Вы находитесь на странице: 1из 9

Predicting condensate collection from HVAC air handling

units.
INTRODUCTION AND PURPOSE
Recent water shortages in the southeastern US and elsewhere have increased the perceived value
of fresh water beyond its financial cost. Local, interstate, and international disputes over water
rights are likely to further this trend. The increasing concern for water resources within ASHRAE is
reflected in two new Standards that address water use in buildings: Standards 189.1-2010
(Standard for the Design of High Performance Green Buildings Except Low-Rise Residential
Buildings) and 191P (Standard for the Efficient Use of Water in Building, Site and Mechanical
Systems). Both standards provide requirements for water using systems, addressing efficient usage
as well as water reclamation and reuse.
Condensate collection from air handling units (AHUs) is one method of water reuse that has been
successfully incorporated in new buildings and is even required in new construction in some
locations. (1) Condensate can most easily be routed directly to a cooling tower sump, but with
storage (and usually in conceit with a rainwater collection system) can be used for irrigation or
ornamental purposes; with further processing it can be used for indoor applications such as
toilet flushing or even potable water.
Tom Lawrence is a Public Service Associate in the Faculty of Engineering at the University of
Georgia, Jason Perry is a Research Engineer in the Faculty of Engineering Outreach Service at
the University of Georgia and Peter Dempsey is an engineering undergraduate student at the
University of Georgia
While incorporating condensate collection into new buildings can berelatively straightforward,
retrofitting existing buildings can be morecomplicated. Since existing buildings comprise
approximately 98% of thebuilding stock (the other 2% being new construction), they represent
asignificantly greater immediate benefit to society in terms of energy orwater consumption savings.
It is thus worthwhile to study and facilitatecondensate collection retrofits in existing buildings.
It is easy to estimate the cost to install a condensate collection system, but it is more difficult to
calculate the financial payback due to water savings. Dire water shortages in some areas may make
the financial question moot, but for now in the majority of cases it is likely that some financial
justification will be necessary.
Currently, prediction methods and tools are not widely available for evaluating whether condensate
collection is worthwhile. Guz (2005) suggests a rule of thumb of 0.1 to 0.3 gallons (0.4--1.1 L)
of condensate per ton of air conditioning, per hour of operation, but this only applies to San
Antonio. A simple online calculator (no longer available) created by Wilcut and Fry determined the
steady-state condensate production rate for a given set of conditions, but was not useful for
predicting condensate over a season of varying weather. Painter (2009) developed a prediction
model for dedicated outdoor air handling units with enthalpy wheel energy recovery, in which he
used the expected difference in humidity ratio on the entering and leaving sides of a cooling coil.
He developed the model to predict condensate production in three locations in Texas using annual
daily average temperature and humidity data.

With this paper we present our methodology for predicting the amount of water collected from an
air handling unit, and we describe an attempt to validate and refine the model with empirical
measurements taken throughout the 2009 cooling season in Athens, Georgia. The model is
designed to be adapted to any location for which hourly data are available.
CONDENSATE COLLECTION SYSTEM DESCRIPTION
The system used in this study was the second condensate collection retrofit installed at the
University of Georgia (UGA), and has been in operation since February 2009. (see Lawrence, et al.,
2010). It is comprised of a stainless steel collection basin measuring about 2 ft (600 mm) square
and 9 in (230 mm) deep, a 1/6 HP (125 W) sump pump with an external diaphragm switch, and an
analog totalizing water meter with 1/10th gallon (0.38 L) resolution. The system is equipped with a
check valve above the pump to prevent backflow into the basin.
The basin was installed so that it could intercept the originalpath of the condensate drain pipe
without changing the slope or thedimensions of the U-trap at the drain outlet from the AHU. An
emergencyoverflow pipe is connected near the top of the basin and leads to theexisting floor drain,
so that the original drain path would be completedin the case of a pump failure.
The meter was installed at eye level in the vertical section of pipe above the pump so that it would
always be measuring full pipe flow. This was a lesson learned from the first installation at UGA in
which the meter was installed horizontally in a section of pipe with essentially open-channel flow,
raising concerns that the meter might be fooled into reporting more water than is really flowing
through it.
After the meter, the pipe runs up and over the AHU, through the penthouse wall, across the roof at
a slope of 1/4 inch per foot (21 mm per m), and joins a pipe from another condensate collection
system before dropping down an exterior wall to the sump of the building's cooling tower.
Measurement Equipment and Methods
Dataloggers were used measure the air temperature and relative humidity at the outdoor air intake
and in the fan section of the AHU. We employed a combination temperature and relative humidity
datalogger, which has a RH measurement accuracy of [+ or -] 3.5% from 25% to 85% over the
range of 59[degrees] to 113[degrees]F (15[degrees] to 45[degrees]C) and [+ or -] 5% from 25% to
95% over the range of 41[degrees] to 131[degrees]F (5[degrees] to 55[degrees]C). The
logger temperature accuracy is [+ or -] 0.72[degrees]F from 32[degrees] to 104[degrees]F ([+ or -]
0.4[degrees]C from 0[degrees] to 40[degrees]C).
We recorded fan speed during the study using fan motor current as proxy data for fan speed and
hence airflow. A current transformer (CT) rated for 50 amperes was placed on one leg of the three
phase motor circuit and connected it to a datalogger. The CT and datalogger combination is rated
as being accurate to [+ or -] 2.25 A.
We synchronized and programmed the three dataloggers to record every five minutes, and we
downloaded data from them about once a month.
Airflow Baseline
From our initial observations of the supple air fan operation, the fan current draw (as indicated on
the variable frequency drive display) tended to be within a fairly narrow range, but did vary some.

We obtained the baseline airflow of the AHU by conducting pitot tube traverses across the supply
air ductwork leading from the AHU, and recorded the current to the fan. The baseline airflow
measurements were made when the fan was in normal operation and the current draw near
the 'nominal' level. We next also conducted pitot tube traverses with the fan speed manually set
near the upper end and then again near the lower end of what our data loggers had recorded as
being the fan normal operating range. From the pitot tube traverses we then calculated the supply
airflow at the 'baseline' current, which was used as the primary reference point for determining the
airflow for all data points during the cooling season.
Water Meter Validation
To ensure that the water meter was not affected by turbulence due to its proximity to the pump, a
calibration procedure was performed using a graduated one gallon (3.8 L) container. One gallon at
a time was added to the system's collection basin until the pump was triggered and the water
pumped out. This process was repeated approximately 15 times, with a recording taken from the
meter each time. There was no significant error between the measured input of water and the
cumulative meter reading at the end of the process.
DESCRIPTION OF THE BASIC MODEL
General method for computing condensation
For simplicity, consider the process of a unit conditioning 100% outdoor air (such as with a
dedicated outdoor air system hvac jobs sacramento ca or DOAS). The psychrometric chart shown in
Figure 1 represents a path of outdoor air as it passes across the cooling coil for the 0.4% cooling
design condition in Athens, Georgia. Assuming a supply air condition of 55[degrees] F
(12.8[degrees] C) and 85% relative humidity (wet bulb T=52.5[degrees] F or 11.4[degrees] C), the
humidity ratio changes across the coil from 0.0141 to 0.0078 lb/[lb.sub.air] (kg/[kg.sub.air]).
The difference in absolute humidity ([omega]) between the incoming outdoor air and supply air
leaving the unit represents the amount of condensation that occurs. Thus, for every pound (or kg) of
air supplied by the unit, 0.0141 - 0.0078 or 0.0063 pounds (kg) of water are condensed.
[FIGURE 1 OMITTED]
The total amount of condensate expected is determined by the equation below:
Condensate collected = Airflow x density x 60 [min/hr] x [DELTA][omega] (1)

Assuming for example 1,000 cfm (472 l/s) of outdoor air is


being conditioned, the total amount of condensate
expected would be.
Condensate = 1,000 [[ft.sup.3]/min] x
[lb/13.133[ft.sup.3]] x 60 [min/hr] x (0.0141 - 0.0078)
[[lb.sub.water]/[lb.sub.dry air]] = 28.8 [lb/hr] (13.1
kg/hr)
This is approximately 3.5 gallons (13.1 liters) per hour at the cooling design condition.

For the condensate prediction study described in this paper, a spreadsheet model was developed
which computed an estimate of the condensate collection rate expected during each five-minute
data logging time period through the course of the cooling season. The model uses the following
data inputs:
* Outdoor air temperature and relative humidity (from data logger)
* Supply air temperature and relative humidity (from data logger)
* Outdoor air and supply air humidity ratio (computed from recorded data set)
* Supply fan input current (from data logger)
* Air handling unit supply airflow rate at 'baseline' flow and specific current input values (measured
using pitot tube traverses at 'normal operating' fan speed and other points by manually adjusting
fan speed at the VFD controller)
Spreadsheet model logic
The following computational steps are performed by the spreadsheet model for each of the fiveminute data recording periods.
1. Compute the differential between outdoor and supply air humidity ratio. ([DELTA][omega])
2. Estimate the supply airflow rate for this period, assumed to be a function of the cube root of the
current.
Supply Flow This Period = [([Current this period/Current at baseline flow]).sup.[1/3]] x Baseline
flow (2)
Baseline current = 33.9 Amps (one leg of 3 phase circuit);
Baseline flow = 19,128 cfm
3. Multiply the supply volumetric airflow by density and 60 min/hr to get supply air mass flow rate
([m.sub.air]) in lbm/hr.
4. Compute the predicted condensate collection rate. Condensate flow = [m.sub.air] x
[DELTA][omega] The result is the predicted condensate collected in lb/hr.
5. Convert the predicted condensate mass flow rate into a volume flow rate, gallons/hr and
gallons/min (gpm).
6. Determine the predicted total condensate produced for this data logging time period Condensate
produced = Volume flow (gpm) x 5 min
The total condensate produced is summed up between each field meter reading period, which was
typically done on a daily basis during each weekday. For each period between field meter readings,
the total predicted condensate is compared to the actual measured amount.
RESULTS DISCUSSION

Baseline model evaluation


We made a total of 108 water meter readings during the 2009 cooling season. Data were recorded
from April 1 through the end of September. By April 1 the installed water meter had already
recorded some condensate collected but our data logging equipment was not installed and
validated until then. A second AHU in this mechanical room was retrofitted with a condensate
collection system in early October, and the output pipe from this new unit connected into the
collection basin used for our study AHU, therefore we had to stop data recording on September 29.
Since this was getting near the end of the condensate collection and cooling season, it was not felt
to be a significant problem.
Readings were made nearly every day during the normal workweek (Monday through Friday; the
building is locked to outsiders on weekends and holidays). The predicted condensation results were
computed using the supply fan airflow as measured in the spring and using the installed data
logger measurements for outdoor air and supply air conditions and these compared to the actual
condensate collected using the installed totalizing flow meter.
Using the prediction method described earlier and the recorded measurements from the
dataloggers, the condensate quantities predicted by the model were consistently lower than the
actual quantities measured throughout the cooling season. The total predicted condensate for
this air handling unit during the cooling season was 134,021 gallons (507,325 liters), but the actual
amount collected was 171,793 gallons (650,307 liters), for a net under-prediction error of 28%.
Figure 2 shows the results for each data reading period in terms of average condensate flow rate
(gallons per minute) during the recording period, which makes for an easier comparison than just
the total predicted or actually collected, as the time lengths between readings varied.
[FIGURE 2 OMITTED]
To check how consistent this error was through the cooling season and if it depended on the
weather conditions, Figure 3 is provided which shows a scatter diagram of the ratio of actual to
predicted total condensate collected versus the average outdoor air humidity ratio. Although the
predicted values seem to be a little closer to the actual during periods of higher ambient humidity,
this is not a strong trend and does not appear to provide any insight to the analysis.
[FIGURE 3 OMITTED]
Evaluation of potential sources of error - Supply airflow rate
The amount of predicted condensate during any given period is a direct linear function of the supply
airflow rate used in the calculation, since the condensate collection predicted is based on
the humidity ratio of mass of water per mass of dry air (lb/lb or kg/kg). Thus, if the actual flow were
say 10% higher than used in the calculation, there would be an underestimation of condensate
collection by 10% even if all other data were perfectly known and the equation was perfectly
accurate and applicable to this situation.
This is illustrated by considering a case where the supply airflow used in the condensate prediction
calculation is arbitrarily increased by 30%, representing a case where the actual airflow were 30%
more than determined by the field measurements. The resulting total condensate predicted for this
cooling season is 174,227 gallons (659,522 liters), or an error compared to the actual measure of
about 1%. The plot of average condensate flow rate for each data recording period shows a fairly
good match as well (Figure 4). While this 30% extra fan flow seems to be a possible explanation for

the difference, it is not the only potential contributor to the error measurement. The 30% error
in airflow measurement is also considered larger than what is generally considered acceptable in
practice (more on this later).
[FIGURE 4 OMITTED]
Evaluation of potential sources of error - Relative humidity measurements
The accurate measurement of relative humidity has been an issue in the past within the HVAC
industry. For example, earlier versions of humidity sensors used in economizer controllers had a
propensity for early failure, leading to bypassing of the economizer control and giving a black eye
to this concept for years.
The particular humidity sensors used for this study have a manufacturer's stated accuracy of [+ or ] 3.5% for the majority of the temperature range that they were used to measure. Since
the calculation of condensate collection potential in this study involved a differential of humidity
ratio between the incoming outdoor air and the supply air, there potentially could be anywhere
between a -7% and +7% error (double one sensor) even if the sensors used were within
the manufacturer's specifications.
Consider the extreme case of this and with the error in the proper direction to bring the predicted
condensate level closer to the actual measured value. This would be if the case were that the actual
relative humidity differential between incoming outdoor air and the supply air were 7% larger. A
plot of the average condensate flow rates during each data recording period is given in Figure 5.
The predicted annual condensate collected under this scenario would be 165,541 gallons (626.643
liters), for a 4% error in the prediction. While this scenario is possible, it relies on a 'best case'
assumption of the error in relative humidity measurements.
[FIGURE 5 OMITTED]
Other scenarios were also evaluated with an assumed larger relative humidity differential of 1% and
3.5% as well. These results had corresponding levels of improvement in the condensate
prediction.
Evaluation of potential sources of error - One realistic possibility
This scenario evaluated one case where the relative humidity and supply fan flow rate error values
would be within that expected for a 'typical' case. For this evaluation, we evaluated the predicted
condensate flow assuming the following errors in sensor readings or measurements.
* Relative humidity - assumed a 3.5% higher difference between outdoor air and supply air than we
measured
* Supply airflow - assumed the supply air fan had a 15% higher flow rate
A 15% error in measurement of the supply fan airflow rate is a very reasonable estimate. For
example, the U.S. Green Building Council's LEED-2009 program for IEQ Credit 1 considers a [+ or ] 15% differential in measured incoming outdoor airflow an acceptable value.
Figure 6 gives a comparison plot of the average condensate flow rates during each data recording
period. The results compare very similarly to the actual measured values, and the total annual

condensate predicted is 170,428 gallons (645,142 liters), for an under-prediction of only 1%


compared to the actual measured value.
[FIGURE 6 OMITTED]
Evaluation of potential model simplifications - Assume constant supply airflow rate
This final section evaluates the impact of using more simplified model approaches. One of these is to
use just an 'average' value for the supply fan flow rate. Since we were not directly measuring the
supply flow, only the electrical current input to the fan, this will have to be approximated.
Fortunately, the fan speed did not vary considerably during any given day or through the course of
the cooling season. In fact, our baseline airflow measurement taken in the early spring was at a fan
speed (based on current reading) considered very representative for the entire cooling season. This
flow rate was measured at 19,128 cfm (9,027 liters/s), so this scenario evaluated the predicted
collection of hvac union sacramento california condensate assuming the supply airflow was
a constant 19,128 cfm (9,027 liters/s). One other point to note is that there is an error introduced
from measuring the current as well; our current transducers and datalogger together are accurate
to [+ or -] 2.25 A and we were measuring current in the range of about 30 to 40 A
The resulting predicted annual condensate was 136,532 gallons (516,830 liters), essentially the
same as the baseline case when a fan speed (using measured current) correction was applied. In
fact, this number is slightly closer to the actual measured amount of condensate collected.
Evaluation of potential model simplifications - Assume constant supply air humidity ratio
Another possible simplification is to assume that the supply air humidity ratio is constant, and thus
there would be no need to measure the supply air temperature and relative humidity. This is an
important simplification that makes estimation of any AHU for condensate collection potential
(retrofit or new installation) much easier.
For this scenario, we assumed that the supply air humidity ratio was that if the supply air
temperature and relative humidity were 56[degrees] F and 85%, respectively. This corresponds to a
humidity ratio of 0.008 [lb.sub.water]/[lb.sub.dryair] ([kg.sub.water]/[kg.sub.dryair]).
The resulting predicted annual condensate was 133,288 gallons (504,548 liters), again essentially
the same as the baseline case using measured temperature and relative humidity of the supply and
the corresponding humidity ratio for those conditions.
Other Sources of Error
Several other potential sources of error might exist, and one of these could include the sensor
locations. For example, the outdoor air intake is shielded from direct sun, but there may still be
some error from that since the intake is on the south side of the building. The supply air conditions
were recorded with the data logger located in an easy to access section of the fan chamber; it was
assumed the air is fairly well mixed but this may not have exactly been the case.
CONCLUSIONS AND RECOMMENDATIONS
This study evaluated a model for predicting condensate collected from an AHU that conditions
100% outdoor air. A number of cases and possible scenarios for the impact of measurement error
were studied to see if these alone could account for the under-prediction of condensate compared

to the measured value during an entire cooling season. A summary of all the evaluation scenarios is
given in Table 1.
Table 1 - Summary of Condensate Prediction Scenario Results Case Condensate Error, %
Collected or Predicted, gal (liters) Actual Measured 171,793 (650,307) - Baseline 134,021
(507,325) 28% Airflow sensitivity 30% higher supply airflow 174,227 (659,522) 1% Humidity
measurement sensitivity 1% greater difference in RH 138,335 (523,654) 24% 3% greater
difference in RH 149,551 (566,112) 15% 7% greater difference in RH 165,541 (626,643)
4% Error attributable to measurement accuracy only? 3.5% greater difference in RH and
170,428 (645,142) 1% 15% higher supply airflow Potential simplifications (using baseline case
values for other parameters) No fan speed correction for airflow 136,532 (516,830) 26% Use
'typical' supply air humidity ratio 133,288 (504,548) 29%
Even though the baseline model using measured values for key parameter inputs such as outdoor
and supply air temperature and relative humidity and an estimation of the supply airflow based on
fan current draw underpredicted the condensate that would be collected, there are several
potential scenarios that could explain this simply by error introduced by sensor (in)accuracy. One
very real possibility was discussed with an assumed 3.5% error in relative humidity
(the manufacturer's advertised accuracy) and 15% error in airflow.
Even if there were a 30% error in predicted condensate, this may be acceptable if the only answer
really desired was if one should install or retrofit a condensation collection system or not. A 30%
error in estimated condensate would result in 30% error of the potential cost of water savings or
recovery, which may or may not be significant to the decision maker.
We also determined that two simplifications could be made to the prediction if one is only
concerned with the total annual condensate collected. For this AHU, a constant supply fan flow
could be assumed. This assumption may not apply to all AHUs across the board as it would depend
on the variation in fan speed expected and how wide that variation is. The assumption of a constant
supply air humidity ratio also can be reasonably assumed, where this should be based on
the average supply air conditions expected.
Based on all these results, we conclude that our model for estimating the condensate collection
potential for any AHU with 100% outdoor air is a relatively simple and valid approach. But what if
the AHU is not 100% outdoor air (as most are not)? We feel the model is applicable there as well,
with it being up to the engineer to determine or estimate the incoming outdoor airflow and variation
in flow to use.
The purpose of this study was to validate our approach for estimating the potential application of
condensate to a new or existing AHU and the amount of water expected. Before this study, we have
done this using typical weather data (Marion and Urban 1995). Based on the fairly successful
results of this study, we can safely recommend applying this model approach using 'typical' weather
data to predict condensate collection during a 'typical' cooling season.
REFERENCES
Guz. K. 2005. "Condensate Water Recovery", ASHRAE Journal 47(6):54-56.
Lawrence, T.M., J. Perry and P. Dempsey, 2010, "Making Every Drop Count: Retrofitting
Condensate Collection on HVAC Air Handling Units", ASHRAE Journal 52(1):48-54.

Marion, W. and K. Urban. 1995. Users Manual for TMY2s. National Renewable Energy Laboratory,
Golden, Colorado
Painter, F. 2009. "Condensate Harvesting from Large Dedicated Outside Air-Handling Units with
Heat Recovery", ASHRAE Transactions 2009, 115(2):xxx
Wilson, A. 2008. "Alternative Water Sources: Supply-Side Solutions for Green Buildings",
Environmental Building News, May 2008. Available
from: http://www.buildinggreen.com/auth/article.cfm/ID/3903/ [accessed December 2009].
T.M. Lawrence, Ph.D.
Member ASHRAE
Jason Perry
Associate Member ASHRAE
Peter Dempsey
Student Member ASHRAE

Вам также может понравиться