Вы находитесь на странице: 1из 8

All-purpose ventilation units

with cross-flow heat exchangers


DUPLEX 1400 10100 Basic-N is a new generation
of all-purpose ventilation units with cross-flow heat recovery
exchangers.
The rooftop version of DUPLEX 1400 10100 Basic-N
compact units are used for comfort ventilation, hot-air
heating and cooling in small facilities, shop floors, stores,
schools, restaurants, shops, sports and industrial halls and
swimming pools.
They are suitable wherever efficient ventilation and possibly
hot-air circulation ventilation and cooling must be provided
atminimum running cost, i.e. the highest efficiency of heat
recovery, low power input of fans and as little noise as
possible.
DUPLEX Basic-N units are compact appliances containing
inasingle cabinet two independently controlled EC fans with
suspended motors, a heat recovery exchanger with large
heat-transfer surface and high efficiency, slide-out supply and
exhaust air class G4, M5 or F7 filters, drain pans and
possibly also an internal bypass with a servo drive and
acirculation damper with a servo drive.
The cabinet has a sandwich structure and consists of
painted metal sheet panels with 30 mm of PIR fill with an
outstanding heat transfer coefficient ( = 0,024 W/mK).
DUPLEX Basic-N ventilation units meet the
requirements of the most stringent European
standards:
Casing properties according to EN 1886
EC motors according to ErP 2015
3
SFP < 0,45 W/(m /h) according to PassivHaus*
Hygienic requests according to VDI6022

Advantages of DUPLEX Basic-N units:


New design of ventilation units with excellent parameters
Great thermal insulation of the casing (class T3)
Reduced thermal idging (class TB2)
Filter side changing
Elegant and efficient connections through the roof
Compact dimensions
Ease of installation
Variable configuration of discharge ports
Unified dimensions of ports
Optional versions with a bypass and circulation damper
High efficiency fans SFP < 0,45 W/(m3/h)*
High heat recovery efficiency of the cross-flow heat
exchanger up to 75 %
Recessed junction box
Integrated control system including temperature sensors
Integrated web server (RD4)
Comfortable unit control with touchscreen CPA
controller (CP)
Comprehensive selection software

*in a limited area


AVAILABLE MODIFICATIONS

B
C
T

(CAN BE COMBINED)

PT
CHF
CHW

with built-in bypass damper


with built-in circulation damper
with built-in hot-water heater

with built-in preheater


with built-in direct chiller
with built-in water-based chiller

Unit ventilators, heat recovery issue 06/2014

OPERATING MODES OF DUPLEX BASIC-N UNITS


i2

T CH

i2

T CH

e2

e2

e2

Mi

Mi

e1

i1

... Fresh outdoor air suction


... Fresh filtered air outlet

Mi

e1

i1

PT

Ventilation with heat recovery


with heating, cooling and preheating

e1
e2

i2

T CH

PT

PT

Ventilation without heat recovery


(via bypass)

Circulation heating
or cooling

i1
i2

e1

i1

... Exhaust air suction


... Exhaust air outlet

T, PT ... Central heating connection


CH ... Cooling connection

SELECTION SOFTWARE

s a v e

y o u r

e n e r g y

For the detailed design of DUPLEX series


units, accessories and control systems
werecommend using our dedicated design
software. You can find it on our website
atwww.atrea.cz or request a CD at our office.

N I T

V E N T I L A T O R S

&

H E A T

ATREA s.r.o., s. armdy 32


466 05 Jablonec n. Nisou
Czech Republic

R E C O V E R Y

Tel.: +420 483 368 111


Fax: +420 483 368 112
E-mail: atrea@atr ea.eu
www.atrea.eu

14 0 0 t o 10 10 0 B a s i c - N

DUPLEX 1400 to 10100


Basic-N Rooftop

PERFORMANCE GRAPHS
DUPLEX BASIC-N

DUPLEX Basic-N
Supply air max. 1)
Extraction air max. 1)
Heat recovery efficiency 2)
Number of versions and positions
Weight 3)
Max. power input
Voltage
Frequency
Revolutions
Heating output T max. 4)
Cooling output CHW max. 4)
Cooling output CHF max. 4)
1)
2)

m3h-1
m3h-1
%

kg
kW
V
Hz
min-1
kW
kW
kW

1 400
1 700
1 680

2 400
2 900
2 700

270330
0,6
230

280340
1,2
230

3 400
20
12
11

2 920
27
18
15

Maximum flow rate through units at zero external pressure


According to air volume

3)
4)

5 400
7 100
6 200
8 300
6 000
7 900
up to 75 %
see table Mounting positions, page 4
340410
400470 450550
2,7
4,8
6,5
400
400
400
50
3 000
2 970
2 700
34
51
64
25
35
51
18
31
48

8 100
8 800
8 700

10 100
11 000
10 700

510620
7,7
400

620740
10
400

2 800
76
60
58

2 570
94
68
65

3 400
4 500
4 400

Depending on equipment
Depending on register type, liquid and flow rates

Pressure reserve pst (Pa)

PERFORMANCE SUMMARY

1 000
Supply section (G4, K750.F)
Supply section with T.3+CHW.5+G4 (K750.F)
Supply section with T.3+CHW.5+F7 (K750.F)
Exhaust section (G4, K750.F)

900
800
700
600
500

asi
0B
010 50.F
X 1 3; K7
PLE M11

7 000

8 000

c-N

6 000

DU

5 000

sic-N

4 000

DUP

0 Ba
540 50.F
LEX110; K7

sic-N

3 000

-N
asic
0B
810 50.F
LEX 2; K7
1
sic-N
DUP M1
0 Ba
710 0:F
LEX116; K75

DUP

2 000

0 Ba
340 0.F
LEX109; K75

1 000

DUP

0
0

sic-N

100

200

0 Ba
240 50.F
LEX108; K7

300

DUP

-N
0 Basic
X 140 .F
DUPLEM107; K750

400

9 000

10 000 11 000 12 000


Air volume (m3/h)

Heat recovery efficiency (%)

HEAT RECOVERY EFFICIENCY

80
70
60

Low limit is without condensation and equal air volume flow (Me = Mi)

1400, 24
0

3400

1400, 2400

5400

71008100

5400

3400

1 000

2 000

3 000

4 000

5 000

10100

7100 8100

50
40
0

10100

6 000

7 000

8 000

9 000

K750.G
K750.F
10 000 11 000 12 000
Air volume (m3/h)

Heating / cooling capacity QT/CH (kW)

HEATING AND COOLING PERFORMANCES

100
80
60

0
0

8100

7100

5400

0
340

40
20

10100

Max. heating capacity data T are valid for


70/50 C water temperature dropand +10
C, r.h. 10 % supply air (after recovery)
Max. cooling capacity data CHW are valid for
30 % water/ethylene-glycol mixture, 6/12 C
temperature drop, +30 C, r.h. 50 % supply air

,
1400
1 000

2400

2 000

maximum heating capacity for T.5


maximum cooling capacity for CHF.5 and CHW.6

3 000

4 000

5 000

6 000

7 000

8 000

9 000

10 000 11 000 12 000


Air volume (m3/h)

DIMENSIONS
BASIC DIMENSIONS

Basic-N Rooftop

BASE FRAME (optional accessorie)

400

B
Y

duct extension
1 000

configuration 4/16

(X+100) x (Y+100)
D

400

22

22

i1
XxY
95

X
D
E

e2
XxY

i1
XxY

75

For position 3 / x

105 X x Y

105

22

105

e2
XxY

XxY

XxY

75

22

XxY

Mi

Me

For position 4 / x

XxY

XxY

B
75

DUPLEX Basic-N
Dimension H
Dimension B
Length L
Dimension N
Dimension U
Dimension P
Dimension J
Dimension M
Condensate drain line
Connecting ports
Dimension X x Y
Base frame
Dimension D
Dimension F
Dimension E
Dimension G (between anchoring holes)
Dimension S
Dimension Q
Dimension T

mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm

1 400
1 605
555
2 560
130
270
135
100
155

2 400
1 605
555
2 560
130
270
135
100
155

3 400
1 605
685
2 560
105
105
105
100
185

5 400
1 605
770
2 560
105
105
105
165
205
32

2 500
1 545
1 228
1 505
795
400
470

2 500
1 545
1 228
1 505
795
400
470

2 500
1 545
1 228
1 505
595
300
370

2 500
1 545
1 228
1 505
595
300
370

TYPES AND DIMENSIONS OF CONNECTING PORTS

Outlet port e2

Outlet port i2

Inlet port i1

Inlet port e1

Y+20

8 100
1 605
1 170
2 560
105
105
105
315
355

95

10 100
1 700
1 390
2 650
105
105
105
340
350

300 x 300 300 x 300 400 x 400 400 x 400 500 x 500 500 x 500 700 x 500

Note: For detailed design and technical data we recommend using our dedicated design software.

X + 20

7 100
1 605
990
2 560
105
105
105
225
265

2 500
1 545
1 228
1 505
395
200
270

2 500
1 545
1 228
1 505
395
200
270

2 590
1 640
1 273
1 600
490
278
287

INSTALLATION AND VERSIONS OF DUPLEX BASIC-N


INSTALLATION VERSIONS AND CONNECTING PORTS

significantly saves the energy lost


DUPLEX units are characterised by a wide range
of accessories the ports may be optionally fitted with flexible
flanges, duct extensions or special hoods if required.

DUPLEX 1400 to 10100 Basic-N units are available in a range


ofversions to facilitate their installation on the roof (outside).
Rooftop units enable to go through the roof which is an excellent
solution that saves material and labour costs in ducting and also

MOUNTING POSITIONS
Position 3; 4 top view
i2

R O O F T O P U N I T S F L AT

e2

i2

e2
e2

e2

3
4

4
4

e1

i1

i1

i1

i1

e1

i1
i1

PORT CONFIGURATION
i2

i2

i2

e2

e2

e2

3/8*

3/10
i1

e1

3/12*
i1

e1

e1
i1

i2

i2

e2

i2

e2

e2
3/14

3/16

e1

e1

3/17
i1

e1

i1

i1
i2

i2

i2

e2

e2

3/18

e2

3/19
e1

e1

3/20*
e1

i1

i1

i1
i2

i2

i2

e2

e2

e2
4/8*

4/10
e1

i1

4/12*

i1

e1

e1
i1

i2

e2

i2

i2

e2

e2
4/14

4/16

4/17

e1

e1

i1

i1

e1

i1
i2

i2

e2

i2

e2
4/18

e2
4/19

e1
i1

* DUPLEX 540010100 Basic-N with max. one coil

i1

4/20*
e1

i1

e1

HANDLING SPACE
MOUNTING POSITIONS CONNECTIONS THROUGH THE ROOF

HANDLING SPACE

condensate drain line. This line must run through a U-bend at least
150 mm high into a sewer. Handling space in front of the unit must
be maintained for replacing filters.
min. 700

DUPLEX units must be installed with the prescribed handling


space around the unit in mind.
Below the unit at least 150 mm must be left to install the DN 32

Handling space

min. 700*

min. T

min.
700*

Mi

Me

min. 700

* only for units with built-in coil

Typ
DUPLEX 1400 Basic-N
DUPLEX 2400 Basic-N
DUPLEX 3400 Basic-N
DUPLEX 5400 Basic-N
DUPLEX 7100 Basic-N
DUPLEX 8100 Basic-N
DUPLEX 10100 Basic-N

T (mm)
600
600
700
800
1 000
1 200
1 400

ACOUSTIC POWER LW AND ACOUSTIC PRESSURE LD1

Type
DUPLEX 1400 Basic-N
DUPLEX 2400 Basic-N
DUPLEX 3400 Basic-N
DUPLEX 5400 Basic-N
DUPLEX 7100 Basic-N
DUPLEX 8100 Basic-N
DUPLEX 10100 Basic-N

Working point
1000 m3/h (200 Pa)
2000 m3/h (200 Pa)
3000 m3/h (200 Pa)
4500 m3/h (200 Pa)
6000 m3/h (200 Pa)
7500 m3/h (200 Pa)
9500 m3/h (200 Pa)

inlet e1
45
62
68
72
71
78
84

Acoustic power Lw [dB(A)]


inlet i1
outlet e2 outlet i2
44
75
73
57
87
89
65
82
86
68
90
84
73
90
87
79
91
92
80
91
95

unit
61
71
71
72
72
78
66

Acoustic pressure LD1 [dB(A)]


at distance of 3 m
40
51
50
52
51
58
46

MODIFICATIONS
DUPLEX BASIC-N BASIC UNIT

DUPLEX xxxx Basic-N


Basic configuration
The compact unit consists of supply and exhaust centrifugal fans with electric motors in anti-vibration mounting,
removable cross-flow air-to-air heat recovery core assembled from thin plastic plates, removable G4, M5 or F7 supply
andexhaust air filters, and a condensate pan with DN 32 flexible hose. Top doors enable easy access to all built-in
components. Front doors for easy filters changing and control system access.

Me.xxx; Mi.xxx
Fans
All units are equipped with high-efficiency fans (ebm-papst and Ziehl Abegg) with free-running impellers and backward
curved blades. Whole range of DUPLEX Basic-N units meets the requirements of the European directive ErP 2015.
Heat recovery core
For every single unit size are two heat recovery exchangers available (K750.F and K750.G),
that differs in heat recovery efficiency and pressure loss.

K750.x

DUPLEX BASIC-N MODIFICATION DESCRIPTION

B.x
By-pass (B)
By-pass of the plate heat recovery core on supply air side. By-pass consists of an opposed-blade damper
andanactuator.
It is fitted next to the recovery core inside the unit; it does not increase size of the unit.
The standard actuator is BELIMO 24 V; other types are available upon request.

C.x
Mixing damper (C)
The mixing damper is used to mix exhaust and supply air. Circulation valve consists of an opposed-blade damper and
actuator. It is fitted next to the recovery core inside the unit, it does not increase the size of the unit.
The standard actuator is BELIMO 24 V; other types are available upon request.

T.x
H o t w a t e r h e a t i n g c o i l ( T )
Built-in water-to-air three-row (possibly multi-row) heating coil; made of copper pipes and aluminum fins. Designed
forsystems up to 110 C and 1,0 MPa. The coil is standardly equipped with flexible connection and a steam-gas
capillary thermostat for freeze protection. Units in modification T (with heating coil) must be equipped with e1 supply
air shutoff damper; an actuator with spring-return function is reccommended. A coil hydraulic kitforheating capacity
control of RE-TPO4 or RE-TPO3 type can be supplied with the coil upon request.

CHF.x
Direct expansion (DX) coil (CHF)
A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage
and a pressure switch for freeze alarm. Three- or multi-row coils with various evaporate temperature are chosen
depending on capacity required, refrigerant type and air parameters. Optionally it is possible to deliver double-circuit
evaporator in division 1:1 or 1:2, or completely atypical with needed capacity.

Chilled water cooling coil (CHW)

CHW.x

A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage.
Three- ormulti-row coils are chosen depending on capacity required, cooling medium type and air parameters.
The cooling coil can be equipped with the R-CHW2 or R-CHW3 hydraulic kit on request.

Integrated pre-heater (PT)

PT.x

Built-in water-to-air three-row heating coil; made of copper pipes and aluminum fins. Designed forsystems up to 110 C

and 1,0 MPa. Non-freezing liquid must be used.

Individual modifications can be freely combined


Example:
DUPLEX-TC (unit with a hot-water heating coil and a mixing damper)
DUPLEX-T-CHF (unit with a hot-water heating coil and a DX coil)

ACCESSORIES
OTHER OPTIONAL ACCESSORIES (BASIC OVERVIEW)

Ke.xxx; Ki.xxx
Shutoff damper e1; i1
Shutoff dampers standardly fitted with BELIMO
actuators are located in the air inlet port.
The following damper types are available:
-- fresh air damper e1 mandatory for C
modification (with mixing damper) and T,
PTmodification (with heating coil)
-- exhaust air damper i1

Fe.xxx; Fi.xxx
Air filtration
All DUPLEX Basic-N units can be equipped with
supply or exhaust air filtration of M5 or F7 class
instead of standard G4 class. Pressure drop of
the filter is then 50 to100 Pa (clean filter)
depending on air flow rate, unit type and dirt
accumulated.

RE-TPO.x
Heating coil
hydraulic kit
Its function is to control heating capacity
ofaheating coil. It consists of a three-speed
pump, two globe shutoff valves and connection
pipes. Further equipment depends on the type:
RE-TPO4 four-way mixing valve with
anactuator for digital control system
RE-TPO3 three-way mixing valve with
anactuator for digital control system

R-CHW.x
Cooling coil
hydraulic kit
Its function is to control cooling capacity of
achilled-water cooling coil. It always consists
oftwo globe shutoff valves and connection pipes.
Further equipment depends on the type:
R-CHW3 three-way mixing valve with
anactuator
R-CHW2 throttling valve with an actuator for
digital control system

Hot water heating coil (TPO)


Separately supplied coil for installation into
round duct.
It is suitable for cramped locations, where
itisimpossible to put the coil inside the unit,
aswell as for rooftop units.
The coil is standardly equipment with the steamgas capillary thermostat.

Electric heating coil (EPO-V)


Separately supplied heating coil to be fitted
into round or rectangular duct. Capacities and
diameters canbefound in respective
catalogue sheets.

FK.x
Spare cartride
filters
Replacement filter cartridges in different sizes
based on the unit type. Available in G4, M5 and
F7 filtration class.

H.P
Flexible
connections
Ports can be equipped with flexible connections
upon request.

CF.XXX
Constant air flow
and pressure
Manometers reading fan pressure together
with controls, enables intelligent fan control of
preselected airflow. This accessory assumes
the unit is equipped with digital controls of DC or
RD4 type. Using a second manometer (optional
accessory) in the supply air duct enables the
user to control constant pressure in the supply
duct.

Duct extension
Rectangular duct extension for connection
through the roof. Standard lenght is 1 m.

MFF
Tu b e m a n o m e t e r s
Accessory for filters for simple view of current
pressure drop. The tube manometers are
obligatory for hygienic unit design in accordance
with the VDI 6022.

Base frame
Dismountable base frame with integrated PIR
(30 mm) insulation and service doors. Standard
heigh 400 mm, others on request.

Feets
The Basic-N units can be equipped with an
adjustable feets (alternative to base frame).

Special hoods
Special weatherproof hoods for inlet (e1) and
outlet (i2) ports. The hood for e1 port in combine
with integrated droplet eliminator.

CONTROLS
DUPLEX Basic-N units are delivered with basic control
components or with complete control systems.
There are three types ofcontrol systems available (Basic,
CPand RD4) according tocustomer needs and an
application. The systems also include variety of sensors
(temperature, humidity, air quality, CO2) for effective
operation control.

Features of the control systems


selection of the most suitable and efficient control
system atthe lowest cost, depending on the application
control system is integrated with the unit, most
components arealready wired and checked in factory,
thus reducing the risk of incorect wiring
no control system project documentation is necessary
forstandard cases, standardized solutions can be used
simple wiring, system simplicity, error indication
qualified technical support and consulting

SUMMARY OF DUPLEX BASIC-N CONTROL SYSTEMS

Type

Use

Basic controls

all electrical components are wired to a junction box


terminal strip inside or outside the unit
standard components are fans, damper actuators,
capillary freeze protection thermostat of hot water
heating coil
more components is included upon customer's
request (exact actuator type, sensors, thermostats,
pressure switches etc.)
suitable for applications with separate delivery of
control system; e.g. large buildings with central control
system etc.

CP controls

RD4 controls

Standard functions
EC fan speed control (stepless)
automatic by-pass damper position
frost protection of heat exchanger
switching of external electric or built-in water heater
input for external switch
inlet and outlet shut-off damper control
minimum and maximum fan speed preselection
analogue input (010 V) for air quality sensor (CO2, RH)
Controller CPA
fully graphic touchscreen
weekly program
party mode
holiday mode
filter change notice
automatic operation based on constant signal
e.g.constant pressure
Controller CPB
rotable controller
switch for heating allowance
Standard functions
EC fan speed control (based on selected mode)
automatic by-pass damper position (heat and cool
recovery)
evaluates and prevents emergency limits based on
measured temperature
ventilation and temperature weekly program setting
A web server and an Ethernet interface built in as
standard connection for remote internet
communication
inputs for switching using 230 V
(4 inputs 3delayed, 1instantenious) switch e.g.
from bathrooms etc.
optional connection of CO2 or RH sensor
max. 2 sensors with a switch or 010 V output
outputs for electric preheater and heater control
(pulse 10 V) or hot-water control (010 V)
Additional RD4-IO module
optional manometer connection to ensure constant
airflow control (see Constant airflow and pressure
control on previous page)
constant pressure control
cooling control outputs (DX- or chilled-water cooling)

Controller

basic version
(fans, actuators, thermostats,
pressure switches
and others on request)

Supervisory control system

Controller CPA
with touchscreen

Controller CPB
rotable controller

CP 18 RD
installation in the standard recessed dual box on the wall

CP 19 RD
installation on wall

Web server
(Standard)

Smartphones Application

Вам также может понравиться