Example: Column base connection under axial compression (GB)

CALCULATION SHEET

SX019a-EN-GB

Title

Example: Column base connection under axial compression

Eurocode Ref

EN 1993-1-8

Made by

Laurent Narboux

Date

Dec 2006

Checked by

Abdul Malik

Date

Jan 2007

Sheet

Document Ref:

of

Localized resource for UK

Example: Column base connection under axial


compression
This worked example deals with the design of a column base subjected to a
compressive axial load. The step by step design procedure given in Section 4
of SN037 is followed throughout.

Created on Tuesday, March 10, 2009


This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

Basic data

Base plate steel grade S275:

fyp = 275 N/mm

Foundation concrete class C25/30:

fck = 25 N/mm

Column axial force

Nj,Ed = 1500 kN

Column section UKC 305 305 118


Height

hc = 314.5 mm

Width

bfc = 307.4 mm

Web thickness

twc = 12 mm

Flange thickness

tfc = 18.7 mm

Dimensions of the foundation :

unknown

Partial factors

Note:

steel

M0 = 1.0

concrete

c = 1.5

The values of the partial factors are specified in the relevant National
Annex.

Design compressive strength of concrete


Concrete design compressive strength:

fcd = cc fck / c

where : fck = 25 N/mm2


The value of cc is given in the National Annex. Its recommended value is:

cc = 1.0
The concrete design strength becomes:
fcd = 1 25 / 1.5 = 16.7 N/mm2

EN 1992-1-1
3.1.6 (1)
SN037
Table 4.1

Example: Column base connection under axial compression (GB)

CALCULATION SHEET

Document Ref:

SX019a-EN-GB

Title

Example: Column base connection under axial compression

Eurocode Ref

EN 1993-1-8

Made by

Laurent Narboux

Date

Dec 2006

Checked by

Abdul Malik

Date

Jan 2007

Sheet

of

Foundation bearing strength


The value of the foundation material coefficient is: j = 2/3.
The foundation dimensions being unknown, take (Ac1/Ac0)0,5 = = 1.5.

SN037

The foundation bearing strength becomes: fjd = jfcd = fcd = 16.7 N/mm .

Table 4.1

307.4

Created on Tuesday, March 10, 2009


This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

314.5

1 : concrete foundation of unknown dimensions


2 : base plate
3 : UKC 305 305 118 column section

Estimation of the base plate area


An estimate of the required base plate area is given as the larger of the
following two values:
2

1)

1 N j, Ed
:

A c0 =
h c b fc f cd
2

1500 103
1

= 83.5 103 mm 2
A c0 =
314.5 307.4 16.7

2) Ac0 =

N j,Ed
f cd

: A c0 =

1500 103
= 89.8 103 mm 2 , which is larger.
16.7

Example: Column base connection under axial compression (GB)

CALCULATION SHEET

SX019a-EN-GB

Title

Example: Column base connection under axial compression

Eurocode Ref

EN 1993-1-8

Made by

Laurent Narboux

Date

Dec 2006

Checked by

Abdul Malik

Date

Jan 2007

Sheet

Document Ref:

of

Choice of the base plate type


As the estimate for
A c0 = 89.8 103 mm2 < 0.95 314.5 307.4 = 91.8 103 mm

A short projection plate will be satisfactory.


Suitable plan dimensions for the short projection base plate are chosen as
follows:
bb = 360 mm

> bfc + 2 tfc = 307.4 + 2 18.7 = 345 mm

hb = 360 mm

> hc + 2 tfc = 314.5 + 2 18.7 = 352 mm

Figure 3.1
Figure 3.2

which gives Ac0 = 360 360 = 130 10 mm > 89.8 10 mm


3

26.3

hc

350

307.4

tfc
tfc
bfc

Figure 4.1
tfc

c twc
c

26.3

Created on Tuesday, March 10, 2009


This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

SN037

314.5

22.8

beff
hp hc + 2 tfc

22.8
360

Verification of the bearing resistance


For a short projection base plate, the value of the additional bearing width,
c, is given by:
c=

B B 2 4 AC
2A

Where: A = +2
B = (bfc twc + hc) = -(307.4 12 + 314.5) = -610 mm

SN037 4

SN037
Table 4.1

Example: Column base connection under axial compression (GB)

CALCULATION SHEET

SX019a-EN-GB

Title

Example: Column base connection under axial compression

Eurocode Ref

EN 1993-1-8

Made by

Laurent Narboux

Date

Dec 2006

Checked by

Abdul Malik

Date

Jan 2007

Sheet

= 0.5 Nj,Ed / fjd (2bfc tfc + 4 tfc2 + 0.5 hc twc tfc twc)

= 0.51500 103 /16.7 (2307.418.7 + 418.72 + 0.5314.512


18.712)
= 30.4 103 mm 2
The additional width is: c =

610 610 2 4 2 30.4 103


= 63 mm
2 2

Check against overlapping of the T-stub areas:


c (hc 2tfc)/2 = 139 mm

OK

Check for adequate base plate width:


Created on Tuesday, March 10, 2009
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

c (bp twc)/2 = 169 mm

OK

The bearing resistance is obtained from:


Nj,Rd = (2 Ac0,f + Ac0,w) fjd

Where: Ac0,f = (307.4 + 2 26.3) (22.8 + 18.7+ 63) = 37.6 103 mm 2


Ac0,w = [314.5 2 (18.7+ 63)] (2 63 + 12) = 20.9 103 mm 2

Therefore:
Nj,Rd = (2 37.6 103 + 20.9 103 ) 16.7 10-3 = 1605 kN

Then : Nj,Ed = 1500 kN < Nj,Rd = 1605 kN OK

Determination of the base plate thickness


The plate thickness shall fulfil the following condition :

tp tp,min =

t p, min =

Document Ref:

c
f y / (3 f jd M0 )

63
= 27 mm
275 / (3 16.7 1.0)

Adopt a base plate thickness: tp = 30 mm

of

Example: Column base connection under axial compression (GB)

SX019a-EN-GB

Quality Record
RESOURCE TITLE

Example: Column base connection under axial compression

Reference

SX019a-EN-GB

Created on Tuesday, March 10, 2009


This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

LOCALISED RESOURCE DOCUMENT


Name

Company

Date

Created by

Laurent Narboux

SCI

Dec 2006

Technical content checked by

Abdul Malik

SCI

Jan 2007

Editorial content checked by

D C Iles

SCI

19/2/07