Вы находитесь на странице: 1из 4

Technical Bulletin 3

Dehumidification and the


Psychrometric Chart
R ELATIVE HUMIDITY

NTRODUCTION

The psychrometric chart has been well documented in a


wide variety of technical textbooks and journals. This technical bulletin will not attempt to cover the chart in detail, but,
will highlight those features of the chart which apply to
refrigerant type dehumidification applications. It will define
the terms which form the nucleus of properly applying a
dehumidifier.

Relative humidity is a misapplied term. It is often used in


place of absolute humidity. The key is the word "relative." To
understand this concept, a law of nature must be Reviewed.
Air is a compressible fluid and its volume is represented by
the following equation:

v=K(T/P)
V = Volume
T = Temperature
P = Pressure
K = Constant

T HE CHART

49

Figure 1 shows a typical psychrometric chart. Dry Bulb temperatures are shown on the chart as vertical lines. The horizontal lines represent Dew Point temperatures. Lines representing Wet Bulb temperatures are the straight diagonal
lines sloping downward from left to right.
The curve forming the top edge of the chart is called the
"saturation curve". Air in a condition that falls on any point
along this curve is totally saturated with moisture. Any additional moisture added could not be absorbed and would
remain in a liquid state as condensation.
The sweeping curved lines that follow the saturation curve
are relative humidity lines expressed as percentages. These
lines represent the degree of volume displaced by moisture
with Respect to the total air volume.

48

105

80

42
RH

80
%
RH
%
70

RH
60
%

Re

lat

ve

Hu

%
50

130

120

110

100

90

Bu

Te

mp
e

RH

80

rat

ur

es

70

RH

%
40

60

30

RH

50

45

40

13

40

12

RH
20%

35

30

30
25

H
10% R

20

Dew Point Temperatures


10

0
20

25

30

35

40
12.5 CU. FT.

45

50

55

60
13.0 CU. FT.

65

70

DRY BULB F

75

80

13.5 CU. FT.

85

90

95

100

14.0 CU. FT.

105

GRAINS OF MOISTURE PER POUND OF DRY AIR

75
RH
%
90

70

33
32
31
65

We
t

lb

60

t
di

140

Dry Bulb Temperatures

TIO
RA
TU

38

SA
37

AT
PY

36

AL
35

TH
EN

39

40

(B

41

TU

/L

B)

43

44

45

170

14

12
11
10
9

180

46

47

100

ti

95

150

30
29

19

15

16

a
ur0
at 5

rv

90

160

28
27

26
25
24
23
22
21
20

18
17

Figure 1

on

Cu55

14.5 CU. FT.


85

34

As the air temperature increases, its total volume increases


and decreases on reduction of temperature. Pressure has
the opposite effect. As pressure increases volume decreases.

This is important to understand because water damage


occurs at an absolute humidity concentration regardless of
its relative humidity. This is known as the constant Dew
Point Temperature.

Water, however, is not compressible. Therefore given a specific amount, it will always occupy the same amount of volume.

S ENSIBLE AND LATENT HEATING AND COOLING


There are four types of energy changes when heat of moisture is added or removed. Sensible heat occurs when heat is
added without the addition or reduction of moisture.
Sensible cooling is the reverse. Latent heat, also known as
humidification, is the addition of moisture without changing
the dry bulb temperature. Latent cooling or dehumidification
is the removal of moisture. Figure 3 shows how these are
displayed on the chart.
49

Figure 2 illustrates how this applies to the psychrometric


chart. As moisture laden air is heated or cooled the air volume changes but the moisture does not. Thus there is a
change in relative humidity, without a change in actual water
content.

48

14.5 CU. FT.


95

100

105

47

90

180

46

92F

170

(B
N

80

42

40

TIO

39

RA
TU

75

38

SA

35

80

RH
RH
80
%

31

RH
%
70

65

88 GR.
90

25

RH

78F

60
%

70F

27

26

28

29

30

100

60

24
23
22

RH

60

50

16

19

17

20

18

40

40

RH

30

15

70

55

RH

50

40
40

12

10

13

11

12

14

45

20%

RH

35

30

30
25

10% R

20

92F
80

%
50

21

Figure 2

110

60

32

90
%

70

33

120

10

0
20

25

30

35

40
12.5 CU. FT.

45

50

55

60
13.0 CU. FT.

65

70

DRY BULB F

75

80

13.5 CU. FT.

85

90

95

100

14.0 CU. FT.

105

GRAINS OF MOISTURE PER POUND OF DRY AIR

TH

130

34

EN

140

37

AT
PY

40% RH

150

36

60% RH

AL

80% RH

160

41

TU

/L

B)

43

44

45

78F

70F

85

TECHNICAL BULLETIN 3

Dehumidification and the Psychrometric Chart


Rarely will these occur as shown but will rather be a mixture
of them. A refrigerant dehumidification system is a combination of sensible and latent cooling and sensible heating.
First the system cools the air to reduce the dry bulb temperature to the dew point. Then latent cooling reduces the
absolute humidity and finally the air is reheated increasing
its dry bulb temperature. Figure 4 graphs this process.

By obtaining the starting and finishing grains per pound, the


amount of moisture to be removed can be calculated. The
amount of moisture to be removed is the difference between
these two values known as GR.
Figure 5 shows how a dehumidification system was sized.
The ambient design was 91F dry bulb and 78F wet bulb.
The desired indoor value was 80F dry bulb and 50% relative humidity. The outside ambient has a moisture content of
124 grains and the indoor design has 78 grains. Thus the
required moisture removal rate is 124-78 = 46 grains per
pound of dry air.

D EHUMIDIFIER SIZING

49

To properly apply a dehumidification system, the amount of


moisture to be removed must be calculated. For most applications the only information available is the dry bulb and relative humidity or dry bulb and wet bulb temperatures. The
psychrometric chart is used to plot these two values by finding their intersection and then following the horizontal line
to the right to determine the moisture content in grains per
pound.

48

14.5 CU. FT.


90

95

100

105

180

46

47

85

(B
N

80

42

40

TIO
RA
TU

38

75

SA
37

AT
PY
AL

130

35

TH

C
120

110
RH

80
%
RH
%
70

65

90
RH

60
%

25

27

26

28

29

30

100

60

24

80

23

RH

50

22

70

40

60

16

15

30

RH

50

40
40

12

10

13

11

12

14

45

20%

RH

35

30

30
25

10% R

20

RH

50

19

17

20

18

21

55

10

0
20

25

30

35

40
12.5 CU. FT.

45

50

55

60
13.0 CU. FT.

65

70

DRY BULB F

75

80

13.5 CU. FT.

85

90

95

100

14.0 CU. FT.

105

GRAINS OF MOISTURE PER POUND OF DRY AIR

RH

90
%

32

70

33

34

EN

140

36

Sensible Heating
Sensible Cooling
Humidification
Dehumidification
31

A.
B.
C.
D.

150

39

Figure 3

160

41

TU

/L

B)

43

44

45

170

49

Figure 4

48

14.5 CU. FT.


90

95

100

105

180

46

47

85

(B

80

42

40

TIO
N

39

TU
RA

140

AT

37

75

38

SA

150

130

35

36

EN
TH
AL
PY

160

41

TU

/L
B)

43

44

45

Total Cooling A-B


Sensible Cooling C-B
Latent Cooling A-C
Specific Humidity A (room air)
Specific Humidity C (supply air)
Total Temperature Rise B-D
WA-WB

QL

80
%

31

RH

32

110

RH

30

70

65

RH

28

90
60

27

26

QS
25

Entering Air

23

60

24

80
50

RH

22

70

19

17
16
15

60

Leaving
Evaporator
Coil

45

14

12

%
30

Reheated
Air (Supply)

RH

WA

GR

WB

50

40
40

13

11

12

10
9

RH

%
40

20

18

21

55

50

GRAINS OF MOISTURE PER POUND OF DRY AIR

RH
90
%

70

33

34

120

100

29

=
=
=
=
=
=
=

QT

QT
QS
QL
WA
WB
T
GR

170

20%

RH

35

30

30
25

10% RH

20

10

0
20

25

30

35

40

50

45

55

60

65

75

70

80

85

90

95

100

105

14.0 CU. FT.

13.5 CU. FT.

DRY BULB F

13.0 CU. FT.

49

12.5 CU. FT.

48

14.5 CU. FT.


90

95

100

105

47

85

180

46

Figure 5

80

40

(B
39

N
TIO
RA
37

75

38

TU
SA

140

130

WA

91F DB/78F WB

35

36

AT
PY
AL
TH

120

RH
80
%

31

RH
%
70

65

90
RH
%
60

25

27

26

28

29

30

100

60

24

0%

23

50

RH

80

80F DB

22

70

%
40

RH

60

50

16

19

17

20

18

21

55

15

%
30

RH

WB

50

40
40

13
12

GR

45

14

12
11
10
9

GRAINS OF MOISTURE PER POUND OF DRY AIR

RH
90
%

110

32

70

33

34

EN

Constant
Total Air Volume
WA-WB
7000 GR/LB Air

=
=
=
=

150

20%

RH

35

30

30
25

10% RH

20

4.5
CFM
GR
7000

160

41

TU

LBS/HR = 4.5 x CFM x GR


7000

42

/L

B)

43

44

45

170

10

0
20

25

30

35

40
12.5 CU. FT.

45

50

55

60
13.0 CU. FT.

65

70

DRY BULB F

75

80

85

90

13.5 CU. FT.

95

100

105

14.0 CU. FT.

8300 West Sleske Court


Milwaukee, WI 53223
(414) 357-7400
FAX: (414) 357-8501
www.desert-aire.com
TB3 1195

Вам также может понравиться