CI - Emergency Water
Project No.:
A00138.310.90
Project Code:
EPSSN
Revision:
V2-00
Date:
2014-07-11
Life cycle:
Final
II. Copyright
Copyright 2014 SMS Siemag AG. All rights reserved.
The reproduction, distribution and utilization of this document as well as the communication of its
contents to others without express authorization is prohibited. Offenders will be held liable for the
payment of damages. All rights reserved in the event of the grant of a patent, utility model or
design. [DIN ISO 16016]
IV. Contact
SMS Siemag AG
SMS Siemag AG
01-02-04-02-14
Page 2 / 9
V. Revision
Revision
V1-00
V1-01
Life cycle
Preliminary
Preliminary
Date
2011-05-02
2014-07-11
Revision
V1-00
V1-01
Life cycle
Preliminary
Preliminary
Comment
Author
zieg
arts
Reviewed
zieg
Approved
preu
preu
01-02-04-02-14
Page 3 / 9
Cover ........................................................................................................................................... 1
II.
Copyright .................................................................................................................................... 2
Revision....................................................................................................................................... 3
(n.a ) ....................................................... 8
01-02-04-02-14
Page 4 / 9
102 56 983
01-02-04-02-14
Page 5 / 9
2.1 General
Emergency cooling water is provided for the following circuits:
Mould cooling circuit / Machine cooling circuit
Spray cooling circuit
The emergency water inlet valves have to be interlocked open so, that they cannot close
during casting operation, i.e. from casting preparations up to the end of tail out.
When the mode prepare cast is achieved, the following sequence will occur for each
system:
Mould-Cooling- and Machine-Cooling-Water:
The control system will verify that PIRAL S11_CA100 PIT0001 (YD02) and
PIRAL S11_CG100 PIT0001 (YE122) does not have low pressure. Upon confirmation of
pressure, the following valve will be pulsed to Automatic and actuated to a defined state:
UV S11_CI100 UV0001 (YW04) Open GOH=1
Spray Cooling Water:
The control system will verify that PIRAL S11_CC100 PIT0001 (YE03) does not have low
pressure. Upon confirmation of pressure, the following valve will be pulsed to Automatic
and actuated to a defined state:
UV S11_CI200 UV0001 (YW23) Open GOH=1
level 1
>H
level 2
>H
Manual on/off-valve
open
GOH=1
Automatic on/off-valve
open
GOH=1
01-02-04-02-14
Page 6 / 9
level
>H
Manual on/off-valve
open
GOH=1
Automatic on/off-valve
open
GOH=1
Automatic on/off-valve
closed
GOL=1
< LL
< LL
< LL
Other Failure:
General break of electric power signal from electrical part
The main cooling water valves will be closed up to the next casting start only in maintenance
mode by the operator.
The switch off of mould cooling water is possible in maintenance mode earliest when tail out
length is 2,5m.
01-02-04-02-14
Page 7 / 9
(n.a )
01-02-04-02-14
Page 8 / 9
Technological Designation
Tag-Number
Start
Cond.
Ready
for
Cast
Warning
Alarm
CI100 LI0001
(YW01)
>H
<L
LISALH
CI100 LI1001
(YW02)
>H
<L
GOH=1
GOH=0
GOH=1
GOH=0
>H
<L
GOH=1
GOH=0
GOH=1
GOH=0
GOL=1
GOH=1
UV
S 11 ;
LISALH
HV
UV
UV
max
LISALH
HV
min
Cast
Stop
S 11 ;
Limit Signals
Fault
Signals
Cast Endangered
during
Cast
CI100 HV0001
(YW03)
CI100 UV0001
(YW04)
CI200 LI0001
(YW21)
CI200 HV0001
(YW22)
CI200 UV0001
(YW23)
CI200 UV1001
(YW24)
01-02-04-02-14
Page 9 / 9