Академический Документы
Профессиональный Документы
Культура Документы
interfaced networks
Manjula Dewadasa
B.Sc (Hons) in Electrical Engineering
Keywords
Distributed generation, Microgrids, Distributed generator protection, Converter
interfaced distributed generators, Protective relays, Inverse time admittance relay,
Relay coordination, Relay Grading, Islanded operation, Re-synchronisation,
Reclosing, Fold back current control, Fault detection, Fault isolation, Arc extinction,
System restoration.
Abstract
With the rapid increase in electrical energy demand, power generation in the
form of distributed generation is becoming more important. However, the
connections of distributed generators (DGs) to a distribution network or a microgrid
can create several protection issues. The protection of these networks using
protective devices based only on current is a challenging task due to the change in
fault current levels and fault current direction. The isolation of a faulted segment
from such networks will be difficult if converter interfaced DGs are connected as
these DGs limit their output currents during the fault. Furthermore, if DG sources are
intermittent, the current sensing protective relays are difficult to set since fault
current changes with time depending on the availability of DG sources. The system
restoration after a fault occurs is also a challenging protection issue in a converter
interfaced DG connected distribution network or a microgrid. Usually, all the DGs
will be disconnected immediately after a fault in the network. The safety of
personnel and equipment of the distribution network, reclosing with DGs and arc
extinction are the major reasons for these DG disconnections.
In this thesis, an inverse time admittance (ITA) relay is proposed to protect a
distribution network or a microgrid which has several converter interfaced DG
connections. The ITA relay is capable of detecting faults and isolating a faulted
segment from the network, allowing unfaulted segments to operate either in grid
connected or islanded mode operations. The relay does not make the tripping
decision based on only the fault current. It also uses the voltage at the relay location.
Therefore, the ITA relay can be used effectively in a DG connected network in which
fault current level is low or fault current level changes with time. Different case
studies are considered to evaluate the performance of the ITA relays in comparison
iii
iv
Table of Contents
List of figures
ix
List of tables
xiii
List of appendices
xv
xvii
vi
vii
References
135
143
Appendix-A
145
Appendix-B
147
Appendix-C
153
viii
List of Figures
Fig. 2.1 Different types of communication networks (Adapted from [55]) .... 24
Fig. 3.1 A radial distribution feeder................................................................. 28
Fig. 3.2 The variation of normalised admittance ............................................. 29
Fig. 3.3 Relay tripping characteristic curve ..................................................... 30
Fig. 3.4 A radial distribution feeder with relays .............................................. 31
Fig. 3.5 Relay protection zones and relay coordination .................................. 32
Fig. 3.6 Relay settings based on different forward and reverse reach ............. 33
Fig. 3.7 Relay connection diagram to the system ............................................ 36
Fig. 3.8 Process of relay tripping decision making ......................................... 36
Fig. 3.9 Relay tripping characteristics of different zones ................................ 41
Fig. 4.1 A radial distribution feeder with relays .............................................. 47
Fig. 4.2 Inverse time overcurrent relay grading .............................................. 47
Fig. 4.3 MHO relay characteristic ................................................................... 50
Fig. 4.4 MHO relay zone settings and timing diagram ................................... 50
Fig. 4.5 ITA relay grading ............................................................................... 52
Fig. 4.6 Faulted line with a relay ..................................................................... 52
Fig. 4.7 ITA relay characteristic in R-X diagram ............................................ 54
Fig. 4.8 Radial distribution feeder with DGs................................................... 55
Fig. 4.9 OC and ITA relay grading .................................................................. 57
Fig. 4.10 OC and ITA relay response when DG1 is connected....................... 58
Fig. 4.11 Distance and ITA relay response when DG1 is connected .............. 58
Fig. 4.12 OC and ITA relay time-current characteristic .................................. 59
Fig. 4.13 ITA relay response in grid connected mode..................................... 60
Fig. 4.14 ITA relay response in islanded mode ............................................... 61
Fig. 4.15 ITA relay response for SLG fault in islanded operation .................. 61
Fig. 4.16 System with two parallel transformers ............................................. 62
Fig. 4.17 Relay response for impedance change ............................................. 62
Fig. 4.18 Distribution feeder with DGs and loads ........................................... 63
Fig. 4.19 ITA relay response when fault resistance is 0.05 ......................... 64
ix
Fig. 4.20 Fault current seen by each ITA relay along the feeder..................... 65
Fig. 4.21 Random load and DG distribution profiles along the feeder............ 66
Fig. 4.22 ITA relay response for random load and DG distribution profiles .. 66
Fig. 4.23 IEEE 34 node test feeder with ITA relays ........................................ 67
Fig. 4.24 ITA relay response for SLG fault at node 858 ................................. 69
Fig. 4.25 ITA relay response for SLG fault at node 842 ................................. 69
Fig. 4.26 ITA relay response for SLG fault at node 862 ................................. 70
Fig. 4.27 Mesh network under study ............................................................... 71
Fig. 4.28 Equivalent representation of the faulted network............................. 74
Fig. 4.29 ITA relay response for different values of fault resistances and DG
currents ............................................................................................ 76
Fig. 5.1 Proposed fold back characteristics ..................................................... 82
Fig. 5.2 System restoration .............................................................................. 85
Fig. 5.3 Simulated radial feeder with DGs ...................................................... 92
Fig. 5.4 Calculated ITA relay response for a three phase fault ....................... 94
Fig. 5.5 DG1 response (a) output voltage (b) output current (c) real power
output................................................................................................. 95
Fig. 5.6 DG1 response (a) output voltage (b) output current (c) real power
output................................................................................................. 97
Fig. 5.7 System behaviour for an arc fault (a) arc voltage (b) arc current (c) arc
resistance (d) relay response ............................................................... 99
Fig. 5.8 DG1 behaviour for an arc fault (a) output voltage (b) output current 99
Fig. 5.9 DG1 behaviour when downstream relay fails (a) output voltage (b)
output current .................................................................................. 100
Fig. 5.10 DG1 response during fault and system restoration ........................ 102
Fig. 5.11 DG1 terminal voltage and output current ....................................... 103
Fig. 6.1 Experimental test feeder ................................................................... 106
Fig. 6.2 Single line diagram of experimental setup ....................................... 106
Fig. 6.3 NI PXI-1042Q chassis ...................................................................... 107
Fig. 6.4 ITA relay implementation on LabVIEW.......................................... 108
Fig. 6.5 Simplified single line diagram of the test feeder .............................. 109
Fig. 6.6 Calculated relay response in different zones for bolted faults ......... 111
Fig. 6.7 The variation of voltage and current for SLG faults at BUS-2 ........ 113
Fig. 6.8 The variation of voltage and current for SLG faults at BUS-3 ........ 114
Fig. 6.9 The variation of voltage and current for SLG faults at BUS-4 ........ 116
Fig. 6.10 The variation of voltage and current for SLG faults at BUS-5 ...... 117
Fig. 6.11 Voltage and current for a fault at BUS-2 ....................................... 118
Fig. 6.12 Voltage and current for a fault at BUS-3 ....................................... 119
Fig. 6.13 Voltage and current for a fault at BUS-4 ....................................... 119
Fig. 6.14 Voltage and current for a fault at BUS-5 ....................................... 119
Fig. 6.15 Change of parameters during a resistive fault at BUS-2 ................ 122
Fig. 6.16 Test feeder with an infeed .............................................................. 123
Fig. 6.17 Change of parameters for a fault at BUS-2 with fault resistance and
infeed ............................................................................................. 124
Fig. 6.18 A SLG fault at synchronous generator connected feeder ............... 125
Fig. 6.19 Current and voltage during a SLG fault ......................................... 126
Fig. 6.20 Values of relay parameters during a SLG fault .............................. 127
Fig. 6.21 Faulted current and voltage during a SLG fault ............................. 128
Fig. 6.22 Values of calculated relay parameters during a SLG fault............. 129
xi
List of Tables
Table 3.1 Selection criterion of a directional element ..................................... 35
Table 4.1 System parameters ........................................................................... 55
Table 4.2 OC relay settings ............................................................................. 56
Table 4.3 Zone characteristics of ITA relay .................................................... 56
Table 4.4 System parameters ........................................................................... 64
Table 4.5 ITA relay forward and reverse reach settings.................................. 68
Table 4.6 System parameters ........................................................................... 71
Table 4.7 Zone-3 grading of ITA relays .......................................................... 72
Table 4.8 Fault clearing time of ITA relays .................................................... 73
Table 5.1 Simulated system data ..................................................................... 92
Table 5.2 Arc model parameters ...................................................................... 97
Table 6.1 System parameters of the experimental setup ............................... 108
Table 6.2 Relay reach setting and tripping characteristic in each zone ......... 110
Table 6.3 ITA relay response for faults at BUS-2 ......................................... 113
Table 6.4 ITA relay response for faults at BUS-3 ......................................... 114
Table 6.5 ITA relay response for faults at BUS-4 ......................................... 115
Table 6.6 ITA relay response for faults at BUS-5 ......................................... 116
Table 6.7 ITA relay response for SLG faults with higher source impedance 118
Table 6.8 Relay parameters during a resistive fault ...................................... 121
Table 6.9 Change of relay parameters due to fault resistance and infeed ..... 123
xiii
List of Appendices
Appendix-A Positive sequence admittance seen by ITA relay.....145
Appendix-B Converter structure and control147
Appendix-C LabVIEW program...153
xv
CB
Circuit breaker
CT
Current transformer
DFT
DG
Distributed generator
FFT
IDG
Ip
Pickup current
IRa, IRb
Ir
ITA
lp
ls
MI
OC
Overcurrent
PCC
R1, R2, R3
Protective relays
Rf
Fault resistance
SLG
TDS
tp
Tripping time
VSC
Vs
Source voltage
xvii
VT
Voltage transformer
Ym
Measured admittance
Yr
Normalised admittance
YRK1
Yt
Total admittance
Zdg
ZLG
Apparent impedance
xviii
Signature:.
Date:.
xix
Acknowledgements
First and foremost, I would like to convey my sincerest and deepest thanks to
my supervisors, Prof. Gerard Ledwich and Prof. Arindam Ghosh, for their
incomparable guidance and endless encouragement throughout my doctoral research.
It has been a great privilege for me to work under this supervision.
I wish to express my thanks to the Faculty of Built Environment and
Engineering, Queensland University of Technology (QUT) for providing me with
financial support during my research candidature.
I would also like to thank staff in the research portfolio office in QUT for their
generous support and assistance throughout the candidature, and the staff in the
School of Engineering Systems for providing such a helpful environment. Further, I
am thankful to staff in the Power Engineering Group for their valuable advice.
I would like to extend my appreciation to all the technical staff who supported
me during the laboratory experiments. Without this support, experimental work
would not have been successful.
I would further like to thank to all of my friends for sharing valuables ideas, for
supporting me during the experimental work, and for making the research period an
enjoyable one. Also, I am grateful to my parents for encouraging me to pursue higher
studies, and I thank them and my relatives for their constant support.
Last but not least, I would like to express my heartiest appreciation to my
beloved wife for her encouragement and support during the period of research in
Australia. Also, I cannot forget my son who brings joy and happiness to our small
nest.
xxi
Chapter 1: Introduction
1.1 Background
With the rapid increase in electrical energy demand, power utilities are seeking
for more power generation capacity. However, environmental and right-of-way
concerns make the addition of central generating stations and the erection of power
transmission lines more difficult. Thus, newer technologies based on renewable
energy are becoming more acceptable as alternative energy generators. This
renewable energy push is starting to spread power generation over distribution
networks in the form of distributed generation and will lead to a significant increase
in the penetration level of distributed generation in the near future. It is expected that
20% of power generation will be through renewable sources by the year 2020 [1].
However, by that time, the penetration level of DGs is expected to be higher in many
countries which are seeking accelerated deployment of renewable technologies. The
DGs based on renewable energy sources will help in reducing greenhouse gas
emissions. Moreover, these DGs can provide benefits for both utilities and
consumers since they can reduce power loss, improve voltage profile and reduce
transmission and distribution costs due to their location close to customers [2, 3].
A microgrid can be considered as an entirely DG based grid that contains both
generators and loads. It is usually connected to the utility grid through a single point:
the point of common coupling (PCC). To the utility grid, the microgrid behaves as a
Chapter 1: Introduction
fully controllable load which at peak hours can even supply power back to the utility
grid. A microgrid can operate in either (utility) grid connected mode or islanded
mode and can seamlessly change between these modes. In an islanded mode, the
DGs connected to the microgrid supply its loads, where a provision for load shedding
exists if the load demand is higher than the total DG generation.
Most of the existing distribution systems are radial where power flows from
substation to the customers in a unidirectional manner. Overcurrent protection is
used for such systems because of its simplicity and low cost [1, 4]. However, once a
DG or a microgrid is connected within the main utility system, this pure radial nature
is lost [2, 5, 6] and the existing protection devices may not respond in the fashion for
which they were initially designed [4]. This change in response may be due to the
change in parameters, such as source impedance, short circuit capacity level and
change of fault currents and fault current directions at various locations.
Solar photovoltaic cells produce power at dc voltage. Similarly, fuel cells and
batteries also produce dc output power. These are then converted into ac voltage
through dc-ac converters. Also, other sources such as wind and microturbines use a
converter stage for grid interconnection. All the converters try to protect themselves
by limiting their output currents. This becomes more crucial during faults. In general,
fault current is usually limited to a value that is twice the converter rated current [7,
8]. As a result of current limiting, the overcurrent devices may not respond or may
operate slowly. This is specifically true when an islanded system is supplied by
current limited converters. The aim of this research was to identify and address the
protection issues of distribution networks in the presence of the DGs and microgrids.
New protection strategies are proposed to overcome the difficulties of the existing
protection schemes.
Chapter 1: Introduction
solution for DG connected distribution networks, the focus was limited to converter
interfaced DGs. Moreover, the protection of DG connected distribution networks
without communication was considered for a simple and cost effective solution.
Chapter 1: Introduction
minimize the protection issues in implementation with the use of the proposed
strategies.
Chapter 1: Introduction
extinction of arc is achieved by reducing the output current of DGs. Furthermore, an
effective method is proposed to coordinate the operations of reclosers and converter
interfaced DGs in a network. The fold back control provides maximum benefits to
customers by reducing outages since the DGs are not disconnected immediately
when there is a fault in the system.
The proposed ITA relay and fold back current control strategy for a converter
interfaced DG provide a complete protection solution for a DG connected network.
The relays detect and isolate faults effectively while the fold back current control
helps in arc extinction, system restoration and recloser coordination with DGs.
Chapter 1: Introduction
features are then compared with the ITA relays. Different case studies are carried out
to show the efficacy of the ITA relays. Moreover, simulation studies related to the
ITA relays are also presented in this chapter. Applications of ITA relays for both
radial and mesh networks are examined and their limitations are identified.
A fold back current control characteristic for a converter interfaced DG is
proposed in Chapter 5. The protection issues related to the system restoration, arc
extinction and reclosing are also addressed in this chapter. Different case studies of
both permanent and temporary faults were carried out and are presented here to show
the efficacy of proposed fold back converter control.
Chapter 6 presents the hardware results obtained through the experimental
laboratory tests. The ITA relay characteristic is modelled using LabVIEW software
and the relay performance is investigated for different fault locations and different
system configurations.
Conclusions drawn from this research and recommendations for future research
are given in Chapter 7. The list of references and a list of publications arsing from
the thesis are provided at the end of the last chapter. In Appendix-A, different types
of relay elements are discussed, while Appendix-B give a detailed description of the
converter structure and control used in simulation studies. The LabVIEW program
used in ITA relay implementation is presented in Appendix-C.
10
11
13
14
15
16
18
19
20
21
22
23
Communication
media
may
be
the
internet,
PLC,
wireless
communication, etc. In [56], PLC based methods are proposed for the coordination
of voltage control, islanding detection for a DG and controlling the interface devices
at the PCC. The Islanding detection method is introduced to minimize the problems
of traditional methods based on frequency and voltage measurements. High
attenuation levels can be expected in distribution lines when their structure is
complex and lines are long. To avoid such problems, repeaters need to be installed in
this implementation. Application considerations of internet as the real time
communication medium for providing the loss of mains protection of a DG has been
studied in [55].
The distribution system becomes a multi-source when one after another DG
gets connected at different locations. This change in system configuration will cause
false tripping and relay coordination problems. As a solution for these problems,
reference [57] has proposed a new current protection scheme based on
communication to a multi-source distribution system. Wide area measurement is
used to decide the appropriate protection actions to locate the fault with the use of
communication channel. An adaptive method is proposed in [58] to set the relay
settings in real time using wide area measurements based on communication. A multi
24
2.3 Summary
In this chapter, a brief summary is presented based on the review of the
previous published research work on the protection issues which arise after the
connections of DGs and microgrids to distribution networks. There are several
benefits available for both the network operator and customer by utilising DGs or
DG based Microgrids. Reliability can increase if the islanded system can continue
the supply to the loads rather than disconnecting all the DGs by anti-islanding
protection schemes. Therefore within the islanded system, a protection scheme
should work satisfactorily. Different types of protection issues have been addressed
in the literatures and different solutions have also been proposed to overcome these
issues.
25
26
27
(3.1)
28
Yr 1
+k
(3.2)
where A, and k are constants, while the tripping time is denoted by tp. The values
for these constants can be selected based on the relay location in a feeder and the
protection requirements. The shape of the proposed inverse time tripping
characteristic can be changed by varying the constants to obtain the required fault
clearing time. When a network consists of different types of protective devices, these
constants can be selected appropriately for coordination purpose. For example, the
coordination between the relay and a fuse can be considered. In this case, these
constants should be selected properly according to the tripping characteristic of the
fuse. The relay tripping characteristic for A = 0.0047, = 0.08 and k = 0 is shown in
Fig. 3.3. The magnitude of the normalized admittance (i.e. Yr) becomes higher as the
fault point moves towards the relay location. As a result, the relay gives a lower
29
(3.3)
31
32
Fig. 3.6 Relay settings based on different forward and reverse reach
33
I Ra + I Ra 0 RK1 1
YRK 0
YRK1 =
VRa
(3.4)
where IRa is the rms line fault current through the relay while IRa0 is the zero
sequence fault current seen by relay and VRa is the faulted phase rms voltage. The
line parameters are used to calculate the ratio of YRK1/ YRK0. The relay reach is set
based on the positive sequence admittance of the protected line segment. This relay
reach and calculated measured admittance in (3.4) are utilized to make the tripping
decision and tripping time calculation.
I I Rb
YRK1 = Ra
VRa VRb
(3.5)
where IRa and IRb are rms phase currents in faulted phases and VRa and VRb are faulted
phase rms voltages. This measured admittance in (3.5) is used by relay logic to detect
a line to line fault in the network.
Operation
Directional
Non-directional
Directional blocking
35
36
37
Yt _ Zone1 =
1
(1.2 Z12 )
(3.6)
0.0037
Yr0.08 1
+ 0.05
(3.7)
38
Yt _ Zone2 =
tp =
1
(2 Z12 )
0.0037
Yr0.1 1
(3.8)
+ 0.15
(3.9)
1
( Z12 + Z f )
(3.10)
Zone-1 and Zone-2 tripping characteristics are same for all the relays.
However, setting of Zone-3 will be different for each relay since coordination time
margin should be kept among the relays. If relays are designed to operate for both
forward and reverse faults, then the relay will have two different tripping
characteristics in Zone-3; one for forward faults which can be denoted by Zone-3F
and other one for reverse faults which can be given by Zone-3R. In this case, the
directional feature should be added to the relay for differentiation of forward and
39
0.0037
+ 1.15
Yr0.1 1
0.0037
Yr0.1 1
(3.11)
+ 0.45
0.0037
Yr0.1 1
0.0037
Yr0.1 1
0.0037
Yr0.1 1
0.0037
Yr0.1 1
+ 0.85
(3.12)
+ 0.75
+ 0.55
(3.13)
+ 1.05
The tripping characteristics of relays R2 and R3 in radial feeder of Fig. 3.4 are
considered to illustrate the Zone-3 operation. The relay characteristics are shown in
Fig. 3.9. In this case, only two relays are considered for clear illustration. Zone-3
40
41
42
3.8 Summary
In this chapter, the basic features of the proposed ITA relay to protect a
distribution network or a microgrid which has several DGs are discussed. The relay
inverse time characteristic and relay reach setting have been explained. Furthermore,
different relay elements and a method of relay setting to achieve fault detection under
higher resistive faults have been explained. Finally, the challenges of implementing
ITA relays and possible solutions to avoid them are identified.
43
45
tp = p
+ B TDS
M 1
(4.1)
where the constants A, B and p are used to select the relay characteristic curve and
time dial setting (i.e. TDS) is used for the coordination between several OC relays. M
is the multiple of pickup current and it is defined by
If
M =
Ip
(4.2)
where If is the fault current seen by the relay and Ip is the relay set current (i.e. pickup
current). Three inverse time OC relay characteristic equations are given in the IEEE
report [37]. They are moderately inverse, very inverse and extremely inverse. Each
relay curve has different constants values in (4.1).
To illustrate the grading of inverse time OC relays, a four bus bar radial feeder
is considered as shown in Fig. 4.1. Relays are located at BUS-1, BUS-2 and BUS-3
and are denoted by R1, R2 and R3 respectively. An upstream relay will provide the
backup protection for the adjacent downstream relay. A time margin, called
coordination time interval (discrimination), is kept between relays to achieve the
relay coordination by setting the TDS of each relay. Inverse time tripping
characteristic of the graded inverse OC relays for this radial system is shown in Fig.
46
47
V phase
(4.3)
I phase + K I 0
48
49
Yr 1
+k
(4.4)
where A, and k are constants, while the tripping time is denoted by tp. To illustrate
the grading of ITA relays, the same four bus bar radial system shown in Fig. 4.1 is
considered. The ITA relays do not have a TDS setting as in the case of OC relays to
achieve coordination. These relays will make the tripping decision based on the
measured admittance to the fault location. The tripping characteristics of graded ITA
relays for the radial system are shown in Fig. 4.5. It has been assumed that each relay
has two zones of protection. The combined tripping characteristic of Zone-1 and
Zone-2 is shown in the figure. Coordination time intervals are denoted by t12 and t23.
In OC protection, the relay near to the source takes longer time to operate. However
in the case of ITA relays, the relay near to the source will take the same time to
operate as other relays do. The measured admittance is the only parameter that will
decide the relay tripping time. This is an advantage of the ITA relay over an OC
relay.
51
(4.5)
52
(4.6)
MI
MV
where M V =
Vx
Vp
(4.7)
Note that while MI is the multiple of the pick up current and MV can be defined as the
multiple of pick up voltage since it is the ratio between faulted voltage to the pick up
voltage. For a fault in the network, MI is greater than one. However, the magnitude of
MV is less than one when a fault occurs in the network. It can be seen from (4.7) that
ITA relay uses both current and voltage multiples instead of only current based
multiple in the OC relay. As a result, the ITA relay has the ability to detect the faults
effectively irrespective of the available fault current level in a network. This may
also result in fault detection under low fault current level environment, specially the
cases where current limited DGs are connected to the network.
To show how the ITA relay can be related to a distance type relay, real
imaginary (R-X) plane representation is considered with the relay tripping curve.
Zone-1 of the ITA relay is considered for this illustration. The ITA relay
characteristic can be represented in both distance-tripping time and R-X plane as
shown in Fig. 4.7. The tripping time characteristic curve of ITA relay can be mapped
into circles in R-X plane, in which each circle has a unique tripping time. For
example, point D on tripping time curve is considered. This point is corresponding to
53
54
investigate the relay response under converter connected DGs in grid connected
and islanded mode operations.
Fig. 4.8 shows a radial distribution network with DG1, DG2 and DG3
connected at BUS-2, BUS-3 and BUS-4 respectively. The relays are located at BUS1, BUS-2 and BUS-3. The parameters of the considered system are given in Table
4.1. Several case studies are considered depending on the system configuration and
the type of protective devices employed.
The OC relay settings for the given system are calculated based on the
maximum and minimum fault current levels at each bus as illustrated in [68],
assuming the relays have moderately inverse OC characteristic [37]. The
discrimination time for the OC relays is chosen as 0.3 s. The calculated OC relay
settings are listed in Table 4.2.
Value
System frequency
50 Hz
11 kV rms (L-L)
Source impedance
Zs = 0.078 + j 0.7854
Feeder impedance
55
R1
R2
R3
CT ratio
200:5
150:5
150:5
4.5
TDS
0.65
0.35
0.1
The constants for the ITA relay characteristic, given in (4.4), are chosen
assuming that the relays have two zones of protection in which Zone-1 covers 120%
of the first line length and Zone-2 covers twice the length of the first line. The
selected constant values for Zone-1 and Zone-2 are given in Table 4.3.
Table 4.3 Zone characteristics of ITA relay
Zone number
Zone-1
0.0037
0.08
0.05
Zone-2
0.0037
0.1
0.1
56
57
Fig. 4.11 Distance and ITA relay response when DG1 is connected
58
59
60
Fig. 4.15 ITA relay response for SLG fault in islanded operation
61
4.5.3 ITA relay response for different DG and load distribution profiles
A radial distribution feeder which has n number of buses as shown in Fig. 4.18
is considered. In this system, utility is connected at BUS-1 which does not have a
load or a DG. Either a DG or a load or their combination is connected to each of the
other buses. All the DGs considered in this study are connected through the current
62
63
Value
System frequency
50 Hz
11 kV rms (L-L)
Source impedance
Zs = 0.078 + j 0.7854
Feeder impedance
DG1=DG2=0.0388 MVA
Fig. 4.20 Fault current seen by each ITA relay along the feeder
65
Fig. 4.21 Random load and DG distribution profiles along the feeder
Fig. 4.22 ITA relay response for random load and DG distribution profiles
66
67
Node 832-860
3825
10.4013+j5.1767
R2
Node 834-848
1740
4.7316 +j 2.3549
R3
Node 860-838
2346
3.9174 + j2.3131
Not considered
R2
Node 834-832
3219
8.7535+j4.3565
R3
Node 860-832
3825
10.4013+j5.1767
68
Fig. 4.24 ITA relay response for SLG fault at node 858
B. Fault at Node 842
A SLG fault is initiated at 0.3 s. The relay R2 responds at 0.401 s as shown in
Fig. 4.25 to isolate the fault. The rest of the system except Region-A operates in grid
connected mode. Since there are no other protection devices between DG1 and the
fault point, DG1 is disconnected after the defined time interval.
Fig. 4.25 ITA relay response for SLG fault at node 842
C. Fault at Node 862
A SLG fault is initiated at 0.3 s and relay R3 operates at 0.490 s to isolate the
fault. The ITA relay response for this fault is shown Fig. 4.26. The rest of the system
except Region-B operates in grid connected mode.
69
Fig. 4.26 ITA relay response for SLG fault at node 862
The above results verify that the ITA relays have the ability to respond under
low fault current levels. These relays isolate the faulted segment from the network
allowing unfaulted segments to operate either in grid connected or islanded mode
operations. Also it is to be noted that proposed ITA relays have the ability to detect
the faults in islanded conditions as well. For example, if an islanded system is
created by opening the circuit breaker at Node 832, the rest of system operates with
adequate protection. However the fault current level will be significantly lower in
such a case.
Value
Voltage
11 kV L-L rms
Frequency
50 HZ
Source impedance
(0.078 + j 0.7854)
(0.585 + j 4.335)
The relays R12, R21, R15, R51, R52 and R25 which are located in the mesh
network have the directional blocking feature in which these relays only respond to
forward faults. This results in proper relay coordination within the mesh network.
For example, consider relay R15. It protects the line segment between BUS-1 and
BUS-5. Also it provides the backup protection for the line segment between BUS-5
71
0.0037
Yr0.1 1
0.0037
Yr0.1 1
0.0037
Yr0.1 1
0.0037
Yr0.1 1
+ 0 .3
t Zone3R _ R43 =
+ 0 .4
t Zone3R _ R32 =
+ 0 .4
t Zone3R _ R21 =
+ 0 .5
t Zone3R _ R25 =
t Zone3R _ R51 =
72
0.0037
Yr0.1 1
0.0037
Yr0.1 1
0.0037
Yr0.1 1
0.0037
Yr0.1 1
0.0037
Yr0.1 1
+ 0 .5
+ 0 .4
+ 0.3
+ 0 .3
+ 0 .2
Rf = 20
R12=0.438,R21=0.774
R12=0.443,R21=0.359
All the loads are supplied in grid connected mode without line Z12
BUS-1 and
BUS-5
R15=0.540,R51=0.774
R15=0.544,R51=0.251
All loads are supplied in grid connected mode without line Z15
BUS-2 and
BUS-5
R25=0.348,R52=0.445
R25=0.458,R52=0.443
All loads are supplied in grid connected mode without line Z25
10% from BUS-2
BUS-2 and
BUS-3
R12=0.150,R52=0.158,
R12=0.459,R52=0.472
R32=0.082
R32=0.480
R12=0.410,R52=0.427,
R12=0.481,R52=0.494
R32=0.075
R32=0.509
R32=0.345,R43=0.615
R32=0.349,R43=0.913
BUS-4
Load1 and Load3 are supplied in grid connected mode while Load2 is
supplied in islanded mode without line Z34
73
Is
1
=
Z f I s + R f ( I s + I DG )
I
Z f + R f 1 + DG
Is
(4.8)
Ym( R2 ) =
I DG
1
=
Z r I DG + R f ( I s + I DG )
I
Z r + R f 1 + s
I DG
(4.9)
74
75
Fig. 4.29 ITA relay response for different values of fault resistances and DG currents
The operation of the ITA relay may be affected by fault resistance and infeed
of DGs located downstream. As a result, the relay may take more time to trip than
expected. The values of line parameters, total admittance setting, fault location, fault
76
4.7 Summary
In this chapter, the ITA relay performances have been compared with the
existing relays. The relay grading and coordination, the effect of DGs on the relay
response and the effect of source impedance on the relay response for both ITA and
OC relays are considered. The ITA relay performances are evaluated in a radial
distribution feeder with DGs considering different DG and load distribution profiles.
Moreover, an application of these relays to IEEE 34 test node feeder has been
demonstrated. The protection of a mesh network which has several converter
interfaced DGs and loads are considered using the ITA relays. Both resistive and
non-resistive faults are simulated to see the efficacy of ITA relays. Finally, the
limitations of ITA relay protection due to the fault resistance and DG connections
have been addressed.
According to the relay performance analysis, it is clear that ITA relays have the
capability to isolate a faulted segment in a DG connected network allowing unfaulted
segments to operate either in grid connected or islanded mode operations. This
results in improving the reliability of a network since customer outages are reduced.
77
79
80
81
t=
kV
+ 10.5 cycles
34.5
(5.1)
where kV is the line to line rated voltage and the unit of time t is cycles. During this
sleep time period, self extinction of arc faults is achieved without disconnecting DGs
from the network.
v=
V2
nV2
i
I r ( 2 n)
( 2 n)
(5.2)
where v and i are the rms voltage and current magnitudes, Ir is the rated current, V2 is
the converter output voltage when it injects 2Ir and n is a small number. It is to be
noted that the rms magnitude is calculated by a moving average filter with a window
of one cycle. During transients, the filter will produce a time-varying output.
Therefore, from knowledge of the value of i at any instant, v can be calculated or
vice versa.
The VSC controller can calculate corresponding voltage/current for a particular
value of current/voltage using (5.2) during the restoration process through the line
CK. Three different cases are considered to explain the restoration process depending
83
84
85
5.2.4 DG protection
It is important to consider the consequences of out of phase reclosing when
DGs are not disconnected during the auto recloser open time. The risk of DG damage
due to the out of phase reclosing is lower, if DG is connected through a converter
[49]. In the proposed reclosing scheme, the recloser is capable of checking the
synchronisation which ensures there is no phase mismatch when it performs live to
live reclosing.
From the point of DG protection, the DG should be protected itself. To achieve
basic DG protection requirements, in the proposed method, a DG is employed with
several protective elements; fold back current control, reverse power flow, over
voltage and synchronism check. The proposed fold back control protects the DG
87
88
1
Gp g p
Tp
(5.3)
89
Ip
; Tp =
lp
Vp l p
(5.4)
where, |i| is the absolute value of the primary arc current, Vp is the arc voltage
gradient, lp is the primary arc length, Ip is the peak value of primary arc current and
is a constant.
dg s
1
= (Gs g s )
dt
Ts
(5.5)
where, Ts is the secondary arc time constant, Gs is the stationary arc conductance and
gs is the instantaneous secondary arc conductance. Gs and Ts can be given by
Gs =
i
Vs ls (t r )
; Ts =
I s1.4
(5.6)
l s (t r )
where |i| is the absolute value of the secondary arc current, tr is the time from
initiation of secondary arc, ls(tr) is the time varying arc length, Is is the steady state
peak secondary arc current and is a constant.
90
dr 'arc
= 20 M /( s m)
dt
(5.7)
g 'min = 50 S m
(5.8)
However, this criterion only considers the thermal extinction of the arc and
there is a probability of dielectric re-ignition of the arc. This has not been considered
in this study.
91
Value
System frequency
50 Hz
11 kV rms (L-L)
Sbase
10 MVA
Vbase
11 kV
DG power output
0.5 MW
The performance of proposed ITA relays in the presence of fold back current
control DGs are also investigated for both permanent and arc faults. Therefore the
ITA relays R1, R2 and R3 are employed to protect the feeder as shown in the figure.
The relays are assumed to have two zones of protection in which Zone-1 covers
120% of the first line and Zone-2 covers twice the length of the first line. The
following constants are chosen for the tripping characteristics of the relays.
For Zone-1: A = 0.0037, p = 0.08, k = 0.005
92
93
Fig. 5.4 Calculated ITA relay response for a three phase fault
The system shown in Fig. 5.3 is simulated in PSCAD for different system
configurations since all the DGs and loads may not be connected at all the time. A
SLG fault is created at 0.305 s at different locations. Different case studies are
considered by changing the DG and load connectivity to the network.
94
Fig. 5.5 DG1 response (a) output voltage (b) output current (c) real power output
95
96
Fig. 5.6 DG1 response (a) output voltage (b) output current (c) real power output
Value
dg p
dt
gp
2.85 10 5 I p 15l p
lp
i
dg s
l s (t r )
=
gs
dt
2.5110 3 I 1s .4 75 I s 0.4 l s (t r )
0.5m
10lpt (t is time)
The arc fault is initiated at the peak of a voltage waveform. A high fault current
flows in the beginning since both utility source and DGs feed the fault. At this stage,
the arc is modelled as a primary arc. Once the relay responds to isolate the fault from
97
Case study-3: Arc fault on the line between BUS-1 and BUS-2
An arc fault is created at 0.305 s. The primary arc has high arc current, low arc
voltage and low arc resistance as can be seen from Fig. 5.7. The relay R1 responds at
0.332 s as shown in Fig. 5.7(d) to isolate the arc fault from upstream (i.e. utility
side). After the response of R1, the arc resistance increases due to the secondary
arcing, as evident from Fig. 5.7(c). The DGs start to reduce the output current
gradually with the initiation of the fault. The response of DG1 is shown in Fig. 5.8.
The relay R2 responds at 0.349 s to isolate the fault from the downstream side. The
isolation of the faulted segment results in the islanded mode of operation containing
all the three DGs. Thereafter, the system recovers successfully when DGs are
switched to the voltage control mode. Fig. 5.8(b) verifies the sinusoidal current
limiting and gradual current decrease in fold back characteristic. It is to be noted that
a hardware current limiter is employed for the VSCs to limit the instantaneous peak
output current to the value 100 A. The fold back current limit is applied once the
hardware limit is reached.
The results reveal that the proposed ITA relay scheme can isolate the faulted
segment from the feeder. It leads to fast restoration of the system. The DGs restore
the system without disconnecting from the feeder thereby increasing the reliability
for even temporary faults.
98
Fig. 5.7 System behaviour for an arc fault (a) arc voltage (b) arc current (c) arc
resistance (d) relay response
Fig. 5.8 DG1 behaviour for an arc fault (a) output voltage (b) output current
Case study-4: Arc fault on the line between BUS-1 and BUS-2, assuming relay R2
fails to operate
The same scenario as Case study-3 is considered here to illustrate the effect of
DGs on arc extinction. However, in this case, it is assumed that the downstream relay
R2 fails to detect the fault. Once R1 responds to the fault, DGs feed the arc in
99
Fig. 5.9 DG1 behaviour when downstream relay fails (a) output voltage (b) output
current
100
101
B. With proposed fold back current control and conventional protection scheme
In this sub-section, the coordination of reclosers and converter interfaced DGs
are discussed assuming the relays employed in the radial feeder shown in Fig. 5.3 are
overcurrent type. Therefore these relays only clear the forward faults from the feeder.
To explain the sequence of operation, a fault on the line between BUS-1 and BUS-2
at 0.305 s is considered. The forward relay R1 detects the fault and isolates it from
102
103
5.5 Summary
A novel control strategy based on fold back current control is proposed for a
converter interfaced DG to overcome the challenging protection issues in a DG
connected distribution feeder. The control strategy enables the fast arc extinction,
system restoration, and reclosing without disconnecting the DGs. The arc extinction
is achieved by reducing the DG output current to a small value, while automatic
system restoration is obtained if DG power generation is sufficient enough to supply
the load demand. Recloser coordination with DGs is considered without any explicit
communication. It can be seen that the reclosing is possible with converter connected
DGs. The only requirement is to determine a sequence of operations with appropriate
time delays between each recloser and DG depending on the system configuration.
The results reveal that the DG benefits can be maximised by increasing the reliability
of the system if fold back current control is employed with converter interfaced DGs.
104
105
106
Value
Source
Feeder impedance
R = 1.12
L = 0.01H ( j 3.15 )
125
1A
Hardware specifications
NI chassis
PXI-1042Q
NI controller
Transducers
Voltage
Differential amplifier
Current
Data acquisition
Analog inputs
PXI-4070 FlexDMM
Digital outputs
Sampling rate
108
109
Zone-1
Yt1 =
t=
Zone-2
Zone-3
1
1.2 (4.48 + j 12.6)
0.0037
Yr0.2 1
+ 0.02
Yt1 =
1
2 (4.48 + j 12.6)
t=
0.003
Yr0.04 1
Yt1 =
t=
+ 0.02
1
3 (4.48 + j 12.6)
0.0025
Yr0.02 1
+ 0.02
The calculated relay response using MATLAB for SLG faults along the feeder
is shown in Fig. 6.6. In this calculation, the fault resistance is considered as zero. The
calculated theoretical tripping times are used to validate the experimental results. As
can be seen from Fig. 6.6, the relay tripping characteristics are selected appropriately
for different zones. For example, consider Zone-1 and Zone-3 tripping
characteristics. Zone-3 should always give higher tripping time than Zone-1 for
faults if tripping characteristics of the zones are properly selected. Otherwise, Zone-3
can give lower tripping time than Zone-1 for bolted faults (i.e. zero resistive faults) if
same tripping characteristics are selected for these zones, since reach setting of Zone3 is higher.
110
Fig. 6.6 Calculated relay response in different zones for bolted faults
The ITA relay has been designed to operate for different fault current levels in
a network. Specifically, when a converter interfaced DG is connected to the network,
different voltage levels can be seen during the faulted condition. However, the ITA
relay response should be same irrespective of the network fault current level/fault
voltage level. Therefore, a number of test runs are carried out under different test
feeder configurations to evaluate the relay performance.
111
Theoretical
Relay
response Actual
run
time (ms)
fault
30
29
30
30
29
29.2
30
30
32
113
Theoretical
Relay
response Actual
run
time (ms)
fault
40
38
39.2
40
37
38
40
39
41
114
Theoretical
Relay
response Actual
run
time (ms)
fault
58
57
62.4
58
58
64
58
59
64.2
115
Theoretical
Relay
response Actual
run
time (ms)
fault
120
119
122
120
118
121
120
116
118
116
117
Theoretical
Relay
response Actual
time (ms)
fault
BUS-2
30
30
34
BUS-3
40
39
42
BUS-4
58
60
61.6
BUS-5
120
118
120
118
119
120
Calculated results
location
Rf=0
Ym
Yr
Experimental results
Rf=10
tp (ms)
Ym
Yr
Rf=10
tp (ms)
Ym
Yr
tp (ms)
BUS-1
0.299 12.0
0.069
0.086 3.471
119
0.087 3.49
117
BUS-2
0.149
6.0
0.088
0.072 2.914
135
0.072 2.88
136
BUS-3
0.099
4.0
0.108
0.061 2.451
158
0.059 2.37
162
BUS-4
0.075
3.0
0.132
0.052 2.090
188
0.050 2.01
197
121
122
Calculated results
Ym
Yr
Experimental results
tp (ms)
Ym
Yr
tp (ms)
BUS-2
0.0709 2.8442
138
0.07
2.8
138
BUS-3
0.0500 2.0071
198
0.049 1.97
201
BUS-4
0.0354 1.4218
374
0.035 1.41
380
123
124
125
126
127
128
129
6.6 Summary
Several experimental tests are carried out at different fault locations and
different system configurations. The results demonstrate that the ITA relay follows
the inverse time characteristic curve as designed based on the measured admittance.
The relay response time closely matches the calculated results. The source voltage
and source impedance do not affect the relay operation. Moreover, the relay can
respond in the same manner with different fault current levels in the feeder. The fault
resistance and infeed may cause delay in the relay operation. The decaying dc
component can also change the relay tripping time slightly during the transient
period of the fault.
130
7.1 Conclusions
The general conclusions of the thesis are:
(1) The connections of DGs or microgrids to a distribution network are gaining
importance with the increase of electrical power requirements and
environmental concerns. However, these DG connections can create challenging
protection issues. It is identified that new protection strategies are required to
overcome these challenges.
(2) Protective devices based on current sensing are usually used to detect the faults
in distribution networks. The connections of DGs change the fault current level
and fault current direction. Moreover, if DGs are connected through intermittent
sources, the fault current contribution from DGs cannot be exactly identified to
set the tripping parameters of current sensing protective devices. Furthermore,
protection with converter interfaced DGs in islanded operation is difficult with
current sensing protective devices due to the lower fault current levels. Unless
viable solutions can be found for the protection issues, DGs have to be
disconnected from the grid after a fault, thereby affecting reliability.
131
132
133
7.2.2 Fold back type current control for rotary type DGs
The fold back current control strategy is implemented for a converter
interfaced DG in this research. This fold back strategy cannot be easily implemented
for rotary type DGs which will continuously supply large fault currents. Therefore,
suitable fold back type control strategies are required for these rotary DGs to achieve
fast arc extinction and system restoration and will be the subject of future research
and development.
134
References
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
of
Grid-connected
Hydropower
Distributed
Generation,"
International Journal of Global Energy Issues, vol. 24, pp. 76-85, 2005.
135
[11]
[12]
[13]
[14]
[15]
[16]
Conference:
Advanced
Metering,
Protection,
Control,
[18]
G. Dalke and et. al, "Application of Islanding Protection for Industrial and
Commercial Generators An IEEE Industrial Application Society Working
Group Report," 59th Annual Conference for Protective Relay Engineers,
2006, pp. 152-163.
[19]
[20]
136
[21]
[22]
[23]
S. Jang and K.-H. Kim, "An Islanding Detection Method for Distributed
Generations Using Voltage Unbalance and Total Harmonic Distortion of
Current," IEEE Transactions on Power Delivery, vol. 19, pp. 745-752, 2004.
[24]
L. Wang, H. Cheung, A. Hamlyn, C. Yang, and R. Cheung, "NetworkIntegrated Protection and Control Strategy for Power Distribution Systems,"
IEEE Large Engineering Systems Conference on Power Engineering, 2007.
[25]
[26]
[27]
[28]
[29]
[30]
137
[31]
Y. Lu, L. Hua, J. Wu, G. Wu, and G. Xu, "A Study on Effect of Dispersed
Generator Capacity on Power System Protection," IEEE Power Engineering
Society General Meeting, pp. 1-6, 2007.
[32]
[33]
[34]
[35]
A. C. Enrquez
[37]
[38]
[39]
[40]
138
[41]
[42]
[43]
[44]
[45]
[46]
[47]
[48]
[49]
[50]
[51]
[52]
Distribution
Networks,"
Conference, 2005.
139
15th
Power
System
Computation
[53]
[54]
V. V. Terzija and H.-J. Koglin, "On the Modeling of Long Arc in Still Air
and Arc Resistance Calculation," IEEE Transactions on Power Delivery, vol.
19, pp. 1012 - 1017 2004.
[55]
[56]
R. Benato and R. Caldon, "Application of PLC for the Control and the
Protection of Future Distribution Networks," IEEE International Symposium
on Power Line Communications and Its Applications, 2007, pp. 499 - 504.
[57]
[58]
[59]
[60]
[61]
B.
Fleming,
"Negative
Sequence
Impedance
Directional
Element,"
[63]
140
[64]
[65]
[66]
[67]
[68]
[69]
[70]
[71]
[72]
[73]
[74]
141
143
Appendix-A
Positive sequence admittance seen by ITA relay
The faulted network for single line to ground (SLG) fault shown in Fig. A.1 is
considered. The relay location is denoted by node R while fault point is at node k.
The fault impedance is represented by Zf. The admittance between the relay and fault
point is denoted by YRK. The voltage and current seen by the relay in faulted phase A
are taken as VRa and Ifa respectively. Negative and zero sequence source voltages are
also considered assuming the source is unsymmetrical during the fault. Moreover, the
zero, positive and negative sequence Thevenin admittances between the relay point
and faulted point are considered as YRk0, YRk1 and YRk2 respectively. The sequence
network for this SLG fault can be represented as shown in Fig. A.1(b).
(a)
(b)
Fig. A.1 SLG fault representation (a) faulted network (b) sequence network
145
VRa 2 = v2 + (I Ra 2 / YRK1 )
VRa 0 = v0 + (I Ra 0 / YRK 0 )
(A.1)
(A.2)
(A.3)
(A.4)
(A.5)
I Ra1 + I Ra 2 + I Ra 0 = I Ra
Using (A.4) and (A.5), positive sequence measured admittance YRK1 can be written
as,
I Ra + I Ra 0 RK1 1
YRK 0
YRk1 =
V Ra
(A.6)
where IRa is the line fault current through the relay while IRa0 is the zero sequence
fault current seen by the relay and VRa is the faulted phase rms voltage.
146
Appendix-B
Converter structure and control
(A). Converter structure
The three phase structure of the converter which is used in PSCAD simulation
is shown in Fig. B.1. It contains three single phase H-bridge converters that are
supplied a common dc bus containing the DG. Three single-phase transformers are
connected to the three converters to provide isolation and voltage boosting. In this
figure, Lf is the leakage reactance of the transformer, Rf is the transformer losses and
L0 is the output inductance of the DG-converter system. The filter capacitor Cf is
used to bypass the switching harmonics. The advantage of the converter structure
shown in Fig. B.1 is that each phase of the converter can be controlled
independently.
converter output voltage maintaining the rated voltages at the terminals. The voltage
reference is chosen such that the power demand can be met. The converter switches
into output feedback current control mode during a fault in the network. In this case,
the reference current is chosen to have a magnitude that is twice the rated current of
the converter. Also in current control mode, the magnitude of the output current can
be changed with time according to the user requirement. However, the defined
currents are only injected in faulted phases. The voltage control mode of the
converter is explained in detail below.
The equivalent circuit of one phase of the converter is shown in Fig. B.2. In
this, uVdc represents the converter output voltage, where u = 1. The main aim of
the converter control is to generate u.
(B.1)
where uc is the continuous time control input, based on which the switching function
u is determined. The discrete-time equivalent of (B.1) can be given by
x(k + 1) = Fx(k ) + Gu c (k )
(B.2)
148
Let the output of the system given in (B.2) be vcf. The reference for this voltage is
given by the instantaneous peak and phase angle of each phase. Let this be denoted
by v*. The input-output relationship of the system in (B.2) can be written as,
vcf ( z )
uc ( z )
M ( z 1 )
(B.3)
N ( z 1)
S ( z 1 ) *
v ( z ) vcf ( z )
R( z 1)
(B.4)
vcf ( z )
v* ( z )
M ( z 1 ) S ( z 1)
N ( z 1) R( z 1 ) + M ( z 1 ) S ( z 1)
(B.5)
(B.6)
where h is a small number. The control in (B. 4) is computed based on the reference
voltage v and the feedback of the capacitor voltage vcf. The reference voltages are
given by
va* = Vnsin(t )
vb* = Vn sin(t 120o )
(B.7)
149
A similar control strategy is also used for current control. The control in (B.4)
is calculated based on the output current ioa and reference currents. The reference
currents for faulted phases are chosen based on the converter rating.
To illustrate how the switching pulses are selected in each mode of operation,
Fig. B.3 is considered. The converter in both voltage and current modes is operated
in output feedback pole shift voltage/current control mode to select R1, S1, R2 and
S2 [B.2] as explained above. Each phase is controlled according to its output voltage
(vcf) or current (ioa). These signals are sampled at 10 s. The output sampled signals
are then used in the discrete-time output feedback controllers shown in this figure.
The controller mode change operations are also indicated in this figure. The
switching pulses are generated either in voltage control mode or current control
mode depending on the selected mode of operations.
Fig. B.3 Single line diagram of the converter structure and control
150
151
152
Appendix-C
LabVIEW Program
153
Fig. C.1 Measured admittance calculation on LabVIEW
155
Fig. C.2 ITA relay implementation on LabVIEW