Вы находитесь на странице: 1из 4

Data sheet

Actuator for three point control


AMV 438 SU (spring up)

Description

AMV 438 actuator is used with two and


three-way valves type VRB, VRG, VF and VL up to
DN 50 diameter.
The advanced design incorporates load related
switch-off to ensure that actuators and valves
are not exposed to overload.
Main data:
Nominal voltage:
- 24 V, 50 Hz/60 Hz
- 230 V, 50 Hz/60 Hz
Control input signal: 3 point
Force: 450 N
Stroke: 15 mm
Speed: 15 s/mm
Max. medium temperature: 150 C
Manual operation
Spring return version: spring up (SU)

Ordering

Type
AMV 438 SU

Technical data

DH-SMT/SI

Supply voltage
24 V AC/DC
230 VAC

Power supply
Power consumption
Frequency
Control input
Close of force
Max. stroke
Speed
Max. medium temperature
Ambient temperature
Storage and transport temperature
Protection class
Degree of protection
Weight
- marking in accordance with
standards

VD.LE.P1.02 Danfoss 08/2009

Code No.
082H0122
082H0123

24 VAC/DC, 230 VAC; +10 to 15%


12 VA
50 Hz/60 Hz
3-point
450 N
15 mm
15 s/mm
150 C
0 55 C
40 +70 C
II
IP 54
2.3 kg
Low Voltage Directive (LVD) 2006/95/EC: EN 60730-1, EN 60730-2-14
EMC Directive 2004/108/EC: EN 60730-1, EN 60730-2-14

Data sheet

Actuator for three point control AMV 438 SU

Installation

Mechanical
The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards. Connecting the actuator to the valve
body does not require a tool. Allow for necessary
clearance for maintenance purposes.

Electrical
Electrical connections can be accessed by
removing the cover. Two holes for M16 1.5
cable can be made. A rubber cable gland is
provided. Note that any cable gland that is used
must not compromise the appliances IP rating
and the cable should have a minimum diameter
of 6.2 mm.

Manual override
4mm

On spring versions manual override is achieved


by disconnecting the power supply, removing
the cover and inserting a 4 mm Allen key
(not supplied) into the top of the positioning
spindle and turning the key against the spring.
Observe the direction of rotation symbol. To
hold a manual override position, the key must be
wedged.

VD.LE.P1.02 Danfoss 08/2009

If manual override has been used then X and Y


signal are not correct until the actuator reaches
its end position. If this is not accepted reset the
actuator, or apply accessory active return kit.

DH-SMT/SI

Data sheet

Actuator for three point control AMV 438 SU

Wiring

Terminals 1, 3:
Control voltage input from the controller.
Terminals 4, 5:
Output used for position indication or
monitoring.

230 Vac version:


Do not touch anything on
the PCB! Lethal voltage!

L
Power supply 24 V~ or 230 V~
N
Common (0 V)

Wiring - accessories

Additional switch (2x)

Disposal

The actuator must be dismantled and the


elements sorted into various material groups
before disposal.

Commissioning

Complete the mechanical and electrical


installation and perform the necessary checks
and tests:
- Apply power
- Apply the appropriate control signal and
check that the valve stem direction is correct
for the application.
The unit is now fully commissioned.

DH-SMT/SI

VD.LE.P1.02 Danfoss 08/2009

Additional switch (2x) and potentiometer

Data sheet

Actuator for three point control AMV 438 SU

Dimensions

Actuator - valve
combinations

VD.LE.P1.02

AMV 438 SU +
VRB, VRG

AMV 438 SU +
VF, VL

Produced by Danfoss A/S 08/2009