Planning Documents

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technische nderungen vorbehalten. Einige Abbildungen und Beschreibungen knnen Sonderausstattungen enthalten.

for the Car Park Management Systems

Planning Manual
Car Park Management Systems

- Planning Documents -

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 1 of 98

Planning Documents
for the Car Park Management Systems

Contents

1
1.1
1.2
1.3
1.4

2
2.1
2.2

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technische nderungen vorbehalten. Einige Abbildungen und Beschreibungen knnen Sonderausstattungen enthalten.

Page

Introduction........................................................................................4
About this Manual......................................................................................................................... 4
Definition of used icons................................................................................................................ 4
Legal information.......................................................................................................................... 4
User instructions........................................................................................................................... 4

Central Computer, Management Computer and Manual Cashier


Station.................................................................................................6
General survey of devices............................................................................................................ 6
Arrangement of components........................................................................................................ 7

Entries, Exits and Passages............................................................8

3.1
3.1.1

Control Devices............................................................................................................................ 8
Terminals for Entry, Exit and Passage for the Side stripe and/or the Barcode System:
PGL20/S; PGL25/S; PL20/S; PL25/S as well as PGL20/B; PGL25/B; PL20/B; PL25/B..........8

3.1.2

Terminals for Entry, Exit and Passage for the ChipCoin System: PGL20/C; PGL25/C;
PL20/C; PL25/C.................................................................................................................... 12
Terminals for Entry, Exit and Passage for the Side stripe System, Barcode System and
ChipCoin System: PGL30/S; PL30/S; PGL30/B; PL30/B as well as PGL30/C; PL30/C......14

3.1.3
3.1.4
3.1.5
3.1.6
3.2
3.3
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
3.4
3.4.1
3.4.2
3.5
3.5.1
3.5.2
3.6
3.6.1
3.6.2
3.7
3.7.1
3.7.2
3.7.3
3.7.4
3.8

Multi Control Unit (MKG)....................................................................................................... 17


Car Park Access Reader for barrier control PCX35...............................................................21
Contactless Card Reader for Access Control for long term parker........................................26
Addition for Entry, Exit and Passage Terminals: Dispensing tray as rain protection...................28
Barriers....................................................................................................................................... 29
Safety.................................................................................................................................... 29
AS20 / AS2000...................................................................................................................... 29
AS30..................................................................................................................................... 33
AS35..................................................................................................................................... 35
Barrier equipment and accessories.......................................................................................37
Prefabricated steel island for devices......................................................................................... 40
Islands made of flat steel....................................................................................................... 40
Islands made of steel tube.................................................................................................... 44
Nudge bar................................................................................................................................... 45
For control devices PGL20 / PL20......................................................................................... 45
For barriers AS20, AS2000.................................................................................................... 47
Loops / Cable ducts.................................................................................................................... 48
Laying of loops...................................................................................................................... 48
Laying of cable ducts............................................................................................................. 51
Situations at the Entry, the Exit and the Passage.......................................................................52
Plan for an Entry Lane........................................................................................................... 52
Plan for an Exit Lane............................................................................................................. 52
Plan for a bi-directional lane.................................................................................................. 53
Plan for a double-sided lane.................................................................................................. 53
Manual Cashiering at the Exit..................................................................................................... 54

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 2 of 98

Planning Documents
for the Car Park Management Systems

4
4.1
4.1.1
4.1.2
4.1.3
4.2
4.2.1

5
5.1
5.2
5.3

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technische nderungen vorbehalten. Einige Abbildungen und Beschreibungen knnen Sonderausstattungen enthalten.

6
6.1
6.2
6.3
6.4

Automatic Pay Stations..................................................................56


PKA2x with banknote processing and optional with non-cash payment.....................................56
Mounting niche for PKA2x..................................................................................................... 61
Illuminated top for PKA2x...................................................................................................... 61
Roofing for Automatic Pay Station PKA2x.............................................................................62
Automatic Pay Station for only non-cash payment.....................................................................66
PAY20/S................................................................................................................................ 66

Ticket / Card Reader for Door Control.........................................68


PTL20......................................................................................................................................... 68
PTL35......................................................................................................................................... 69
PTL36......................................................................................................................................... 72

Complements...................................................................................74
Steel Mast for Signals (for example mast for Multi Control Unit)................................................74
Holder for alternation sign for wall mounting...........................................................................79
Signal Indication......................................................................................................................... 80
Displays for S&B Guidance Systems.........................................................................................82

Mounting of the Device...................................................................91

Wiring Diagram................................................................................92

8.1
8.2

9
9.1
9.2
9.2.1
9.2.2
9.2.3
9.2.4

Legend....................................................................................................................................... 93
Safety Instructions...................................................................................................................... 94

Information about Power Supply and Overvoltage Protection 95


General Information.................................................................................................................... 95
Information about Screening...................................................................................................... 95
LON networks........................................................................................................................ 95
RS485 networks.................................................................................................................... 95
Ethernet networks................................................................................................................. 95
Power Supply PTL36............................................................................................................. 95

List of illustrations.................................................................................97

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 3 of 98

Planning Documents
Chapter 1: Introduction

1 Introduction
1.1 About this Manual
This Planning Manual contains technical information about major components of the
Scheidt & Bachmann Car Park Management Systems, as well as information about
the installation and the connection of these components. The shown installation
variants can be modified and show a basic representation only. Final planning and
installation is made project-related complying with the minimum dimensions.

1.2 Definition of used icons


The following icons will be used in this Planning Manual:
Power supply / Power consumption

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technische nderungen vorbehalten. Einige Abbildungen und Beschreibungen knnen Sonderausstattungen enthalten.

Connections
kg

Weight
Incidentals
Conformity and Certification
Mounting / Installation
Ambience conditions

1.3 Legal information


The "Planning Manual" and all its parts is protected by copyright. Scheidt &
Bachmann GmbH reserve all rights concerning the work. Each utilization, which is not
expressly approved from the copyright law, requires the previous approval of Scheidt
& Bachmann GmbH. This applies in particular to duplication, revision, translation,
microfilming as well as storing and processing in electronic systems.
Since references and facts are subject to technological changes, no responsibility can
be taken for the given information. Changes of technical details regarding data and
illustrations in the Planning Manual are reserved. Always pay attention to the update
index.

1.4 User instructions


For detailed information please contact the sales and marketing department of
Scheidt & Bachmann GmbH and their subsidiaries and authorized partners. The
contact persons for your country and region can be found in the Internet on our
homepage: www.scheidt-bachmann.com.
This Planning Manual is not intended to provide instructions through self-study.
Concerning the users of this Planning Manual, technical understanding and
Scheidt & Bachmann GmbH
Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 4 of 98

Planning Documents
Chapter 1: Introduction

knowledge is taken for granted as well as previous experience regarding stationary


traffic and parking facilities. The execution of work may only take place after briefing
and/or training by specialized personnel of Scheidt & Bachmann GmbH or their
subsidiaries and authorized partners.

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technische nderungen vorbehalten. Einige Abbildungen und Beschreibungen knnen Sonderausstattungen enthalten.

Concerning special solutions, this manual does not claim to be complete.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 5 of 98

Planning Documents
Chapter 2: Central Computer, Management Computer and Manual Cashier Station

2 Central Computer, Management Computer and Manual


Cashier Station
2.1 General survey of devices
CRT Monitor

LCD Monitor

Customer display

285

90

380

344

225

342

370

150

400

195
375

Barcode scanner

Read / Write Unit


SL20/C

75

290

Read / Write Unit


SL20

120

190

Functional keyboard

288

PC keyboard

465

Mouse and Pad

200

UPS (Uninterruptible Power


Supply)

165

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Receipt printer

220

Printer

165

Computer

185

120

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 6 of 98

Planning Documents
Chapter 2: Central Computer, Management Computer and Manual Cashier Station

POS25/B

POS25/C

POS20-R/S

POS20-R/B

POS20-R/C

POS25/S

LAR20

POS20/C

LR20

POS20/B

ZAR20

POS20/S

ZR20

2.2 Arrangement of components

CRT Monitor
LCD Monitor
Customer
display
Computer

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Printer
Receipt Printer

SL20

Barcode scanner

SL20/C

POS keyboard

PC keyboard
Mouse and Pad

UPS
Legend:
= Standard
= Optional available
- = not available / not needed
Note:
For thermal reasons, at least 10 cm behind and 10 cm above the PC must be left
free for ventilation.
All dimensions are the actual dimensions of the devices. When planning, reserves
must be planned for voltage and control line connectors (approx. 10 cm).
For the connection of peripheral devices to the PC, appropriate cabling possibilities
must be planned, taking into account that the maximally permissible standard
lengths are not exceeded.
Dependent on the execution, the dimensions of the devices may vary and may be
changed by the respective manufacturer.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 7 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3 Entries, Exits and Passages


3.1 Control Devices
3.1.1 Terminals for Entry, Exit and Passage for the Side stripe and/or the Barcode
System: PGL20/S; PGL25/S; PL20/S; PL25/S as well as PGL20/B;
PGL25/B; PL20/B; PL25/B
Entry terminal as dispenser for short term parker tickets for Side stripe and
Barcode tickets and card reader for long term parker cards.
PGL20/S, PGL25/S: Entry terminal for the Side stripe System
PGL20/B, PGL25/B: Entry terminal for the Barcode System
Exit and Passage terminal as ticket / card reader for short term parker and long
term parker for Side stripe and Barcode tickets.
PL20/S, PL25/S: Exit and passage terminal for the Side stripe System
PL20/B, PL25/B: Exit and passage terminal for the Barcode System

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Technical Data

230 V/50 Hz or 115 V/60 Hz


PGL20/S, PGL20/B: 300 VA
PGL25/S, PGL25/B: 200 VA
PL20/S, PL20/B: 250 VA
PL25/S, PL25/B: 160 VA
Additional 700VA used for heating /
ventilation

Power supply
Network
Intercom
Serial interface RS232
Binary Inputs (electrically isolated)
Binary Outputs (electrically isolated)

Ticket specification for Side stripe


tickets: S&B 04 26743
Ticket specification for Barcode
tickets: S&B 04 26670

The machine will be mounted by


Scheidt & Bachmann on a base that
must be provided by the customer
according to our specification.
Concrete foundation B25 must be
suitable for winter condition.
Vertical installation to be ensured.
Drilling template: S&B 04 17490

kg

For indoor and outdoor installation


Temperature range: - 20 C+ 50 C
Humidity: 095 % (not condensing)

60 kg net weight

UL, CUL, CE

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 8 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

PGL20/S; PGL25/S; PL20/S; PL25/S as well as PGL20/B; PGL25/B; PL20/B;


PL25/B
Size / foundation plan (dimensions in mm):

min. 1330

1100

1020

935

385

415
560
min. 170
min. 830

600
320

Concrete foundation B25.


Curb height between 130 and 170 mm.
Must be suitable for winter condition!

560

295

270

61

64,5

265

194

170

14

215,5

600

Curb
Lane

4 fixing holes in housing.


Fixing with 4 tie bolts FAZ 10/50.
Drilling template S&B 04 17490.

Conduit or ducting
for signal- and mains cable.

86 86881 (c) PGL20S_B PL20S_B_e

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).
Scheidt & Bachmann GmbH
Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

680

830

420

Area for device opening

Device

Curb and/or
island
Lane

282501455.doc
Page 9 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

680

PGL20/S; PGL25/S; PL20/S; PL25/S as well as PGL20/B; PGL25/B; PL20/B;


PL25/B
HGV/Truck extension: Size / foundation plan (dimensions in mm):

420

275

420

15 x 30

265
320
600
385
320

Concrete foundation B25.


Curb height between 130 and 170 mm.
Must be suitable for winter condition!

14

550

295

270

600

61

64,5

265

215,5

Curb
Lane
4 fixing holes in housing.
Fixing with 4 tie bolts FAZ 10/50.
Drilling template S&B 04 17490.

Conduit or ducting for


signal cable and mains cable.

86 60095 (-) LKW-Bus Adapter fr PGL20_e

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

325

50

25

385

Device

Curb and/or
island
Lane

282501455.doc
Page 10 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

25

PGL20/S; PGL25/S; PL20/S; PL25/S as well as PGL20/B; PGL25/B; PL20/B;


PL25/B
Prefabricated foundation frame (galvanized)

320
25

Angle 50x50x5
DIN 1028
St 37-2

outside 17 cm

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

45

Curb

370

A-B

30

M12

50

50

95
235
370

86 86993 (-) Fundamentrahmen PGL20

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 11 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.1.2 Terminals for Entry, Exit and Passage for the ChipCoin System: PGL20/C;
PGL25/C; PL20/C; PL25/C
Entry terminal as dispenser for short term parker ChipCoins and for checking of
long term parker cards based on transponder technology.
Designation: PGL20/C; PGL25/C
Exit and Passage terminal for checking of short term parker ChipCoins and long
term parker cards based on transponder technology.
Designation: PL20/C; PL25/C

Technical Data

ChipCoin specification:
S&B 04 18399

230 V/50 Hz or 115 V/60 Hz


PGL20/C, PL20/C: 200 VA
PGL25/C, PL25/C: 150 VA

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Additional 700VA used for heating /


ventilation
UL, CUL, CE

Power supply
Network
Intercom
Serial interface RS232
Binary Inputs (electrically isolated)
Binary Outputs (electrically isolated)

kg

The machine will be mounted by


Scheidt & Bachmann on a base that
must be set up by the customer
according to our specifications.
Concrete foundation B25 must be
suitable for winter condition.
Vertical installation to be ensured
Drilling template: S&B 04 17781

85 kg net weight

For indoor and outdoor installation


Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 12 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

PGL20/C; PGL25/C; PL20/C; PL25/C


Size (dimensions in mm):
Min. 1100

30

850

387

390

89

600

4 fixing holes in housing.


Fixing with 4 tie bolts FAZ 10/50.
Drilling template S&B 04 17781.

480

464

600

Concrete foundation B25.


Curb height between 130 and 170 mm.
Must be suitable for winter condition!

200

300

200

172

290

122

Curb

Lane
Conduit or ducting
for signal- and mains cable.
86 85257 (c) PGL_PL20C_e

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

810

840

970

1025

1500

Area for device opening

Device

Curb and/or
island
Lane

282501455.doc
Page 13 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.1.3 Terminals for Entry, Exit and Passage for the Side stripe System, Barcode
System and ChipCoin System: PGL30/S; PL30/S; PGL30/B; PL30/B as
well as PGL30/C; PL30/C
Entry terminal as dispenser for short term parker tickets and / or ChipCoins and
for checking of long term parker cards based on Side stripe, Barcode and
ChipCoin technology.
PGL30/S: Entry terminal for the Side stripe system
PGL30/B: Entry terminal for the Barcode system
PGL30/C: Entry terminal for the ChipCoin system
Exit and Passage Terminal for checking of short term parker tickets and long term
parker tickets or transponder cards based on the Side stripe, Barcode and
ChipCoin technology.
PL30/S: Exit and passage terminal for the Side stripe system
PL30/B: Exit and passage terminal for the Barcode system
PL30/C: Exit and passage terminal for the ChipCoin system

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Technical Data

230 V/50 Hz or 115 V/60 Hz


PGL30/S, PGL30/B: 300 VA
PGL30/C: 200 VA
PL30/S, PL30/B: 250 VA
PL30/C: 200 VA

For indoor and outdoor installation


Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

additional 700VA used for heating /


ventilation

Power supply
Network
Intercom
Serial interfaces RS232
Binary Inputs (electrically isolated)
Binary Outputs (electrically isolated)

kg

PGL30/S: 63 kg
PGL30/B: 60 kg
PGL30/C: 62 kg

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

Ticket specification for Side stripe


tickets: S&B 04 26743
Ticket specification for Barcode
tickets: S&B 04 26670
ChipCoin specification:
S&B 04 18399

The machine will be mounted by


Scheidt & Bachmann on a base that
must be set up by the customer
according to our specifications.
Concrete foundation B25 must be
suitable for winter condition.
Vertical installation to be ensured.

282501455.doc
Page 14 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

PGL30/S; PL30/S; PGL30/B; PL30/B as well as PGL30/C; PL30/C


Size (dimensions in mm):

min. 445

Area for device opening

700

min.
100

330

418
570

570

min. 880

150

86 61805 (-) PGL_PL30 Ansicht_e

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

1160

min. 1605

410

360

Device

Curb and/or
island
Lane

282501455.doc
Page 15 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

PGL30/S; PL30/S; PGL30/B; PL30/B as well as PGL30/C; PL30/C


Foundation plan (dimensions in mm)
600
330

Concrete foundation B25.


Curb height between 130 and 170 mm.
Must be suitable for winter condition!

270

35

77

240

307

198

216

370

600

340

16

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Curb
Lane
4 fixing holes in housing.
Fixing with 4 tie bolts FAZ 10/50.

Conduit or ducting
for signal- and mains cable.
86 61805 (-) PGL_PL30 Fundamentplan_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 16 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.1.4 Multi Control Unit (MKG)


Size (dimensions in mm):
Area for device opening

348

Max. installation depth 310


372

min. 340

252

Cable feeding

150

80

Front plate with


cylinder lock
Overall size: 342 x 222
Assembly dimension:
270 x 190

1100

200

160

86 68468 (c) MKG_e

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

10

95

Device

Curb and/or
island
Lane

282501455.doc
Page 17 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Multi Control Unit (MKG)


Foundation plan (dimensions in mm)
150

150

150

Base plate
Concrete foundation B25.
Curb height between 100 and 150 mm.
Must be suitable for winter condition!

200

160

Cable feeding
inside.

200

Base plate

80

4 fixing holes in housing.


Fixing with 4 tie bolts FAZ-A4 10/30
and cap nuts.
Curb
Lane
86 68470 (a) MKG-Fundamentplan_e

Wall mounting (dimensions in mm)


410
252

348

Max. installation depth 310


40
372

120

40

250

Cable
feeding

50

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

12

265
340
This mounting allows that the
housing is swinging around to to 50.
(25 in both directions)

This mounting allows that the


housing is swinging around to to 30.
(15 in both directions)
86 79552 (a) MKG Wandmontage_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 18 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Multi Control Unit (MKG)


For cars and lorries (dimensions in mm)

110

Lorries

465

1100

1850

Cars

350

86 86501 (-) MKG-LKW_e

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

410

Device

Curb and/or
island
Lane

282501455.doc
Page 19 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Multi Control Unit (MKG)


Foundation plan for double MKG (Cars and lorries) dimensions in mm

Island outer edge

280

Base plate

350

280

110

20 Dick
280

465

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

25

350

Concrete foundation B25


Must be suitable for
winter condition!

Conduit or ducting for


signal cable and mains cable.

Island outer edge


Direction of traffic
86 86501_2 (-) Fundamentplan MKG-LKW_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 20 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.1.5 Car Park Access Reader for barrier control PCX35


Access control device for barrier control at entries, exits and passages.
The following media can be processed:
Side stripe tickets and cards
Barcode tickets and cards
ChipCoins and Transponder cards (S&B)
Proximity cards (third party)
Additional hardware S2000 required which can be located in the barrier.
Mixtures of the media mentioned above corresponding with the table below:
Options

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Basic function

With

Without

(1)

display

display

Side stripe

Side stripe

(MKV/Motor)

(insert card)

Barcode

Transponder

Barcode

Transponder

Side stripe
(MKV/Motor)

Side stripe
(insert card)

Proximity

Code

Proximity

Code

O = Combination possible within one device


- = Combination not possible within one device
(1) = Devices for code-input are available with display only.

S&B tickets (season parker, short-term parker, value cards, etc.) can only (!)
be processed with the MKV Terminal (motor reader with write function) and
not with an insert card reader.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 21 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Technical Data PCX35

230 V/50 Hz or 115 V/60 Hz


approx. 150 VA
Additional 30VA used for heating /
ventilation

Power supply
Dialogue (RS485)
Intercom

Ticket specification for Side stripe


tickets: S&B 04 26743
Ticket specification for Barcode
tickets: S&B 04 26670
ChipCoin -Specification:
S&B 04 18399

CE

kg

Stand or wall mounting

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

approx. 5 kg net weight

For indoor and outdoor installation.


Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 22 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

PCX35
Size (dimensions in mm):

122

220

340

40

35

220

220

470

86 60810 (b) PCX35 Ansicht

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

1171

75

Device

Curb and/or
island
Lane

282501455.doc
Page 23 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

PCX35
Foundation plan (dimensions in mm)
480
220

160

220

Concrete foundation B25.


Curb height between 130 and 170 mm.
Must be suitable for winter condition!

160

600

12

250

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

R 55

Cable feeding inside rectangular tube.


Tube ends in the center of the base plate.
Inner width approx. 34 x 66 mm.
Curb
Lane

167

4 fixing holes in housing.


Fixing with 4 tie bolts FAZ-A4 10/30
and cap nuts.
86 60810 (b) PCX35 Fundamentplan_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 24 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

PCX35 insert card


Size / Foundation plan (dimensions in mm)
315
214

370

220

55

533

220
160
R 55
12

313

160

220

185
405

PCX Steckleser (-)

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

815

1185

180

Device

Curb and/or
island
Lane

282501455.doc
Page 25 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.1.6 Contactless Card Reader for Access Control for long term parker
Contactless card reader for HID cards as long term parker cards for access control
at entries, exits or passages

Technical Data

12 or 24 VDC
approx. 25 W

HID cards
Typical maximum* range of reading:
ProxCard -II card: max. 73 cm
ISOProx -II card: max. 50 cm
ProxKey -II key chain: max. 43 cm
ProxCard -Plus card: max. 25 cm
SmartProx card: max. 43 cm
ProxPass : max. 2,40 m

Power supply

*According to local installation.

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

kg

Approx. 1.,4 kg net weight


(without stand)
UL; CE, US-DTI (MPT 1337)

For indoor and outdoor installation


Temperature range: -30 C+65 C
Humidity: 095 % (not condensing)

Stand mounting

Additional technical data:


Frequency: 125 kHz

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 26 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Example for contactless card reader: MaxiProx reader


Size (dimensions in mm)

300 (0,98')

300 (0,98')

MaxiProx

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

985 (3,23')

25,4
(0,08')

Device

Curb and/or
island
Lane

282501455.doc
Page 27 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.2

Addition for Entry, Exit and Passage Terminals: Dispensing tray as rain
protection
152
12

50

12

144

40
70

Bearing surface
(with double-sided
adhesive tape)

04 24597 (a) Regenschute PGL_PL_e

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Example: Dispensing tray as rain protection at the entry terminal for the Side stripe
System
Area for device opening

Tray as
rain protection
0
2
4

70
0
3
3
1
.
n
im

415
min. 170

560
min. 840

Regenschute an PGL20_S_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 28 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.3 Barriers
3.3.1 Safety
The barrier is exclusively suitable for traffic with average passenger cars.
The barrier is not suitable for traffic with pedestrians, cyclists and
motorcyclists. Depending on the type of traffic and application, the operation
of barriers may be subject to various rules for the prevention of accidents
and DIN standards. Therefore, the manufacturer strongly advises to apply
suitable instructions, notes, signs and structural measures in order to keep
the danger zone of the barrier free from traffic with pedestrians, cyclists and
motorcyclists.

3.3.2 AS20 / AS2000

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Barrier as a gate for parking areas. The barrier is intended for the use as "Class II
barrier for the commercial ( five-family house / apartment, hotels, garages, shops)
and general (public entry / exit) access control for vehicles".
Special functions: Barrier reverses when touching an obstacle; Automatic opening
of the barrier in the case of power failure as an option.
Not suitable for applications with increased safety requirements, i.e.
protection against crossing danger (railway), breakthrough barricade (ferry
access road, military safety area), or similar!

Technical Data

230 V/50 Hz or 115 V/60 Hz


approx. 200 VA

For indoor and outdoor installation


Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

Power supply via entry and exit control


devices (PGL / PL) or via separate
fuse-protected supply line
Control and acknowledgement signals

CE
AS2000: CE, UL, CUL

kg

Approx. 60 kg net weight without


barrier arm

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

The machine will be mounted by


Scheidt & Bachmann on a base that
must be set up by the customer
according to our specifications.
Concrete foundation B 25 must be
suitable for winter condition.
Vertical installation to be ensured

282501455.doc
Page 29 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Additional technical data:


Length or barrier arms (standard):

AS20:
2.5 m; 3.0 m; 3.5 m
AS2000: 2.5 m; 3.0 m; 3.5 m; (5.4 m with
extras)

Time for barrier opening:


AS20:
approx. 1.5 s for a 90-degree movement
AS2000: after 1.2 s approx. 80 degrees of final position and after 2.3 s 90 degrees.
Time for barrier closing:
AS20:
approx. 1.5 s for a 90-degree movement
AS2000: after 1.2 s approx. 25 degrees of final position and after 2.4 s 0 degrees.

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

In case of a closure with a magnetic impact post, slower closing can be


set by means of a DIP switch!

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 30 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

AS20 / AS2000
Size / foundation plan (dimensions in mm):
Area for device opening

420
354

1098

min. 1300

442

334

Concrete foundation B25


Curb height between 130 and 170 mm.
Must be suitable for winter condition!

334

62,5

300

274

208

290
550

420

14

195

600

600

Curb
Lane

Conduit or ducting
for signal- and mains cable

4 fixing holes in housing.


Fixing with 4 tie bolts FAZ 10/50.
Drilling template S&B 04 18333.
86 85055 (f) Schranke AS20_e

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

900

420

Device

Curb and/or
island
Lane

282501455.doc
Page 31 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

AS20
Prefabricated foundation frame (galvanized) (dimensions in mm)

15

Cut A - B
45

Angle 50x50x5
DIN 1028
St 37-2

edge 17 cm

300

Curb outer

330

A-B

30

M 12 x 35

15

M12
40

40

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

95
235
370

86 86994 (-) Fundamentrahmen AS20_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 32 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.3.3 AS30
Barrier as a gate for parking areas.
Not suitable for applications with increased safety requirements, i.e.
protection against crossing danger (railway), breakthrough barricade (ferry
access road, military safety area), or similar!

Technical Data

230 V/50 Hz or 115 V/60 Hz


approx. 200 VA

For indoor and outdoor installation.


Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Power supply via entry and exit control


devices (PGL / PL)
Control and acknowledgement signals

CE
AS2000: CE, UL, CUL

kg

Approx. 60 kg net weight without


barrier arm

The machine will be mounted by


Scheidt & Bachmann on a base that
must be set up by the customer
according to our specifications.
Concrete foundation B25 must be
suitable for winter condition.
Vertical installation to be ensured

Additional technical data:


Length of barrier arms (standard): 2.5 m; 3.0 m; 3.5 m
Time for barrier opening: after 1.2 s approx. 80 degrees of final position and after
2.3 s 90 degrees.
Time for barrier closing: after 1.2 s approx. 25 degrees of final position and after
2.4 s 0 degrees.
In case of a closure with a magnetic impact post, slower closing can be set
by means of a DIP switch!

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 33 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

AS30
Size / foundation plan [dimensions in mm (ft)]:
Area for device opening
437 (1,43')

min. 1200 (3,94')

min. 20
(0,07')

334 (1,10')

418 (1,37')

600 (1,97')
300 (0,98')

16
(0,05')

355 (1,16')

290 (0,95')

Curb

Conduit or ducting
for signal and
mains cable.

146 (0,48')

4 fixing holes in housing.


Fixing with 4 tie bolts
FAZ 10/50.

Concrete foundation B25.


Curb height between 130 mm (0,43')
and 170 mm (0,56').
Must be suitable for winter condition!

418 (1,37')

230 (0,75')

212 (0,70')

338 (1,11')

98 (0,32')

334 (1,10')

600 (1,97')

Lane

86 61806 (a) AS30_e

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

1020 (3,35')

438 (1,44')

909 (2,98')

357 (1,17')

Device

Curb and/or
island
Lane

282501455.doc
Page 34 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.3.4 AS35
Barrier as a gate for parking areas.
Not suitable for applications with increased safety requirements, i.e.
protection against crossing danger (railway), breakthrough barricade (ferry
access road, military safety area), or similar!

Technical Data

230 V/50 Hz or 115 V/60 Hz


approx. 200 VA

For indoor and outdoor installation.


Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Power supply via entry and exit control


devices (PGL / PL)
Control and acknowledgement signals

kg

Approx. 60 kg net weight without


barrier arm

The machine will be mounted by


Scheidt & Bachmann on a base that
must be set up by the customer
according to our specifications.
Concrete foundation B25 must be
suitable for winter condition.
Vertical installation to be ensured.

CE
AS2000: CE, UL, CUL

Additional technical data:


Length for barrier arms (standard): 2.5 m; 3.0 m
Time for barrier opening: after 1.2 s approx. 80 degrees of final position and after
2.3 s 90 degrees.
Time for barrier closing: after 1.2 s approx. 25 degrees of final position and after
2.4 s 0 degrees.
In case of a closure with a magnetic impact post, slower closing can be set
by means of a DIP switch!

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 35 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

AS35
Size / foundation plan (dimensions in mm):
Area for device opening
280
300

min. 1300

246

206

900

Cut A-A

min. 20

180

250

250

320

600
250

Conduit or ducting
for signal cable and
mains cable.

Concrete foundation B25.


Curb height between 130 and 170 mm.
Must be suitable for winter condition!

210

150

16

332

150

310

470

280

600

170

Curb
Lane

4 fixing holes in housing.


Fixing with 4 tie bolts FAZ-A4 10/30
and cap nuts.
86 61794 (-) AS35_e

When the device is mounted on an


island, the stated dimensions referred
to the lane are possibly increased by
the height of the curb or island (approx.
130 170 mm).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

1012

174

Device

Curb and/or
island
Lane

282501455.doc
Page 36 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.3.5 Barrier equipment and accessories


The following barrier arm profiles are possible:
Round profile
Octagonal
profile
(with rubberised
lower edge)

AS20
AS2000
AS30
AS35
Articulated arm

Square
profile
(with rubberised
lower edge)

possible
not possible

Articulated barrier arm

Barrier arm
profile

max. 3450

100

~ 2205

18

~ 2040

Barrier arm (square profile)

903

Rubberised lower edge

Upper edge curb


Lane

130 - 170

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Barrier arm as articulated barrier arm (possible with AS20; AS2000; AS30)
Dimensions in mm

Schrankenbaum

Always keep the minimum distance between the articulated barrier arm
and the ceiling (country-specific) when the barrier is open.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 37 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Formed part for barrier arm profiles (dimensions in mm)


For reasons of safety, a formed rubber (polyurethane) part can be attached
on the freely swinging end of the barrier arm as well as a piece of rubber
profile. Possible injury can thus not be completely excluded, the degree of
injury, however, can be decreased.

47

45

17

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

100

130

M3

46

20

(Polyurethane)
Fa. Wimmer (BM 316874)
86 95305 (-) Formstck Schranke

End pieces of formed part glued in hollow part of the profile bar

Formed part (86 95305)

Rubber profile

Arm profile with warning marks


(Colour and distance
project-specific)

Rubber
profile
86 86984 (-) Fertigungshinweis

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 38 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Length of barrier arms up to 5.40 m (only possible with AS2000)


Barrier length: 6.00 m
Dimensions in mm

500
442

380

354

300

Conduit or ducting for


signal- and mains cable.

334

900

420

130 - 170

600

130 - 170

1100

max. 4,66 m

208

274

195

290

420

600

550

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

100

4 fixing holes
in housing.
Fixing with 4 tie
bolts FAZ 10/50.
Drilling template
S&B 04 17490.

130
550
600

600

Necessary clearance zone


for counterweight.

Curb

14

Lane

Concrete foundation B25.


Curb height between 130 and 170 mm.
Must be suitable for winter condition!

86 61022 (-) AS2000 5m_e

From an arm length of 3.40 m (corresponds to a barrier length of 4.00 m),


counterweights are used.
The following arm lengths are available for the AS2000 with counterweights:
Length barrier arm
(in m)

Corresponding
barrier length (in m)

3.40

4.00

3.90

4.50

4.40

5.00

5.40

6.00

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 39 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.4 Prefabricated steel island for devices


3.4.1 Islands made of flat steel
Variant 1: Double-sided island entry/exit, centred mast connection
Size (dimensions in mm):
Exit
Tube 600 mm
15 00108
or similar

(2770)
(617)

(2770)

800

30
165

240

255

300

300

320

340

460

240

460

340

320

300

300

255

240

165

(5000)

Ground fixing 86 61229


(even with lower edge)

Flat steel 150 x 8

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Tube 600 mm
15 00108
or similar

View X

Entry

Mast for camera / traffic sign


Protective bollard

Ticket dispenser at entry


Entry barrier

Ticket reader at exit


Exit barrier

86 61584_1 (e) Flachstahlinsel_e

Note: All mounting screws are screwed in when the island is manufactured, and the
screw thread is covered with an insulating plastic tube (M12 x 50 or M16 x 50).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 40 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Variant 2: Island for a double-sided lane for entry and exit


Tube 600 mm
15 00108
or similar

Exit

(2770)
(617)

(617)

(2770)

30

800

240
650

30

350

320

300

460

240

300

1860

460

350

240
300

300

320

650

(5000)

Tube 600 mm
15 00108
or similar

View X

Ground fixing 86 61229


(even with lower edge)

Flat steel 150 x 8

Entry

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Mast for camera / traffic sign


Protective bollard

Ticket dispenser at entry


Entry barrier

Ticket reader at exit


Exit barrier

86 61584_2 (e) Flachstahlinsel_e

Note: All mounting screws are screwed in when the island is manufactured, and the
screw thread is covered with an insulating plastic tube (M12 x 50 or M16 x 50).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 41 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Variant 3: Island for Entry and/or Exit

(2770)

800

(617)

240
650

30

320

741

459

240

459

560

300

(4580)

Tube 600 mm
15 00108
or similar

Traffic direction for


entry resp exit

Mast for camera / traffic sign


Protection bollard

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Ground fixing 86 61229


(even with lower edge)

Flat steel 150 x 8


View X

Ticket dispenser at entry resp


Ticket reader at exit

Entry barrier resp


Exit barrier

86 61584_3 (e) Flachstahlinsel_e

Note: All mounting screws are screwed in when the island is manufactured, and the
screw thread is covered with an insulating plastic tube (M12 x 50 or M16 x 50).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 42 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Variant 4: Double-sided island for Entry / Exit with truck extension


(2770)
(617)

(617)

(2770)

30

Tube 600 mm
15 00108
or similar

800

30

240
650

320

320

165

240

350

80

Tube 600 mm
15 00108
or similar

300

1860

Flat steel 150 x 8

80

300

(5848)

239

View X

350

240

320
239

320

650

165

Ground fixing 86 61229 (even with lower egde)

Traffic direction for entry resp exit

150

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Mast for camera / traffic sign


Protective bollard
Ticket dispenser at entry
*Ticket dispenser at entry
with truck extension
Entry barrier
Ticket reader at exit
*Ticket reader at exit
with truck extension
Exit barrier

86 61584_4 (e) Flachstahlinsel_e

Note: All mounting screws are screwed in when the island is manufactured, and the
screw thread is covered with an insulating plastic tube (M12 x 50 or M16 x 50).

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 43 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.4.2 Islands made of steel tube


Size (dimensions in mm):
Exit

5228

768

Entry

Ticket dispenser at entry


Entry barrier

Ticket reader at exit


Exit barrier

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

86 60428 (a) Rundrohr-Insel_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 44 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.5 Nudge bar


3.5.1 For control devices PGL20 / PL20
Variant 1 Size (dimensions in mm):
400

10

500

374

14

60

100

100

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

220

86 60818 (-) Rammschutzbgel

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 45 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Nudge bar for control devices PGL20 / PL20


Variant 2 Size (dimensions in mm):
100

100

14

400

485

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

60

600

339

419

10

86 60819 (-) Rammschutzbgel_2 PGL_PL

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 46 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.5.2 For barriers AS20, AS2000


Size (dimensions in mm):
100

100

14

400

440

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

60

500

280

340

10

86 60820 (-) Rammschutzbgel_AS

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 47 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.6 Loops / Cable ducts

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

3.6.1 Laying of loops


Procedure
The most common way of laying loops is by milling slots in the asphalt or concrete,
into which a 1.5 mm2 plastic-coated copper conductor is laid in several turns. The slot
is approx. 5 mm wide and approx. 30 mm deep. The connecting groove between the
loop and the detector connection is milled a bit wider so that the twisted line will fit in.
The loop is grouted in with cold grouting compound.
It is not recommended to lay the loops before the concrete or asphalt is finished.
However, if this should be necessary, prefabricated loops with a protective coating
should be used, which are laid into the prefabricated geometrical form in order to
be covered with concrete or asphalt then.
If concrete slabs are used as road topping, expansion joints are often required. If
the loop wire crosses an expansion joint, an extra turn must be made in order to
avoid that the loop is cut when the concrete slabs are moving. Never lay loops and
loop supply lines directly into the expansion joints.
When loops are laid under the pavement, never lay the loop wire directly into the
sand. In such a case always use prefabricated loops, which must be laid onto a
firm subsoil so that it cannot break. When loops are laid under the pavement it
must also be noted that rainwater may seep into the layer of sand so that the
inductivity of the loop may change. The damp soil and/or sand layer then works
in particular in connection with thawing salt like (relatively badly conducting)
metal, i.e. the loop is like vaporized. In addition, the prefabricated loops may not be
laid to deep into the sand layer, since otherwise the distance between the upper
edge of the pavement and the loop will be too large causing a worse sensitivity.
The loop supply line should be laid as far away as possible from mains supply lines
(min. 20 cm). In no case, loop supply lines and mains supply lines may be laid in the
same duct or conduit.
Loop supply lines should also be laid as firm as possible so that they cannot move.
This also applies when laid within the switch cabinet. Even in this case, the line must
be twisted. If a connection between the loop and the loop supply line must be made in
the proximity of the loop or even in the ground or next to the ground, it must be
ensured that the connection is waterproof and protected against damage.
Basic rules when laying loops
The loop size must be adjusted to the expected vehicle size.
Loops may not be laid in manoeuvre areas.
Loops may not be laid in the swivelling range of metal gates.
Loops must be laid at least 5 cm higher than steel reinforcement or metal vapour
barriers (metal foils) or the reinforcement must be made outside the loop area.
With rectangular loops the corners are slanted in order to avoid a too high
mechanical load on the loop wire at the corners, which could lead to parting of the
cable or defects in insulation.
Manhole covers, sewage piping, hydrants, etc., which are located in the sphere of
influence of the loop, must have a minimum distance of approx. 0.5 m to the loop.
The loop and the supply line must be laid very carefully.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 48 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Recommended number of turns with rectangular loops


Loop circumference
<3m
34m
46m
6 12 m
> 12 m

Number of turns
6
5
4
3
2

100 (0.33') x 45

Size (dimensions in mm)

1800 (5.91')
300 (0.98')

1800 (5.91')
300 (0.98')

300 (0.98')

320 (1.05')

240 (0.79')

Twisted loop ends


20 turns for 50 cm (1.64').

Twisted loop ends


20 turns for 50 cm (1.64').

Empty tube EN20

5 (0.02')

Cut A - A

Empty tube EN20

Sealed with special synthetic


25 - 30
(0.08' - 0.10')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

600
(1.97')

600
(1.97')

300 (0.98')

min. 2500 (8.20')

100 (0.33') x 45

min. 2500 (8.20')

Number of loop turns: 4


86 68017 (f) Schleifenverlegung_e

Barrier
Device for Entry, Exit and / or Passage

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 49 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Laying of loops

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Substructure
Pavement
Sand
Lean concrete
Loop
Supply line

Laying under pavement

Reinforcement

Cut-in loops
86 67748 (a) Schleifen_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 50 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.6.2 Laying of cable ducts

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Cut A-A
Mounting screw
Front side of device

Empty tube EN20


Outer edge of curb

Bottom of device
86 71667 (a) Kabelschutzrohr Induktionsschleifen_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 51 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.7 Situations at the Entry, the Exit and the Passage


3.7.1 Plan for an Entry Lane

0,60

0,60

0,60

1,50

1,80

min. 2,50

1,50

3,00 - 3,60

0,30

Mast* for camera / traffic light


Entry barrier
Protection bollard
Closing loop
Ticket dispenser at entry
Backout loop (optional)
Presence loop
* Possibility for additional using as a feeding
conduit for power supply.
86 85046 (d) Lageplan EF_e

3.7.2 Plan for an Exit Lane

0,60

0,60

1,80

0,30

min. 0,60

Dimensions in m

Min. 2,50

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

0,30

min. 0,60

Dimensions in m

3,00 - 3,60

0,30

Mast* for camera


Closing loop
Protection bollard
Ticket reader at exit
Presence loop
Exit barrier
* Possibility for additional using as a feeding
conduit for power supply.
86 85046 (d) Lageplan AF_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 52 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.7.3 Plan for a bi-directional lane


Dimensions in m
1,00

Exit

0,60

Entry

2,40

1,80

0,30

3,00

3,50

Mast* for camera / traffic light


Protective bollard
Ticket dispenser at entry

Closing loop
Ticket reader at exit

Presence loop
Entry barrier /
Exit barrier

* Possibility for additional using as a feeding


conduit for power supply.

The final location of the devices must be determined on site, in coordination with the
supervision of works, possibly by means of driving tests. In the range of the induction
loops "I", the reinforcement must be covered by a layer of 6 cm min.

3.7.4 Plan for a double-sided lane


Dimensions in m
1,00
(3.28')

0,90
(2.95')

3,00 - 3,50 (9.84' - 11.48')

0,34 (1.12')

min 2,50 (8.20')

0,30 (0.98')

Exit


0,80
(2.62')

0,60 (1.97')
1,45 (4.76')

0,60
(1.97')

0,60
(1.97')

0,32 (1.05')

3,00 - 3,50 (9.84' - 11.48')

Mast* for camera/traffic light


Protective bollard
Ticket dispenser at entry

min 2,50 (8.20')

Entry

0,34 (1.12')

1,80 (5.91')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

01 082801 Wechselspur_e

Presence loop
Entry barrier
Closing loop

1,02
(3.35')

Ticket reader at exit


Exit barrier
Backout loop (optional)

* Possibility for additional using as a feeding


condiut for power supply.

86 85046 (d) Lageplan PH Standard_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 53 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

3.8 Manual Cashiering at the Exit


In this case, the parking fee to be paid is paid with an employee of the car park at the
exit with cash or with credit card. Without leaving the car, the customer inserts the
parking ticket into the ticket reader. The ticket insert is located at the outside of the
cashier booth. The cashier collects the parking fee. Only after payment was made, an
opening signal is transmitted to the barrier and the customer can pass the open
barrier.
Example of the basic arrangement of the devices (dimensions in mm)
6700 (21.98')
6500 (21.33')
4200 (13.78')
3900 (12.80')
2700 (8.86')

10

600 (1.97')

600 (1.97')

250 (0.82')

150 (0.49')

1000 (3.28')

12
11

1800 (5.91')

2750
(9.02')

450 (1.48')

450 (1.48')

1000 (3.28')
2200 (7.22')

min 4500 (14.76')

5800 (19.03')

min 100
(0.33')

900 (2.95')

Protective Bollard
Mast for camera / sign
Protective bollard
Presence loop

Closing loop
Exit barrier
10 Cashier booth

11
12

LPR loop (License plate recognition)


Approximate coverage of the camera

600
(1.97')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

1800 (5.91')

2000 (6.56')

2000 (6.56')

86 90464 (b) Ausfahrtskassierung_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 54 of 98

Planning Documents
Chapter 3: Entries, Exits and Passages

Example of a detail of the customer transaction panel at the cashier booth


Note: When planning the cashier booth, the provisions of the country-specific
workplace regulations concerning, among others,
-

dimensions

air conditioning

solar radiation

illumination

protective measures against the intrusion of exhaust fumes (e.g. overpressure)

and others

must be applied.

Display

Ticket
insert

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

86 91662 (-) Ausfahrtskassierung_Detail

Customer transaction panel exit cashiering


Booth (Dimensions are specific to the project)
Card reader (SL20)

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 55 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

4 Automatic Pay Stations


4.1 PKA2x with banknote processing and optional with non-cash payment
Automatic Pay Station for payment of parking fees. The fee is calculated in
accordance with the stored tariff data and displayed after the parking ticket/card or
the ChipCoins has been inserted. Payment can be effected with various means of
payment.
Designation:
PKA20/S, PKA25/S, PKA26/S: Side stripe system
PKA20/B, PKA25/B, PKA26/B: Barcode system
PKA20/C, PKA25/C, PKA26/C: ChipCoin system

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Technical Data

230 V/50 Hz or 115 V/60 Hz


270 VA
Banknote processing: 7 VA (quiescent
current) 60 VA (operating current)
Additional 700 VA for heating /
ventilation.
Illuminated top: 18 VA

For indoor or protected outdoor


installation.
Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

Ticket specification for Side stripe


tickets: S&B 04 26743
Ticket specification for Barcode
tickets: S&B 04 26670

Power supply
Network
Intercom

UL, CUL, CE

kg

220 kg net weight w/o banknote


processing and pedestal
Mounting on a steel or concrete
pedestal or on a pedestal referring the
specification.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 56 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

PKA2x
Size (dimensions in mm):

Optional:
Illuminated top

550

100

View of front panel may not


be equivalent to the original!

PAY PARKING HERE

Coins
Help

950

940
735

600

Change

450

270

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Banknotes

1950

1400

Parking ticket

450

900

86 60789 (a) PKA Masszeichnung_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 57 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

PKA2x
Foundation plan for concrete pedestal [Dimensions in cm (ft)]

Cut A -A
110 (3,61')
90 (2,95')

5 (0,16')

Concrete foundation B25


must be suitable for winter
condition!
5 (0,16')

Front edge concrete pedestal

10 (0,33')

5 (0,16')
7 (0,23')
8 (0,26')

Cut B - B
Housing

Concrete
pedestal
Concrete
foundation

Plain for compensation

A
45 (1,48')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Tube jointing
sleeve
2,5 (0,08')

65 (2,13')

5 (0,16')

7 (0,23')

45 (1,48')

7 (0,23')

10 (0,33')

10 (0,33')
3 (0,10')
5 (0,16')
7 (0,23')

10 (0,33')

Cylinder thread stands M12


or srew for stones
Plug M12
86 65447 (d) Fundamentplan PKA_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 58 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

PKA2x
Steel pedestal
Size and fixing [dimensions in mm (ft)]

450 (1,48')

900 (2,95')

450 (1,48')

Cable feeding

14 (0,05')

50 (0,16')
100 (0,33')

450 (1,48')

800 (2,62')

30 (0,10')

900 (2,95')

340 (1,12')

134 (0,44')
185
(0,61')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Pedestal fixing dimensions

50 (0,16')

130 (0,43')

86 60789 (a) Befestigung Stahlsockel_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 59 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

PKA2x
Prefabricated foundation frame (galvanized) (dimensions in mm)

25

177,5

395

30

A-B

50

50

Front
200

160

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

900

Cut A - B
45

Weld nut
M12 - Nirosta

86 86995 (-) Fundamentrahmen PKA2x_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 60 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

4.1.1 Mounting niche for PKA2x


Dimensions in mm

100 (0.33')

100 (0.33')

100 (0.33')

Einbaunische PKA20_e

4.1.2 Illuminated top for PKA2x


As an option, the Series PKA2x automatic pay station can be provided with an
illuminated top. In this case, attention must be paid to the resulting new total height of
the automatic pay station.

100 (0.33')

Illuminated top
round

450 (1.48')

900 (2.95')

550 (1.80')

450 (1.48')

500 (1.64')

100 (0.33')

Size (dimensions in mm):

550 (1.80')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

100 (0.33')

PAY PARKING HERE

900 (2.95')

Illuminated top
cornered

R 2000 (6.56')

Beleuchtungsaufsatz_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 61 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

4.1.3 Roofing for Automatic Pay Station PKA2x


Various roofings are available for the outdoor installation of automatic pay stations.
These roofings are not only a weather protection for the automatic pay stations but
also for the customers who have to pay the parking fees at the automatic pay station.
Variant 1:
Roofing for an automatic pay station: Dimensions in mm (ft)

2000 (6.56')

Glass

Galvanized
sheet steel

1000 (3.28')

20 (0.07')

Detail flange plates

120 (0.39')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Glass

60
(0.20')

60 (0.20')

1410 (4.63')

1500 (4.92')

2240 (7.35')

2240 (7.35')

1500 (4.92')

2000 (6.56')

1500 (4.92')

1000 (3.28')

Execution of side parts


must be stated in the order.

12 (0.04')
20 (0.07')

86 60218_1 (a) berdachung_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 62 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

Roofing for PKA2x


Foundation plan [dimensions in mm (ft)]
1500 (4.92')
1410 (4.63')

1000 (3.28')

Glass

250 (0.82')

Control side

1910 (6.27')

Foundation:
Armoured concrete plate stripes
min 160 mm (0.52') thick, concrete B25
welded wire mesh Q188 bottom
and top, all-around the plate edge
2 12 (0.04') and stirrup 188 (0.62').

150
(0.49')

Cable entry
2 x empty tube EN32

1410 (4.63')

160 (0.52')

Frost resisting
foundation

1300 (4.27')

Autom.
pay station
520 (1.71')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

685 (2.25')

1000 (3.28')

150
(0.49')

Per support
4 shear connectors
M10 x 130 (0.43')

250 (0.82')

Armouring and foundation work are not part of our scope of performances.
This work must be provided by the customer.
86 60218_2 (a) berdachung_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 63 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

200 (0.66')

Roofing for PKA2x


Variant 2:
Roofing for two automatic pay stations: Dimensions [in mm (ft)]

1800 (5.91')

12
(0.04')

120
(0.39')

2610 (8.56')

20 (0.07')

120 (0.39')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

2400 (7.87')

2730 (8.96')

1350 (4.43')

Water drain

20 (0.07')

86 61757 (-) Kassenhausunterstand_e

The foundation (structural concrete foundation B25) must be made in accordance


with the manufacturer's instructions. Frost resisting execution must be ensured.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 64 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

Roofing for PKA2x


Variant 3:
Roofing for an automatic pay station: Dimensions [in mm (ft)]

50 (0.16')

93

77

85 (0.28')

1950 (6.40')

1000 (3.28')

460 (1.51')
100
225 (0.74')

450 (1.48')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

2220 (7.28')

PAY PARKING HERE

450 (1.48')

Camera (optional)
(Position angle depends on
the incidence of light)

PKA Dach_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 65 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

4.2 Automatic Pay Station for only non-cash payment


4.2.1 PAY20/S
Automatic Pay Station for non-cash payment of parking fees based on Side stripe
tickets with credit cards

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Technical Data

230 V / 50 Hz or 115 V / 60 Hz
approx. 790 VA
100 VA additional for heating /
ventilation

Thermal receipt paper, Article No:


S&B 50 82010
Reel diameter: 90 mm; Reel width: 58
mm

Power supply
Network
Intercom

UL; CUL; CE

Wall mounting: with a recommended


ticket insert height of 1400 mm
Mounting on steel pedestal

kg

Approx. 80 kg net weight

For indoor or protected outdoor


installation
Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 66 of 98

Planning Documents
Chapter 4: Automatic Pay Stations

PAY20/S
Size [dimensions in mm (ft)]:
60 (0.20')

Area for device opening


306 (1.0')

534 (1.75')

Illuminated top

612 (2.01')

795 (2.61')

min. 100
(0.33')

PAY20_e

35,5

318

23

830 (460*)

Size pedestal (dimensions in mm):

389

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

470 (1.54')

235
306

04 26140 (a) PAY20-Sockel

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 67 of 98

Planning Documents
Chapter 5: Ticket / Card Reader for Door Control

5 Ticket / Card Reader for Door Control


5.1 PTL20
On-line door reader for checking the validity of short-term parking tickets and longterm parking tickets or ChipCoins and transponder cards. A valid ticket /card /
ChipCoin generates an open signal for a normal door or a sliding door.
PTL20/B: Door reader for the Barcode system
PTL20/S: Door reader for the Side stripe system
PTL20/C: Door reader for the ChipCoin system

Technical Data

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

230 V/50 Hz or 115 V/60 Hz


approx. 250 VA
30VA additional for heating / ventilation

Power supply
Network
Intercom

For indoor or outdoor installation


Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

UL, CUL, CE

kg

For wall and stand mounting

18 kg net weight

The housing of the PTL20 is corresponding with the Multi Control Unit (MKG).
For sizes and illustrations see page 17.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 68 of 98

Planning Documents
Chapter 5: Ticket / Card Reader for Door Control

5.2 PTL35
Access control device for normal door and sliding door controls.
The following media can be processed:
Side stripe tickets and cards
Barcode tickets and cards
ChipCoins and transponder cards (S&B)
Proximity cards (third party)
Mixtures of the media mentioned above

Survey
The door readers are named by means of the following abbreviations so that the
specific features can be seen from the name.

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

PTL35-

D
L
T
P
Code
Key

= with display
= On-line
= with S&B transponder reader
= with Proximity card reader (various products)
= with code keyboard
= with key-operated switch
/
B
= with barcode reader
C
= with reader for ChipCoin and S&B transponder
cards
S
= with slot reader

Technical Data

24 V DC (to be provided by the


customer, power upon can be
delivered upon request)
max. 5 VA
30VA additional for heating / ventilation

For indoor and outdoor installation


Temperature range: -20 C+50 C
Humidity: 095 % (not condensing)

UL, CUL, CE
Power supply
Network (only PTL35-L/B and
PTL35-LD/B)
Intercom
Potential-free contact (optionally as
break or make contact)

kg

Wall mounting: with a recommend


height of the ticket dispensing tray or
the ChipCoin antenna of 1200 mm
Stand mounting: on optional pedestal
made of rectangular tube

5 kg net weight

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 69 of 98

Planning Documents
Chapter 5: Ticket / Card Reader for Door Control

PTL35
Size / Foundation plan (dimensions in mm):
122
220

75

340

40

980

929

220

70
220

480
220

Concrete foundation B25.


Must be suitable for winter condition!

160

Conduit or ducting
for signal and mains cable.
12

30

220

130

160

480

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

835

1175

40

130

4 fixing holes in housing.


Fixing with 4 tie bolts FAZ-A4 10/30 and cap nut.
Drilling template S&B 04 17490.
86 60802 (a) PTL35_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 70 of 98

Planning Documents
Chapter 5: Ticket / Card Reader for Door Control

PTL35
Wall mounting (dimensions in mm)

38

Back view

340

270

Mounting holes

Cable feeding
40
25

32

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

52,5
145

PTL35 Wandbefestigung_e

Mounting holes:
4 x 8 drilling (min. drilled hole depth 55 mm)

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 71 of 98

Planning Documents
Chapter 5: Ticket / Card Reader for Door Control

5.3 PTL36
Access control device for Side stripe tickets and / or ChipCoins and Transponder
cards for normal door and sliding door controls.
PTL36/S: for the Side stripe system
PTL36/C: for the ChipCoin system

Technical Data

8-12 V AC or DC (to be provided by


the customer, transformer can be
delivered upon request)
approx. 2 VA

Only indoor installation!

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

UL, CUL, CE
Power supply
Network (only PTL36-L/S and
PTL36-L/C)
Potential-free contact (as make
contact)

Wall mounting: at a recommended


height of 1200 mm

kg

0.7 kg net weight

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 72 of 98

Planning Documents
Chapter 5: Ticket / Card Reader for Door Control

PTL36
Size (dimensions in mm):
123

19

37

190

EN screw fitting

Wall mounting (dimensions in mm)


60
49

80

14

55

134

5,5

7,6

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

86 60935 (-) PTL36 Ansicht

Mounting holes
86 60935 (-) Wandmontage_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 73 of 98

Planning Documents
Chapter 6: Complements

6 Complements
6.1 Steel Mast for Signals (for example mast for Multi Control Unit)

108 x 3,6

350

280

102

62

Size (dimensions in mm):

2900

280

Concrete foundation B25


must be suitable for
winter condition!

350

Cut A - A

20

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

10

86 60069 (-) Mast_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 74 of 98

Planning Documents
Chapter 6: Complements

Signal mast
Prefabricated foundation frame for signal mast (galvanized) (dimensions in mm)

45

A-B

280

Angle 50x50x5
DIN 1028
St 37-2

35

350

35

Cut A - B

M16 x 55
35

35

85
225
2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)
Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

350

86 60015 (-) Fundamentrahmen fr Signalmast_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 75 of 98

Planning Documents
Chapter 6: Complements

Signal mast
Frame foundation cage (dimensions in mm)

257

M20

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

800

Threaded rod
M20x1060

86 61282 (-) Rahmen Fundamentkorb_e

320

280

25

40

280
320

86 86944 (-) Blech Fundamentkorb

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 76 of 98

Planning Documents
Chapter 6: Complements

Steel mast for Signs


Size [dimensions in mm (ft)]

400 (1.31')

Cut A - B
Scale 1 : 5

280 (0.92')

28 (0.09')

Pole placed in sole


plate and welded

350 (1.15')

85 (0.28')

20 (0.07')

1580 (5.18')

85 (0.28')

55 (0.18')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Mounting part

4480 (14.70')

D=133 (0.44')

Pole covering cap

280 (0.92')
350 (1.15')

86 62940 (c) Transparentmast_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 77 of 98

Planning Documents
Chapter 6: Complements

Steel mast for Signs


Foundation plan [dimensions in mm (ft)]
Ground level
300
(0.98')

Conduit EN63

1050 (3.44')

1400 (4.59')

200
(0.66')

1000 (3.28')

Anchor bolt M20 x 1050 (3.44')


S&B 04 00470

360
(1.18')

280 (0.92')

280 (0.92')

Detail X

350 (1.15')

Ground plate
sign mast

350 (1.15')

Concrete
foundation

Detail Y

500 (1.64')

1000 (3.28')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Anchor plate
500 (1.64')
1000 (3.28')

360
(1.18')

Concrete foundation B25


must be frost resisting
condition!
Reinforcing steel BSt 500/550
86 65017 (e) Stahlmast-Fundament_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 78 of 98

Planning Documents
Chapter 6: Complements

6.2 Holder for alternation sign for wall mounting


Dimensions (in mm):

64
Attaching
to the wall

80

200

116

100

50

64

116

50

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

42

Fixing
of the sign

18
100

86 79185 (a) Wechseltransparent_Wandmontage_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 79 of 98

Planning Documents
Chapter 6: Complements

6.3 Signal Indication


Signal indication with 1 light Dimensions [in mm (ft)]:

504 (1.65')

476 (1.56')

280 (0.92')

348 (1.14')

270 (0.89')

309 (1.01')

190 (0.62')

403 (1.32')

Signal_1

Signal indication with 2 lights Dimensions [in mm (ft)]:

190 (250)
0.62' (0.82')

757 (892)
2.48' (2.93')

280 (350)
0.92' (1.15')

785 (925)
2.58' (3.03')

280 (350)
0.92' (1.15')
403 (540)
1.32' (1.77')

626 (771)
2.05' (2.53')

270 (350)
0.89' (1.15')

420 (567)
1.38' (1.86')

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

420 (1.38')

111 (0.36')

111
0.36'

309 (456)
1.01' (1.50')

Signal transmitter either available in


200 mm (0.66') or 300 mm (0.98') execution.

Signal_2_e

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 80 of 98

Planning Documents
Chapter 6: Complements

Signal indication with 3 lights Dimensions (in mm):

1042

280

280

906

1065

280

270

420

190

309

403

Signal_3

208

Laid-in templates for signal indication (directional arrows according to StVO traffic
regulations)

208

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

111

Einlegeschablonen

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 81 of 98

Planning Documents
Chapter 6: Complements

6.4 Displays for S&B Guidance Systems


Parking guidance system displays / interior mounting
LED Matrix displays
Application:
Device type:
Symbol height:
Reading distance:
Symbol colour:
Device mounting:

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Operating temperature:
Air humidity:
Supply voltage:
Power consumption:
Approval:

Interior, without direct solar radiation


Complete device, maintenance-free, ready for connection,
one-side display
Max. 120 mm
up to 40 m
red, yellow, green
Prepared for wall mounting, ceiling mounting and mast
mounting, individually adjustable angle of inclination. Wall
and ceiling fixtures included in the delivery!
-20 +50 C
10 90 % (not condensing)
20 40 V DC
max. 5 W (with full illumination level, colour yellow)
- CE mark
- Electrical safety acc. to EN 60950
- Radio interference acc. to EN 50081-1 (residential area)
- Jamming resistance acc. to EN 50082-2 (industrial area)

Variants
Resolution
in Pixel
(H x B)

For the
display of:

LED
display
surface
in mm
(H x D)

Housing
dimensions
in mm
(H x W x D)

16 x 16

1 special
symbol

120 x 120

200x200x45

16 x 32

3-digit
remaining
lots

120 x 240

200x322x45

16 x 48

Combination

120 x 360

200x444x45

16 x 64

Combination

120 x 480

200x566x45

IM1
IM2

IM3
IM4

Examples of special symbols (16 x 16 Pixel)

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 82 of 98

Planning Documents
Chapter 6: Complements

Parking guidance system displays / exterior mounting (selection)


Small information sign

1000

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Mast fixing
optional left or right

600

P1
Staff
Car Park only

Front side

R 70

D=133

Kleines Hinweistransparent_e

Caution: Customer-specific realization of the inscription (texts, symbols, etc.) and of


the colour!
- Mounting: - Mast mounting (optionally right or left) or
- Rear-side mounting or
- Mounting suspended from the ceiling

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 83 of 98

Planning Documents
Chapter 6: Complements

Small information sign with alternating information

1000

Front side

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

160

Mast fixing
optional left or right

160

600

Market Place

520

R 70

D=133

86 86372 (b) Kl. Wechseltransparent_e

Caution: Customer-specific realization of the inscription (texts, symbols, etc.) and of


the colour!
Execution with 2 positions: FULL / OPEN:
- Alternating texts:

FULL red background, white letters


OPEN green background, white letters

- Electrical connections 230 V for 2 positions:


Protective conductor PE, neutral conductor N; L1 illumination; L2 Open; L3 Full
- Mounting: - Mast mounting (optionally right or left) or
- Rear-side mounting or
- Mounting suspended from the ceiling

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 84 of 98

Planning Documents
Chapter 6: Complements

Information sign P-sign


1000

1500
160
160

400

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Mast fixing
optional left or right

400

Front side

R 70
133

Hinweistransparent_e

Caution: Colour not corresponding with the original!


Customer-specific realization of the inscription (texts, symbols, etc.)!

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 85 of 98

Planning Documents
Chapter 6: Complements

Information sign P-sign with alternating text


1000

1500
160
160

400

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Mast fixing
optional left or right

400

Front side

520

R 70

133

Transparent_e

Caution: Colour not corresponding with the original!


Customer-specific realization of the inscription (texts, symbols, etc.)!
Notes:
Standard execution:
2 positions FULL / OPEN
- Alternating texts:

FULL red background, white letters


OPEN green background, white letters

- Electrical connections 230 V for 2 positions:


Protective conductor PE, neutral conductor N; L1 illumination; L2 Open; L3 Full
- Colours: - Background: blue
- Light edges, arrow, P-symbol and (if applicable) writing: white
- Window: clear

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 86 of 98

Planning Documents
Chapter 6: Complements

Optional execution:
3 positions FULL / OPEN / CLOSED
- Alternating text:

FULL red background, white letters


OPEN green background, white letters
CLOSED red background, white letters

- Electrical connections 230 V for 3 positions:


Protective conductor PE, neutral conductor N; L1 illumination; L2 Open; L3 Full;
L4 Closed

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

- Colours: - Background: blue


- Light edges, arrow, P-symbol and (if applicable) writing: white
- Window: clear

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 87 of 98

Planning Documents
Chapter 6: Complements

P-sign with LED display


1000

160

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

400

105

1500

Mast fixing
optional left or right

400

Front side

720

R 70

133

LED-Transparent_e

Caution: Colour not corresponding with the original!


Customer-specific realization of the inscription (texts, symbols, etc.)!
- Electrical connections 230 V:
Protective conductor PE, neutral conductor N; L1 illumination; L2 LED display
- Colours: - Background: blue
- Light edges, arrow, P-symbol and (if applicable) writing: white
- Window: clear
- Text colours:

Figures: yellow
Open: yellow
Full: red
Closed: red

Description of the LED display


Application:
Exterior installation, well readable even with direct sun
exposure
Device type:
Complete device, ready for connection, one-side display
Symbol height:
Max. 100 mm
Number of characters:
8 characters, 12 x 8 Pixel each
Scheidt & Bachmann GmbH
Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 88 of 98

Planning Documents
Chapter 6: Complements

Reading distance:
Symbol colour:
Types of presentation:
Lettering:
Device mounting:
Operating temperature:
Air humidity:
Supply voltage:
Power consumption:

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Approval:

up to 40 m
red, yellow
Still, running, blinking texts, alternating texts
according to customer's instructions with P, arrow, name
of the car park and coloured operator's logo; background
lighting
Prepared for wall mounting and mast mounting
-20 +50 C
Hoseproof and dustproof (IP65)
100 240 V / 50 60 Hz
approx. 100 W
Approx. 200 W with background lighting switched on
- CE mark
- Electrical safety acc. to EN 60950
- Radio interference acc. to EN 50081-1 (residential area)
- Jamming resistance. to EN 50082-2 (industrial area)

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 89 of 98

Planning Documents
Chapter 6: Complements

Display of remaining lots with LED / LCD display


The displays are project-specifically designed in coordination with the customer.
Therefore, the dimensions vary depending on the functionalities.
The following examples show a selection of already realized displays of remaining
lots.

(LED display)

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

(LED display)

(LCD display

(LED display)

Description of the LED display


Application:
Exterior installation, well readable even with direct sun
exposure
Device type:
Complete device, ready for connection as flush version,
one-side display
Symbol height:
Max. 100 mm
Number of characters:
4 characters, 12 x 8 Pixel each
Reading distance:
up to 40 m
Housing dimensions:
approx. 160 x 420 mm
Display surface (H x W): approx. 100 x 360 mm
Symbol colour:
yellow
Operating temperature: -20 +50 C
Air humidity:
10 90 % (not condensing)
Supply voltage:
100 240 V / 50 60 Hz
Power consumption:
approx. 50 W
Approval:
- CE mark
- Electrical safety acc. to EN 60950
- Radio interference acc. to EN 50081-1 (residential area)
- Jamming resistance. to EN 50082-2 (industrial area)

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 90 of 98

Planning Documents
Chapter 7: Mounting of the Device

7 Mounting of the Device


For mounting, stay bolts of Messrs. Fischer are recommended. These bolts have the
technical approval and therefore guarantee the required strength und application
safety.

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Nm

d
t
h
l
n

Diameter of the drill (mm)


Min. depth of the borehole (mm)
Min. anchoring depth (mm)
Overall length (mm)
Max. effective length (mm)
Thread
Wrench size across flats (mm)
Torque (Nm)
Material

FAZ 10/50
10
130
60
133
50
M 10
17
45
electrogalvanized

FAZ-A4 10/30
10
110
60
113
30
M 10
17
45
rustproof steel

The above stay bolts can also be ordered from S&B directly:
- FAZ 10/50:

S&B 50 82334

- FAZ-A4 10/30:

S&B 50 82335

- Cap nut:

S&B 70 03037

- Plain washer:

S&B 70 03177

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 91 of 98

Planning Documents
Chapter 8: Wiring Diagram

8 Wiring Diagram

(6)
(6)
(6)

S&B 04 24292 (3m)

(9)

(6*)

LON/Ethernet

Intercom

(2)
(4)

12 V

24 V

(6)

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

(1)

(6)

(0)

(8)
(0)
(0)

(0)
(0)
(6)

(3)

(4)
(8)
(6*)
(1)

(8)

(0)

(1)
(8)

(8)

(3)

(6*)

(8)
(0)

(1)
(0)

(0)

(0)

(6*)
(8)
(1)

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

(8)
(6*)
(1)

282501455.doc
Page 92 of 98

Planning Documents
Chapter 8: Wiring Diagram

8.1 Legend
Devices:
Central computer (POS20, POS25, ZR20)

Entry control (PGL20, PGL25, PGL30)

Passage and exit control (PL20, PL25, PL30)

Barrier (AS20, AS2000, AS30, AS35)

Automatic pay station for cash payment (PKA20, PKA25, PKA26)

Automatic pay station for non-cash payment (PAY20)

Entry / exit / passage control PCX35

Door reader PTL35

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

Door reader PTL36

Information sign

Intercom central office

Cables/tubes:
(0) Empty tube EN20
(1) Mains supply 3 x 2,5 230V~ 10 % 16A, protected by separate fuses
(2) Mains supply 4 x 2,5 230V~ 10 % 16A, protected by separate fuses for a
permanent phase and an illumination phase
(3) Power cable 3 x 2,5
(4) Power cable 5 x 2,5
(6) Control cable 2 x 2 x 0,8 (max. 1000m with PCX35, PTL35, PTL36 with RS485)
(6*) If Ethernet is used, CAT5 cable must be used instead of (6)
(max. 95 m).
(8) Control cable 6 x 2 x 0,8 (with RS485 max. 1000m)
(9) 5-fold multipoint connector, to be provided by the customer
Other notes:
- All power cables NYY or NYM.
- All control cables screened A2YF(L)2YST ||| BD (VDE 0816)
or JE-Y(ST)YBD SI (VDE 0815).
- All cables to be provided and laid by the customer.
- All cables must be laid with a reserve length of approx. 1.5 m.
- The cross sections stated for mains supply cables apply up to a maximum length of
150 m.
- Larger cross sections must be used in the case of longer supply cables.
Scheidt & Bachmann GmbH
Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 93 of 98

Planning Documents
Chapter 8: Wiring Diagram

8.2 Safety Instructions


The electrical installation must be made in accordance with the EVU provisions for
electrical connections and the VDE provisions DIN VDE 0100 Part 702, as well as in
accordance with the rules for the prevention of accidents concerning electrical
installations and equipment UBG 4 and GUV 2.10.
According to EN standard 60950 and IEC standard 60950 a leakage current >3.5 mA
per device is permissible in the case of stationary consumers with pluggable or firmly
connected mains connection.

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

This must be taken into consideration when planning the personal protection by
means of residual current operated devices in the mains supply.
Depending on the number of devices, several residual current operated devices must
be used.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 94 of 98

Planning Documents
Chapter 9: Information concerning Power Supply and Overvoltage Protection

9 Information about Power Supply and Overvoltage


Protection
9.1 General Information
The devices of the Car Park Management System Families are tolerant concerning
voltage fluctuations. Partially the devices are provided with a buffer battery in order
to complete the just started booking procedure in a defined way in the case of power
failure. In addition, even longer periods of power failure can be bridged by using
"Uninterruptible power supply (UPS). The buffer period depends on the UPS
capacity. In this case, the devices are shut down automatically in order to avoid
damage to the devices.

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

However, short overvoltages due to lightning stroke may cause damage to the
devices and downtime. The legally required and device-specifically standardized
jamming resistance tests have been carried out for all the devices mentioned.
On principle, devices at exposed locations are particularly endangered by lightning
stroke. This includes automatic pay stations as well as entries and exits in open
space. The operator is responsible for the overvoltage protection.
Overvoltage protection measures can also be carried out by Scheidt & Bachmann.
Quotations will be prepared upon special request. The expenditure strongly depends
on the facilities already existing on the site, e.g. power supply and network
components. Network connections by means of optical cables, for example, are less
endangered by lightning stroke that a network on the basis of copper cables.

9.2 Information about Screening


9.2.1 LON networks
If there is no LON distributor plate (only a few field devices), the screening is applied
only one-sided on the field device.
If there is a LON distributor plate, screening is made on both sides between the field
device and the LON distributor plate. Between the cell computer/POS and the LON
distributor plate the screening is only made one-sided on the cell computer.

9.2.2 RS485 networks


The screening is made on the connection box S2000 coming from the POS by means
of an earth clip connected to the ground. On the field devices, the screening is left
open, i.e. not connected. The two leads of the dialogue signals must be twisted into a
pair of leads. The Gnd connection must be connected with the GND of the field
device. Never use the screening for Gnd!

9.2.3 Ethernet networks


The LAN cable coming from the ground must be applied to a CAT5 coupling in the
device, which is connected with the earthing of the housing.
Scheidt & Bachmann GmbH
Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 95 of 98

Planning Documents
Chapter 9: Information concerning Power Supply and Overvoltage Protection

9.2.4 Power Supply PTL36

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

The PTL36 is provided with an integrated rectifier so that it can be operated with 8
-12V dc or ac voltage. It must be ensured that screened lines are used for voltage
supply. The screening must be applied one-sided on the power pack or on the
earthing bar connected to the power pack.

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 96 of 98

Planning Documents
Chapter: List of Illustrations

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

List of illustrations
86 86881 (c) PGL20S_B PL20S_B_e........................................................................................ 9
86 60095 (-) LKW-Bus Adapter fr PGL20_e...........................................................................10
86 86993 (-) Fundamentrahmen PGL20..................................................................................11
86 85257 (c) PGL_PL20C_e.................................................................................................... 13
86 61805 (-) PGL_PL30 Ansicht_e.......................................................................................... 15
86 61805 (-) PGL_PL30 Fundamentplan_e.............................................................................16
86 68468 (c) MKG_e................................................................................................................ 17
86 68470 (a) MKG-Fundamentplan_e.....................................................................................18
86 79552 (a) MKG Wandmontage_e.......................................................................................18
86 86501 (-) MKG-LKW_e....................................................................................................... 19
86 86501_2 (-) Fundamentplan MKG-LKW_e.........................................................................20
86 60810 (b) PCX35 Ansicht.................................................................................................... 23
86 60810 (b) PCX35 Fundamentplan_e..................................................................................24
PCX Steckleser (-)................................................................................................................... 25
MaxiProx.................................................................................................................................. 27
04 24597 (a) Regenschute PGL_PL_e....................................................................................28
Regenschute an PGL20_S_e.................................................................................................. 28
86 85055 (f) Schranke AS20_e................................................................................................ 31
86 86994 (-) Fundamentrahmen AS20_e.................................................................................32
86 61806 (a) AS30_e............................................................................................................... 34
86 61794 (-) AS35_e................................................................................................................ 36
Schrankenbaum....................................................................................................................... 37
86 95305 (-) Formstck Schranke............................................................................................ 38
86 86984 (-) Fertigungshinweis............................................................................................... 38
86 61022 (-) AS2000 5m_e...................................................................................................... 39
86 61584_1 (e) Flachstahlinsel_e............................................................................................ 40
86 61584_2 (e) Flachstahlinsel_e............................................................................................ 41
86 61584_3 (e) Flachstahlinsel_e............................................................................................ 42
86 61584_4 (e) Flachstahlinsel_e............................................................................................ 43
86 60428 (a) Rundrohr-Insel_e................................................................................................ 44
86 60818 (-) Rammschutzbgel............................................................................................... 45
86 60819 (-) Rammschutzbgel_2 PGL_PL............................................................................46
86 60820 (-) Rammschutzbgel_AS........................................................................................ 47
86 68017 (f) Schleifenverlegung_e.......................................................................................... 49
86 67748 (a) Schleifen_e......................................................................................................... 50
86 71667 (a) Kabelschutzrohr Induktionsschleifen_e..............................................................51
86 85046 (d) Lageplan EF_e................................................................................................... 52
86 85046 (d) Lageplan AF_e................................................................................................... 52
01 082801 Wechselspur_e...................................................................................................... 53
86 85046 (d) Lageplan PH Standard_e...................................................................................53
86 90464 (b) Ausfahrtskassierung_e.......................................................................................54
86 91662 (-) Ausfahrtskassierung_Detail.................................................................................55
86 60789 (a) PKA Masszeichnung_e.......................................................................................57
86 65447 (d) Fundamentplan PKA_e.......................................................................................58
86 60789 (a) Befestigung Stahlsockel_e.................................................................................59
86 86995 (-) Fundamentrahmen PKA2x_e..............................................................................60
Einbaunische PKA20_e........................................................................................................... 61
Beleuchtungsaufsatz_e............................................................................................................ 61
86 60218_1 (a) berdachung_e.............................................................................................. 62
86 60218_2 (a) berdachung_e.............................................................................................. 63
86 61757 (-) Kassenhausunterstand_e....................................................................................64
PKA Dach_e............................................................................................................................ 65
PAY20_e.................................................................................................................................. 67
04 26140 (a) PAY20-Sockel..................................................................................................... 67
Scheidt & Bachmann GmbH
Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 97 of 98

Planning Documents
Chapter: List of Illustrations

2005 by Scheidt & Bachmann GmbH, Mnchengladbach (Germany)


Technical modifications reserved. Some of the illustrations and descriptions may also include special options.

86 60802 (a) PTL35_e............................................................................................................. 70


PTL35 Wandbefestigung_e...................................................................................................... 71
86 60935 (-) PTL36 Ansicht..................................................................................................... 73
86 60935 (-) Wandmontage_e................................................................................................. 73
86 60069 (-) Mast_e................................................................................................................. 74
86 60015 (-) Fundamentrahmen fr Signalmast_e..................................................................75
86 61282 (-) Rahmen Fundamentkorb_e.................................................................................76
86 86944 (-) Blech Fundamentkorb......................................................................................... 76
86 62940 (c) Transparentmast_e............................................................................................. 77
86 65017 (e) Stahlmast-Fundament_e....................................................................................78
86 79185 (a) Wechseltransparent_Wandmontage_e...............................................................79
Signal_1................................................................................................................................... 80
Signal_2_e............................................................................................................................... 80
Signal_3................................................................................................................................... 81
Einlegeschablonen................................................................................................................... 81
Kleines Hinweistransparent_e................................................................................................. 83
86 86372 (b) Kl. Wechseltransparent_e...................................................................................84
Hinweistransparent_e.............................................................................................................. 85
Transparent_d.......................................................................................................................... 86
LED-Transparent_e................................................................................................................. 88

Scheidt & Bachmann GmbH


Systems for Car Parks and Leisure Centres
www.scheidt-bachmann.de

Planning Manual
Version 1.0
86 93587

282501455.doc
Page 98 of 98