Although industrial buildings can be designed to support
mezzanine floors and cranes, they are primarily loaded by their self weight, service loads, imposed loads or snow loads and wind loads. Service loads tend to be project specific but a nominal value of around 0.05 kN/m2 should always be considered in structural design to allow for loads from nominal lighting. This value will increase if more substantial services such as sprinkler systems or air-conditioning are incorporated. The self weights of false ceilings over intermediate floors are often also treated as service loads. Snow loads and wind loads are site specific and are influenced by the geometry of the structure and its orientation. Snow loads are determined by reference to EN 1991-1-3 and its UK National Annex. Wind loads are determined by reference to EN 1991-1-4 and its UK National Annex, but designers might also like to refer to Reference [5]. Clause 3.3.2 (1) of EN 1991-1-1 states that on roofs, imposed loads and snow loads or wind loads should not be applied together simultaneously. This implies (1) that snow load and imposed load should not appear together in any given load combination, and (2) that imposed load and wind load should not appear together in any given load combination. The basis for this clause is that it would be unreasonable to consider that maintenance would be undertaken in severe weather conditions. The first implication is in line with current practice in the UK, where, for roofs that are not accessible except for normal maintenance and repair, the loading would typically be taken as the larger of an imposed load of 0.6 kN/m2 or the snow load (i.e. the imposed loads and snow loads are not applied simultaneously). The same value of 0.6 kN/m2 is also recommended for roof slopes less than 30 in Table NA.7 of the UK National Annex to EN 1991-1-1. The second implication is that for cases where the snow load is less than 0.6 kN/m2, then it is only this lesser value that would be applied in combination with the wind load, which, coupled with the fact that the combination factor for snow loading (0 = 0.5) is lower than that for imposed loading (0 = 0.7), may result in significantly lower roof loading (in combination with wind) than is used in current UK practice. It is recommended in this guide that imposed loads and wind loads continue to be considered in combination for the design of portal frames in the UK. Given the different combination factors for snow and imposed loading, the snow load would have to be greater than 1.4 times the imposed load (i.e. greater than 0.84 kN/m2) to be critical in the wind (leading) plus imposed or snow load combination. Where the imposed load or snow load is the leading variable action, the snow load simply needs to exceed the imposed load to become critical.
The concept of factors was introduced in Section 3 and Table 5.1
presents the factors that are relevant to portal frame design. In Table 5.1, Gkc = permanent crane action and Gkc + Qkc = total crane action (from Clause A.2.3 of EN 1991-3 Annex A).
Table 5.1: factors relevant to portal frame structures
Imposed loads on roofs
Snow loads at altitude less than
or equal to 1000 m Wind loads
Crane loads
0.7
0.0
0.0
0.5
0.2
0.0
1.0
0.9
Gkc/(Gkc+Qkc)
0.5
0.2
0.0
5.1.1 EN 1991-1-3: 2003 - Snow loading
In Section 2 of EN 1991-1-3, Classification of actions, snow loads are classified as variable fixed actions unless otherwise specified in the code. In this section it also states that exceptional snow loads and exceptional snow drifts may be treated as accidental actions, depending on geographical locations. The UK National Annex confirms this in clauses NA.2.4 and NA.2.5 and also states that Annex B should be used to determine the drifted snow load case. This approach is consistent with current UK practice for designers using BS 6399-3 and BRE Digest 439 [9] to determine uniform snow loads and the loads caused by the build up of drifted snow. 5.1.2 EN 1991-1-4: 2003 - Wind loading Wind actions are defined as variable fixed actions. The process for determining wind pressures is based on a 10-minute mean wind velocity and a new map has been provided in the UK National Annex. Designers who have been working with BS 6399-2 will find the approach for determining wind pressures very similar although some terminology has changed. The publication Designers Guide to EN 1991-1-4 Eurocode 1: Actions on structures, general actions part 1-4. Wind actions [2] is very important in explaining the limitations of the new European Standard. Although wind pressures vary depending on site location, altitude, orientation etc, the pressure and force coefficients depend only on the external shape of the structure. By looking at the overall pressure coefficients, irrespective of the actual site wind pressures, it is possible to determine the critical load cases. The majority of portal frames have roof pitches of 5, 6 or 10. Figures 5.1c, 5.1d and 5.1e have been produced for portal frames with these roof pitches and present overall pressure coefficients. Figures 5.1a and 5.1b have been included to show the intermediate steps required to arrive at the figures in 5.1c. Similar intermediate steps have not been included for Figures 5.1d and 5.1e, although some extended expressions have been shown. External pressure coefficients for the walls have been extracted from Table 7.1 of EN 1991-1-4 assuming an h/d ratio 0.25. Table 7.4a of EN 1991-1-4 cannot be used for roof coefficients; instead, the UK National Annex directs us to use Table 10 of BS 6399-2. Once the basic external coefficients have been established, to comply with the requirements of Clauses 5.3 and 7.2.2 of EN 1991-1-4 two addition factors must be applied to the external force coefficients: 1. The structural factor cscd for the majority of portal frames the height will be less than 15 m and the value of cscd is taken as 1. 2. For buildings with h/d 1, most portal frames, the external wind forces on the windward and leeward faces are multiplied by 0.85.