Вы находитесь на странице: 1из 3

HYA3-6 M6 INS

POWERED BY:

L100N6-GEHCS
6KVA at 60Hz

Generating Set Performance

60 Hz

SERVICE
Rated output
Active power output at 1.0 p.f.
Rated speed
Standard voltage

kVA
kW
r.p.m
V

Prime Power
(P.R.P) - (L.T.P)
5.2
5.2

Max. Standby Power


(F.S.P)

5.8
5.8
3600
220/120

Performance data refers to Standard Reference Conditions of ISO 8528: +25C,100m ALT,relative humidity 30%.
During running-in period the output increases by approx. 5% which is taken into consideration at delivery.
Power reduction acc. to DIN ISO 3046.Standard values : Above 100 m ALT approx.1% per 100m , Above 25(77) approx.4% per 10(50)

Himoinsa reserves the right to modify any charateristic without prior notice

Prime Mover Performance


Prime

SERVICE
Rated output
Manufacturer
Engine model
4 Stroke Diesel Engine - Injection type
Aspiration type
Cylinders, number and arrangement
Bore x Stroke
Total displacement
Cooling system
Lube oil specifications
Specific fuel consumption
Specific oil consumption (at full load)
Compression Ratio
Lube oil maximum capacity
Lube oil minimum capacity
Speed governor
Air filter

Kw

mm
L

Lts./h

L
L
Type
Type

Standby

6.6

7.4
YANMAR
L100N6 GEHCS
Direct
Natural Aspirated
1-L
86 x75
0.435
Air
APIclass CD,SAE grade 10W-30
1.72
23.5
1.6
0.6
Mechanical
DRY light duty

PRIME POWER(P.R.P):The prime power is the maximum power available with variable loads for an unlimited number hours. The
average power output during a 24h period pf operation must no exceed 80% of the declared prime power between the prescribed
maintenance intervals and at standard environmental conditions.
STANDARD-BY POWER: Is the maximum power available for a period of 500 hours/year with a mean load factor of 90% of the
declared stand-by power.No kind of overload is permissible for this use.

Synchronous Generator*
Poles
Winding connections (Standard)
Frame mounting
Insulation
Enclose (according to IEC-34-5)
Phases
Voltage regulator
Steady voltage precision

Class

2
Flange B Extention 6
H
IP22
1+N
AVR (Electronic)
Within +/-1.5% from no load to full load with cos0.8-1

* Alternators used by HIMOINSA Gensets meet the requirement of following Standard:IEC 34-1;CEI 2-3; BS 4999-5000; VDE 0530; NF 51-100, 111

HYA3-6 M6 - 6KVA at 60Hz

Generating Set Installation Data

3000 rpm

EXHAUST SYSTEM
Max. exhaust temperature at full load
Exhaust gas flow
Heat rejected to exhuast
M Maximum allowed back pressure
AIR REQUIREMENT
Air requirement for combustion at 100% load / rated load

C
F
m/min
Kcal/Kwh
mm/H20

400
752
2.1
TBA
292.93

m/min
ft/min

0.9
31.78

kW
CV
Ah
Vcc.

1.1 0.3
1.49 0.4
28
12

1.6

14.5

mm
mm
mm
m
kg
dBA

1000
570
825
0.5
180
72.5

ELECTRIC STARTING SYSTEM


Starting motor output
Minimum recommended battery capacity
Auxiliary voltage
LIQUID CAPACITY
Lube oil system including sump, filter, etc..
FUEL TANK CAPACITY
Soundproofed
WEIGHT AND DIMENSIONS SOUNDPROOFED GENSET
Length
Width
Height
Shipping volume seaworthy packing (standard supplier)
Dry weight (with standard accessories)
Noise Level at 7 mt.

* Weights and dimmensions based on standard product configuration(this information could change for optional configurations)

Local distributor

Factory: Ctra.Murcia - San Javier,Km.23.6


30730 SAN JAVIER(Murcia) Spain
Tel:+34 968 19 11 28 / + 34 902 19 11 28
Fax: + 34 968 19 12 17 Export Fax:+ 34 968 19 04 20
info@himoinsa.com www.himoinsa.com

Control & Power Panel

Standard model

Control & Power Panel


1.Start switch
2. Main Line Circuit Breaker for overload protection.
3.Volmeter.
4.Oil lamp.
5. DC Protection.
12VDC out put.

6.