FOR SPC-24
PHOTOELECTRIC
BEAM DETECTOR
Contents
Contents .................................................................................................................... 2
1. General Description .............................................................................................. 4
1.1. Detection principle........................................................................................................................ 4
3. Maintenance........................................................................................................ 15
3.1. General ........................................................................................................................................ 15
3.2. Visual check ................................................................................................................................ 15
3.3. Operation checks......................................................................................................................... 15
3.4. Precautions for insulation resistance checking ........................................................................ 15
3.5. Re-initialisation after cleaning or re-adjustment ..................................................................... 15
6. Specification ........................................................................................................ 19
7. Sensitivity selection ............................................................................................ 20
8. Troubleshooting................................................................................................... 21
8.1. Operating indicator LED fails to flash ...................................................................................... 21
8.1.1. Receiver ................................................................................................................................ 21
8.1.2. Emitter ................................................................................................................................. 21
8.2. Fire signal continues after reset ................................................................................................ 21
8.3. Fault signal cannot be reset....................................................................................................... 21
8.3.1. Fire also occurs..................................................................................................................... 21
8.3.2. Fault only ............................................................................................................................. 21
8.4. Detector generates fire - panel does not register condition ..................................................... 22
8.5. Detector generates a fault - panel does not register condition ................................................ 22
1. General Description
The photo-electric beam detector consists of an emitter and a receiver which face each
other at a distance of between 5 and 100 meters.
In the event of fire the smoke generated will decrease the amount of near infra-red light
incident on the receiver. This decrease is electronically interpreted to identify the
occurrence of fire. An important feature of the detector is that it monitors the protected
space linearly. This enables the detector to identify a fire before it spreads, even when the
smoke is scattered over a large area.
The fire detection sensitivity is switch selectable in 3 settings of 25%, 50% and 70%
beam obscuration.
Wireless
Where the distance between top and bottom of the space is less than 0.5m
Detector Housing
Mounting Plate
Expanded View
Expanded View
Locked
Slide Down
Mounting Plate
A: After mounting the detector to the mounting plate, install the rocking screw.
B: Prevents removal of the detector from the mounting plate.
Expanded View
Press Here
Detector Housing
Detector Cover
b
Expanded View
a
Note: Do not touch the black window of cover
for dew condensation prevention.
2.4. Installation
Refer to section 2.4.1 for installation details:
1 Emitter
1 Receiver
2 Metal mounting brackets
1 Installation manual
4 Fixing screws
Hooking plate
Emitter
24V+
Emitter
E1
E1
E1
E1
E2
E2
E2
E2
24V
24V
24V
24V
0V
0V
0V
0V
zone+
F1
F1
F1
F1
zone-
F2
F2
F2
F2
T1
T2
T1
T2
24V-
Receiver
Receiver
Emitter
24V+
24V-
Emitter
E1
E1
E1
E1
E2
E2
E2
E2
24V
24V
0V
24V
24V
0V
0V
zone+
End of Line Resistor
Value dependant on Control Panel.
Check with manufacturer.
0V
F1
F1
F1
F1
F2
F2
F2
F2
T1
T2
T1
T2
Receiver
Receiver
10
Detector Housing
Detector Cover
Note: Do not touch the black window of cover
for dew condensation prevention.
11
When installing the units in a dimly lit area, it may be difficult to see the receiver and
emitter. In this case alignment can be made by turning the alignment adjustment wheels
until the alignment setting LED can be seen in the centre of the sight hole.
Set the distance switch on the emitter according to the monitoring distance, then close
the cover on the emitter. Then adjust the optical axis on the receiver similarly. (refer to
figure 12).
Sight Hole
Other Detector
ON
ange
5m35m
20m100m
SW1
SW2
12
ensitivity
djusutment
25%
50%
70%
ON
SW1
SW3
Not use
SW2
SW4
Fault signal reset
auto
manual
Emitter
Fault lamp
(yellow)
(green)
Synchronization in
progress
(green)
Automatic adjustment in
progress
(green)
Monitoring in progress
Fire
Fault
Monitor LED
(yellow/
green/red)
Monitor
Optical axis
lamp (green) lamp (green)
*1
*1
*1
(green)
*1
(red)
*1
*1
(green)
*1
*2
*1
13
If the detector goes into fault after initialisation the following conditions may have
occurred :
The cover of the receiver was closed, but the sensitivity was left OFF
The sensitivity has been set but the cover of the receiver was not closed
The light level is too low or too high reaching the beam
The distance setting switch of the emitter has not been set correctly
Run through the alignment and signal strength procedure again until the beam detector
will initialise correctly.
Sensitivity
setting (%)
25%
50%
70%
Type of test
Filter
Value
Filter Number
TSK-B100
SPB-24N
Operation
36%
No.3.5
Non-operation
19%
No.2.5
Operation
65%
No.5
Non-operation
36%
No.3.5
Operation
85%
No.6
Non-operation
50%
No.4.5
14
25%
setting
50%
setting
70%
setting
3. Maintenance
3.1. General
The detector contains an automatic compensation function, which allows the detector to
operate correctly even when the amount of signal reaching the receiver has changed (the
compensation rate is 1%/20 minutes). This means that minor changes due to
contamination and beam alignment will not affect the sensitivity of the detector. There is
of course a limit that the detector can compensate for and this is -50% and +50% of the
initial setting. In order to maintain proper performance the detector should be checked
every six months.
15
Operating Indicator
LED (Green)
E2
E2
E1
E1
Figure 12 Emitter Construction
4.2. Receiver
Push Switch
Sensitivity Switches
SW1, SW2
NC NC
T2
T1
F2
F2
F1
F1
0V
0V 24V 24V
The receiver cover has been left open for three hours
The cover of the receiver was closed, but the sensitivity was left OFF
The sensitivity has been set but the cover of the receiver was not closed within
5 minutes
The limit of contamination has been reached. The detector is only able to
compensate for contamination or alignment change up to a certain point
The obscuration is greater than 90% (a fire alarm signal will also be
produced(This can be changed by configuration. See Chapter 2.6.2.))
17
18
6. Specification
Installation Environment
Principle of Operation
Rated Voltage
Rated Current
Operating voltage range
Peak surge voltage
Supervisory current(average)
Compensation method
Compensation limits
Fire condition
Fault condition
Monitor condition
Monitor condition flash repetition time
1 per 3 seconds
Maximum humidity
Coverage
Sensitivity
Allowable Line Resistance
19
7. Sensitivity selection
If requirements or standards are provided for the sensitivity of the photoelectric beam
detector and a test filter, the selection of sensitivity and its test should be performed in
accordance with them. Otherwise, set the sensitivity select switch so that the sensitivity
falls within the sensitivity setting range recommended by the manufacturer in accordance
with the monitoring distance. See table 3.
100
90
80
70
60
50
40
30
20
10
0
S3(70%)
S2(50%)
Shall not
Alarm
S1(25%)
10
20
30
40 50 60 70
Beam Span L [m]
80
Beam Span
Recommended Sensitivity
Light Obscuration Percentage)
1032.1m
31.867.9m
57.5100m
S1(25%)
S2(50%)
S3(70%)
90
20
100
8. Troubleshooting
The following conditions relate to the SPC-24 itself.
Receiver is damaged
Ensure that the receiver has been powered for more than 120 seconds and that the power
at the receiver is greater than 15V.
8.1.2. Emitter
The operating indicator LED should flash every 3 seconds. If it does not the reason may
be as follows :
Emitter is damaged
Ensure that the emitter has been powered for more than 120 seconds and that the power
at the emitter is greater than 15V.
The optical axis has been altered suddenly. The beam will need re-alignment.
The emitter has stopped working. Check the voltage is present at the emitter.
Insufficient time between fire and reset. At least 3 seconds are required before
resetting the beam after the fire signal has occurred.
21
Contamination limit has been exceeded (light received has changed by more
than 50%)
The CPU is unable to initialise the detector correctly as the values read are out
of range
The detector cover has been closed without setting the sensitivity
To clear these conditions the set up and adjustment procedure should be repeated.
The zone is incorrectly wired to the beam detector. The wiring must be done in
accordance with the relevant wiring diagram
fault
panel
does
not
The zone is incorrectly wired to the beam detector. The wiring must be done in
accordance with the relevant wiring diagram
22
H=ceiling height
l1=side wall distance
P=distance between optical axes
h=mounting height
l2=back wall distance
L=distance between Emitter/Receiver
23
24
25
26
In a room where an air inlet is positioned in the ceiling the beam detector should be
placed near to the air inlet.
Select an appropriate installation place where the detector is unaffected by air being
drawn into a ventilated opening.
The distance between the receiver and the wall immediately behind the receiver
should be less than 11.5.
If more than one detector is installed they must be positioned in such a manner that
they cannot affect each others operation.
The detector should be positioned such that it will not be affected by a shutter or
hanging wall.
The detector should be positioned such that it will be unaffected by moving objects.
The detector should not be installed in a roof top or place where open air circulates.
The detector should be installed where the distance between top and bottom of the
space is greater than 1.7.
The monitoring distance between the emitter and receiver is 32.8 to 328 and the
maximum distance of coverage between the line of the beam is 23.
If there is a probability of people walking in the area of the beam then the beam
detector should be installed at least 9 from the floor.
The beam detector should not be installed at a height greater than 82 unless the fire
detection system is connected directly to the fire brigade or via a central station and
rapid attendance by the fire brigade is possible. In any case the maximum installation
height is 131.