Section
Sheet no./rev. 1
Date
Calc. by
Dr. C. Sachpazis
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Chk'd by
Date
18/01/2014
App'd by
Date
Spanx = 7200 mm
Spany = 7200 mm
lx = 400 mm
ly = 400 mm
lx1 = 250 mm
ly1 = 250 mm
ex = lx1 / 2 = 125 mm
ey = ly1 / 2 = 125 mm
Lx = Spanx lx = 6800 mm
Ly = Spany ly = 6800 mm
ex
ey
1
Span x
Span x
lx
lx
l y1
Sp
an
lx1
ly
Sp
an
ly
Slab details
Depth of slab;
h = 250 mm
1
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Sheet no./rev. 1
Calc. by
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
fcu = 35 N/mm
fy = 500 N/mm
m = 1.15
2
2
c = 20 mm
c = 20 mm
Loading details
2
Gk = 7.000 kN/m
Qk = 5.000 kN/m
G = 1.4
Q = 1.6
b = 1.0
i = 1.0
L = 7000 mm
Depth of reinforcement;
d = 200 mm
Midspan moment;
Support moment;
m = i m = 74.823 kNm/m
Design reinforcement
Lever arm;
K = m / (d fcu) = 0.053
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 187.3 mm
Area of reinforcement designed;
As_des = m / (z fy / m) = 919 mm /m
2
As_prov = D / (4 s) = 2094 mm /m
PASS - Span reinforcement is OK
Check deflection
Design service stress;
2
2
Modification factor;
0.9 26 k1 = 36.151
L / d = 35.000
2
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Sheet no./rev. 1
Calc. by
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
L = 6800 mm
Depth of reinforcement;
d = 202 mm
Midspan moment;
Support moment;
m = i m = 51.442 kNm/m
Design reinforcement
Lever arm;
K = m / (d fcu) = 0.036
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 191.9 mm
2
As_des = m / (z fy / m) = 617 mm /m
As_prov = D / (4 s) = 1005 mm /m
PASS - Span reinforcement is OK
Check deflection
2
Modification factor;
0.9 26 k1 = 37.469
L / d = 33.663
m = 2 i m = 149.646 kNm/m
Lever arm;
K = m / (d fcu) = 0.107
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 172.5 mm
Area of reinforcement required;
As_des = m / (z fy / m) = 1996 mm /m
2
As_prov = D / (4 s) = 2094 mm /m
PASS - Support reinforcement is OK
3
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Sheet no./rev. 1
Calc. by
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
Internal column C3
Consider the reinforcement concentrated in half width strip over the support
Depth of reinforcement;
d = 200 mm
Support moment;
m = 2 i m = 102.884 kNm/m
Lever arm;
K = m / (d fcu) = 0.073
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 182.1 mm
2
As_des = m / (z fy / m) = 1300 mm /m
As_prov = D / (4 s) = 1571 mm /m
PASS - Support reinforcement is OK
B = 7200 mm
Edge distance;
e = 125 mm
Depth of reinforcement;
d = 200 mm
Support moment;
kNm/m
Lever arm;
K = m / (d fcu) = 0.113
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 170.5 mm
Area of reinforcement required;
As_des = m / (z fy / m) = 2134 mm /m
2
As_prov = D / (4 s) = 2513 mm /m
PASS - Support reinforcement is OK
B = 7200 mm
Edge distance;
e = 125 mm
Depth of reinforcement;
d = 200 mm
Support moment;
kNm/m
4
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Calc. by
Dr. C. Sachpazis
Lever arm;
Date
Chk'd by
Date
18/01/2014
App'd by
Date
K = m / (d fcu) = 0.078
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 180.9 mm
2
As_des = m / (z fy / m) = 1383 mm /m
As_prov = D / (4 s) = 1571 mm /m
PASS - Support reinforcement is OK
Corner column A1
Depth of reinforcement;
d = 206 mm
A = lx ly1 = 0.100 m
Support moment;
Lever arm;
2
1/3
K = m / (d fcu) = 0.067
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 189.3 mm
2
As_des = m / (z fy / m) = 1211 mm /m
As_prov = D / (4 s) = 1340 mm /m
PASS - Support reinforcement is OK
d = 202 mm
A = lx1 ly = 0.100 m
Support moment;
Lever arm;
2
1/3
K = m / (d fcu) = 0.055
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 188.8 mm
Area of reinforcement required;
As_des = m / (z fy / m) = 956 mm /m
2
As_prov = D / (4 s) = 1149 mm /m
5
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Calc. by
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
Provide 16 dia bars @ 150 centres - 'U' bars with 1600 mm long legs
Area of reinforcement provided;
As_prov = D / (4 s) = 1340 mm /m
PASS - Edge reinforcement is OK
Distribution reinforcement
Provide 12 dia bars @ 300 centres
Area of reinforcement provided;
As_prov = D / (4 s) = 377 mm /m
L = 7000 mm
Depth of reinforcement;
d = 220 mm
Midspan moment;
Support moment;
m = i m = 74.823 kNm/m
Design reinforcement
Lever arm;
K = m / (d fcu) = 0.044
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 208.6 mm
2
As_des = m / (z fy / m) = 825 mm /m
As_prov = D / (4 s) = 1571 mm /m
PASS - Span reinforcement is OK
Check deflection
2
Modification factor;
0.9 26 k1 = 36.942
L / d = 31.818
L = 6800 mm
6
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Sheet no./rev. 1
Calc. by
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
Depth of reinforcement;
d = 222 mm
Midspan moment;
Support moment;
m = i m = 51.442 kNm/m
Design reinforcement
Lever arm;
K = m / (d fcu) = 0.030
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 210.9 mm
2
As_des = m / (z fy / m) = 561 mm /m
As_prov = D / (4 s) = 1005 mm /m
PASS - Span reinforcement is OK
Check deflection
2
Modification factor;
0.9 26 k1 = 42.062
L / d = 30.631
d = 220 mm
Support moment;
m = 2 i m = 149.646 kNm/m
Lever arm;
K = m / (d fcu) = 0.088
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 195.7 mm
Area of reinforcement required;
As_des = m / (z fy / m) = 1758 mm /m
2
As_prov = D / (4 s) = 2094 mm /m
PASS - Support reinforcement is OK
Internal column C3
Consider the reinforcement concentrated in half width strip over the support
Depth of reinforcement;
d = 220 mm
7
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Sheet no./rev. 1
Calc. by
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Support moment;
m = 2 i m = 102.884 kNm/m
Lever arm;
Date
K = m / (d fcu) = 0.061
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 204.0 mm
Area of reinforcement required;
As_des = m / (z fy / m) = 1160 mm /m
2
As_prov = D / (4 s) = 1571 mm /m
PASS - Support reinforcement is OK
B = 7200 mm
Edge distance;
e = 125 mm
Depth of reinforcement;
d = 220 mm
Support moment;
kNm/m
Lever arm;
K = m / (d fcu) = 0.093
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 194.1 mm
Area of reinforcement required;
As_des = m / (z fy / m) = 1875 mm /m
2
As_prov = D / (4 s) = 2094 mm /m
PASS - Support reinforcement is OK
e = 125 mm
Depth of reinforcement;
d = 220 mm
Support moment;
kNm/m
Lever arm;
K = m / (d fcu) = 0.064
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Calc. by
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
As_des = m / (z fy / m) = 1233 mm /m
As_prov = D / (4 s) = 1571 mm /m
PASS - Support reinforcement is OK
d = 222 mm
A = ly1 lx = 0.100 m
Support moment;
Lever arm;
2
1/3
K = m / (d fcu) = 0.045
Compression reinforcement is not required
z = min((0.5 + (0.25 (K / 0.9))), 0.95) d = 210.1 mm
2
As_des = m / (z fy / m) = 859 mm /m
As_prov = D / (4 s) = 1149 mm /m
PASS - Support reinforcement is OK
Provide 16 dia bars @ 200 centres - 'U' bars with 1600 mm long legs
Area of reinforcement provided;
As_prov = D / (4 s) = 1005 mm /m
PASS - Edge reinforcement is OK
PUNCHING SHEAR
Corner column A1
Design shear transferred to column;
Column perimeter;
uc = lx1 + ly = 650 mm
d = h c - p = 214 mm
2
2
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Date
Calc. by
Dr. C. Sachpazis
Chk'd by
Date
18/01/2014
App'd by
Date
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 1731 mm
1/3
1/4
vc = 0.707 N/mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 2161 mm
1/3
1/4
vc = 0.707 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 2592 mm
1/3
1/4
vc = 0.707 N/mm
Nominal design shear stress at perimeter;
10
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Date
Calc. by
Dr. C. Sachpazis
Chk'd by
Date
18/01/2014
App'd by
Date
Column perimeter;
uc = (2 lx1)+ ly = 900 mm
d = h c - p = 214 mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 3588 mm
1/3
1/4
vc = 0.757 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 4628 mm
1/3
1/4
vc = 0.756 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 5669 mm
1/3
1/4
vc = 0.756 N/mm
11
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Sheet no./rev. 1
Date
Calc. by
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Dr. C. Sachpazis
Chk'd by
Date
18/01/2014
App'd by
Date
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 6710 mm
1/3
1/4
vc = 0.755 N/mm
Nominal design shear stress at perimeter;
Column perimeter;
uc = (2 lx1)+ ly = 900 mm
d = h c - p = 214 mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 2989 mm
1/3
1/4
vc = 0.712 N/mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 3862 mm
1/3
1/4
vc = 0.712 N/mm
12
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Calc. by
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 4734 mm2
Design concrete shear stress;
1/3
1/3
1/4
vc = 0.712 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 5607 mm
1/3
1/4
vc = 0.711 N/mm
Nominal design shear stress at perimeter;
Column perimeter;
uc = lx + (2 ly1) = 900 mm
d = h c - p = 214 mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 4066 mm
13
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Calc. by
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
1/3
1/4
vc = 0.789 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 5241 mm
1/3
1/4
vc = 0.788 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 6416 mm
1/3
1/4
vc = 0.788 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 7592 mm
1/3
1/4
vc = 0.787 N/mm
Nominal design shear stress at perimeter;
14
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Calc. by
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
2
2
Column perimeter;
d = h c - p = 214 mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 9601 mm2
Design concrete shear stress;
1/3
1/3
1/4
vc = 0.847 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 12559 mm
1/3
1/4
vc = 0.847 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 15516 mm
1/3
1/4
15
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Date
Calc. by
Dr. C. Sachpazis
Chk'd by
Date
18/01/2014
App'd by
Date
vc = 0.847 N/mm
Nominal design shear stress at perimeter;
Column perimeter;
d = h c - p = 214 mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 7636 mm
1/3
1/4
vc = 0.785 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 9988 mm
1/3
1/4
vc = 0.785 N/mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
16
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Date
Calc. by
Dr. C. Sachpazis
Chk'd by
Date
18/01/2014
As_ten = 12340 mm
App'd by
Date
1/3
1/4
vc = 0.785 N/mm
Nominal design shear stress at perimeter;
Column perimeter;
uc = lx + (2 ly1) = 900 mm
d = h c - p = 214 mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 2989 mm
1/3
1/4
vc = 0.712 N/mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 3862 mm
1/3
1/4
vc = 0.712 N/mm
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Calc. by
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 4734 mm
1/3
1/4
vc = 0.712 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 5607 mm2
Design concrete shear stress;
1/3
1/3
1/4
vc = 0.711 N/mm
Nominal design shear stress at perimeter;
Column perimeter;
d = h c - p = 214 mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 7636 mm
1/3
1/4
vc = 0.785 N/mm
Nominal design shear stress at perimeter;
18
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Date
Calc. by
Dr. C. Sachpazis
Chk'd by
Date
18/01/2014
App'd by
Date
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 9988 mm
1/3
1/4
vc = 0.785 N/mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 12340 mm
1/3
1/4
vc = 0.785 N/mm
Nominal design shear stress at perimeter;
Column perimeter;
2
2
d = h c - p = 214 mm
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 6544 mm
19
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Calc. by
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
1/3
1/4
vc = 0.746 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 8560 mm
1/3
1/4
vc = 0.746 N/mm
Nominal design shear stress at perimeter;
As_ten = (ky (px + (kx k d)) Asy_ten) + (kx (py + (ky k d))
Asx_ten)
As_ten = 10576 mm
1/3
1/4
vc = 0.746 N/mm
Nominal design shear stress at perimeter;
1/2
r = (lx ly / )
1/3
= 1601
mm
Minimum curtailment length in x-direction;
Corner column
Radius of yield line;
ly))
r = (lx1 ly / )
1/2
1/3
r = 863 mm
Minimum curtailment length in x-direction;
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Calc. by
Dr. C. Sachpazis
Date
Chk'd by
Date
18/01/2014
App'd by
Date
Edge columns
Radius of yield line in x-direction;
ly))
r = (lx1 ly / )
1/2
1/3
r = 1130 mm
Minimum curtailment length in x-direction;
r = (lx ly1 / )
1/2
1/3
ly1))
r = 1130 mm
Minimum curtailment length in y-direction;
21
Job Ref.
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Date
Calc. by
Dr. C. Sachpazis
Chk'd by
Date
18/01/2014
A
ex
1
Sheet no./rev. 1
ey
Span x
l y1
e
s
Date
Span x
l x1
App'd by
f
s
0.2 x Spany
Span y
c
a
e
x
2
j
Span y
f
ly
0.5 x Spany
q
d
p
3
k
k
q
0.2 x Spanx
lx
0.5 x Spanx
When the effective span in the x direction, Lx, is greater than the effective span in the y direction, Ly, the
reinforcement in the outer layer is assumed to be that in the x direction otherwise it is assumed to be that in the y
direction.
22
Section
Civil & Geotechnical Engineering Consulting Company for
Structural Engineering, Soil Mechanics, Rock Mechanics,
Foundation Engineering & Retaining Structures.
Tel.: (+30) 210 5238127, 210 5711263 - Fax.:+30 210 5711461 Mobile: (+30) 6936425722 & (+44) 7585939944, costas@sachpazis.info
Sheet no./rev. 1
Date
Calc. by
Dr. C. Sachpazis
Job Ref.
Chk'd by
18/01/2014
Date
App'd by
Date
REINFORCEMENT KEY
23