The sound
of silence
Designing and producing silent transformers
Ramsis Girgis, Jan Anger, Donald Chu
Silence is a source of great strength. Although these words were first coined by the ancient Chinese philosopher Lao Tzu, they could equally well apply to modern power transformers. As important as these devices are in assuring our power supply, it is important
not to ignore the negative sides of their operation. One of the major issues here is that
they produce annoying noise.
Probably the strictest noise ordinance in the world is enforced in New York City. To be
able to supply transformers for installation here, ABB had to meet extremely demanding
requirements. Through the companys deep and detailed understanding of transformer
vibrations and noise, it was able to fulfill these demands and is now well poised to supply
low and ultra low noise transformers to other major cities, around the world.
47
oday, the world is showdecibels (dB), where, a deci1 Noise level contours around a small substation with two 40 MVA
ing increasing concern
bel is defined as 10 Log10
transformers. Where such noise exceeds certain levels, it can be of
over environmental matters,
(sound pressure). Sound
great discomfort to humans.
and the minimization of
levels are typically presented
T -180
noise in the vicinity of resiand specified in A-weighted
dential areas is one aspect
decibels; dB(A), where the
N
that is growing in imporsound levels are attenuated
PLOTTED:
BAND:
tance. Transformers exhibit
according to their frequencies
Octave
Total
vibrations while operating,
per an A-filter, which deSPL dB (A)
and generate a characteristic
picts the frequency response
50
hum classified as noise 1 .
of the human ear 3 .
45
This noise is characterized
40
by mainly four pure tones,
There are at present industry
35
the frequencies of which are
standards (IEEE and IEC) that
30
in the range of human
specify how transformer noise
25
speech 2 . The noise, being
is to be measured. However,
20
of a marked tonal character,
some customers require recauses irritation and discomporting of the total collective
fort. It is hence important to
noise level of the transformer
ferred to in this article as the silent
assure that residential areas are not
in dB(A), whereas others require retransformers, to the ConEd company
disturbed. This work is of especial importing of individual frequency comin Manhattan, NY, where the noise
portance in urban areas where houses
ponents. Some customers require
ordinance is the toughest in the world.
are built very close to power-transmismeasurement of only the core and fan
This is discussed in more detail later in
sion and distribution-size transformers.
noise, and some require measurement
this article.
of the total noise level of the transIn many countries, local and national
former, including load noise.
Noise level and frequency spectrum
governments have stipulated maxiSound produces minute oscillatory
Transformer noise
mum permissible noise levels. These
There are three sources of sound/
changes in air pressure and is audible
permissible levels vary in value from
noise in power transformers:
to the human ear when its level is
normal levels in rural areas, to lower
Core noise, caused by magnetostricabove a certain threshold and the frevalues near large metropolitan cities,
tion effects
quency of the pressure oscillations is
and to ultra-low values in some parts
Load noise, caused by electromagin the 20 Hz to 20 kHz range. Sound
of New York City.
netic forces in the windings and
level limitations are typically deterstructural parts due to leakage flux
mined by the human perception of
In order to fulfill these noise restricassociated with the current
sound, which is both logarithmic and
tions, it is necessary to understand the
Noise generated by the operation of
frequency dependent. For example,
total process of sound generation, transthe cooling equipment, fans and
the human ear is ten times less sensimission and radiation. Such knowledge
pumps
tive to sound at 100 Hz than it is to
has enabled ABB to successfully design
sound at 1,000 Hz, and each doubling
and build quiet transformers for cusCore noise, caused by magnetostriction
of the absolute sound pressure is felt
tomers in different parts of the world.
Magnetostriction is a term used for
as a small addition on the sound
Most recently, ABB delivered a number
the small mechanical deformations of
level. Sound is therefore measured in
of ultra-low-noise transformers, reTypical frequency spectrum of noise produced by a 60 Hz power
transformer
80
0
-10
Attenuation, dB
70
60
50
-20
-30
40
-40
30
0
120
240
360
480
600
720
Frequency / Hz
48
840
960
1080 1200
10
20
40
100
200
400
1k
2k
4k
10k
20k
Frequency / Hz
Lower-noise transformers
Lower core noise
-2.0
-1.0
0.0
1.0
2.0
-1
2
Flux density (T)
49
50
But these were not the only challenges. The ConEd requirements impose
other design restrictions. These are:
Tight limits on weight, width, and
height to permit transportation in
Manhattan
Tight limits on transformer impedance variation across the range of
the tap changer
Significant overload requirements
(up to 200 percent)
Limits on temperatures of hot-spots
in the windings at different loads
The designs requested by ConEd were
for their standardized 65 MVA and
93 MVA network transformers.
Solutions for the ConEd transformer
Octave band
center
frequency (Hz)
125
250
500
Permissible
level (dB)
71
64
57
10
11
For the next few years, the ABB technology development team worked
very hard on all of the seven noiserelated technology areas discussed in
this article. As a result of the progress
achieved, ConEd awarded ABB the
contract to produce the first ultra-lownoise 93 MVA transformers. These
transformers were designed using the
technology available at that point in
time and it was successfully tested
and delivered in 2005. The first of
these was equipped with a sound
enclosure 9 . The second and third
transformers had only sound panels
attached to the tank walls 10 .
Ramsis Girgis
ABB Inc.
St. Louis, MO, USA
ramsis.girgis@us.abb.com
Jan Anger
ABB Inc.
Ludvika, Sweden
jan.anger@se.abb.com
Donald Chu
ConEd
New York, NY, USA
chud@coned.com