Control & Relay Protection Philosophy for 400KV KOSAMBA Sub Station
A) Bus Bar Configuration
400kV System : Two Main Bus (1 & I type scheme)
220kV System : Three Bus (Two Main and Transfer)
66kV System : Two Bus (Two Main Bus)
Isolator system
400kV System: Five isolator configuration for Dia (One each for Bus &
Line/ICT/Reactor and Three for Tie Bay)
220kV System: Four isolator configuration (Three Bus isolators and a Line isolator)
66kV System: Three isolator configuration (Two Bus isolators and a Line isolator)
B) Control Voltage
220V DC
C) Control & Relay panels
Control & protection Panels to be mounted in Yard Kiosk
D) PLCC panels
PLCC Panels to be mounted in Control Room
PLCC BCU panel to be mounted in Control Room for interface between Control &
protection Panels and PLCC Panels, through GOOSE commands
E) Nos. of Bays & Bus Bar Protection
400 KV System
220 KV System
Page 1 of 4
66 KV System
220 KV Bay
BCPU with
Protocol
66 KV Bay
IEC
61850
220 KV Lines
66 KV Lines
Protection Adopted
Type of Relay
1 Two Distance Protection
Numerical Relays
[shall be of two different make (i.e. 61850 Protocol
from different manufacturers) or of
same make with two different
platforms with same specifications]
-Main-I Protection &
-Main II Protection
with
IEC
Protection Adopted
1 Differential Protection
Type of Relay
Numerical Relay
61850 Protocol
with
IEC
Numerical Relays
61850 Protocol
with
IEC
Numerical Relays
61850 Protocol
with
IEC
-Integrated
Protection
Differential
in
- 220KV side
- Separate static relay
5 Local Breaker Backup (LBB) Protn.
- 400 KV side
-Integrated
in
Differential
Protection
and
Bus
Bar
protection
- 220 KV side
6
7
8
9
10
1
220/66KV Transformer
4
5
6
7
1
2
3
4
Page 3 of 4
in
and
Differential
Bus
Bar
- 66 KV side
66/11 KV Transformer
7
8
9
10
11
1
Buchholz Relay
Pressure Relief Device
Oil & Wdg Temp. Alarm & Tripping
OLTC Oil Surge Relay
Oil Level Low Alarm
Differential Protection
- Integrated in BCPU
Integrated in Transformer
Integrated in Transformer
Integrated in Transformer
Integrated in Transformer
Integrated in Transformer
Numerical Relay with IEC
61850 Protocol
Integrated in Bay Control &
Protection Unit (BCPU) with IEC
61850 Protocol
Integrated in BCPU
Integrated in Transformer
Integrated in Transformer
Integrated in Transformer
Integrated in Transformer
Integrated in Transformer
Numerical Relay
61850 Protocol
Numerical Relay
61850 Protocol
with
IEC
with
IEC
Page 4 of 4