SHEET i OF i
30421007-3CL00011-P0B
33 kV MV CABLE
SIZING REPORT
DESIGN BASIS
FOR
33kV MV CABLE SIZING
DOCUMENT NO : 30421007-3CL-00011-P0B
AUGUST 2004
ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST.MARK'S ROAD
BANGALORE 560001
INDIA
CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O.BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL.00966-1-4633660 : FAX.00966-1-4631150
P0B
30.10.2004
MP
SR
P0A
28.08.2004
MP
SR
PREPARED BY
CHECKED BY
277755671.xls
SECTION :cover sheeet
CLEARED BY
APPROVED BY
SHEET 1 OF 13
277755671.xls
SECTION :cover sheeet
PREPARED BY
CHECKED BY
CLEARED BY
APPROVED BY
SHEET 2 OF 13
CONTENTS
SECTION
DESCRIPTION
1.0
SCOPE
2.0
3.0
GENERAL PARAMETERS
4.0
SIZING CRITERIA
5.0
CONCLUSION
6.0
277755671.xls
SECTION :Index
SHEET 3 OF 13
277755671.xls
SECTION :Index
SHEET 4 OF 13
SCOPE
Scope of this report is to calculate the 33kV Cable size (18/30kV Grade) from Existing Switchgear to Station
Transformer T401 or T402.
2.0
2.1
2.2
IEC 60364-5-523 Selection and erection of electrical equipment-Current Carrying capacities in wiring system.
2.3
2.4
Key One Line Diagram for Arar Plant Drawing No:KA667481, REV P0D
2.5
3.0
GENERAL PARAMETERS
- Depth of Burried Cables
- Ground Temperature at a depth of 1 meter
- Average Thermal Soil resistivity
- Ambient air Temperature
- Short Circuit current
4.0
=
=
=
=
=
1 meter
35 Deg C
2 Deg C-m/w
50 Deg C
31.5 kA for 1 second
SIZING CRITERIA
The Power Cable size shall be selected on the basis of :
- Short circuit Rating.
- Current Carrying Capacity.
- Permissible Voltage Drop.
4.1
31500 x 1
142
221.831
Sqmm
Minimum nearest cable size is 240 Sqmm (Refer SAUDI CABLE COMPANY)
277755671.xls
SECTION :Notes and Sizing Cal
SHEET 5 OF 13
However, as per the Cl.No. 3.03-12 of PTS-1022, page 40 of 336 the size for 33kV (18/30kV grade) cable
to Station Transformers is selected as 1C x 630 Sqmm/Phase Cu, XLPE Unarmoured cable.
4.2
7.5 MVA
=
3 x 33 kV
= 131.21Amps
According to SAUDI CABLE COMPANY Catalogues for Medium Voltage Cable System,the nominal
current carrying capacities are,
Laying Conditions(in duct)
Laid directly in ground or duct ways, Ground
temp.in flat formation 30 DegC and Thermal
resistivity of soil = 1.2K m/W, depth of laying =
0.8m
730
990
975
The following Derating factors have been considered as per SAUDI CABLE COMPANY Catalogues
for the site conditions specified:
Derating factor Kd for Cable Laid in Duct ways :(for both Flat/trefoil formation)
-
Derating Factor Kd
Kd
=
=
K1 x K2 x K3 x K4
0.6256
Derating factor Ka for Cable installed in free air:(for both Flat/trefoil formation)
- ambient Air Temperature 50 DegC
K5
- Laying on Cable Tray(in touching form)
K6
according to:
- installation system in three phase circuits
277755671.xls
SECTION :Notes and Sizing Cal
=
=
0.89
0.86
SHEET 6 OF 13
- No of trays = 3
Derating Factor Ka
Ka
=
=
K5 x K6
0.7654
According to the above, the maximum current carrying capacity of the selected 1C x 630Sqmm/phase
cable is as follows
Maximum current carrying capacity of Cable Laid in Duct ways(after considering derating factor)
Laying cable in flat formation, current
=
Laying cable in trefoil formation, current =
670 x Kd =
730 x Kd =
419.17
456.71
=
=
990 x Ka =
975 x Ka =
757.75
746.27
As per above calculation, 1C x 630 Sqmm/Phase cable can carry the required load current of 131.21Amps
under all site conditions.
4.3
5.0
CONCLUSION
From 33kV Switchgear to Station Transformer T 401 or T 402
18/30 kV Grade(33kV), XLPE insulated, Copper Conductor of size 1C x 630 Sqmm/Phase,
Unarmoured cable has been selected based on the above calculations.
277755671.xls
SECTION :Notes and Sizing Cal
SHEET 7 OF 13
277755671.xls
SECTION :Notes and Sizing Cal
SHEET 8 OF 13
V P0D
277755671.xls
SECTION :Notes and Sizing Cal
SHEET 9 OF 13
t/trefoil formation)
t/trefoil formation)
277755671.xls
SECTION :Notes and Sizing Cal
SHEET 10 OF 13
Amps
Amps
277755671.xls
SECTION :Notes and Sizing Cal
SHEET 11 OF 13
277755671.xls
SECTION :Notes and Sizing Cal
SHEET 12 OF 13
FEEDER DESCRIPTION
LOAD
VOLTAGE
kVA
VOLTS
FULL
LOAD
CURRENT CARRYING CAPACITY OF CABLE (SINGLE
CABLE SIZE SELECTED
CURRENT
RUN)
IFL
AMPS
SQ.MM
IN DUCT
BANKS
7500
33000
277755671.xls
SECTION :Cable Sizing Report Summary
131.22
IN AIR
1 RUN OF 1 RUN OF
1C X 630
1C X
/Phase
630 /Phase
DERATING FACTOR
CABLE LAID IN AIR(CABLE CABLE LAID IN DUCT CABLE LAID IN AIRCABLE LAID IN DUCT
CABLE LAID IN AIR(CABLE
BANKS
CABLE TRAYS
TRAY)
BANKS
TRAY)
(IN BOTH
(IN
FLAT/TREFOIL
BOTH FLAT/TREFOIL
IN FLAT
IN TREFOIL
IN FLAT
IN TREFOIL
IN FLAT
IN TREFOIL
IN FLAT
IN TREFOIL
FORMATION)
FORMATION)
FORMATION FORMATION FORMATION FORMATION
FORMATION FORMATION FORMATION FORMATION
CABLE LAID IN DUCT
BANKS
670.00
730.00
990.00
975.00
0.6256
0.7654
419.15
456.69
757.75
746.27
LENGTH
OF
CABLE
% VOLTAGE
DROP
KM
0.35
0.024
SHEET 13 OF 13