IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 11, NOVEMBER 2013

An Islanding Microgrid Power Sharing Approach


Using Enhanced Virtual Impedance Control Scheme
Jinwei He, Student Member, IEEE, Yun Wei Li, Senior Member, IEEE, Josep M. Guerrero, Senior Member, IEEE,
Frede Blaabjerg, Fellow, IEEE, and Juan C. Vasquez

AbstractIn order to address the load sharing problem in islanding microgrids, this paper proposes an enhanced distributed
generation (DG) unit virtual impedance control approach. The proposed method can realize accurate regulation of DG unit equivalent
impedance at both fundamental and selected harmonic frequencies. In contrast to conventional virtual impedance control methods, where only a line current feed-forward term is added to the DG
voltage reference, the proposed virtual impedance at fundamental and harmonic frequencies is regulated using DG line current
and point of common coupling (PCC) voltage feed-forward terms,
respectively. With this modification, the impacts of mismatched
physical feeder impedances are compensated. Thus, better reactive and harmonic power sharing can be realized. Additionally,
this paper also demonstrates that PCC harmonic voltages can be
mitigated by reducing the magnitude of DG unit equivalent harmonic impedance. Finally, in order to alleviate the computing load
at DG unit local controller, this paper further exploits the bandpass capability of conventionally resonant controllers. With the
implementation of proposed resonant controller, accurate power
sharing and PCC harmonic voltage compensation are achieved
without using any fundamental and harmonic components extractions. Experimental results from a scaled single-phase microgrid
prototype are provided to validate the feasibility of the proposed
virtual impedance control approach.
Index TermsDistributed generation (DG), droop control, microgrid, point of common coupling (PCC) harmonic voltage compensation, power sharing, resonant controller, virtual impedance.

I. INTRODUCTION
UE to the growing importance of renewable energybased distributed power generation and the advancement
in power electronics technologies, a large number of inverterbased distributed generation (DG) units have been installed in
conventional low-voltage power distribution systems [1], [2]. To
achieve better operation of multiple DG units, the microgrid concept using coordinated control among parallel DG interfacing

Manuscript received July 19, 2012; revised October 24, 2012; accepted
January 16, 2013. Date of current version May 3, 2013. This paper was presented
in part at the 3rd International Symposium on Power Electronics for Distributed
Generation Systems (PEDG2012) and the Applied Power Electronics Conference and Exposition (APEC2013). Recommended for publication by Associate
Editor A. Kwasinski.
J. He and Y. W. Li are with the Department of Electrical and Computer
Engineering, University of Alberta, Edmonton, AB T6G 2R3, Canada (e-mail:
hjinwei@ualberta.ca; yunwei.li@ece.ualberta.ca).
J. M. Guerrero, F. Blaabjerg, and J. C. Vasquez are with the Institute of
Energy Technology, Aalborg University, 9220 Aalborg , Denmark (e-mail:
joz@et.aau.dk; fbl@et.aau.dk; and juq@et.aau.dk.)
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TPEL.2013.2243757

converters has been well accepted [3][12]. As an important


component of the future smart grid, microgrid can operate in
both grid-connected and intentional islanding modes. As a result, it offers more reliable power to critical loads.
When the microgrid is disconnected from the utility grid to
form an autonomous islanding system, the droop control method
can be applied to realize decentralized power sharing among DG
units [3][17], [27][29]. In this situation, the response of interfacing inverter is similar to the synchronous generator [3].
Nevertheless, the accuracy of power sharing and the stability
of droop-controlled DG units are often affected by DG unit
feeder impedances [4][6]. To cope with stability issues, conventional droop control was modified using virtual frequencyvoltage frame or virtual real and reactive power concept [7], [8].
However, by using modified droop control methods, the accuracy of reactive power sharing can hardly be improved at the
same time. On the other hand, virtual impedance-based methods have been reported in a few literature references, where
the main focus is the behavior of virtual impedance at fundamental frequency [4], [5], [9][11]. In addition to the stability
improvement, the combination of droop slope adjustment and
virtual impedances control [4] also reduces steady-state reactive
power sharing errors. As a result, virtual impedance aided DG
operation is often considered to be a promising way to enhance
microgrid performances [5], [17].
On the other hand, the islanding microgrid may have serious
power quality problems due to the increasing presence of nonlinear loads. To mitigate harmonic distortions, more passive or
active power filters are required. Further, considering that DG
units normally have higher control bandwidth compared to synchronous generators, they can also provide ancillary power line
conditioning service through their interfacing converter control [12][16], [28]. In [12] and [13], the shunt resistive active power filter (R-APF) concept was embedded in the current
control schemes of grid-connected DG unit. Unfortunately, the
current-controlled method can hardly be used to achieve power
sharing among parallel islanded DG units. To solve this issue, an
improved active power filtering method was proposed for multiple DG units in islanded systems [14]. In this method, only an
inductor is adopted as the DG output filter. When LC or LCL
filters are applied, it may not be able to address the inherent resonances of high-order filters. Alternatively, the voltage-controlled
active power filtering method using the adjustment of DG unit
equivalent harmonic impedances was recently proposed in [15].
However, only grid-tied operation of DG units was verified.
Also, the phase angle of DG equivalent harmonic impedance
equals to the phase angle of existing physical feeder impedance.

0885-8993/$31.00 2013 IEEE

HE et al.: ISLANDING MICROGRID POWER SHARING APPROACH USING ENHANCED VIRTUAL IMPEDANCE CONTROL SCHEME

Fig. 1.

5273

Diagram of a single-phase microgrid with parallel DG units.

When multiple DG units are connected to PCC by feeders with


mismatched impedance phase angle, the harmonic impedance
shaping method in [15] will cause harmonic circulating currents
among DG units.
In response to the aforementioned issues, this paper proposes
an enhanced control method using virtual impedance at the fundamental and selected harmonic frequencies. At first, this paper
discusses a reactive power sharing improvement method using virtual fundamental impedance regulation. Afterward, PCC
harmonic voltage compensation and accurate harmonic load
sharing through the adjustment of DG unit equivalent harmonic
impedances are also presented. In addition, with the flexible
arrangement of resonant voltage controllers, the proposed virtual fundamental and harmonic impedances are implemented
without any obvious interference between them, and the fundamental and harmonic components extractions in the DG unit
local controller are avoided. Finally, experimental results are
obtained from a single-phase islanding microgrid prototype.

II. OPERATION PRINCIPLE OF ISLANDING MICROGRID


Fig. 1 illustrates an example of microgrid, where N parallel
single-phase inverters are interfaced to PCC with feeders (Ri,1
to Ri,N and Li,1 to Li,N ). Note that when grid-connected DG
units with LCL filters are switched to islanding operation with
filter capacitor voltage control, the PCC side filter inductors
shall be lumped together with DG feeders. The microgrid also
consists of linear and nonlinear loads at PCC. To provide enhanced voltage quality to PCC loads, DG units shall compensate
PCC voltage distortions through their local voltage regulation.
Finally, the microgrid also has a control center, which sends
the measured PCC harmonic voltage signals to DG local controllers with a low-bandwidth communication system [16], [33].
With this communication link, remote PCC voltage measurement is not necessary for DG unit local controllers. The details
of the communication technique will be explained later in this
section.

A. Principle of Droop Control


The droop control method was developed based on the analysis of steady-state power flow in an inductive feeder [10]. The
conventional frequency and voltage magnitude droop controllers
in a DG unit are shown in (1) and (2) as
DG = DP Pave

(1)

EDG = E Dq Qave

(2)

where and DG respectively are the nominal and reference angular frequencies of the DG unit; E and EDG are
the nominal and reference DG voltage magnitudes; Pave and
Qave are the measured power after low-pass filtering [9], [10];
and Dp and Dq are the droop coefficients of the controllers.
With the knowledge of reference voltage magnitude and angular frequency, the instantaneous DG unit reference voltage
Vdro op can be obtained accordingly. Note that strict frequency
and voltage magnitude ranges [such as DG = (1 1.0%)
and EDG = (1 5%)E ] shall be applied to avoid any dissynchronizations between islanding DG units [8]. Consequently,
the reference voltage Vdro op is always sinusoidal with little
distortion. As will be discussed later, this feature can be further utilized to alleviate the computing complexity of DG local
controllers.
B. Reactive Power Sharing
To share the fundamental load demand in proportion to DG
rated power, the droop slope shall be designed in inverse proportion to their rated power [27]. For the islanded microgrid with
N parallel inverters as shown in Fig. 1, the droop slopes yield
the following formulas:
DP ,1 PRated,1 = DP ,2 PRated,2 = = DP ,N PRated,N
(3)
DQ ,1 QRated,1 = DQ ,2 QRated,2 = = QQ ,N QRated,N
(4)

5274

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 11, NOVEMBER 2013

where DP ,1 to DP ,N are the real power droop slopes of DG units


1 to N, PRated,1 to PRated,N are the rated real power of DG units
1 to N . Similarly, DQ ,1 to DQ ,N and QRated,1 to QRated,N are
the reactive power droop slopes and the rated reactive power of
DG units 1 to N , respectively.
With the aforesaid constraints, an accurate real power sharing
can be achieved at steady state [4], [25]. Nevertheless, the accuracy of reactive power sharing is affected by mismatched DG
unit feeder impedances [4], [25], [27]. To eliminate the reactive power sharing errors, the DG unit equivalent fundamental
impedance shall also be designed to be in inverse proportion to
DG rating. Accordingly, following constraints on DG equivalent
fundamental impedances shall also be satisfied:
RDGf ,1 PRated,1 = RDGf ,2 PRated,2
= = RDGf ,N PRated,N

(5)

XDGf ,1 QRated,1 = XDGf ,2 QRated,2


= = XDG f ,N QRated,N

ZDGf = RDGf + jXDGf = (Ri + j Li ) + (Rv f + j Lv f )


(7)
where Ri and Li are the physical DG feeder resistance and inductance, respectively. Rv f and Lv f are the virtual fundamental
impedance to be implemented by the DG unit. It is obvious that
with the knowledge of physical feeder impedance and the desired DG equivalent fundamental impedance ZDGf , the virtual
fundamental impedance can be determined accordingly. The
DG physical feeder impedance can be estimated through either
online or offline methods. For instance, an on-line estimation
method through the injection of low frequency noncharacteristic
current distortions during DG unit grid-tied operation has been
proposed in [21]. Nevertheless, further discussion on detailed
estimation schemes is out of the scope of this paper.
Once the virtual fundamental impedance is determined, its
associated voltage drop Vv f shall be deducted from Vdro op as
shown in (8):

Vv f

= Vdro op

(Rv f ILinef

Illustration of series virtual fundamental impedance control using (8).

Without considering the dynamics of closed-loop DG voltage


tracking, the equivalent circuit of a DG unit at fundamental
frequency is illustrated in Fig. 2. It can be seen that the virtual
impedance is placed between the physical feeder impedance Ri
and Li , and the voltage reference Vdro op derived from droop
control in (1) and (2). Note again that the small out impedance
[5] associated with the closed-loop DG voltage tracking is not
included in this diagram.

(6)

where RDGf ,1 to RDGf ,N are the resistance of DG equivalent


fundamental impedances, and XDG f ,1 to XDG f ,N are the reactance of DG equivalent fundamental impedances.
Without considering the small output impedance introduced
by DG unit closed-loop voltage tracking [5], the DG equivalent
fundamental impedances in (5) and (6) are composed of two
series parts:

Vref = Vdro op

Fig. 2.

C. Harmonic Power Sharing


For a microgrid with intensive nonlinear loads, an inaccurate sharing of load harmonic currents may lead to DG unit
over current protection [30]. To solve this issue, DG equivalent
harmonic impedance can also be adjusted to ensure better harmonic current sharing. In a microgrid with multiple DG units at
the same power rating, DG units equipped with the same equivalent harmonic impedance will minimize the harmonic circulating current between them. Furthermore, when the magnitude
of DG unit equivalent harmonic impedance is properly reduced,
the PCC voltage quality can be improved [15]. To regulate DG
equivalent harmonic impedances, a line harmonic current feedforward term was added to the DG voltage reference [9], [10].
However, it should be pointed out that previous research was
mainly focused on the situation with small DG physical feeder
impedance. In a weak microgrid with higher feeder impedance,
the harmonic voltage drops on the feeder impedance must be
addressed during DG equivalent harmonic impedance regulation.
To compensate the harmonic voltage drops on the DG feeder,
negative series virtual harmonic impedance can be produced in
a similar way:
Vref = Vdro op

= Vdro op

Vv h


(Rv h ILineh

h Lv h ILineh )

h=3,5,7

Lv f ILinef

(8)

where Vref is the modified voltage reference considering virtual


fundamental impedance regulation, ILinef is the fundamental
component of DG unit line current, and ILinef is obtained
by delaying ILinef for quarter-fundamental cycle. Note that
in the case of a single-phase DG unit, it can be described in
the artificial reference frame, where the -axis describes
the instantaneous values of the system and -axis describes the
orthogonal components.

(9)
where Vref is the modified voltage reference considering series
virtual harmonic impedance control, Vv h is the voltage drop
on the harmonic virtual impedance, Rv h and Lv h are the negative virtual resistance and inductance at hth harmonic order,
ILineh is the hth line harmonic current, and LLineh is obtained by delaying ILineh for quarter-hth harmonic cycle. The
associated equivalent circuit at the selected harmonic frequencies is illustrated in Fig. 3. As shown, the DG unit is modeled
as virtual harmonic impedance connecting to ground, as the

HE et al.: ISLANDING MICROGRID POWER SHARING APPROACH USING ENHANCED VIRTUAL IMPEDANCE CONTROL SCHEME

5275

plex number gain-based compensation strategy at each selected


harmonic frequency as

Fig. 3.

Illustration of series virtual harmonic impedance control using (9).

RDGh + jh LDG h = (Ri + jh Li )/(1 + Gcom plex h )


(12)
where RDGh and LDG h are the equivalent DG resistance and
inductance at hth harmonic frequency, and Gcom plex h is the
complex number feedback gains.
According to (12), the real and imaginary part of the feedback
gain number is obtained as
Gcom plex

voltage reference Vdro op derived from droop control contains


only fundamental component. Nevertheless, to implement virtual series harmonic impedances, the extraction of line harmonic
currents at all selected harmonic orders is necessary. Moreover,
to ensure accurate equivalent harmonic impedance regulation,
preknowledge of harmonic frequency responses of DG feeders
is required. However, the feeder impedance detection method
in [21] is mainly focused on the response around fundamental frequency, and the physical feeder inductance may attenuate
at harmonic frequencies. Therefore, the assumption of fixed
feeder inductance at harmonic frequency may cause capacitive
DG equivalent harmonic impedance (due to over compensation),
which can adversely affect the stability of the system.
Alternatively, another DG unit equivalent harmonic impedance shaping method was proposed in [15], where the DG unit
voltage reference from droop control is modified by deducting
an additional term associated with PCC harmonic voltages as

Gh VPCCh
Vref = Vdro op Vv h = Vdro op
h=3,5,7

(10)
where Vref is the modified voltage reference to adjust DG unit
equivalent harmonic impedance, Vv h is the harmonic voltage
reference. Gh and VPCCh are the real number feedback gain
and the PCC harmonic voltage component at the harmonic order
h, respectively. Note that if the harmonic PCC voltages in (10)
are provided by microgrid central controller, the measurement
of PCC harmonic voltage is not necessary for DG unit local
controllers.
With a positive gain Gh , the magnitude of DG unit equivalent
harmonic impedance ZDGh can be reduced as

ZDGh = (Ri + jh Li )/(1 + Gh ).

(11)

From (11), it can be further seen that the equivalent harmonic


impedance is inductive as long as the physical feeder impedance
is inductive and therefore it provides better stability performance. To eliminate harmonic circulating currents among parallel DG units in a microgrid, the equivalent harmonic impedance
ZDGh of all DG units shall have the same phase angle in addition to magnitude requirements. However, the equivalent harmonic impedance tuning method using real number gain Gh in
(11) cannot regulate the phase angle of the equivalent harmonic
impedance. Accordingly, harmonic circulating current appears
for multiple DG units with unequal feeder impedance angles.
To overcome the impacts of unequal feeder impedance phase
angle among multiple DG units, this paper proposes a com-

= GR h + jGI h = (Ri + jh Li )/

(RDGh + jh LDG h ) 1.

(13)

For virtual harmonic impedance control using complex feedback


gains, the complex number representation of reference harmonic
voltage is illustrated as


(GR h + jGI h )VPCCh
Vv h = Re
h=3,5,7

= Re

GR

VPCCh

h=3,5,7

+ Re

GI

jVPCCh .

(14)

h=3,5,7

As will be discussed in the next subsection, the low-bandwidth


communication system is employed to send the PCC harmonic voltages VPCCh and their respective conjugated signals VPCCh from the microgrid central controller to the DG
unit local controller. It is obvious that they satisfy VPCCh =
jVPCCh , which can be further utilized to simplify associated
terms in (14). As a result, (14) is revised as

Vv h = Re

GR

VP C C h

h = 3 , 5 , 7

+ Re

GI

jVP C C h

h = 3 , 5 , 7

= Re

GR

VP C C h

h = 3 , 5 , 7

+ Re

GI

j(jVP C C h

h = 3 , 5 , 7


h = 3 , 5 , 7

GR

VP C C h

GI

VP C C h

(15)

h = 3 , 5 , 7

With the harmonic voltage reference in (15), the DG unit equivalent circuit at the selected harmonic frequencies is tuned as
presented in Fig. 4, where the combined effects of DG unit
harmonic voltages and physical feeder impedance in the upper
part are modeled as small equivalent harmonic impedance in the
lower part.

5276

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 11, NOVEMBER 2013

At the DG local controller, the received signals need to be


transformed back to the original harmonic signals using InversePark Transformations. Considering that the DG unit fundamental voltage (see Fig. 6) is linked with PCC fundamental voltage
with very little phase angle difference, a DG local PLL is employed to get the angle for Inverse-Park Transformations.
III. PROPOSED VOLTAGE CONTROLLER

Fig. 4. Illustration of equivalent harmonic impedance regulation using PCC


harmonic voltage feedbacks.

By combining the virtual fundamental impedance control in


(8) and harmonic impedance control in (15) together, a new voltage control reference to regulate both equivalent fundamental
and harmonic impedances is obtained in (16) as
Vre f = Vd ro o p

Vv f Vv h

= Vre f d ro o p (Rv f IL in e f Lv f IL in e f )



GR h VP C C h
GI h VP C C h

h = 3 , 5 , 7

In order to minimize the interference between virtual fundamental impedance and virtual harmonic impedance, the control
method discussed so far involves fundamental/harmonic components extraction. This is challenging for low-cost DG units
with limited computing capability. In addition to the adoption
of low-bandwidth communication to avoid the measurement
and extraction of PCC harmonic voltages, the DG unit local
controller can be further simplified. In this section, a modified resonant controller is proposed to combine the fundamental/harmonic components extraction and the closed-loop voltage
tracking together.
A. Conventional Double-Loop Voltage Tracking Scheme

h = 3 , 5 , 7

(16)
D. PCC Harmonic Voltage Measurement
In the previous subsections, the PCC harmonic voltages (with
in the subscript) and their corresponding conjugated signals (with in the subscript) are utilized for single-phase DG
unit equivalent harmonic impedance shaping. These PCC harmonic voltage signals can be transmitted from the microgrid
central controller to the DG unit local controller by using a
synchronized phase-locked loop (PLL)-based communication
algorithm in [16], [27], [28], and [34], where the three-phase
system was selected for case study. For the single-phase system,
various types of single-phase PLL methods have been developed [26]. In this paper, the sliding discrete Fourier transformation (SDFT) [32] method is adopted to construct the PLL
systems. The detailed diagram of the low-bandwidth system is
shown in Fig. 5.
At the microgrid central controller, the fundamental and harmonic PCC voltages are first extracted by SDFT. The fundamental voltage components are adopted to determine the PCC
voltage phase angle PCC as
1
tan (VPCCf /VPCCf )
if VPCCf 0
PCC =
.
1
tan (VPCCf /VPCCf ) + if VPCCf < 0
(17)
Afterward, the harmonic components are transformed into the
values at their corresponding synchronized rotating frames by
Park Transformations. For the steady-state harmonic voltage
signals, they behave as dc components at their respective rotating
frames. These signals at rotating frames are sent to DG unit local
controller by the low-bandwidth communication bus.

First, the DG unit using conventional double-loop voltage


tracking scheme [20] is briefly reviewed in this subsection. The
diagram of DG local controller is presented in Fig. 6. Because of
the whack a mole effects [16], mitigation of PCC harmonics
will inevitably introduce some DG unit voltage distortions. Additionally, due to the interactions between DG harmonic voltage
and harmonic line current, the power calculation using measured
DG voltages and line currents will introduce some steady-state
dc power offsets, which cannot be filtered out by LPFs. As a
result, the fundamental DG voltage VDGf and line current
ILinef components and their conjugate signals VDGf and
ILinef are preferred to be extracted to calculate the fundamental power Pave and Qave . For a single-phase DG unit, its
fundamental power is calculated in the stationary artificial
frame as
Pave = 1/2 (VC f

ILinef

+ VC f

ILinef

(18)

Qave = 1/2 (VC f

ILinef

VC f

ILinef

).

(19)

Moreover, these fundamental voltage and current components


are also needed to carry out another two tasks. The first one is
to form the DG unit local PLL, which is important to realize the
low-bandwidth communication-based PCC harmonic voltage
acquisition as shown in Fig. 5. Additionally, the fundamental
components of DG line current are also utilized to calculate the
voltage drops on the virtual fundamental impedance in (8).
As shown in Fig. 6, the modified voltage referenceVref can be
obtained by combining the voltage reference from droop control,
virtual fundamental impedance regulation, and virtual harmonic
impedance regulation together. Afterward, the double-loop voltage controller is adopted to track this modified voltage reference.
In this diagram, the outer loop uses proportional controllers and
multiple quasi-resonant controllers as shown in (20)

2Kih c s
(20)
GOuter (s) = KP +
s2 + 2c s + h2
h=f ,3,5,7,9

HE et al.: ISLANDING MICROGRID POWER SHARING APPROACH USING ENHANCED VIRTUAL IMPEDANCE CONTROL SCHEME

Fig. 5.

PCC harmonic voltage measurement using low-bandwidth communication system.

Fig. 6.

Power sharing and harmonic compensation using conventional double-loop voltage controller.

where Kp is the outer loop proportional gain, Kih is the gain


of resonant controller at different frequencies, h is the angular frequency, and c is the cutoff bandwidth of resonant
controllers.
The inner loop is a simple proportional control KInner with
filter inductor current feedback as
GInner (s) = KInner .

(21)

B. Proposed Controller Without Fundamental-Harmonic


Components Separation
This section discusses the opportunities of realizing virtual
impedance regulation without using any fundamental and harmonic components extractions (SDFT) in the DG unit local
controller.
First, the input of DG unit local PLL is replaced by the voltage reference Vdro op and its quarter-cycle delayed conjugate
signal Vdro op . This is very convenient as these voltage references are always sinusoidal with little harmonics. Moreover,
when a small equivalent fundamental impedance RDGf and
LDG f is considered for the reactive power sharing accuracy enhancement, the voltage reference Vdro op is even closer to
PCC fundamental voltage VPCCf , compared to the case using
measured filter capacitor fundamental voltage (see Fig. 2). Accordingly, the accuracy of PCC harmonic voltage measurement
in Fig. 5 is also improved.

5277

Furthermore, in the proposed implementation method, the


power calculation uses the voltage references Vdro op and
Vdro op from droop control and nonfiltered DG line current
ILine and ILine . As Vdro op and Vdro op are ripple free,
the harmonic ripples in DG line harmonic current ILine and
ILine will not introduce any steady-state dc power offset and
the dominant ripples in the calculated power are at 120 Hz (due
to the contribution of third harmonic line current). Therefore,
the power ripples can be easily filtered out by first-order LPFs.
The formula of power calculation is then expressed as
Pave =

L P F
(Vd ro o p
2(s + L P F )

IL in e

+ Vd ro o p

IL in e

(22)
Qave

L P F
(Vd ro o p
=
2(s + L P F )

IL in e

Vd ro o p

IL in e

(23)
where LPF is the cutoff frequency of LPFs.
Finally, the voltage reference for virtual fundamental
impedance control is also obtained without using DG line current fundamental components. The fundamental/harmonic component extraction blocks (SDFT) in Fig. 6 can be completely
removed in the proposed method. This can be done by using the
modified voltage drop on fundamental virtual impedance as
Vvf = Rv f ILine

f Lv f ILine .

(24)

5278

Fig. 7.

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 11, NOVEMBER 2013

Power sharing improvement and PCC harmonic compensation using proposed modified voltage controller.

Note that ILine and ILine in (24) are the DG line current
without any filtering.
When (24) is used as the reference voltage drop on virtual
fundamental impedance, it seems that the ripple voltages in Vvf
will have some interferences with virtual harmonic impedance
control. However, it can also be seen that harmonic filtering capability has already been embedded in the resonant controller
in (20). By the flexible arrangement of parallel resonant controllers, the harmonic voltages in Vvf can also be easily filtered
out without any additional efforts.
The improved DG voltage controller is shown in Fig. 7, where
the power calculation, PCC harmonic voltage measurement, and
voltage drop on fundamental virtual impedance are obtained
without any fundamental and harmonic components separation.
To achieve similar performance compared to the case using the
control scheme in Fig. 6, the conventional double-loop voltage
controller is revised as a controller with multiple inputs.
The detailed expression of the proposed outer loop voltage
tracking controller is described as

Ire f =

KP 1

2Ki f c s
+ 2
s + 2c s + f2

+ KP 2 +


h = 3,5,7,9


(Vd ro o p

Vvf VC

2Ki h c s
(0 Vv h VC
s2 + 2c s + h2

(25)
where the voltage drop Vvf for the fundamental virtual
impedance control is mainly regulated by fundamental resonant controller. Therefore, the majority of the harmonic ripples
in Vvf can be filtered out automatically. Meanwhile, resonant
controllers at harmonic frequencies are responsible for the DG
unit harmonic voltage tracking.
It is true that the proportional gain KP 1 and KP 2 can still introduce minor interference between fundamental and harmonic
voltage regulations. However, as indicated by [23] and [24], to
maintain proper system stability margin, the proportional gains
in the PR controller are normally very small compared to resonant controller gains. In [24], it even suggested that the proportional controller gains can be set to zero to achieve better performance. In this paper, as very small values (KP 1 = KP 2 = 0.11)

Fig. 8.

Simplified diagram of single-phase experimental setup.

are selected, proportional gains will not cause any noticeable


disturbances.

IV. EXPERIMENTAL RESULT


Experiments have been performed on a simple single-phase
islanding microgrid, where two H-bridge-based DG units at
the same power rating are connected to PCC with different
feeder impedances. The simplified diagram of the single-phase
experimental setup is shown in Fig. 8. To emulate the behavior
of low-bandwidth communication system, the measured PCC
harmonic voltage signals are sent to DG unit local controller
using a zero-order hold with 0.5 ms delay [16]. The detailed
circuit and control parameters of the system are provided in
Table I.
First, to verify the effectiveness of the proposed reactive
power sharing enhancement method, a low power factor linear RL load is placed at PCC. The corresponding power sharing
performance is presented in Fig. 9. As shown, when the conventional droop control without virtual impedance (corresponding
to Vv f = 0 and Vv h = 0 in Fig. 6) is used in Region1, the real
power sharing is accurate while reactive power sharing appears
as nontrivial errors. On the other hand, the proposed virtual
fundamental impedance control can significantly reduce the reactive power sharing error as shown in Region3. To avoid excess
real power jittering in the beginning of the reactive power compensation, the virtual fundamental impedance is slowly changed
from zero to the desired value in Region2.

HE et al.: ISLANDING MICROGRID POWER SHARING APPROACH USING ENHANCED VIRTUAL IMPEDANCE CONTROL SCHEME

5279

TABLE I
PARAMETERS IN EXPERIMENTS

Fig. 10. Experimental results without the implementation of virtual


impedance. (a) DG unit1 voltage (100 V/div); (b) DG unit2 voltage (100 V/div);
(c) DG unit1 line current (2 A/div); and (d) DG unit2 line current (2 A/div).
(Voltage controller in Fig. 6 is adopted.)

Fig. 11. Experimental results with the implementation of virtual fundamental


impedance. (a) DG unit1 voltage (100 V/div); (b) DG unit2 voltage (100 V/div);
(c) DG unit1 line current (2 A/div); and (d) DG unit2 line current (2 A/div).
(Voltage controller in Fig. 7 is adopted.)

Fig. 9. Power sharing performance in the microgrid. (a) DG unit1 real power
(20 W/div); (b) DG unit2 real power (20 W/div); (c) DG unit1 reactive power
(20 Var/div); and (d) DG unit2 reactive power (20 Var/div).

The associated current and voltage waveforms are also obtained in Figs. 10 and 11. Fig. 10 describes the performance of
the microgrid before the implementation of virtual fundamental
impedance. It can be seen that there are noticeable magnitude
and phase errors between DG unit1 and DG unit2 line currents.
After the implementation of the virtual fundamental impedance,
the enhanced performance is illustrated in Fig. 11. It can be noticed that line currents of DG unit1 and DG unit2 are almost
identical.
To investigate the effectiveness of the proposed virtual harmonic impedance control method, the linear load at PCC is

Fig. 12. Experimental voltage waveform without the implementation of virtual


impedance. (a) DG unit1 voltage (100 V/div); (b) DG unit2 voltage (100 V/div);
and (c) PCC voltage (100 V/div). (Voltage controller in Fig. 6 is adopted.)

replaced by a diode rectifier load. The performance without using any virtual impedance is presented in Figs. 12 and 13. In
Fig. 12, it can be seen that the voltages of DG unit1 and DG
unit2 are sinusoidal with 3.91% and 3.81% THD (total harmonic
distortions), respectively. On the other hand, PCC voltage (with
10.55% THD) is distorted by the harmonic voltage drop on the
DG unit feeders.

5280

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 11, NOVEMBER 2013

Fig. 13. Experimental current waveform without the implementation of virtual


impedance. (a) DG unit1 line current (2 A/div); and (b) DG unit2 line current
(2 A/div). (Voltage controller in Fig. 6 is adopted.)

Fig. 15. Experimental voltage waveform with the implementation of virtual


fundamental and harmonic impedances. (a) DG unit1 line current (2 A/div); and
(b) DG unit2 line current (2 A/div). (Voltage controller in Fig. 7 is adopted.)

Fig. 16. Voltage harmonic spectrum without the implementation of the proposed virtual impedance (corresponding to Fig. 12).
Fig. 14. Experimental voltage waveform with the implementation of virtual
fundamental and harmonic impedances. (a) DG unit1 voltage (100 V/div); (b)
DG unit2 voltage (100 V/div); and (c) PCC voltage (100 V/div).) (Voltage
controller in Fig. 7 is adopted.)

Meanwhile, the harmonic current sharing performance without the control of virtual impedance is presented in Fig. 13.
As virtual harmonic impedance control is not activated in this
test, the DG equivalent harmonic impedance equals to its feeder
harmonic impedance. It is obvious that the DG unit1 absorbs
more harmonic currents as it has smaller equivalent harmonic
impedance.
The microgrid voltage waveforms with the control of the
proposed virtual fundamental and harmonic impedances are
illustrated in Fig. 14. In this experiment, the desired equivalent harmonic impedances for these two DG units are the same
as listed in Table I, and the voltage controller as presented in
Fig. 7 is responsible for voltage tracking. It can be seen from
Fig. 14 that when smaller DG equivalent harmonic impedance
is selected for both DG units, the PCC voltage distortions is
mitigated with 6.24% THD. Meanwhile, due to whack a mole
effects [14], [16], the DG voltages are polluted since the harmonic voltage drops on DG feeders are compensated by DG
units. In this case, the THDs of DG unit1 and DG unit2 are
5.70% and 15.04%, respectively.
The allocation of nonlinear currents with the control virtual
harmonic impedance is obtained in Fig. 15. It shows that the
harmonic load currents are almost equally shared by these two
DG units.

Fig. 17. Voltage harmonic spectrum after the implementation of the proposed
virtual impedance (corresponding to Fig. 14).

To get a better understanding of microgrid harmonic voltage compensation performance using the proposed method, the
THDs of DG units and PCC are illustrated in Figs. 16 and 17.
In Fig. 16, it obviously shows that the PCC harmonic voltage
is higher than DG harmonic voltages without the DG virtual
impedance control, and the dominate PCC voltage distortion
is the third harmonic voltage. After the implementation of the
proposed virtual impedance, it can be seen from Fig. 17 that the
PCC harmonic voltage is mitigated. In this case, the harmonic
voltage drops on DG feeders are compensated by DG local voltage control, and therefore DG unit voltage appears with more
distortions.
Finally, the performance comparison between the proposed
virtual impedance control method and the conventional methods is provided in Table II. It demonstrates that the combination

HE et al.: ISLANDING MICROGRID POWER SHARING APPROACH USING ENHANCED VIRTUAL IMPEDANCE CONTROL SCHEME

5281

TABLE II
PERFORMANCE SUMMARY OF DIFFERENT CONTROL METHODS

of the proposed virtual impedance control and the revised DG


unit voltage controller can realize accurate power sharing performance with reduced DG unit local controller complexity.
V. CONCLUSION
In this paper, an enhanced virtual impedance control scheme
is proposed for islanding microgrids. The proposed method
can realize decoupled control of DG equivalent impedances
at fundamental and harmonic frequencies. When DG equivalent impedance is properly regulated, an accurate power sharing
and the improved PCC voltage quality can be achieved. Furthermore, by exploiting the capability of the conventional droop
control method and resonant voltage controllers, the fundamental and harmonic components extraction in the DG unit local
controller is removed. Experimental results verified the correctness of the proposed accurate power sharing and PCC voltage
quality improvement strategies.
REFERENCES
[1] J. M. Carrasco, L. G. Franquelo, J. T. Bialasiewwicz, E. Galvan,
R. C. P. Guisado, M. A. M. Prats, J. I. Leon, and N. Moreno-Alfonso,
Power-Electronic systems for the grid integration of renewable energy
sources: A survey, IEEE Trans. Ind. Electron., vol. 53, no. 4, pp. 1002
1016, Aug. 2006.
[2] F. Blaabjerg, Z. Chen, and S. B. Kjaer, Power electronics as efficient
interface in dispersed power generation systems, IEEE Trans. Power
Electron., vol. 19, no. 5, pp. 11841194, Sep. 2004.
[3] Qing-Chang Zhong and G. Weiss, Synchronverters: Inverters that mimic
synchronous generators, IEEE Trans. Ind. Electron., vol. 58, no. 4,
pp. 12591267, Apr. 2011.
[4] Y. W. Li and ChingNan Kao, An accurate power control strategy for
power-electronics-interfaced distributed generation units operation in a
low voltage multibus microgrid, IEEE Trans. Power Electron., vol. 24,
no. 12, pp. 29772988, Dec. 2009.
[5] J. He and Y. W. Li, Analysis, design and implementation of virtual
impedance for power electronics interfaced distributed generation, IEEE
Trans. Ind. Appl., vol. 47, no. 6, pp. 25252538, Nov./Dec. 2011.
[6] A. Tuladhar, H. Jin, T. Unger, and K. Mauch, Control of parallel inverters
in distributed AC power system with consideration of line impedance
effect, IEEE Trans Ind. Appl., vol. 36, no. 1, pp. 131138, Jan./Feb.
2000.
[7] K. D. Brabandere, B. Bolsens, J. V. D. Keybus, A. Woyte, J. Driesen, and
R. Belmans, A voltage and frequency droop control method for parallel
inverters, IEEE Trans. Power Electron., vol. 22, no. 7, pp. 11071115,
Jul. 2007.
[8] Y. Li and Y. W. Li, Power management of inverter interfaced autonomous
microgrid based on virtual frequency-voltage frame, IEEE Trans. Smart
Grid, vol. 2, no. 3, pp. 3040, Mar. 2011.
[9] J. M. Guerrero, L. G. Vicuna, J. Matas, M. Castilla, and J. Miret, Output
impedance design of parallel-connected UPS inverters with wireless load

[10]

[11]

[12]

[13]

[14]

[15]
[16]

[17]

[18]
[19]
[20]
[21]
[22]
[23]

[24]
[25]

sharing control, IEEE Trans. Ind. Electron., vol. 52, no. 4, pp. 11261135,
Aug. 2005.
J. M. Guerrero, L. G. Vicuna, J. Matas, M. Castilla, and J. Miret, A
wireless controller to enhance dynamic performance of parallel inverters
in distributed generation systems, IEEE Trans. Power Electron., vol. 19,
no. 4, pp. 12051213, Sep. 2004.
W. Yao, M. Chen, J. Matas, J. M. Guerrero, and Z. Qian, Design and
analysis of the droop control method for parallel inverters considering the
impact of the complex impedance on the power sharing, IEEE Trans.
Ind. Electron., vol. 58, no. 2, pp. 576588, Feb. 2011.
R. I. Bojoi, L. R. Limongi, D. Roiu, and A. Tenconi, Enhanced power
quality control strategy for single phase inverters in distributed generation
systems, IEEE Trans. Power Electron., vol. 26, no. 3, pp. 798806, Mar.
2011.
C. J. Gajanayake, D. M. Vilathgamuwa, P. C. Loh, R. Teodorescu, and
F. Blaabjerg, Z-source-inverter-based flexible distributed generation system solution for grid power quality improvement, IEEE Trans. Energy
Convers., vol. 24, no. 3, pp. 695704, Sep. 2009.
T.-Z. Lee and P.-T. Cheng, Design of a new cooperative harmonic filtering
strategy for distributed generation interface converters in an islanding
network, IEEE Trans. Power Electron., vol. 22, no. 5, pp. 19191927,
Sep. 2007.
J. He, Y. W. Li, and S. Munir, A flexible harmonic control approach
through voltage controlled DG-grid interfacing converters, IEEE Trans.
Ind. Electron., vol. 59, no. 1, pp. 444455, Jan. 2012.
X. Wang, F. Blaabjerg, Z. Chen, and J. M. Guerrero, A centralized control
architecture for harmonic voltage suppression in islanded microgrids, in
Proc. Conf. Rec. 37th Annu. Conf. IEEE Ind. Electron. Soc. (IECON12),
Melbourne, Australia, 2012, pp. 30703075.
J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. de Vicuna, and M. Castilla,
Hierarchical control of droop-controlled AC and DC microgridsA general approach toward standardization, IEEE Trans. Ind. Electron., vol. 55,
no. 1, pp. 158172, Jan. 2011.
D. N. Zmood, D. G. Holmes, and G. H. Bode, Stationary frame current
regulation of PWM inverters with zero steady-state error, IEEE Trans.
Power Electron., vol. 18, no. 3, pp. 814822, Mar. 2003.
P. C. Loh and D. G. Holmes, Analysis of multiloop control strategies for
LC/CL/LCL-filtered voltage-source and current source inverters, IEEE
Trans Ind. Appl., vol. 41, no. 2, pp. 644654, Mar./Apr. 2005.
Y. W. Li, Control and resonance damping of voltage source and current
source converters with LC filters, IEEE Trans. Ind. Electron., vol. 56,
no. 5, pp. 15111521, May 2009.
L. Asiminoaei, R. Teodorescu, F. Blaabjerg, and U. Borup, A digital
controlled PV-inverter with grid impedance estimation for ENS detection,
IEEE Trans. Power Electron., vol. 20, no. 6, pp. 14801490, Nov. 2005.
Z. Staroszczyk, A method for real-time, wide-band identification of the
source impedance in power systems, IEEE Trans. Instrum. Meas., vol. 54,
no. 1, pp. 377385, Feb. 2005.
J. He and Y. W. Li, Generalized closed-loop control schemes with embedded virtual impedances for voltage source converters with LC or LCL
filter, IEEE Trans. Power Electron., vol. 28, no. 4, pp. 18501860, Apr.
2012.
Z. Li, Y. Li, P. Wang, H. Zhu, C. Liu, and F. Gao, Single-loop digital
control of high-power 400-Hz ground power unit for airplanes, IEEE
Trans. Ind. Electron., vol. 57, no. 2, pp. 532543, Feb. 2010.
J. He and Y. W. Li, An enhanced microgird load demand sharing strategy, IEEE Trans. Power Electron., vol. 27, no. 9, pp. 39843995, Jan.
2013.

5282

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 11, NOVEMBER 2013

[26] L. Asiminoaei, F. Blaabjerg, and S. Hansen, Detection is key-harmonic


detection methods for active power filter applications, IEEE Ind. Appl.
Mag., vol. 13, no. 4, pp. 2233, Jul./Aug. 2007.
[27] Q. Zhang, Robust droop controller for accurate proportional load sharing
among inverters operated in parallel, IEEE Trans. Ind. Electron., vol. 60,
no. 4, pp. 12811290, Apr. 2013.
[28] M. Savaghebi, A. Jalilian, J. C. Vasquez, and J. M. Guerrero, Autonomous voltage unbalance compensation in an islanded droopcontrolled microgrid, IEEE Trans. Ind. Electron., vol. 60, no. 4, pp. 1390
1402, Apr. 2013.
[29] Y. W. Li, D. M. Vilathgamuwa, and P. C. Loh, Design, analysis and realtime testing of a controller for multibus microgrid system, IEEE Trans.
Power Electron., vol. 19, no. 5, pp. 11951204, Sep. 2004.
[30] P. Jintakosonwit, H. Fujita, H. Akagi, and S. Ogasawara, Implementation
and performance of cooperative control of shunt active filters for harmonic
damping throughout a power distribution system, IEEE Trans. Ind. Appl.,
vol. 39, no. 2, pp. 556564, Mar./Apr. 2003.
[31] J. C. Vasquez, J. M. Guerrero, M. Savaghebi, J. Eloy-Garica, and
R. Teodorescu, Modeling, analysis, and design of stationary reference
frame droop controlled parallel three-phase voltage source inverters, in
IEEE Trans. Ind. Electron., vol. 60, no. 4, pp. 12711280, Apr. 2013,
online early access.
[32] E. Jacobsen and R. Lyons, The sliding DFT, IEEE Signal Process. Mag.,
vol. 20, no. 2, pp. 7480, Jan. 2004.
[33] M. Savaghebi, A. Jalilian, J. C. Vasquez, and J. M. Guerrero, Secondary
control scheme for voltage unbalance compensation in an islanded droopcontrolled microgrid, IEEE Trans. Smart Grid., vol. 3, no. 2, pp. 797807,
Jun. 2012.
[34] J. He, Y. W. Li, J. M. Guerrero, J. C. Vasquez, and F. Blaabjerg, An islanding microgrid reactive power sharing scheme enhanced by programmed
virtual impedances, in Proc. 3rd IEEE Int. Symp. Power Electron. Distrib.
Generation Syst., Jun. 2012, pp. 229235.

Jinwei He (S10) received the B.Eng. degree from


Southeast University, Nanjing, China, in 2005, and
the M.Sc. degree from the Institute of Electrical Engineering, Chinese Academy of Sciences, Beijing,
China, in 2008. He is currently working toward the
Ph.D. degree at the University of Alberta, Edmonton,
AB, Canada.
In 2007, he was a visiting student at Shanghai
Maglev Transportation Engineering R&D Centre,
Shanghai, China, where he worked on a linear induction motor design project. From 2008 to 2009, he
was with China Electronics Technology Group Corporation. In 2012, he was a
Visiting Scholar in the Department of Energy Technology, Aalborg University,
Aalborg, Denmark. He is the author of more than 40 technical papers in refereed
journals and conferences. His research interests include microgrid, distributed
generation, active power filter, electromagnetic design of linear electric machine, and high-power converter for railway traction drives.

Yun Wei Li (S04M05SM11) received the


B.Sc.Eng. degree in electrical engineering from Tianjin University, Tianjin, China, in 2002, and the Ph.D.
degree from Nanyang Technological University,
Singapore, in 2006.
In 2005, he was a Visiting Scholar with the Aalborg University, Aalborg, Denmark, where he was
involved in the medium voltage dynamic voltage restorer system. From 2006 to 2007, he was a Postdoctoral Research Fellow at Ryerson University, Toronto,
ON, Canada, working on the high-power converter
and electric drives. In 2007, he also worked with Rockwell Automation Canada,
Cambridge, ON, and was responsible for the development of power factor compensation strategies for induction motor drives. Since 2007, he has been with
the Department of Electrical and Computer Engineering, University of Alberta,
Edmonton, AB, Canada, initially as an Assistant Professor and then an Associate Professor from 2013. His research interests include distributed generation,
microgrid, renewable energy, power quality, high-power converters, and electric
motor drives.
Dr. Li serves as an Associate Editor for the IEEE TRANSACTIONS ON
INDUSTRIAL ELECTRONICS and a Guest Editor for the IEEE TRANSACTIONS
ON INDUSTRIAL ELECTRONICS Special Session on Distributed Generation and
Microgrids.

Josep M. Guerrero (S01M04SM08) received


the B.S. degree in telecommunications engineering,
the M.S. degree in electronics engineering, and the
Ph.D. degree in power electronics all from the Technical University of Catalonia, Barcelona, Spain, in
1997, 2000, and 2003, respectively.
He was an Associate Professor in the Department of Automatic Control Systems and Computer Engineering, Technical University of Catalonia,
teaching courses on digital signal processing, fieldprogrammable gate arrays, microprocessors, and control of renewable energy. In 2004, he was at the Renewable Energy Laboratory,
Escola Industrial de Barcelona. Since 2011, he has been a Full Professor in
the Department of Energy Technology, Aalborg University, Aalborg, Denmark,
where he is responsible for the microgrid research program. Since 2012, he
has also been a Guest Professor at the Chinese Academy of Science, Beijing,
China, and the Nanjing University of Aeronautics and Astronautics, Nanjing,
China. His research interests include different microgrid aspects, including
power electronics, distributed energy-storage systems, hierarchical and cooperative control, energy management systems, and optimization of microgrids and
islanded minigrids.
Dr. Guerrero is an Associate Editor for the IEEE TRANSACTIONS ON POWER
ELECTRONICS, the IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, and the
IEEE Industrial Electronics Magazine. He has been a Guest Editor of the IEEE
TRANSACTIONS ON POWER ELECTRONICS Special Issues: Power Electronics for
Wind Energy Conversion and Power Electronics for Microgrids, and the IEEE
TRANSACTIONS ON INDUSTRIAL ELECTRONICS Special Sections: Uninterruptible
Power Supplies systems, Renewable Energy Systems, Distributed Generation
and Microgrids, and Industrial Applications and Implementation Issues of the
Kalman Filter. He is the Chair of the Renewable Energy Systems Technical
Committee of the IEEE Industrial Electronics Society.
Frede Blaabjerg (F13) received the Ph.D. degree
from Aalborg University, Aalborg, Denmark, in 1992.
He was with ABB-Scandia, Randers, Denmark,
from 1987 to 1988. He Joined Aalborg University
in 1988, where he became an Assistant Professor in
1992, an Associate Professor in 1996, and a Full Professor in power electronics and drives in 1998. He
has been a part-time Research Leader with Research
Center Risoe, Denmark, in wind turbines. In 2006
2010, he was the Dean of the Faculty of Engineering,
Science and Medicine and became a Visiting Professor at Zhejiang University, Zhejiang, China, in 2009. His research interests
include power electronics and its applications like in wind turbines, PV systems,
and adjustable speed drives.
Dr. Blaabjerg has been the Editor-in-Chief of the IEEE Transactions on
Power Electronics from 2006 to 2012. He was a Distinguished Lecturer for
the IEEE Power Electronics Society in 20052007 and for the IEEE Industry
Applications Society from 2010 to 2011. He has been the Chairman of the
European Conference on Power Electronics in 2007 and the Power Electronics
for Distributed Generation Systems in 2012, both held at Aalborg. He received
the 1995 Angelos Award for his contribution in modulation technique and the
Annual Teacher Prize at Aalborg University. In 1998, he received the Outstanding Young Power Electronics Engineer Award from the IEEE Power Electronics
Society. He has received 13 IEEE Prize Paper Awards and another Prize Paper
Award at Power Electronics and Intelligent Control for Energy Conservation,
Poland, in 2005. He received the IEEE Power Electronics Society Distinguished
Service Award in 2009 and the Power Electronics and Motion Control Conference (EPE-PEMC) 2010 Council Award. Finally, he has received a number of
major research awards in Denmark.
Juan C. Vasquez received the B.S. degree in electronics engineering from the Autonoma University of
Manizales, Manizales, Colombia, in 2004. In 2009,
he received the Ph.D. degree from the Department of
Automatic Control Systems and Computer Engineering, Technical University of Catalonia, Barcelona,
Spain.
At the Autonoma University of Manizales, he
taught courses on digital circuits, servo systems, and
flexible manufacturing systems. He was as a Postdoctoral Assistant at the Technical University of Catalonia, where he taught courses based on renewable energy systems. He is currently
an Assistant Professor at Aalborg University, Aalborg, Denmark. His research
interests include modeling, simulation, and power management applied to the
distributed generation in microgrids.

Вам также может понравиться