603

Elec - Substantial - Communications

A 00101 C3 Mechanical room

1E-603/1E-603

Elec - Substantial - Communications

A 00101 C3 Mechanical room

1E-603/1E-603

Elec - Substantial - Communications

A 00101 D3 elevators

1E-606/1E-606

Elec - Substantial - Communications

A 00101 D3 elevators

1E-606/1E-606

Plumb - Substantial - Plumbing Specialties

A 00101 B3 Green RM
changing

1W-391/1W-391

6439
6441
6442

6443

6444
6451
6456
6465
6469
6474
6479
6482
6486
6488
6489

6490
6493
6494

6497

Description
Not to specification/drawings-SVR-001 1W-700; All optical fibre patch panels shall be
labelled and unused ports shall be capped
Not to specification/drawings-SVR-001 1W-700 : Every copper BIX patch panel shall
be labelled as per specification
Not to specification/drawings-SVR-001 1W-700: Multipair cabling from MER to 1W700 and 1W-702 is not OSP. Cabling shall be removed and replaced.
Not to specification/drawings-SVR-001 1W-700: Multipair cabling from MER stops on
level one room 1W-700 before travelling to above floors. Contractor shall install
cabling continuously from MER to each TR
Not to specification/drawings-SVR-001 1W700: Multipair cabling from MER stops on
level one room 702 before travelling to above floors. Contractor shall install cabling
continuously from MER to each TR.
Not to specification/drawings-SVR-001 2W-705 : Every copper BIX patch panel shall
be labelled per specification
Not to specification/drawings-SVR-001 2W-701: Every copper BIX patch panel shall
be labelled per specification
Not to specification/drawings-SVR-001 3W-600 : Every copper BIX patch panel shall
be labelled per specification.
Not to specification/drawings-SVR-001 4W-503: Every copper BIX patch panel shall
be labelled per specification.
Not to specification/drawings-SVR-001 4W-500: Every copper BIX patch panel shall
be labelled as per specification
Not to specification/drawings-SVR-001 5W-500: Every copper BIX patch panel shall
be labelled as per specification
Not to specification/drawings-SVR-001 5W-502: Every copper BIX patch panel shall
be labelled as per specifications
Not to specification/drawings-SVR-003 7W-603: all optical fibre patch panels shall be
labelled and unused ports shall be capped
Not to specification/drawings-SVR-003 7W-603: every copper BIX patch panel shall be
labelled as per specifications
Not to specification/drawings-SVR-001 1E-602: all optical fibre patch panels shall be
labelled and unused ports shall be capped.
Not to specification/drawings-SVR-001 1E-602: 25th pair on copper voice back bone
cable has not been terminated as per specifications. Terminate 24th and 25th at port
24 of patch panel.
Not to specification/drawings-SVR-001 1E 606: all optical fibre patch panels shall be
labelled per specification
Not to specification/drawings-SVR-001 1E-606: every copper BIX patch panel shall be
labelled per specifications
Not to specification/drawings-M-SVR 21 item 28 TMV-1 (thermostatic mixing valves)
for visitors changing/shower rooms 1-W 322 and 323 need to be reviewed for
temperature discharge of 35C/95F .

PAG HSS SNAGR REPORT

ID

Type
Fire - Substantial - Sprinkler System

Drawing
A 00105 A3 TR

Location
5W-501/5W-501

Description
Not to specification/drawings-M-SVR 23 Item 71 5W-501 : single upright; Sprinkler
Engineer to confirm coverage on either side of beam and distance of head from ceiling

Fire - Substantial - Sprinkler System

A 00105 A3 TR

5W-501/5W-501

Plumb - Substantial - Fixtures

A 00101 B3 Uniform laundry


storage
A 00106 A3 B TR

1W-503/1W-503

Not to specification/drawings-M-SVR 23 item 74 5W-501: single upright ; Sprinkler


Engineer to confirm coverage on either side of beam and distance of of head from
ceiling
Not to specification/drawings-M-SVR 24 Item 75 Uniform Laundry 1W-503 ; provide
dome strainer at bottom of trench
Not to specification/drawings-M-SVR 24 item 91 Hang FE unit on wall

A 00101 B3 Main Electrical


Room

1W-703/1W-703

6501

6502
6503
Fire - Substantial - Standpipe and Hose
6506 System
Mech - Substantial - HVAC Air Filtration
6542
LOW PRIORITY ITEMS
Ext - Substantial - Landscaping

6W-502/6W-502

General view

3509
Ext - Substantial - Concrete Paving
5426

Site Services Drawing

Site Services/Site Services

Not to specification/drawings-M-SVR24 item 242 L1 Main Elec. Rooms; AC units still


not ducted
Not to specification/drawings-Morrison Hershfield Report #2 Behind the Hosting Patio
a scissor lift has been driven through the planting bed, all of the disturbed plants must
be replanted.
Not to specification/drawings-Replace 1 panel of sidewalk at Gate 3 Spring work.