ALD24VAV-LON

VAV room controller with display


Two 0...10 V outputs, LON-communication

ALD24VAV-LON is a controller for zone control of VAV and heating with LON Works communication

Setpoint 030C
Internal or external sensor
Setpoint offset +/- 3K
0...10 V outputs for VAV-control and heating

Input for occupancy control


Input for CO2 sensor
Input for external 010 V transferred to LON net
LON Mark profile 8502 network variables

Function
ALD24VAV-LON is a room controller for wall mounting. It has
built-in temperature sensor and two 010 V outputs for control
signal to VAV-controller and heating valve actuator. The
controller has adjustable P- and I-time and input for occupancy
control and CO2-sensor. There is also an extra 010 V input
that is transfered as a network variable to the LON Works
network. Settings are made using the menu system in the
display or by the LON Works network. Actual temperature and
output levels are shown continuously in the display. All settings
are also possible to shift via the LON network.
Sensors
The controller has built-in sensor. Alternatively external sensor
(Regin NTC 030C) can be used. In this mode the jumper
external/internal inside is reset. It is also possible to send
temperature sensor value to the controller via the LON network.
Setpoint
Is set in the setting-level menu. The controller uses heating
setpoint and cooling (VAV) setpoint. The settings are factory
set to 21C or 23C. If occupancy control is used there are
different setpoints in different states.
Setpoint offset
By pressing [+] or [-] button on the front individual setpoint
adjustments can easily be made, without entering the setting
level of the menu system (settable +/- 3K in 0.5 steps).
Heating output
Is possible to activate/deactivate via the menu system.
VAV output
For connection to a damper actuator or VAV-damper controller
for 010 V input. Minimum and maximum air volume can be set
in the VAV-damper controller. Minimum limit can also be set via
LON Works network.
Occupancy control
The controller has an input for closing contact from the

occupancy detector or similar device. When presence is


determined the controller runs with comfort setpoint for heating
respectively VAV(cooling). If presence is not detected, the
controller works in unoccupied mode, with reduced setpoint for
heating and raised setpoint for cooling.
Via the LON network it is possible to control the occupancy
status in three states:
Occupied
Unoccupied
Energy hold-off
Energy hold-off
Via LON network it is possible to set the controller in energyhold-off mode. Both outputs are set to zero and the room
temperature is allowed to decrease to frost level (10 degrees)
or increase to 30 degrees. Below 10C the heating output is
activated and above 30C the cooling output is activated.
CO 2 sensor input
ALD24VAV-LON also has an input for 010 V signal from CO2sensor. When the CO2 level exceeds a preset level (factory
setting 800 ppm) the VAV output signal is forced to increase, in
order to increase the air volume to the room. The CO2-level
setpoint can be changed via the display.

Display and menu system


To access the menu settings, do as follows:
Press buttons [< ] and [>] continously for five seconds.
The display shows the current software version. Then press
button [] three times, the controller enters setting level and
gives access to setpoints, control parameters etc.
To send a service-pin message over the LON-network, the
buttons [>] and [-] are held down followed by a press on the [-]
button. The display shows lon. If a wink message is received,
the display blinks between showing lon and showing for
10 seconds to indicate the physical location of the device. See
overleaf.
section position

2-229
Nov 03

Technical data
Supply voltage
Power consumption
Ambient temp
Storage temp
Ambient humidity
Protection class

Inputs
External sensor
Occupancy
External 010 V
CO2 sensor
Outputs
Control (output) signal
Communication

Settings (menu)
Temperature
At occupancy control

24 V AC +/- 15% 50-60 Hz


4 VA
050C (working range built-in sensor 030C)
40...+50C
Max 90% RH
IP20
This product confirms with the requirements of European EMC standards
CENELEC EN50081-1 and EN50082-1 and carries the CE-mark
030C (NTC sensor)
Closing contact from i.e. presence detector IR24-P
Can be used to transfer the VAV position to the LON works network
010 V corresponding to 02000 ppm CO2-level
Two, 010 V DC, 1 mA
LON Works, electrical interface FT 3120
Network variable interface according to LON Mark profile 8502
See separate specification: LON Interface description.
Factory settings (rangeability 0...30C)
21C, Heating setpoint
24C, VAV (cooling) setpoint
Heating setpoint comfort 21C
VAV(cooling) setpoint comfort 23C
Heating setpoint unoccupied 16C
VAV(cooling) setpoint unoccupied 28C

P-band
I-time
Calibration (temp. sensor)
Occupancy function
Heating output
Jumper BY1

0.599.9 K (5 K)
0999 s (0 means integration function not active)
+/- 3 K (internal or external sensor)
Active or inactive (Factory setting: Unactivated)
Active or inactive (Factory setting: Unactivated)
Right= Internal sensor (factory setting)
Left= External sensor

Network variables

File: network_variables_ALD24VAV-LON... (file can be reqired from regin by mail or from our web site)

Display

Bargraph for heating and cooling (VAV) output

Occupancy control,
Person in room (the frame) means occupied
Person out of room means unoccupied

Actual temperature is displayed in 0.1C steps

Wiring and dimensions


1
2
3
4
5
6
7
8

Supply voltage 24 V AC
System voltage neutral 24 V AC
Output 010 V, (heating)
Signal neutral
Output 010 V, VAV (cooling)
Signal neutral
External sensor
Occupancy control input

9
10
11
12
13
14
15

Input 010 V external signal


Signal neutral
Input 010 V CO2-sensor
Signal neutral
LON net B
LON net A
Protective earth

115 mm

86 mm

AB Regin
Box 116, SE-428 22 Kllered, Sweden
Besksadress: Bangrdsvgen 35

Telefon: +46 31 720 02 20


Fax:
+46 31 94 01 46
www.regin.se, info@regin.se

Depth: 27 mm