AEA REG 2013019

Engine-Generator Sets (18 Gensets)

January 10, 2013

ALASKA ENERGY AUTHORITY


PROJECT #REG-12-053
813 West Northern Lights
Anchorage, AK 99503

Index
Tab 1 - Engine & Generators
John Deere Engines
Scania Engine
Newage Generators
Caterpillar CDVR
Tab 2 Engine-Mounted Accessories
Aeroquip FC-300 Hose
Cooper DC Circuit Breaker, #187-030-F-00
Crydom Starter Relay, 100A # D06D-100L w/Diode
Donaldson Air Cleaners
Donaldson Restriction Gauge #X002251
Eustis Exhaust Gas Temperature Sensor #RGA7B203B02WT
Flexfab Glycol Hose 5526-038
Noshok Sensors
Wix 24019 Coolant filter w/24069 Element
Tab 3 Controls and Instrumentation
Murphy Powerview PV-101A
Hoffman Enclosure, A16H12ALP, & Accessories
Tab 4 Ship-Loose Accessories
Silencers
Caldyne RJC Spring Isolators
Battery Charger, SENS
Tab 5 Drawings
M1.1
M1.2
M2.1
M2.2
M2.3
E1.1
E1.2
E1.3
E1.4

Tab 1
Engine & Generators

PowerTech PlusTM 4.5L Engine


Model: 4045HF485

ENGINE PERFORMANCE CURVE


Rating:
Gross Power
Application: Generator (60 Hz)
Target:
125 kWe Standby Market

179 hp (134 kW) Prime


197 hp (147 kW) Standby
[See Option Code Tables]

STANDARD CONDITIONS

Nominal Engine Power @ 1800 RPM


Prime

Generator
Efficiency
%
88-92

HP

kW

HP

kW

179

134

197

147

Fan Power
(6% of Standby)
hp

kW

8.7

6.5

Air Intake Restriction ...................12 in.H2O (3 kPa)


Exhaust Back Pressure ........... 30 in.H2O (7.5 kPa)

Standby

Prime Rating 2

Power
Factor
0.8

Standby Rating
1,2

kWe

kVA

kWe

kVA

112-117

140-146

124-129

155-161

ISO 8528 G2
Block Load
Capability
NA

Note 1: Based on nominal engine power. Derate - - -% for 100% block load capability.
Note 2: kWe / kVA rating assumes 90% efficiency. Generator Efficiency % will vary.

Gross power guaranteed within + or - 5% at SAE J1995


and ISO 3046 conditions:
77 F (25 C) air inlet temperature
29.31 in.Hg (99 kPa) barometer
104 F (40 C) fuel inlet temperature
0.853 fuel specific gravity @ 60 F (15.5 C)
Conversion factors:
Power: kW = hp x 0.746
Fuel: 1 gal = 7.1 lb, 1 L = 0.85 kg
Torque: Nm = lb-ft x 1.356
All values are from currently available data and are subject
to change without notice.

- PRIME

- STANDBY

Fuel -- lb/hr (kg/hr)

Notes:

All OEM Gen Set Engine Applications must be prescreened for torsional vibration compatibility with the
respective alternator end hardware.

70
(32)

OEM Engine Application Engineering will perform this


computer-based analysis work upon request.

50
(23)
30
(14)

Tier-3 Emission Certifications:

Certified by:

CARB; EPA

40
(30)

Engine Performance Curves

60
(45)

80
(60)

120
100
140
(90) (104)
(75)
Brake Power -- hp (kW)

160
(119)

180
(134)

4045 - Generator

Ref: Engine Emission Label


* Revised Data
Curve 4045HF4851800197 ............................. Sheet 1 of 2
October 2006

April 2008

Engine Installation Criteria


General Data
Model ............................................................... 4045HF485
Number of Cylinders ......................................................... 4
Bore and Stroke--in. (mm).............. 4.19 x 5.00 (106 x 127)
Displacement--in.3 (L) ...........................................275 (4.5)
Compression Ratio ................................................... 17.0:1
Valves per Cylinder--Intake/Exhaust ............................ 2 / 2
Firing Order............................................................. 1-3-4-2
Combustion System ....................................... Unit Injection
Engine Type ................................................ In-line, 4-Cycle
Aspiration ......................................................Turbocharged
Charge Air Cooling System................................... Air-to-Air
Engine Crankcase Vent System ................................ Open
Physical Data
Length--in. (mm) .................................................33.9 (860)
Width--in. (mm) ...................................................24.1 (612)
Height--in. (mm) ................................................40.9 (1039)
Weight, with oil--lb (kg).......................................1083 (491)
(Includes flywheel hsg., flywheel & electrics)
Center of Gravity Location (Estimated based on Tier 2)
From Rear Face of Block (X-axis)--in. (mm) ...9.8 (249)
Right of Crankshaft (Y-axis)--in. (mm) ..............2.2 (55)
Above Crankshaft (Z-axis)--in. (mm) ..............5.7 (145)
Max. Allow. Static Bending Moment at Rear
Face of Flywhl Hsg w/ 5-G Load--lb-ft (Nm) ..600 (814)
Rearward
Thrust Bearing Load Limit --lb (N) Forward
Intermittent............................899 (4000) .....450 (2000)
Continuous ...........................495 (2200) .....225 (1000)
Max. Front of Crank. Torsional Vibration--DDA............ 0.25
Max. Continuous Damper Temp--F (C) ...............180 (82)
12 Volt
24 Volt
Electrical System
Min. Battery Capacity (CCA)--amp............ 800 ............ 570
Max. Allow. Start. Circt Resist.--Ohm .. 0.0012 ......... 0.002
Starter Rolling Current:
At 32 F ( 0 C)--amp ............................ 920 ............ 600
At -22 F (-30 C)--amp....................... 1300 ............ 700
Min. Volts at ECU while Cranking--volts.........6 .............. 10
Max. ECU Temperature--F (C) ..................221 (105)
Max. Harness Temperature--F (C) ............248 (120)
Maximum Voltage From Engine Crankshaft/
Generator Shaft to Ground--VAC*......... 0.15*.........0.15*
Prime
Standby
Air System
Max. Allowable Temp Rise--Ambient Air to
Engine Inlet--F (C).....................................15 (8)
Maximum Air Intake Restriction
Dirty Air Cleaner--in.H2O (kPa)...............25 (6.25)
Clean Air Cleaner--in.H2O (kPa).............15 (3.75)
Engine Air Flow--ft3/min (m3/min) ......322 (9.1) ..374 (10.6)
Air Cleaner Efficiency--% .................................99.9

Engine Performance Curves

Charge Air Cooling System


Prime
Standby
Air/Air Exchanger Heat Rejection-BTU/min (kW) .................................1537 (27.0)* .. 1708 (30.0)
Compress. Dischrg. Temp.(Rated)
@ 77 F (25C) Amb. Air--F (C) 336 (169) ..... 394 (201)
Compress. Dischrg. Temp.(Max.)
@ 47C amb. and
80 kPa bar.--F (C) .....................455(235) .... 500(260)
Press. Drop, thru CAC--in.H2O (kPa)
Max. ........................................................52 (13)
Min. ......................................................... 20 (5)*
Intake Manifold Pressure--psi (kPa) .23(160.2) ... 30(206.3)
CAC Out Temp @ 77F (25C) Amb.--F (C)
Max. ...................................................... 126 (52)*
Min. ......................................................... 118 (48)
CAC Out Temp @ any Ambient--F (C)
Max. .........................................................190 (88)
Prime
Standby
Cooling System
Engine Heat Reject.--BTU/min (kW). 4041(71.0) .. 4480 (78.7)
Coolant Flow--gal/min (L/min)..............63(240) ...... 63(240)
Thermostat Start to Open--F (C) ...............180 (82)
Thermostat Fully Open--F (C)...................203 (95)
Engine Coolant Capacity--qt (L) ................ 9.5 (9.0)*
Min. Pressure Cap--psi (kPa) ...................14.5 (100)
Max. Top Tank Temp--F (C) .................... 230 (110)
Min. Coolant Fill Rate--gal/min (L/min) ............ 3 (11)
Min. Air-to-Boil Temperature--F (C) .......... 117 (47)
Min. Pump Inlet Pressure--psi (kPa).............4.4 (30)

Lubrication System
Prime
Standby
Oil Press. at Rated Speed--psi (kPa)............. 46 (320)
Min. Oil Pressure--psi (kPa)........................... 15 (105)
Max. Oil Carryover in Blow-by--lb/hr (g/hr) 0.002 (1.0)
Max. Airflow in Blow-by--gal/min (l/min)......... 26 (100)
Max. Crankcase Pressure--in. H2O (kPa).........2 (0.5)

Prime
Standby
Performance Data
Rated Power--hp (kW) ................... 179 (134)...... 197 (147)
Rated Speed--rpm ................................ 1800............. 1800
Low Idle Speed--rpm .............................1150..............1150
Rated Torque--lb-ft (Nm)............... 961 (709).... 1057 (780)
BMEP--psi (kPa) .......................... 287 (1980).... 316 (2178)
Friction Power
@ Rated Speed--hp (kW) .............. 17 (13).......... 17 (13)
Altitude Capability--ft (m) ............... 7500 (2286) .....5500 (1676)
Ratio--Air : Fuel................................. 22.1 : 1......... 22.6 : 1
Smoke @ Rated Speed--Bosch No. ...... 0.31.............. 0.31
Noise--dB(A) @ 1 m ............................. 89.7*............. 90.0*
Fuel Consumption -- lb/hr (kg/h)

Prime

Standby

25 % Power .................................19.6 (8.9) ........ 19.4 (8.8)


50 % Power ...............................32.0 (14.5) ...... 35.1 (15.9)
75 % Power ...............................48.7 (22.1) ...... 52.0 (23.6)
100 % Power .............................61.5 (27.9) ...... 69.4 (31.5)

Prime
Standby
Exhaust System
Exhaust Flow--ft3/min (m3/min)........833 (23.6) .. 938 (26.6)
Exhaust Temperature--F (C) ...........950(510) ..941 (505*)
Max. Exhaust Restriction----in. H2O (kPa)......30 (7.5)
Min. Exhaust Restriction----in. H2O (kPa)..... 12 (3.0)*
Max. Bend. Moment, Turbo Out.--lb-ft (Nm) .5.2 (7.0)
Max. Shear on Turbo Outlet--lb (kg) ................24 (11)
Prime
Standby
Fuel System
ECU Description ................................. L14 Controller*
Fuel Injection Pump .................................Denso HP3
Governor Type ............................................ Electronic
Total Fuel Flow--lb/hr (kg/hr)...........147(66.7) .... 167 (75.8)
Fuel Consumption--lb/hr (kg/hr)...........61(28) ...... 70 (31.6)
Max. Fuel Inlet Temp.--F (C) .......................176 (80)
Fuel Temp. Rise, Inlt to Retrn--F (C)84.2(47) ..... 94.1(52)
Max. Fuel Inlet Restriction--in. H2O (kPa) .......80 (20)
Max. Fuel Inlet Pressure--in. H2O (kPa) ........NA (NA)
Max. Fuel Return Pressure--in. H2O (kPa) ......80 (20)

4045 - Generator

All values at rated speed and power with standard options unless otherwise noted.

* Revised Data
Curve 4045HF4851800197................................ Sheet 2 of 2
October 2006

April 2009

POWERTECH 4.5 L Engine


Model: 4045TFM75

ENGINE PERFORMANCE CURVE


Rating:

Marine
98 hp (73 kW) @ 1800 rpm
74 hp (55 kW) @ 1500 rpm

Application: Generator
Prime Power
Keel Cooled

Generator
Efficiency %

1500 (50)

88-92

--

--

1800 (60)

88-92

--

--

Brake Power -- hp (kW)

Speed
rpm (Hz)

(no fan)

Power
Factor

Calculated Gen-Set Rating


kW

kVA

0.8

48-51

60-64

0.8

64-67

80-84

120
(89)
10% Overload Power

100
(70)

Air Intake Restriction ...................12 in.H2O (3 kPa)


Exhaust Back Pressure ........... 30 in.H2O (7.5 kPa)
Gross power guaranteed within + or - 5% at SAE J1995
and ISO 8665 conditions:
77 F (25 C) air inlet temperature
29.31 in.Hg (99 kPa) barometer
104 F (40 C) fuel inlet temperature
0.853 fuel specific gravity @ 60 F (15.5 C)
Conversion factors:
Power: kW = hp x 0.746
Fuel: 1 gal = 7.1 lb, 1 L = 0.85 kg
Torque: Nm = lb-ft x 1.356

Prime Power

All values are from currently available data and are subject
to change without notice.

10% Overload Power

80
(60)

Prime Power

Notes:

1500 rpm
1800 rpm
Engine Speed -- rpm

- 1500 rpm

- 1800 rpm

Fuel -- gal/hr (L/hr)

1800 RPM
Emission Certifications:

6
(22.7)

10% Overload Power

EPA Commercial Marine

1500 RPM
Emission Certifications:
IMO Exempt*

(40 CFR Part 94)

IMO Exempt*

4
(15.1)

10% Overload Power

Ref: Engine Emission Label

Ref: Engine Emission Label

Certified by:

2
(7.6)

0
(0)

Engine Performance Curves

20
(15)

40
(30)

60
(45)

80
100
(60)
(75)
Brake Power -- hp (kW)

120
(89)

140
(104)

Marine - Generator

* Revised Data
Curve 4045TFM7598MG ................................. Sheet 1 of 2
April 2004

November 2005

Engine Specification Data


General Data

Lubrication System

Model ...............................................................4045TFM75
Number of Cylinders ......................................................... 4
Bore and Stroke--in. (mm)............... 4.2 x 5.0 (106.5 x 127)
Displacement--in.3 (L) ...........................................275 (4.5)
Compression Ratio ................................................. 17.6 : 1
Valves per Cylinder--Intake/Exhaust ............................ 1 / 1
Firing Order............................................................. 1-3-4-2
Combustion System .................................... Direct Injection
Engine Type ................................................ In-line, 4-Cycle
Aspiration ......................................................Turbocharged
Engine Crankcase Vent System ................................ Open
Max. Crankcase Pressure--in. H2O (kPa) .................2 (0.5)

Physical Data
Length--in. (mm) .................................................34.8 (885)
Width--in. (mm) ...................................................28.0 (712)
Height, Crank Center to Top--in. (mm) ................24.4 (620)
Height, Crank Center to Bottom--in. (mm) .......... 11.5 (292)
Weight, dry--lb (kg).............................................1019 (462)
(Includes flywheel housing, flywheel & electrics)
Center of Gravity Location From
Rear Face of Block (X-axis)--in. (mm) ..........10.6 (270)
Right of Crankshaft (Y-axis)--in. (mm) ............ -1.0 (-25)
Above Crankshaft (Z-axis)--in. (mm) ...............7.9 (200)
Max. Allow. Static Bending Moment at Rear Face
of Flywhl Hsg w/ 5-G Load--lb-ft (Nm) ..........600 (814)
Thrust Brng. Load Limit (Forward)--lb (N)....900 (4003)
Maximum Installation Angle
Front up--degrees ....................................................12*
Front down--degrees................................................... 0

Air System

1800 rpm 1500 rpm

Min. Ventilation Area--in.2 (m2) .....49.6(0.032) .34.1(0.022)


Maximum Allowable Air Temperature Rise,
Ambient to Engine Inlet--F (C) ......30 (17) ........30 (17)
Engine Air Flow--ft3/min (m3/min) .....184 (5.2) .....124 (3.5)
Maximum Air Intake Restriction
Dirty Air Cleaner--in. H2O (kPa) ....25 (6.25) .....25 (6.25)
Clean Air Cleaner--in. H2O (kPa)....12 (3.0) .......12 (3.0)
Intake Manifold Pressure--psi (kPa)* 9.7 (67)* ..... 4.6 (32)*

Engine Performance Curves

Cooling System

1800 rpm 1500 rpm

Eng. Heat Reject.--BTU/min (kW).....3523 (62) ... 2681 (47)


Eng. Radiated Heat--BTU/min (kW) ..564 (9.9) .... 404 (7.1)
Coolant Flow--gal/min (L/min).......... 32* (125*) .. 30* (116*)
Min. Coolant Fill Rate--gal/min (L/min) .........3.2 (12)
Thermostat Start to Open--F (C) ...............180 (82)
Thermostat Fully Open--F (C)...................203 (95)
Maximum Top Tank Temp--F (C) ............212 (100)
Minimum Sea Water-to-Boil--F (C) .............90 (32)
Min. Water Pump In. Press.--in. H2O (kPa) ...00 (00)
Recd. Pressure Cap--psi (kPa) .....................10 (70)
Max. Pressure Drop
Across Keel Cooler--psi (kPa)...........4 (30) ......... 3 (20)
Engine Coolant Capacity--qt (L) ...........15 (14) ....... 15 (14)

Electrical System

12 Volts

24 Volts

Recommended Battery Capacity


CCA @ 32 F (0 C)--amp .................... 640 ............. 570
Max. Starting Circuit Resist.--Ohm ...... 0.0012 .......... 0.002
Starter Rolling Current
@ 32 F ( 0 C)--amp ........................... 780 ............. 600

Sea Water System

Performance Data

1800 rpm 1500 rpm

Rated Prime Power--hp (kW) .............98 (73) ........ 74 (55)


10% Overload Engine Power--hp (kW)107 (80) ...... 82 (61)
Low Idle Speed--rpm .............................. 1150 ............1150
Rated Torque--ft-lb (Nm).................285 (386) .... 260 (353)
BMEP--psi (kPa) ............................155 (1071) .... 142 (980)
Friction Power @ Rated Speed--hp (kW)17 (13)..... 13 (10)
Smoke @ Rated Speed--Bosch No. .......... NA.............. NA

1800 rpm 1500 rpm

1800 rpm 1500 rpm

Exhaust Gas Flow--ft3/min (m3/min) 463 (13.1) .... 300 (9.0)


Exhaust Temperature--F (C) ..........889 (476) ... 851 (455)
Min. Exhaust Pipe Dia. Dry--in. (mm) ..2.5 (65) ...... 2.0 (50)
Min. Exhaust Pipe Dia. Wet--in. (mm) .3.0 (75) ...... 2.5 (65)
Max. Allow. Back Press.--in. H2O (kPa)........30 (7.5)
Max. Weight on Turbo--lb (kg) .................26.5 (12.0)

Fuel System

1800 rpm 1500 rpm

Sea Water Pump Flow--gal/min (L/min) 22 (84) ....... 18 (70)


Max. Inlet Restriction--in. H2O (kPa) ..120 (30) ..... 100 (25)
Max. Outlet Press--psi (kPa)...............20 (135) ..... 20 (135)
Max. Suction Lift--ft (m) .......................10 (3.0) ...... 10 (3.0)

Fuel Consumption

Exhaust System

1800 rpm 1500 rpm

Oil Press. at Rated Speed--psi (kPa)..50 (345) ..... 45 (311)


Oil Pressure at Low Idle--psi (kPa) .....15 (105) ..... 15 (105)

1800 rpm

10% Overload Power-- gal/hr (L/hr).5.6 (21.1) .... 4.1 (15.7)

1500 rpm

Fuel Injection Pump--Stanadyne.................... DE-10


Governor Type .......................................... Electronic
Governor Regulation--percent ............... 0 to 5 .......... 0 to 6
Total Fuel Flow--lb/hr (kg/hr)..............212 (96) ...... 205 (93)
Total Fuel Flow--gal/hr (L/hr)..............30 (113) ...... 29 (109)
Min. Recd. Fuel Line ID--in. (mm)................0.25 (6)
Min. Recd. Fuel Line Size ..................................... -5
Fuel Cons. Prime --lb/hr (kg/hr)....36.8 (16.7) .. 26.5 (12.0)
Fuel Cons. Prime --gal/hr (L/hr) .....5.2 (19.7) .... 3.7 (14.1)
Max Leak-off Line Press.--psi (kPa) ................3 (20)
Max Leak-off Return Height--ft (m) .................8 (2.5)
Max. Fuel Trans. Pump Suction--ft (m).........10 (3.0)
Max. Fuel Ht. Above Inj.Pump--ft (m) ...........10 (3.0)
Max. Fuel Inlet Temp. w/o derate--F (C) .212 (100)
Fuel Filter @ 98% Efficiency--Microns.................... 2

Marine - Generator

Prime:
25 % Power-- gal/hr (L/hr) .......1.5 (5.8) ...... 1.2 (4.6)
50 % Power-- gal/hr (L/hr) .....2.8 (10.7) ...... 2.0 (7.6)
75 % Power-- gal/hr (L/hr) .....4.0 (15.3) .... 2.9 (10.8)
100 % Power-- gal/hr (L/hr) .....5.2 (19.7) .... 3.7 (14.1)

Data based on keel-cooled engine.

All values at rated speed and power with standard options unless otherwise noted.

* Revised Data
Curve 4045TFM7598MG ................................... Sheet 2 of 2
April 2004

July 2007

ENGINE PERFORMANCE CURVE

Generator

Marine

Application:

Generator (60 Hz)


Prime Power

Power Calculated Gen-Set Rating Prime Power 10% Overload Power

Efficiency (%) Factor

88-92

Rating:

0.8

kW

kVA

hp (kW)

hp (kW)

195-204

244-255

297 (222)

327 (244)

297 hp @ 1800 RPM


222 kW @ 1800 RPM
285 hp @ 2100 RPM
See Option Code Table
213 kW @ 2100 RPM
See Option Code Table

(Propeller Power is approximately 97% of Crankshaft Power)

REFERENCE
CONDITIONS
REFERENCE
CONDITIONS

Air Intake Restriction......................................................................12 in.H 2O (3 kPa)


Exhaust Back Pressure................................................................ 30 in.H2O (7.5 kPa)

Air Intake Restriction.


Rated speed
power
Exhaust
Backand
Pressure

Gross power guaranteed within 5% at SAE J1995 and ISO 3046


J1995 and ISO 3046 conditions:
77 F (25 C) air inlet temperature
29.31 in.Hg (99 kPa) barometric pressure
104 F (40 C) fuel inlet temperature
Rated speed and power
0.853 fuel specific gravity @ 60 F (15.5 C)

12 in.H2O (3 kPa)

30 in.H2O (7.5 kPa)

J1995 and ISO 3046 conditions:

Fuel Consumption

Ambient air temperature is defined to be the temperature of ambient air close to


F is
(25not
C) influenced
air inlet temperature
operating vessel77
that
in any manner by operating characteristics of the
vessel (free field temp).

20
(76)
20.0

29.31 in.Hg (99 kPa) barometer

Conversion factors:
104 F (40 C) fuel inlet temperature
Power: kW = hp x 0.746
0.853 Fuel:
fuel specific
600.85
F (15.5
C)
1 gal = gravity
7.1 lb, 1@
L=
kg
Torque: Nm = lb-ft x 1.356

10% Overload Power


16
(61)
16.0

Fuel - gal/hr (L/hr)

PowerTechTM 9.0L Engine


Model: 6090AFM75
Model:
6090AFM75
JD Electronic
Control

All values from currently available data. Subject to manufacturing and measurement
variations and to change without notice.
Actual performance is subject to application and operation conditions outside of John
Deere control.

Conversion factors:

12
(45)
12.0

Power: kW = hp x 0.746

Prime Power

Notes:

Fuel: 1 gal = 7.1 lb, 1 L = 0.85 kg

Torque:
Nm
= lb-ft
x 1.356
Marine Generator
: The
Marine
generator
engine rating is the power available under

88.0
(30)

normal varying electrical load factors for an unlimited number of hours per year in
commercial applications.
This rating incorporates a 10% overload capability, and conforms to ISO 8528 prime power.
Average load over a 24-hour period shall not exceed 67% of the prime rating, of which no
more than 2 hours are between 100% and 110% of the prime rating.

44.0
(15)

The marine generator rating is restricted to generator applications only. The criteria used to
establish marine generator application ratings are the same used to establish industrial
prime power generator application ratings

0 (0)
0.0
50
50

(37)

100
100

(75)

150
150
(112)

200
200
(149)

250
250
(186)

300
300

(224)

350
350
(261)

Designed/Calibrated to meet:

Certified by:

EPA Commercial Marine Tier 2


IMO MARPOL Annex VI Compliant

Brake Power - hp (kW)

Ref: Engine Emission Label

Performance Curve: 6090AFM75_E


All values at rated speed, power, and standard conditions, per SAE J1995 unless otherwise noted.
Engine Performance Curves

6090 - Marine Generator

July 2011

Engine Installation Criteria


General Data

Physical Data

M75
ntrol

Model

ower)

Number of Cylinders

RPM
RPM
able

Bore

118 mm

Stroke

127 mm

Displacement

6090AFM75

Length

66.2 in

938 mm

36.9 in

4.6 in

Height, centerline to top

665 mm

26.2 in

5.0 in

Height, centerline to bottom

319 mm

12.6 in

1011 kg

2229 lb

434 mm

17.8 in

9.0 L

549 in
16.0:1

Compression Ratio

Weight, with oil, no coolant (includes engine,


flywheel housing, flywheel, and electronics)

2/2

Valves per Cylinder, Intake/Exhaust


Combustion System

1682 mm

Width

Center of Gravity Location, X-axis From Rear

Direct injection

Face of Block

Firing Order

1-5-3-6-2-4

Center of Gravity Location, Y-axis Right of Crankshaft

4.5 mm

0.18 in

Engine Type

In line, 4 Cycle

Center of Gravity Location, Z-axis Above Crankshaft

106 mm

4.2 in

Turbocharged and Aftercooled

Max. Allowable Static Bending Moment At Rear Face

814 Nm

600 lb-ft

Thrust Bearing Load Limit, Forward Continuous

8.6 kN

1933 lbf

Thrust Bearing Load Limit, Forward Intermittent

13 kN

2923 lbf

Thrust Bearing Load Limit, Rearward Continuous

4 kN

900 lbf

Thrust Bearing Load Limit, Rearward Intermittent

6 kN

1349 lbf

Aspiration
Aftercooling System

Engine coolant
Closed

Engine Crankcase Vent System

Cooling System*
Engine Coolant Heat Rejection**

202 kW

11498 BTU/min

Max. Pressure Drop Across Keel Cooler

40 kPa

5.8 psi

Coolant Flow

of Flywheel Housing with 5-G Load

Electrical System

282 L/min

74.6 gal/min

Thermostat Start to Open

82 C

180 F

Min. Recommended Battery Capacity, 12V @32 F (0 C)

1100 amps

Thermostat Fully Open

94 C

202 F

Min. Recommended Battery Capacity, 24V @32 F (0 C)

750 amps

Engine Coolant Capacity, HE

47.5 L

12.5 gal

Starter Rolling Current, 12V @32 F (0 C)

920 amps

Engine Coolant Capacity, KC

43.5 L

11.5 gal

Starter Rolling Current, 24V @32 F (0 C)

600 amps

Min. Coolant Fill Rate

12 L/min

3 gal/min

Min. Voltage at ECU during Cranking, 12V

6 volts

Min. Pressure Cap

110 kPa

16 psi

Min. Voltage at ECU during Cranking, 24V

10 volts

30 kPa

4.4 psi

Max. Allowable Start Circuit Resistance, 12V

0.0012 ohms
0.002 ohms

Min. Pump Inlet Pressure


Max. External Coolant Restriction

40 kPa

5.8 psi

Max. Allowable Start Circuit Resistance, 24V

Normal Operation Max Top Tank Temperature

100 C

212 F

Recommended Starter Cable, 12V 100"

5% of Total Operating Time Top


Tank Temperature

100-110 C

212-230 F

Absolute Max Top Tank Temperature

110 C

230 F

Recommended Fuel Cooler

TBD kW

TBD BTU/min

#00

Recommended Starter Cable, 24V 100"

#2

Recommended Starter Cable, 12V 200"

#0000 or 2 #00
#0

Recommended Starter Cable, 24V 200"


Electrical Component Maximum Temperature Limit

125 C

257 F

* The cooling system should be capable of typical at ambient up to the maximum


conditions in which the vessel will operate.
Typical operation is defined as the average load sustainable in the vessel over 10 min.
** Reference 32 C Sea Water Temperature

Performance Curve: 6090AFM75_E

All values at rated speed and power at standard conditions per SAE J1995 unless otherwise noted.
Engine Performance Curves

6090 - Marine Generator

Sheet 2 - July 2011

Engine Installation Criteria


Fuel System

Air Intake System


L14

ECU Description
Fuel Injection Pump
Governor Type
Volumetric Fuel Consumption
Mass Fuel Consumption
Total Fuel Volumetric Flow

15.1 m3/min 533.3 ft3/min

Engine Air Flow

Denso HP4

Intake Manifold Pressure

153.2 kPa

22.2 psi

Electronic

Manifold Air Temperature

92 C

198 F

130 C

266 F

17 C

30 F

55.5 L/hr

14.6 gal/hr

47.2 kg/hr

104 lb/hr

240 L/hr

63.4 gal/hr

Maximum Manifold Air Temperature


Max. Allowable Temperature Rise, Ambient
Air to Engine Inlet

204 kg/hr

450 lb/hr

Max. Air Intake Restriction, Clean Air Cleaner

3 kPa

12 in.H2O

Max. Fuel Inlet Restriction*

30 kPa

120 in.H2O

Max. Air Intake Restriction, Dirty Air Cleaner

6.25 kPa

25 in.H2O

Max. Fuel Inlet Pressure

20 kPa

80 in.H2O

Min. Ventilation Area

0.093 m2

144 in2

Max. Fuel Height Above Transfer Pump

2.41 m

7.9 ft

Max Fuel Return Pressure

20 kPa

80 in.H2O

Max. Leak-off Return Height

2.41 m

7.9 ft

Prime Power

222 kW

297 hp

40 C

104 F

10% Overload Power

244 kW

327 hp

Max. Fuel Inlet Temperature

100 C

212 F

Rated Speed

Min. Recommended Fuel Line Inside Diameter

8.3 mm

0.33 in

Low Idle Speed

Total Fuel Mass Flow

Normal Operation Fuel Temperature

1177 Nm

868 lb-ft

10 mic

BMEP, Prime

1643 kPa

238 psi

Rated Pferdestrke, Prime

Lubrication System
Oil Pressure at 1800 RPM

265 kPa

38.4 psi

Max. Crankcase Pressure

2 kPa

8 in.H2O

Maximum Installed Angle, Front Down

1000 RPM

Prime Torque

2 mic

Secondary Fuel Filter

1800 RPM

-6

Min. Recommended Fuel Line Size


Primary Fuel Filter

Performance Data

0 deg

298.6 ps

Front Drive Capacity, Intermittent

550 Nm

Front Drive Capacity, Continuous

468 Nm

Software and Label Convertible to 50 Hz?

406 lb-ft
348 lb-ft
NO

Exhaust System
39.7 m3/min

1402 ft3/min

Maximum Installed Angle, Front Up

12 deg

Engine Angularity Limits Any Direction, Continuous

20 deg

Exhaust Flow @ gas STP

Engine Angularity Limits Any Direction, Intermittent

30 deg

Exhaust Temperature

506 C

943 F

Max. Allowable Exhaust Restriction

7.5 kPa

30 in.H2O

11 kg

24 lb

7 Nm

5.2 lb-ft

Min. Exhaust Pipe Diameter, Dry

101.6 mm

4.0 in

Min. Exhaust Pipe Diameter, Wet

114.3 mm

4.5 in

* With clean filters

Exhaust Flow

Max. Shear on Turbocharger Exhaust Outlet


Max. Bending Moment on Turbocharger Exhaust
Outlet

16.4 m /min 579.2 ft3/min

Performance Curve: 6090AFM75_E


All values at rated speed and power at standard conditions per SAE J1995 unless otherwise noted.
2011

Engine Performance Curves

6090 - Marine Generator

Sheet 3 - July 2011

Engine Installation Criteria


Engine Performance Data Table
Engine Power
25%
50%
75%
100%
110%

Crank Power

Crank Torque

Fuel Consumption

BSFC

kW

hp

Nm

lb-ft

L/hr

gal/hr

g/kW-hr

55.5
110.9
166.4
221.8
244

74.4
148.7
223.1
297.4
327

294
588
883
1177
1295

217
434
651
868
955

16.5
29.4
42.7
55.5
61.2

4.3
7.8
11.3
14.7
16.2

252.2
225.2
218.2
212.7
213.3

Performance Curve: 6090AFM75_E


All values at rated speed and power at standard conditions per SAE J1995 unless otherwise noted.
2011

Engine Performance Curves

6090 - Marine Generator

Sheet 4 - July 2011

Connection to engine control unit

Connection to engine control unit


General
A number of different connector sets are
delivered with the engine depending on
customer-selected functionality and
parameters. The following section describes
the different connectors.
If the customer did not order Scanias Plug and
Play system, the customer must connect his
system to connectors B1 and B7 on EMS.

Connector B1
A description of the pins on connector B1 is
provided below.
Connector Pin
B1
1
2
3
4
5
6
7
8
9
10

Function
Supply voltage U30
GND (ground) U31
Ignition U15
Not connected
Not connected
Supply voltage U30
GND (ground) U31
Not connected
CAN high (gold plated)
CAN low (gold plated)

Connector B1

Note: There must be two connections for GND


(U31) and two for voltage (U30). GND (U31)
must be the same for all control units.

Scania CV AB 2008, Sweden

11

Connection to engine control unit

Connector B7
A description of the pins on connector B7 is
provided below.
Connector Pin
B7
1
2

Function
Engine Running Status
signal*)
Not connected

*) +24 V at engine speeds higher than idling


Connector kit 1 757 384 for EMS contains the
following parts:
Quantity
1
4
3
2
2

Part no.
1 426 460
1 380 386
1 380 388
1 427 320
1 126 474

Designation
Contact housing
Cable connector
Seal
Sealing plug
Secondary lock

Connector B7.

Tools for connector kit 1 757 384:


Crimping tool
Removal tool

588 204
99 592

Scania CV AB 2008, Sweden

13

Connection to engine control unit

Limp-home throttle
connection
A reserve accelerator pedal can be used if the
regular accelerator pedal malfunctions.

D9 A
D12 A
D16 A
D12 M
D16 M

1 520 205

1 456 342

Another alternative is to accelerate directly via


an input on engine control unit S6.
Different connector kits are used depending on
engine type. Refer to the table.

Connector kit 1 520 205


The connector must be connected as follows:
Note: If there is an existing connector, its
connections must be in the same position
Pin
5
7
8

Function
Earth connection to potentiometer
5 V supply to potentiometer
Signal from potentiometer to
the control unit
0 - 100% throttle =
0.485 V - 2.693 V*
* A fault code is set if the value from the
potentiometer is < 0.1 V or > 4.9 V

Connector kit 1 520 205 for connecting reserve


throttle/throttle directly to the engine control
unit contains the following parts:
Quantity
1
6
6
7
2

Part no.
1 426 473
1 380 386
1 380 388
1 427 320
1 426 475

Designation
Contact housing
Cable connector
Seal
Sealing plug
Lock

Tools for connector kit 1 520 205:


Crimping tool
Removal tool

16

588 204
99 592

Scania CV AB 2008, Sweden

1 716 164

Scania CV AB 2010, Sweden

13 litre engines with PDE

S6

Engine Management System

EMS

Sheet 3

Issue 1 en-GB

16:90-12

1 717 205

Scania CV AB 2011, Sweden

Applies to engines manufactured from July 2011

9 and 13 litre engines with PDE

S6

Engine Management System

EMS

Sheet 1

Issue 1 en-GB

16:90-29

HCI 434D/444D - Winding 311

APPROVED DOCUMENT

Technical Data Sheet

HCI434D/444D
SPECIFICATIONS & OPTIONS

STANDARDS

TERMINALS & TERMINAL BOX

Stamford industrial generators meet the requirements of BS EN


60034 and the relevant section of other international standards
such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2
100, AS1359.
Other standards and certifications can be considered on request.

Standard generators are 3-phase reconnectable with 12 ends


brought out to the terminals, which are mounted on a cover at
the non-drive end of the generator. A sheet steel terminal box
contains the AVR and provides ample space for the
customers' wiring and gland arrangements. It has removable
panels for easy access.

VOLTAGE REGULATORS
SHAFT & KEYS
AS440 AVR - STANDARD
With this self-excited system the main stator provides power via
the Automatic Voltage Regulator (AVR) to the exciter stator.
The high efficiency semi-conductors of the AVR ensure positive
build-up from initial low levels of residual voltage.
The exciter rotor output is fed to the main rotor through a threephase full-wave bridge rectifier. The rectifier is protected by a
surge suppressor against surges caused, for example, by short
circuit or out-of-phase paralleling.
The AS440 will support a range of electronic accessories,
including a 'droop' Current Transformer (CT) to permit parallel
operation with other ac generators.

All generator rotors are dynamically balanced to better than


BS6861:Part 1 Grade 2.5 for minimum vibration in operation.
Two bearing generators are balanced with a half key.
INSULATION/IMPREGNATION

APPROVED DOCUMENT

The insulation system is class 'H'.


All wound components are impregnated with materials and
processes designed specifically to provide the high build
required for static windings and the high mechanical strength
required for rotating components.
QUALITY ASSURANCE

MX341 AVR
This sophisticated AVR is incorporated into the Stamford
Permanent Magnet Generator (PMG) control system.
The PMG provides power via the AVR to the main exciter, giving
a source of constant excitation power independent of generator
output. The main exciter output is then fed to the main rotor,
through a full wave bridge, protected by a surge suppressor.
The AVR has in-built protection against sustained overexcitation, caused by internal or external faults. This de-excites
the machine after a minimum of 5 seconds.
An engine relief load acceptance feature can enable full load to
be applied to the generator in a single step.
If three-phase sensing is required with the PMG system the
MX321 AVR must be used.
We recommend three-phase sensing for applications with
greatly unbalanced or highly non-linear loads.

Generators are manufactured using production procedures


having a quality assurance level to BS EN ISO 9001.
The stated voltage regulation may not be maintained in the
presence of certain radio transmitted signals. Any change in
performance will fall within the limits of Criteria 'B' of EN
61000-6-2:2001. At no time will the steady-state voltage
regulation exceed 2%.
DE RATES
All values tabulated on page 8 are subject to the following
reductions
5% when air inlet filters are fitted.
3% for every 500 metres by which the operating altitude
exceeds 1000 metres above mean sea level.
3% for every 5C by which the operational ambient
temperature exceeds 40C.
Note: Requirement for operating in an ambient exceeding
60C must be referred to the factory.

MX321 AVR
The most sophisticated of all our AVRs combines all the features
of the MX341 with, additionally, three-phase rms sensing, for
improved regulation and performance.
Over voltage protection is built-in and short circuit current level
adjustments is an optional facility.

WINDINGS & ELECTRICAL PERFORMANCE


NB Continuous development of our products entitles us to
change specification details without notice, therefore they
must not be regarded as binding.

All generator stators are wound to 2/3 pitch. This eliminates


triplen (3rd, 9th, 15th ) harmonics on the voltage waveform
and is found to be the optimum design for trouble-free supply of
non-linear loads. The 2/3 pitch design avoids excessive neutral
currents sometimes seen with higher winding pitches, when in
parallel with the mains. A fully connected damper winding
reduces oscillations during paralleling. This winding, with the 2/3
pitch and carefully selected pole and tooth designs, ensures very
low waveform distortion.

Front cover drawing typical of product range.

HCI434D/444D
WINDING 311
CONTROL SYSTEM
A.V.R.
VOLTAGE REGULATION

SEPARATELY EXCITED BY P.M.G.


MX321

MX341

0.5 %

1.0 %

With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT

REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

CONTROL SYSTEM

SELF EXCITED

A.V.R.
VOLTAGE REGULATION
SUSTAINED SHORT CIRCUIT

AS440
1.0 %

With 4% ENGINE GOVERNING

WILL NOT SUSTAIN A SHORT CIRCUIT

INSULATION SYSTEM

CLASS H
IP23

PROTECTION

0.8

RATED POWER FACTOR

DOUBLE LAYER LAP

STATOR WINDING
WINDING PITCH

TWO THIRDS

WINDING LEADS

12

APPROVED DOCUMENT

STATOR WDG. RESISTANCE

0.0124 Ohms PER PHASE AT 22C SERIES STAR CONNECTED

ROTOR WDG. RESISTANCE

1.05 Ohms at 22C

EXCITER STATOR RESISTANCE

0.068 Ohms PER PHASE AT 22C

EXCITER ROTOR RESISTANCE


R.F.I. SUPPRESSION

18 Ohms at 22C

BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

WAVEFORM DISTORTION

NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%

MAXIMUM OVERSPEED
BEARING DRIVE END
BEARING NON-DRIVE END

2250 Rev/Min
BALL. 6317 (ISO)
BALL. 6314 (ISO)

1 BEARING

2 BEARING

WEIGHT COMP. GENERATOR

940 kg

950 kg

WEIGHT WOUND STATOR

415 kg

415 kg

WEIGHT WOUND ROTOR

361 kg

338 kg

4.0771 kgm2
1010 kg

3.8783 kgm2
1010 kg

155 x 87 x 107(cm)

155 x 87 x 107(cm)

WR INERTIA
SHIPPING WEIGHTS in a crate
PACKING CRATE SIZE
TELEPHONE INTERFERENCE

50 Hz

60 Hz

THF<2%

TIF<50

0.8 m/sec 1700 cfm

COOLING AIR
VOLTAGE SERIES STAR

380/220

400/231

VOLTAGE PARALLEL STAR

190/110

200/115

VOLTAGE SERIES DELTA


kVA BASE RATING FOR
REACTANCE VALUES
Xd DIR. AXIS SYNCHRONOUS

220/110

0.99 m/sec 2100 cfm

415/240

440/254

416/240

440/254

460/266

480/277

208/120

220/127

208/120

220/127

230/133

240/138

230/115

240/120

254/127

240/120

254/127

266/133

277/138

300

300

300

290

344

360

375

375

3.16

2.85

2.65

2.28

3.60

3.37

3.21

2.95

X'd DIR. AXIS TRANSIENT

0.20

0.18

0.17

0.15

0.22

0.21

0.20

0.18

X''d DIR. AXIS SUBTRANSIENT

0.14

0.13

0.12

0.10

0.15

0.14

0.14

0.12

Xq QUAD. AXIS REACTANCE

2.66

2.40

2.23

1.92

3.09

2.89

2.75

2.53

X''q QUAD. AXIS SUBTRANSIENT

0.39

0.36

0.33

0.28

0.40

0.38

0.36

0.33

XL LEAKAGE REACTANCE

0.07

0.06

0.06

0.05

0.09

0.09

0.08

0.07

X2 NEGATIVE SEQUENCE

0.26

0.24

0.22

0.19

0.28

0.27

0.25

0.23

0.10
X0 ZERO SEQUENCE
REACTANCES ARE SATURATED
T'd TRANSIENT TIME CONST.
T''d SUB-TRANSTIME CONST.
T'do O.C. FIELD TIME CONST.
Ta ARMATURE TIME CONST.
SHORT CIRCUIT RATIO

0.09
0.08
0.07
0.10
0.09
0.09
0.08
VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
0.08s
0.019s
1.7s
0.018s
1/Xd

50
Hz

HCI434D/444D
Winding 311
THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT
4

60
Hz

HCI434D/444D
Winding 311
THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT
5

HCI434D/444D
Winding 311
Locked Rotor Motor Starting Curve

50
Hz

MX
346V

380V

400V 415V

440V

25

20

20

P E R C E N T T R A N S IE N T V O L T A G E D IP .

25

15

10

0
0

100

200

300

400

500

600

700

800

900

LOCKED ROTOR kVA

346V

30

APPROVED DOCUMENT

P E R C E N T T R A N S IE N T V O L T A G E D IP .

30

SX
380V 400V

415V

440V

15

10

0
0

1000

100

200

300

400

500

600

700

800

LOCKED ROTOR kVA

60
Hz

MX
380V

30

416V

440V

460V 480V

20

P E R C E N T T R A N S IE N T V O L T A G E D IP .

P E R C E N T T R A N S IE N T V O L T A G E D IP .

25

15

10

SX
380V

30

416V

440V

460V

480V

25

20

15

10

0
0

100

200

300

400

500

600

700

800

900

1000

100

200

300

400

500

LOCKED ROTOR kVA

LOCKED ROTOR kVA

600

700

800

900

HCI434D
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.

50
Hz

10000

SYMMETRICAL

CURRE NT (Am ps)

ASYMMETRICAL

1000

0.01

0.1

TIME (secs)

Sustained Short Circuit = 1,200 Amps

60
Hz

CURRE NT (Am ps)

10000

1000

100
0.001

APPROVED DOCUMENT

100
0.001

0.01

0.1

TIME (secs)

10

SYMMETRICAL
ASYMMETRICAL

10

Sustained Short Circuit = 1,300 Amps


Note 1
The following multiplication factors should be
used to adjust the values from curve between
time 0.001 seconds and the minimum current
point in respect of nominal operating voltage :
50Hz
Voltage
380v
400v
415v
440v

3-phase

60Hz
Factor
X 1.00
X 1.05
X 1.09
X 1.16

Voltage
416v
440v
460v
480v

Note 2
The following multiplication factor should be used to convert the
values calculated in accordance with NOTE 1 to those applicable
to the various types of short circuit :

Factor
X 1.00
X 1.06
X 1.10
X 1.15

The sustained current value is constant irrespective


of voltage level

2-phase L-L 1-phase L-N


x 1.30
x 3.20
x 2.50
2 sec.

Instantaneous
x 1.00
x 0.87
Minimum
x 1.00
x 1.80
Sustained
x 1.00
x 1.50
Max. sustained duration
10 sec.
5 sec.
All other times are unchanged

Note 3
Curves are drawn for Star (Wye) connected machines. For other
connection the following multipliers should be applied to current
values as shown :

HCI434D/444D
Winding 311 / 0.8 Power Factor
RATINGS
Class - Temp Rise

50
Hz

Hz

Cont. H - 125/40C

Standby - 150/40C

Standby - 163/27C

Series Star (V)

380

400

415

440

380

400

415

440

380

400

415

440

380

400

415

440

Parallel Star (V)

190

200

208

220

190

200

208

220

190

200

208

220

190

200

208

220

Series Delta (V)

220

230

240

254

220

230

240

254

220

230

240

254

220

230

240

254

kVA

280

280

280

270

300

300

300

290

320

320

320

310

330

330

330

320

kW

224

224

224

216

240

240

240

232

256

256

256

248

264

264

264

256

Efficiency (%) 93.1

93.4

93.5

93.8

92.7

93.0

93.2

93.6

92.3

92.7

92.9

93.3

92.1

92.5

92.7

93.2

258

248

277

276

276

266

287

285

285

275

kW Input

241

240

240

230

259

258

Series Star (V)

416

440

460

480

416

440

460

480

416

440

460

480

416

440

460

480

Parallel Star (V)

208

220

230

240

208

220

230

240

208

220

230

240

208

220

230

240

Series Delta (V)

240

254

266

277

240

254

266

277

240

254

266

277

240

254

266

277

kVA

315

335

345

345

344

360

375

375

365

385

400

400

375

395

415

415

kW

252

268

276

276

275

288

300

300

292

308

320

320

300

316

332

332

Efficiency (%) 93.3

93.3

93.4

93.6

92.9

93.0

93.1

93.3

92.5

92.6

92.7

93.0

92.4

92.5

92.5

92.8

287

296

295

296

310

322

322

316

333

345

344

325

342

359

358

kW Input

270

APPROVED DOCUMENT

60

Cont. F - 105/40C

DIMENSIONS

APPROVED DOCUMENT
Head Office Address:

Barnack Road, Stamford


Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100
www.cumminsgeneratortechnologies.com

Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved


Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.

HC4D-311-TD-EN-SG-A

HCI 534D/544D - Winding 311

APPROVED DOCUMENT

Technical Data Sheet

HCI534D/544D
SPECIFICATIONS & OPTIONS

STANDARDS

TERMINALS & TERMINAL BOX

Stamford industrial generators meet the requirements of BS EN


60034 and the relevant section of other international standards
such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2
100, AS1359.
Other standards and certifications can be considered on request.

Standard generators are 3-phase reconnectable with 12 ends


brought out to the terminals, which are mounted on a cover at
the non-drive end of the generator. A sheet steel terminal box
contains the AVR and provides ample space for the
customers' wiring and gland arrangements. It has removable
panels for easy access.

VOLTAGE REGULATORS
SHAFT & KEYS
AS440 AVR - STANDARD
With this self-excited system the main stator provides power via
the Automatic Voltage Regulator (AVR) to the exciter stator.
The high efficiency semi-conductors of the AVR ensure positive
build-up from initial low levels of residual voltage.
The exciter rotor output is fed to the main rotor through a threephase full-wave bridge rectifier. The rectifier is protected by a
surge suppressor against surges caused, for example, by short
circuit or out-of-phase paralleling.
The AS440 will support a range of electronic accessories,
including a 'droop' Current Transformer (CT) to permit parallel
operation with other ac generators.

All generator rotors are dynamically balanced to better than


BS6861:Part 1 Grade 2.5 for minimum vibration in operation.
Two bearing generators are balanced with a half key.
INSULATION/IMPREGNATION

APPROVED DOCUMENT

The insulation system is class 'H'.


All wound components are impregnated with materials and
processes designed specifically to provide the high build
required for static windings and the high mechanical strength
required for rotating components.
QUALITY ASSURANCE

MX341 AVR
This sophisticated AVR is incorporated into the Stamford
Permanent Magnet Generator (PMG) control system.
The PMG provides power via the AVR to the main exciter, giving
a source of constant excitation power independent of generator
output. The main exciter output is then fed to the main rotor,
through a full wave bridge, protected by a surge suppressor.
The AVR has in-built protection against sustained overexcitation, caused by internal or external faults. This de-excites
the machine after a minimum of 5 seconds.
An engine relief load acceptance feature can enable full load to
be applied to the generator in a single step.
If three-phase sensing is required with the PMG system the
MX321 AVR must be used.
We recommend three-phase sensing for applications with
greatly unbalanced or highly non-linear loads.

Generators are manufactured using production procedures


having a quality assurance level to BS EN ISO 9001.
The stated voltage regulation may not be maintained in the
presence of certain radio transmitted signals. Any change in
performance will fall within the limits of Criteria 'B' of EN
61000-6-2:2001. At no time will the steady-state voltage
regulation exceed 2%.
DE RATES
All values tabulated on page 8 are subject to the following
reductions
5% when air inlet filters are fitted.
3% for every 500 metres by which the operating altitude
exceeds 1000 metres above mean sea level.
3% for every 5C by which the operational ambient
temperature exceeds 40C.
Note: Requirement for operating in an ambient exceeding
60C must be referred to the factory.

MX321 AVR
The most sophisticated of all our AVRs combines all the features
of the MX341 with, additionally, three-phase rms sensing, for
improved regulation and performance.
Over voltage protection is built-in and short circuit current level
adjustments is an optional facility.

WINDINGS & ELECTRICAL PERFORMANCE


NB Continuous development of our products entitles us to
change specification details without notice, therefore they
must not be regarded as binding.

All generator stators are wound to 2/3 pitch. This eliminates


triplen (3rd, 9th, 15th ) harmonics on the voltage waveform
and is found to be the optimum design for trouble-free supply of
non-linear loads. The 2/3 pitch design avoids excessive neutral
currents sometimes seen with higher winding pitches, when in
parallel with the mains. A fully connected damper winding
reduces oscillations during paralleling. This winding, with the 2/3
pitch and carefully selected pole and tooth designs, ensures very
low waveform distortion.

Front cover drawing typical of product range.

HCI534D/544D
WINDING 311
CONTROL SYSTEM
A.V.R.
VOLTAGE REGULATION

SEPARATELY EXCITED BY P.M.G.


MX321

MX341

0.5 %

1.0 %

With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT

REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

CONTROL SYSTEM

SELF EXCITED

A.V.R.
VOLTAGE REGULATION
SUSTAINED SHORT CIRCUIT

AS440
1.0 %

With 4% ENGINE GOVERNING

SERIES 4 CONTROL DOES NOT SUSTAIN A SHORT CIRCUIT CURRENT

INSULATION SYSTEM

CLASS H
IP23

PROTECTION

0.8

RATED POWER FACTOR

DOUBLE LAYER LAP

STATOR WINDING
WINDING PITCH

TWO THIRDS

WINDING LEADS

12

APPROVED DOCUMENT

STATOR WDG. RESISTANCE

0.0049 Ohms PER PHASE AT 22C SERIES STAR CONNECTED

ROTOR WDG. RESISTANCE

1.77 Ohms at 22C

EXCITER STATOR RESISTANCE


EXCITER ROTOR RESISTANCE
R.F.I. SUPPRESSION

17 Ohms at 22C
0.092 Ohms PER PHASE AT 22C

BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

WAVEFORM DISTORTION

NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%

MAXIMUM OVERSPEED
BEARING DRIVE END
BEARING NON-DRIVE END

2250 Rev/Min
BALL. 6220 (ISO)
BALL. 6314 (ISO)

1 BEARING

2 BEARING

1393 kg

1395 kg

WEIGHT COMP. GENERATOR


WEIGHT WOUND STATOR

657 kg

657 kg

WEIGHT WOUND ROTOR

563 kg

535 kg

8.0068 kgm2
1485 kg

7.7289 kgm2
1485 kg

166 x 87 x 124(cm)

166 x 87 x 124(cm)

WR INERTIA
SHIPPING WEIGHTS in a crate
PACKING CRATE SIZE
TELEPHONE INTERFERENCE

50 Hz

60 Hz

THF<2%

TIF<50

1.035 m/sec 2202 cfm

COOLING AIR
VOLTAGE SERIES STAR

380/220

400/231

VOLTAGE PARALLEL STAR

190/110

200/115

VOLTAGE SERIES DELTA


kVA BASE RATING FOR REACTANCE
VALUES
Xd DIR. AXIS SYNCHRONOUS

220/110

1.312 m/sec 2780 cfm

415/240

440/254

416/240

440/254

460/266

480/277

208/120

220/127

208/120

220/127

230/133

240/138

230/115

240/120

254/127

240/120

254/127

266/133

277/138

500

550

500

500

575

594

625

644
2.96

3.02

2.99

2.53

2.25

3.52

3.25

3.13

X'd DIR. AXIS TRANSIENT

0.16

0.15

0.13

0.12

0.17

0.16

0.15

0.14

X''d DIR. AXIS SUBTRANSIENT

0.11

0.11

0.09

0.08

0.12

0.11

0.11

0.10

Xq QUAD. AXIS REACTANCE

2.48

2.46

2.08

1.85

2.87

2.65

2.55

2.41

X''q QUAD. AXIS SUBTRANSIENT

0.27

0.28

0.23

0.20

0.31

0.29

0.28

0.26

XL LEAKAGE REACTANCE

0.05

0.04

0.04

0.04

0.06

0.06

0.05

0.05

X2 NEGATIVE SEQUENCE

0.19

0.19

0.16

0.14

0.22

0.20

0.20

0.10
X0 ZERO SEQUENCE
REACTANCES ARE SATURATED
T'd TRANSIENT TIME CONST.
T''d SUB-TRANSTIME CONST.
T'do O.C. FIELD TIME CONST.
Ta ARMATURE TIME CONST.
SHORT CIRCUIT RATIO

0.10

0.08
0.07
0.10
0.09
0.09
VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
0.08s
0.012s
2.2s
0.018s
1/Xd

0.19
0.08

50
Hz

HCI534D/544D
Winding 311
THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT
4

60
Hz

HCI534D/544D
Winding 311
THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT
5

HCI534D/544D
Winding 311
Locked Rotor Motor Starting Curve

50
Hz

MX
346V

380V 400V

415V

440V

25

20

20

P E R C E N T T R A N S IE N T V O L T A G E D IP .

25

15

10

0
0

200

400

600

800

1000

1200

1400

1600

LOCKED ROTOR kVA

346V

30

APPROVED DOCUMENT

P E R C E N T T R A N S IE N T V O L T A G E D IP .

30

SX
380V

400V

415V

440V

15

10

1800

200

400

600

800

1000

1200

1400

LOCKED ROTOR kVA

60
Hz

MX
380V

30

416V

440V 460V 480V

20

P E R C E N T T R A N S IE N T V O L T A G E D IP .

P E R C E N T T R A N S IE N T V O L T A G E D IP .

25

15

10

SX
380V

30

416V

440V

460V

480V

25

20

15

10

0
0

200

400

600

800

1000

1200

1400

1600

1800

2000

LOCKED ROTOR kVA

200

400

600

800
LOCKED ROTOR kVA

1000

1200

1400

1600

HCI534D/544D
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.

50
Hz

100000
SYMMETRICAL

CURRENT (Amps)

ASYMMETRICAL

10000

1000

APPROVED DOCUMENT

100
0.001

0.01

0.1
TIME (secs)

Sustained Short Circuit = 2,400 Amps

60
Hz

100000

CURRENT (Amps)

10000

1000

100
0.001

0.01

0.1
TIME (secs)

10

SYMMETRICAL
ASYMMETRICAL

10

Sustained Short Circuit = 2,500 Amps


Note 1
The following multiplication factors should be
used to adjust the values from curve between
time 0.001 seconds and the minimum current
point in respect of nominal operating voltage :
50Hz

Voltage
380v
400v
415v
440v

Factor
X 1.00
X 1.06
X 1.09
X 1.12

60Hz

Voltage
416v
440v
460v
480v

Note 2
The following multiplication factor should be used to convert the
values calculated in accordance with NOTE 1 to those applicable
to the various types of short circuit :
3-phase

Factor
X 1.00
X 1.06
X 1.12
X 1.20

The sustained current value is constant irrespective


of voltage level

2-phase L-L 1-phase L-N

Instantaneous
x 1.00
x 0.87
x 1.30
Minimum
x 1.00
x 1.80
x 3.20
Sustained
x 1.00
x 1.50
x 2.50
Max. sustained duration
10 sec.
5 sec.
2 sec.
All other times are unchanged
Note 3
Curves are drawn for Star (Wye) connected machines. For other
connections the following multipliers should be applied to current
values as shown :
Parallel Star = Curve current value X 2
Series Delta = Curve current value X 1.732

HCI534D/544D
Winding 311

0.8 Power Factor

RATINGS
Class - Temp Rise

50
Hz

Hz

Cont. H - 125/40C

Standby - 150/40C

Standby - 163/27C

Series Star (V)

380

400

415

440

380

400

415

440

380

400

415

440

380

400

415

440

Parallel Star (V)

190

200

208

220

190

200

208

220

190

200

208

220

190

200

208

220

Series Delta (V)

220

230

240

254

220

230

240

254

220

230

240

254

220

230

240

254

kVA

450

495

450

450

500

550

500

500

515

575

515

515

550

590

550

530

kW

360

396

360

360

400

440

400

400

412

460

412

412

440

472

440

424

Efficiency (%) 94.8

94.7

95.0

95.1

94.5

94.3

94.8

94.9

94.4

94.1

94.7

94.9

94.1

94.0

94.5

94.8

422

421

436

489

435

434

468

502

466

447

kW Input

380

418

379

379

423

467

Series Star (V)

416

440

460

480

416

440

460

480

416

440

460

480

416

440

460

480

Parallel Star (V)

208

220

230

240

208

220

230

240

208

220

230

240

208

220

230

240

Delta (V)

240

254

266

277

240

254

266

277

240

254

266

277

240

254

266

277

kVA

519

538

563

588

575

594

625

644

588

625

655

675

606

644

673

694

kW

415

430

450

470

460

475

500

515

470

500

524

540

485

515

538

555

Efficiency (%) 94.7

94.8

94.9

94.9

94.5

94.6

94.6

94.7

94.4

94.4

94.5

94.5

94.3

94.3

94.4

94.4

454

475

496

487

502

529

544

498

530

554

571

514

546

570

588

kW Input

438

APPROVED DOCUMENT

60

Cont. F - 105/40C

DIMENSIONS

APPROVED DOCUMENT
Head Office Address:

Barnack Road, Stamford


Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100
www.cumminsgeneratortechnologies.com

Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved


Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.

HC5D-311-TD-EN-SG-A

UCI274C - Winding 311

APPROVED DOCUMENT

Technical Data Sheet

UCI274C
SPECIFICATIONS & OPTIONS
STANDARDS

WINDINGS & ELECTRICAL PERFORMANCE

Stamford industrial generators meet the requirements of


BS EN 60034 and the relevant section of other international
standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34,
CSA C22.2-100, AS1359.
Other standards and certifications can be considered on
request.

All generator stators are wound to 2/3 pitch. This eliminates


triplen (3rd, 9th, 15th ) harmonics on the voltage waveform
and is found to be the optimum design for trouble-free supply
of non-linear loads. The 2/3 pitch design avoids excessive
neutral currents sometimes seen with higher winding pitches,
when in parallel with the mains. A fully connected damper
winding reduces oscillations during paralleling. This winding,
with the 2/3 pitch and carefully selected pole and tooth
designs, ensures very low waveform distortion.

VOLTAGE REGULATORS
SX460 AVR - STANDARD

TERMINALS & TERMINAL BOX


With this self excited control system the main stator supplies
power via the Automatic Voltage Regulator (AVR) to the exciter
stator. The high efficiency semiconductors of the AVR ensure
positive build-up from initial low levels of residual voltage.
The exciter rotor output is fed to the main rotor through a three
phase full wave bridge rectifier. This rectifier is protected by a
surge suppressor against surges caused, for example, by short
circuit.

APPROVED DOCUMENT

Standard generators are 3-phase reconnectable with 12 ends


brought out to the terminals, which are mounted on a cover at
the non-drive end of the generator. A sheet steel terminal box
contains the AVR and provides ample space for the
customers' wiring and gland arrangements. It has removable
panels for easy access.
SHAFT & KEYS

AS440 AVR

All generator rotors are dynamically balanced to better than


BS6861:Part 1 Grade 2.5 for minimum vibration in operation.
Two bearing generators are balanced with a half key.

With this self-excited system the main stator provides power via
the AVR to the exciter stator. The high efficiency semiconductors of the AVR ensure positive build-up from initial low
levels of residual voltage.
The exciter rotor output is fed to the main rotor through a threephase full-wave bridge rectifier. The rectifier is protected by a
surge suppressor against surges caused, for example, by short
circuit or out-of-phase paralleling.
The AS440 will support a range of electronic accessories,
including a 'droop' Current Transformer (CT) to permit parallel
operation with other ac generators.
MX341 AVR

INSULATION/IMPREGNATION
The insulation system is class 'H'.
All wound components are impregnated with materials and
processes designed specifically to provide the high build
required for static windings and the high mechanical strength
required for rotating components.
QUALITY ASSURANCE
Generators are manufactured using production procedures
having a quality assurance level to BS EN ISO 9001.

This sophisticated AVR is incorporated into the Stamford


Permanent Magnet Generator (PMG) control system.
The PMG provides power via the AVR to the main exciter,
giving a source of constant excitation power independent of
generator output. The main exciter output is then fed to the
main rotor, through a full wave bridge, protected by a surge
suppressor. The AVR has in-built protection against sustained
over-excitation, caused by internal or external faults. This deexcites the machine after a minimum of 5 seconds.
An engine relief load acceptance feature can enable full load to
be applied to the generator in a single step.
If three-phase sensing is required with the PMG system the
MX321 AVR must be used.
We recommend three-phase sensing for applications with
greatly unbalanced or highly non-linear loads.

The stated voltage regulation may not be maintained in the


presence of certain radio transmitted signals. Any change in
performance will fall within the limits of Criteria 'B' of EN
61000-6-2:2001. At no time will the steady-state voltage
regulation exceed 2%.
DE RATES
All values tabulated on page 8 are subject to the following
reductions
5% when air inlet filters are fitted.
3% for every 500 metres by which the operating altitude
exceeds 1000 metres above mean sea level.
3% for every 5C by which the operational ambient
temperature exceeds 40C.
Note: Requirement for operating in an ambient exceeding
60C must be referred to the factory.

MX321 AVR
The most sophisticated of all our AVRs combines all the
features of the MX341 with, additionally, three-phase rms
sensing, for improved regulation and performance.
Over voltage protection is built-in and short circuit current level
adjustments is an optional facility.

NB Continuous development of our products entitles us to


change specification details without notice, therefore they
must not be regarded as binding.
Front cover drawing typical of product range.

UCI274C
WINDING 311
CONTROL SYSTEM
A.V.R.
VOLTAGE REGULATION

SEPARATELY EXCITED BY P.M.G.


MX321

MX341

0.5 %

1.0 %

With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT

REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

CONTROL SYSTEM

SELF EXCITED

A.V.R.
VOLTAGE REGULATION
SUSTAINED SHORT CIRCUIT

SX460

AS440

1.0 %

1.0 %

With 4% ENGINE GOVERNING

SERIES 4 CONTROL DOES NOT SUSTAIN A SHORT CIRCUIT CURRENT

INSULATION SYSTEM

CLASS H
IP23

PROTECTION

0.8

RATED POWER FACTOR

DOUBLE LAYER CONCENTRIC

STATOR WINDING
WINDING PITCH

TWO THIRDS

WINDING LEADS

12

APPROVED DOCUMENT

STATOR WDG. RESISTANCE

0.059 Ohms PER PHASE AT 22C SERIES STAR CONNECTED

ROTOR WDG. RESISTANCE

1.12 Ohms at 22C

EXCITER STATOR RESISTANCE


EXCITER ROTOR RESISTANCE
R.F.I. SUPPRESSION

20 Ohms at 22C
0.091 Ohms PER PHASE AT 22C

BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

WAVEFORM DISTORTION

NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%

MAXIMUM OVERSPEED
BEARING DRIVE END
BEARING NON-DRIVE END

2250 Rev/Min
BALL. 6315-2RS (ISO)
BALL. 6310-2RS (ISO)

1 BEARING

2 BEARING

406 kg

420 kg

WEIGHT COMP. GENERATOR


WEIGHT WOUND STATOR

131 kg

131 kg

WEIGHT WOUND ROTOR

133.78 kg

122.82 kg

1.0288 kgm2
439 kg

0.9781 kgm2
452 kg

105 x 67 x 103(cm)

105 x 67 x 103(cm)

WR INERTIA
SHIPPING WEIGHTS in a crate
PACKING CRATE SIZE
TELEPHONE INTERFERENCE

50 Hz

60 Hz

THF<2%

TIF<50

0.514 m/sec 1090 cfm

COOLING AIR
VOLTAGE SERIES STAR

380/220

400/231

VOLTAGE PARALLEL STAR

190/110

200/115

VOLTAGE SERIES DELTA


kVA BASE RATING FOR REACTANCE
VALUES

220/110

0.617 m/sec 1308 cfm

415/240

440/254

416/240

440/254

460/266

480/277

208/120

220/127

208/120

220/127

230/133

240/138

230/115

240/120

254/127

240/120

254/127

266/133

277/138

100

100

100

N/A

112.5

117.5

117.5

125

Xd DIR. AXIS SYNCHRONOUS

2.45

2.21

2.05

2.76

2.58

2.36

2.30

X'd DIR. AXIS TRANSIENT

0.20

0.18

0.17

0.24

0.22

0.21

0.20

X''d DIR. AXIS SUBTRANSIENT

0.14

0.13

0.12

0.16

0.15

0.14

0.13

Xq QUAD. AXIS REACTANCE

1.59

1.43

1.33

1.58

1.48

1.35

1.32

X''q QUAD. AXIS SUBTRANSIENT

0.18

0.16

0.15

0.23

0.21

0.20

0.19

XL LEAKAGE

REACTANCE

0.07

0.06

0.06

0.08

0.07

0.07

0.07

X2 NEGATIVE SEQUENCE

0.16

0.14

0.13

0.19

0.18

0.16

0.10
X0 ZERO SEQUENCE
REACTANCES ARE SATURATED
T'd TRANSIENT TIME CONST.
T''d SUB-TRANSTIME CONST.
T'do O.C. FIELD TIME CONST.
Ta ARMATURE TIME CONST.
SHORT CIRCUIT RATIO

0.09

0.08
0.12
0.11
0.10
VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
0.028 s
0.001 s
0.8 s
0.007 s
1/Xd

0.16
0.10

50
Hz

UCI274C
Winding 311
THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT
4

60
Hz

UCI274C
Winding 311
THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT
5

UCI274C
Winding 311
Locked Rotor Motor Starting Curve

50
Hz

MX
346V

30

380V

400V

415V

346V

30

380V

400V

415V

25

25

20

15

10

0
0

50

100

150

200

250

APPROVED DOCUMENT

P E R C E N T T R A N S IE N T V O L T A G E D IP

20
P E R C E N T T R A N S IE N T V O L T A G E D IP

SX

15

10

300

LOCKED ROTOR kVA

50

100

150

200

250

300

LOCKED ROTOR kVA

60
Hz

MX
380V

30

416V 440V 460V 480V

416V

440V

460V

480V

25

20
P E R C E N T T R A N S IE N T V O L T A G E D IP

20
P E R C E N T T R A N S IE N T V O L T A G E D IP

380V

30

25

SX

15

10

15

10

0
0

50

100

150

200

250

300

350

400

450

LOCKED ROTOR kVA

50

100

150

200

LOCKED ROTOR kVA

250

300

350

UCI274C
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.

50
Hz

10000
SYMMETRICAL

CURRENT (Amps)

ASYMMETRICAL

1000

100

0.01

Sustained Short Circuit = 430 Amps

60
Hz

CURRENT (Amps)

10000

1000

100

10
0.001

0.01

APPROVED DOCUMENT

10
0.001

0.1
TIME (secs)

0.1
TIME (secs)

10

SYMMETRICAL
ASYMMETRICAL

10

Sustained Short Circuit = 550 Amps


Note 1
The following multiplication factors should be
used to adjust the values from curve between
time 0.001 seconds and the minimum current
point in respect of nominal operating voltage :
50Hz

Voltage
380v
400v
415v

Factor
X 1.00
X 1.07
X 1.12

60Hz

Voltage
416v
440v
460v
480v

Note 2
The following multiplication factor should be used to convert the
values calculated in accordance with NOTE 1 to those applicable
to the various types of short circuit :
3-phase

Factor
X 1.00
X 1.06
X 1.12
X 1.17

The sustained current value is constant irrespective


of voltage level

2-phase L-L 1-phase L-N


x 1.30
x 3.20
x 2.50
2 sec.

Instantaneous
x 1.00
x 0.87
Minimum
x 1.00
x 1.80
Sustained
x 1.00
x 1.50
Max. sustained duration
10 sec.
5 sec.
All other times are unchanged

Note 3
Curves are drawn for Star (Wye) connected machines. For other
connection the following multipliers should be applied to current
values as shown :
Parallel Star = Curve current value X 2
Series Delta = Curve current value X 1.732

UCI274C
Winding 311 / 0.8 Power Factor
RATINGS
Class - Temp Rise

50
Hz

Hz

Cont. H - 125/40C

Standby - 150/40C

Standby - 163/27C

Series Star (V)

380

400

415

440

380

400

415

440

380

400

415

440

380

400

415

440

Parallel Star (V)

190

200

208

220

190

200

208

220

190

200

208

220

190

200

208

220

Series Delta (V)

220

230

240

254

220

230

240

254

220

230

240

254

220

230

240

254

kVA 84.0

84.0

84.0

N/A

100.0 100.0 100.0

N/A

106.0 106.0 106.0

N/A

110.0 110.0 110.0

N/A

kW 67.2

67.2

67.2

N/A

80.0

80.0

80.0

N/A

84.8

84.8

84.8

N/A

88.0

88.0

88.0

N/A

Efficiency (%) 90.7

91.1

91.3

N/A

89.8

90.3

90.6

N/A

89.5

90.0

90.4

N/A

89.2

89.8

90.2

N/A

kW Input 74.1

73.8

73.6

N/A

89.1

88.6

88.3

N/A

94.7

94.2

93.8

N/A

98.7

98.0

97.6

N/A

APPROVED DOCUMENT

60

Cont. F - 105/40C

Series Star (V)

416

440

460

480

416

440

460

480

416

440

460

480

416

440

460

480

Parallel Star (V)

208

220

230

240

208

220

230

240

208

220

230

240

208

220

230

240

Series Delta (V)

240

254

266

277

240

254

266

277

240

254

266

277

240

254

266

277

kVA 97.5

106.3 106.3 112.5 112.5 117.5 117.5 125.0 116.3 125.0 125.0 132.5 120.0 127.5 127.5 137.5

kW 78.0

85.0

85.0

90.0

90.0

94.0

94.0

100.0

93.0

100.0 100.0 106.0

96.0

102.0 102.0 110.0

Efficiency (%) 90.9

91.0

91.4

91.5

90.2

90.6

91.0

91.1

90.0

90.2

89.8

90.1

kW Input 85.8

93.5

93.0

98.4

99.8

103.8 103.3 109.8 103.4 110.9 110.3 116.7 106.9 113.2 112.6 121.4

DIMENSIONS

90.7

90.8

90.6

90.6

APPROVED DOCUMENT
Head Office Address:

Barnack Road, Stamford


Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100
www.cumminsgeneratortechnologies.com

Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved


Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.

UC274C-311-TD-EN-SG-A

UCI274F - Winding 311

APPROVED DOCUMENT

Technical Data Sheet

UCI274F
SPECIFICATIONS & OPTIONS
STANDARDS

WINDINGS & ELECTRICAL PERFORMANCE

Stamford industrial generators meet the requirements of


BS EN 60034 and the relevant section of other international
standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34,
CSA C22.2-100, AS1359.
Other standards and certifications can be considered on
request.

All generator stators are wound to 2/3 pitch. This eliminates


triplen (3rd, 9th, 15th ) harmonics on the voltage waveform
and is found to be the optimum design for trouble-free supply
of non-linear loads. The 2/3 pitch design avoids excessive
neutral currents sometimes seen with higher winding pitches,
when in parallel with the mains. A fully connected damper
winding reduces oscillations during paralleling. This winding,
with the 2/3 pitch and carefully selected pole and tooth
designs, ensures very low waveform distortion.

VOLTAGE REGULATORS
SX460 AVR - STANDARD

TERMINALS & TERMINAL BOX


With this self excited control system the main stator supplies
power via the Automatic Voltage Regulator (AVR) to the exciter
stator. The high efficiency semiconductors of the AVR ensure
positive build-up from initial low levels of residual voltage.
The exciter rotor output is fed to the main rotor through a three
phase full wave bridge rectifier. This rectifier is protected by a
surge suppressor against surges caused, for example, by short
circuit.

APPROVED DOCUMENT

Standard generators are 3-phase reconnectable with 12 ends


brought out to the terminals, which are mounted on a cover at
the non-drive end of the generator. A sheet steel terminal box
contains the AVR and provides ample space for the
customers' wiring and gland arrangements. It has removable
panels for easy access.
SHAFT & KEYS

AS440 AVR

All generator rotors are dynamically balanced to better than


BS6861:Part 1 Grade 2.5 for minimum vibration in operation.
Two bearing generators are balanced with a half key.

With this self-excited system the main stator provides power via
the AVR to the exciter stator. The high efficiency semiconductors of the AVR ensure positive build-up from initial low
levels of residual voltage.
The exciter rotor output is fed to the main rotor through a threephase full-wave bridge rectifier. The rectifier is protected by a
surge suppressor against surges caused, for example, by short
circuit or out-of-phase paralleling.
The AS440 will support a range of electronic accessories,
including a 'droop' Current Transformer (CT) to permit parallel
operation with other ac generators.
MX341 AVR

INSULATION/IMPREGNATION
The insulation system is class 'H'.
All wound components are impregnated with materials and
processes designed specifically to provide the high build
required for static windings and the high mechanical strength
required for rotating components.
QUALITY ASSURANCE
Generators are manufactured using production procedures
having a quality assurance level to BS EN ISO 9001.

This sophisticated AVR is incorporated into the Stamford


Permanent Magnet Generator (PMG) control system.
The PMG provides power via the AVR to the main exciter,
giving a source of constant excitation power independent of
generator output. The main exciter output is then fed to the
main rotor, through a full wave bridge, protected by a surge
suppressor. The AVR has in-built protection against sustained
over-excitation, caused by internal or external faults. This deexcites the machine after a minimum of 5 seconds.
An engine relief load acceptance feature can enable full load to
be applied to the generator in a single step.
If three-phase sensing is required with the PMG system the
MX321 AVR must be used.
We recommend three-phase sensing for applications with
greatly unbalanced or highly non-linear loads.

The stated voltage regulation may not be maintained in the


presence of certain radio transmitted signals. Any change in
performance will fall within the limits of Criteria 'B' of EN
61000-6-2:2001. At no time will the steady-state voltage
regulation exceed 2%.
DE RATES
All values tabulated on page 8 are subject to the following
reductions
5% when air inlet filters are fitted.
3% for every 500 metres by which the operating altitude
exceeds 1000 metres above mean sea level.
3% for every 5C by which the operational ambient
temperature exceeds 40C.
Note: Requirement for operating in an ambient exceeding
60C must be referred to the factory.

MX321 AVR
The most sophisticated of all our AVRs combines all the
features of the MX341 with, additionally, three-phase rms
sensing, for improved regulation and performance.
Over voltage protection is built-in and short circuit current level
adjustments is an optional facility.

NB Continuous development of our products entitles us to


change specification details without notice, therefore they
must not be regarded as binding.
Front cover drawing typical of product range.

UCI274F
WINDING 311
CONTROL SYSTEM
A.V.R.
VOLTAGE REGULATION

SEPARATELY EXCITED BY P.M.G.


MX321

MX341

0.5 %

1.0 %

With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT

REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

CONTROL SYSTEM

SELF EXCITED

A.V.R.
VOLTAGE REGULATION
SUSTAINED SHORT CIRCUIT

SX460

AS440

1.0 %

1.0 %

With 4% ENGINE GOVERNING

SERIES 4 CONTROL DOES NOT SUSTAIN A SHORT CIRCUIT CURRENT

INSULATION SYSTEM

CLASS H
IP23

PROTECTION

0.8

RATED POWER FACTOR

DOUBLE LAYER CONCENTRIC

STATOR WINDING
WINDING PITCH

TWO THIRDS

WINDING LEADS

12

APPROVED DOCUMENT

STATOR WDG. RESISTANCE

0.024 Ohms PER PHASE AT 22C SERIES STAR CONNECTED

ROTOR WDG. RESISTANCE

1.52 Ohms at 22C

EXCITER STATOR RESISTANCE


EXCITER ROTOR RESISTANCE
R.F.I. SUPPRESSION

20 Ohms at 22C
0.091 Ohms PER PHASE AT 22C

BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

WAVEFORM DISTORTION

NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%

MAXIMUM OVERSPEED
BEARING DRIVE END
BEARING NON-DRIVE END

2250 Rev/Min
BALL. 6315-2RS (ISO)
BALL. 6310-2RS (ISO)

1 BEARING

2 BEARING

530 kg

545 kg

WEIGHT COMP. GENERATOR


WEIGHT WOUND STATOR

200 kg

200 kg

WEIGHT WOUND ROTOR

188.67 kg

177.71 kg

1.555 kgm2
563 kg

1.5044 kgm2
577 kg

123 x 67 x 103(cm)

123 x 67 x 103(cm)

WR INERTIA
SHIPPING WEIGHTS in a crate
PACKING CRATE SIZE
TELEPHONE INTERFERENCE

50 Hz

60 Hz

THF<2%

TIF<50

0.514 m/sec 1090 cfm

COOLING AIR
VOLTAGE SERIES STAR

380/220

400/231

VOLTAGE PARALLEL STAR

190/110

200/115

VOLTAGE SERIES DELTA


kVA BASE RATING FOR REACTANCE
VALUES
Xd DIR. AXIS SYNCHRONOUS

220/110

0.617 m/sec 1308 cfm

415/240

440/254

416/240

440/254

460/266

480/277

208/120

220/127

208/120

220/127

230/133

240/138

230/115

240/120

254/127

240/120

254/127

266/133

277/138

160

160

160

N/A

181.3

190

190

206.3
2.16

2.24

2.02

1.88

2.53

2.37

2.17

X'd DIR. AXIS TRANSIENT

0.19

0.17

0.16

0.21

0.20

0.18

0.18

X''d DIR. AXIS SUBTRANSIENT

0.13

0.12

0.11

0.14

0.13

0.12

0.12

Xq QUAD. AXIS REACTANCE

1.38

1.25

1.16

1.53

1.43

1.31

1.31

X''q QUAD. AXIS SUBTRANSIENT

0.17

0.15

0.14

0.20

0.19

0.17

0.17

XL LEAKAGE REACTANCE

0.07

0.06

0.06

0.09

0.08

0.08

0.08

X2 NEGATIVE SEQUENCE

0.14

0.13

0.12

0.16

0.15

0.14

0.08
X0 ZERO SEQUENCE
REACTANCES ARE SATURATED
T'd TRANSIENT TIME CONST.
T''d SUB-TRANSTIME CONST.
T'do O.C. FIELD TIME CONST.
Ta ARMATURE TIME CONST.
SHORT CIRCUIT RATIO

0.08

0.07
0.10
0.09
0.09
VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
0.035 s
0.011 s
0.9 s
0.009 s
1/Xd

0.14
0.09

50
Hz

UCI274F
Winding 311
THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT
4

60
Hz

UCI274F
Winding 311
THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT
5

UCI274F
Winding 311
Locked Rotor Motor Starting Curve

50
Hz

MX
346V

30

380V

400V

415V

SX
346V

30

380V

400V

415V

25

25

20
P E R C E N T T R A N S IE N T V O L T A G E D IP

15

10

0
0

100

200

300

400

APPROVED DOCUMENT

P E R C E N T T R A N S IE N T V O L T A G E D IP

20

15

10

0
0

500

LOCKED ROTOR kVA

50

100

150

200

250

300

350

400

450

LOCKED ROTOR kVA

60
Hz

MX
380V

30

416V

440V 460V

416V

440V

400

450

460V 480V

25

20
P E R C E N T T R A N S IE N T V O L T A G E D IP

20
P E R C E N T T R A N S IE N T V O L T A G E D IP

380V

30

25

480V

SX

15

10

15

10

0
0

100

200

300

400

500

600

700

LOCKED ROTOR kVA

50

100

150

200

250

300

LOCKED ROTOR kVA

350

500

550

UCI274F
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.

50
Hz

10000
SYMMETRICAL

CURRENT (Amps)

ASYMMETRICAL

1000

100

0.01

Sustained Short Circuit = 750 Amps

60
Hz

CURRENT (Amps)

10000

1000

100

10
0.001

0.01

APPROVED DOCUMENT

10
0.001

0.1
TIME (secs)

0.1
TIME (secs)

10

SYMMETRICAL
ASYMMETRICAL

10

Sustained Short Circuit = 920 Amps


Note 1
The following multiplication factors should be
used to adjust the values from curve between
time 0.001 seconds and the minimum current
point in respect of nominal operating voltage :
50Hz

Voltage
380v
400v
415v

Factor
X 1.00
X 1.07
X 1.12

60Hz

Voltage
416v
440v
460v
480v

Note 2
The following multiplication factor should be used to convert the
values calculated in accordance with NOTE 1 to those applicable
to the various types of short circuit :
3-phase

Factor
X 1.00
X 1.06
X 1.12
X 1.17

The sustained current value is constant irrespective


of voltage level

2-phase L-L 1-phase L-N


x 1.30
x 3.20
x 2.50
2 sec.

Instantaneous
x 1.00
x 0.87
Minimum
x 1.00
x 1.80
Sustained
x 1.00
x 1.50
Max. sustained duration
10 sec.
5 sec.
All other times are unchanged

Note 3
Curves are drawn for Star (Wye) connected machines. For other
connection the following multipliers should be applied to current
values as shown :
Parallel Star = Curve current value X 2
Series Delta = Curve current value X 1.732

UCI274F
Winding 311 / 0.8 Power Factor
RATINGS
Class - Temp Rise

50
Hz

Cont. F - 105/40C

Standby - 163/27C

380

400

415

440

380

400

415

440

380

400

415

440

380

400

415

440

Parallel Star (V)

190

200

208

220

190

200

208

220

190

200

208

220

190

200

208

220

Series Delta (V)

220

230

240

254

220

230

240

254

220

230

240

254

220

230

240

254

kVA 145.0 145.0 145.0

N/A

160.0 160.0 160.0

N/A

170.0 170.0 170.0

N/A

175.0 175.0 175.0

N/A

kW 116.0 116.0 116.0

N/A

128.0 128.0 128.0

N/A

136.0 136.0 136.0

N/A

140.0 140.0 140.0

N/A

92.8

N/A

92.0

92.5

N/A

91.7

92.3

N/A

91.6

92.2

N/A

kW Input 125.7 125.3 125.0

N/A

139.1 138.7 138.4

N/A

148.3 147.7 147.3

N/A

152.8 152.2 151.8

N/A

92.6

92.3

APPROVED DOCUMENT

Hz

Standby - 150/40C

Series Star (V)

Efficiency (%) 92.3

60

Cont. H - 125/40C

92.1

92.0

Series Star (V)

416

440

460

480

416

440

460

480

416

440

460

480

416

440

460

480

Parallel Star (V)

208

220

230

240

208

220

230

240

208

220

230

240

208

220

230

240

Series Delta (V)

240

254

266

277

240

254

266

277

240

254

266

277

240

254

266

277

kVA 162.5 172.5 172.5 187.5 181.3 190.0 190.0 206.3 187.5 200.0 200.0 212.5 192.5 206.3 206.3 218.8
kW 130.0 138.0 138.0 150.0 145.0 152.0 152.0 165.0 150.0 160.0 160.0 170.0 154.0 165.0 165.0 175.0
Efficiency (%) 92.5

92.7

92.9

92.9

92.1

92.4

92.7

92.7

92.0

92.2

92.5

92.6

91.9

92.1

92.4

92.5

kW Input 140.5 148.9 148.5 161.5 157.5 164.5 164.0 178.0 163.0 173.5 173.0 183.6 167.6 179.2 178.6 189.2

DIMENSIONS

APPROVED DOCUMENT
Head Office Address:

Barnack Road, Stamford


Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100
www.cumminsgeneratortechnologies.com

Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved


Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.

UC274F-311-TD-EN-SG-A

D I G I T A L
V O L T A G E

R E G U L A T O R

The Cat Digital Voltage Regulator is a


microprocessor based control designed
to provide precise voltage control, robust
transient response, and generator protection
with industry leading features and versatility.

Caterpillar is leading the power generation


marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.

FEATURES

Microprocessor based control featuring choice


of three control modes standard:
Automatic Voltage Regulation (AVR)
Power Factor Regulation (PF)
Reactive Power Regulation (Var)
Programmable stability settings
Soft start control with an adjustable time
setting in AVR control mode
Dual Slope Underfrequency (volts/hertz)
regulation
Three-phase or single-phase generator voltage
(RMS) sensing/regulation in AVR mode
Single-phase generator current sensing for
regulation purposes
Field current and field voltage sensing
Five contact sensing inputs for system interface
One common LED for visual indication of
Alarm and Shutdown fault conditions
Fault Shutdown Driver and Alarm Output
Driver for indication of Alarm and Shutdown
fault conditions
Generator paralleling with reactive droop
compensation and reactive differential
compensation
Line drop compensation
Remote communication interface via CAN 2.0B
Ten generator protective functions
UL 508A Recognized and CE certified

WORLDWIDE PRODUCT SUPPORT


Worldwide parts availability through the
Caterpillar dealer network
Over 1,800 dealer branch stores operating
in 166 countries.
99.7% of parts orders filled within 24 hours.
The best product support record in the industry.
Caterpillar dealer service technicians are
trained to service every aspect of your electric
power generation system.
COMPLETE SYSTEM INTEGRATION
Fully designed and factory tested to work
seamlessly with Cat Generator using Shunt,
PMG, or AREP excitation systems and
EMCP controls.

LEHE3225

W H E R E

T H E

W O R L D

T U R N S

F O R

P O W E R

D I G I T A L
V O L T A G E

R E G U L A T O R

SPECIFICATIONS
General Specifications
Voltage Regulation
Temperature Drift
Response Time
Variable Sensing Range
Control Power
Regulator Filtering
Harmonic Tolerance
Weight
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Salt Spray
Vibration
Shock
Certifications
CE Approved
UL Recognized
CSA Listed

0.25% no load to full load


1.0% for a 40 C change
Maximum of 10 milliseconds
90 to 600 Volts
24 Vdc Supply (18 to 30 Vdc, 5VA)
THF 3% per IEC34-1
TIF of 50 NEMA MG1-22.43
0.5% Voltage regulation with 40% THD
1.47 kg (3.25 lb)
40 C to 70 C (40 F to 158 F)
40 C to 85 C (40 F to 185 F)
95% non-condensing 30 C to 60 C
5% for 48 hrs at 38 C at 115% nominal operating voltage
4.5G (peak) 18-2000 Hz in 3 perpendicular planes
20G

PROTECTIVE FUNCTIONS

Generator Overvoltage
Generator Undervoltage
Loss of Excitation
Instantaneous Field Overcurrent
Over Excitation
Loss of Sensing
Diode Fault Monitor
Internal Watchdog Failure
Internal Memory Failure
Fault Reset Closed Too Long

LEHE3225

D I G I T A L
V O L T A G E

R E G U L A T O R

Programmable Variables
Voltage vs Frequency Characteristic
Fine Voltage Level
Droop Adjustment
Overvoltage Setpoint
Overvoltage Time Delay
Undervoltage Setpoint
Undervoltage Time Delay
Gain
Single Phase or Three Phase Sensing
Under Frequency Point
Knee Frequency
Minimum Voltage Setpoint
Var Operating Mode
PF Operating Mode
Line Drop (IR) Compensation
Loss of Excitation
Loss of Excitation Time Delay
Over Excitation
Time Delay Fixed Time Option
Loss of Sensing Time Delay
Diode Fault Monitor
Soft Start Function

Range of Adjustment
Two slope ranges adjustable from 1 to 10 PU in 0.1 increments
10% to +10% in 0.1% increment
0 to 10% in 0.1% increment
105 to 135% of rated voltage in 1.0% increment
2 to 30 seconds in 1 second increments
60 to 95% of rated voltage in 1.0% increment
10 to 120 seconds in 1 second increments
1 to 20% in 0.1% increments
20 to 40 Hz
45 to 65 Hz in 0.1 Hz increments
50 to 100% of rated voltage
100% to 100% in 0.001 increments
0.6 lead to 0.6 lag in 0.01 increments
0 to 10% in 0.1% increment
0.1 to 1.0 PU leading vars
0.1 to 9.9 seconds in 0.1 second increments
0 to 12 Adc in 0.1 Adc increments
0 to 10 sec in 0.1 sec increments
0 to 25 sec in 1 sec increments
1 to 10A rms field ripple current
1 to 120 sec

LEHE3225

D I G I T A L
V O L T A G E

R E G U L A T O R

REGULATION CHARACTERISTIC FIGURE 1


Underfrequency Point (20-40 Hz)
100

Generator Output Voltage


Decreasing Slope 1 (1 10 V/HZ)

75
Decreasing Slope 2 (1 10 V/HZ)
50

5 Hz (Fixed)

25

Minimum Voltage Setpoint (50-100%)


Knee Frequency
20

40

60

80

100

% of Nominal Frequency

LEHE3225

D I G I T A L
V O L T A G E

R E G U L A T O R

OUTLINE DRAWING FIGURE 2


10.88 (276.4)

P6

7.50 typ.
(190.5)

P12

P9
J4

6.38 (162.1)

5.50 typ.
(139.7)
2.87 (72.9)
2.81 (71.4)

0.59 (15.0)
0
0.16 (4.06)

LEHE3225

D I G I T A L
V O L T A G E

R E G U L A T O R

EXAMPLE CONNECTION DIAGRAM FIGURE 3


A
11

GEN

CTB

10

52

PMG

10

8
9

10

10

P6-4 (F2,-)

P6-5 (F1,+)

P6-1

FIELD OUTPUT

P6-2

P6-3

POWER INPUT

VAR/PF
CONTROL

EXCITATION
DISABLE

FAULT
RESET

P9-9

P9-7

P9-8

P12-1

P12-2

P12-10

CURRENT
SENSING
RAISE/LOWER
INPUTS
P9-6

P12-11

P12-12

VOLTAGE
SENSING

P9-4

P9-5
4

P12-8 (+)

P12-7 (-)

24 Vdc CONTROL
POWER

ALARM
DRIVER
P12-4 (-)

24 Vdc _

SHUTDOWN
FAULT DRIVER

P12-9 (+)

P12-5 (-)

52a

P12-6 (+)

S1
2

Required only for Var/PF control. Var/PF is active with 52a closed, inactive with 52a open.

Excitation is disabled when closed, enabled when open.

Momentary closure resets any shutdown fault.

S1 (SPDT, spring -return to center-off position) adjusts regulator setpoint.

Normally-off, turns on for user alarm or trip.

Analog input voltage between -10 and +10 Vdc provides adjustment of operating setpoint.

External fuses should be sized to match the PMG and protect the field. Maximum fuse size
should be limited to Bussmann type KTK-12 or equivalent.

Three-phase PMG is shown. For single-phase PMG, omit P6-3 connection.

Sensing potential transformer is required if line voltage exceeds 660 Vac.

10

Item not supplied by Caterpillar.

11

When generator rotation is ACB, the connections shown for CTB should be reversed.

LEHE3225

GROUND

+/-10 VDC
CONTROL INPUT

10
1

P6-6

P12-3 (-)

D I G I T A L
V O L T A G E

R E G U L A T O R

LEHE3225

D I G I T A L
V O L T A G E

R E G U L A T O R

www.CAT-ElectricPower.com

U.S. and European sourced


LEHE3225 (8-03)

2003 Caterpillar
All rights reserved.
Printed in U.S.A.
Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.

Tab 2
Engine Mounted Accessories

MANUAL RESET CIRCUIT BREAKERS WITH SWITCH FUNCTION


SPECIFICATIONS
Single Pole Thermal Type Breakers
Applications: Typically used in DC power systems in marine applications
(as a main or branch circuit breaker), truck and bus systems, RV systems,
add-on protection for accessories, lift gates, etc. This unit is external ignition protected and weatherproof.
Rating: 25-150A, 48VDC.
Interrupt Rating: Main Breaker Protection Interrupt Rating (5kA @
12VDC). (Consult factory for higher voltage interrupt ratings.)
Operating Temperature Rating: 40F (40C) to 185F (85C).
Storage Temperature Rating: 40F (40C) to 260F (125C).
Materials: Black UL-Rated 94V-0 thermoset plastic body. Cover and lever
are UL-Rated 94V-0 thermoplastic.
Marking: Standard marking includes amp/volt ratings. Custom markings
also available.
Termination: 5/16-18 threaded studs.
Torque Rating: 75in-lbs (8.5Nm) max.
Mounting Torque Rating: Panel or surface-mount options; 50in-lb (5.6
Nm) max.
Ingress Protection Rating: IP66.
Features / Options: A manual reset circuit breaker with On-Off switch
capability.
Compliances: ABYC E-11; CE; SAE J1171 (Ignition Protected).

Bussmann

SERIES 187 MARINE RATED CIRCUIT BREAKER (MRCB)

Consult factory for time characteristic curves.

DIMENSIONS (Dims. are shown for reference only. Consult factory for latest prints)
Base Mount

Panel Mount
57.68
[2.271]
BUSS
MRCB

BUSS R
MRCB

58.15
[2.289]

OFF
TRIP

60.34
[2.375]

25A
48V DC MAX

2.72
[69.0]

OFF

3.44
[87.3]

26.81
[1.056]

25A
48V DC MAX
RE

SE

RE
SE

1.64
[41.6]
1.72
1.06
[43.8]
[27.1]

ON
WEATHERPROOF

IGNITION PROTECTED

16.76
[.660]

ON
WEATHERPROOF
IGNITION PROTECTED

28.84
[1.135]

2.32
[59.0]
53.47
[2.105]

.73
[18.6]

1.46
[37.1]

.16
[3.9]

PART NUMBERING SYSTEM


Series

Rating

Mounting

Hardware

025 25 amps
030 30 amps
035 35 amps
040 40 amps
050 50 amps
060 60 amps
070 70 amps
080 80 amps
100 100 amps
110 110 amps
120 120 amps
135 135 amps
150 150 amps

F Surface mount
P Panel mount

00 No hardware
1 Standard marking; Part Number,
03 Stainless nuts &
Amp Rating
lockwashers - installed
(Consult
factory for special marking options.)
on studs
04 Stainless nuts &
lockwashers - supplied
bulk packed

1 8 7

187 Manual Reset - Switching


Style Circuit Breaker

Marking

Cooper Bussmann Transportation Products Phone: 1-888-867-8194 Website: http://www.coopertp.com

MARINE-RATED CIRCUIT PROTECTION

69.85
[2.750]

2.24
[56.8]

33

MEDIUM DUST AIR CLEANERS

FRG Air Cleaners


Durable, Vibration Resistant
Variety of Sizes in Two Separate Housing Styles
Applications
t)PSJ[POUBMJOTUBMMBUJPO
t .FEJVNBOEIFBWZEVTU
environments
t Style A - From 82 to 795 cfm airow
throughput per air cleaner in body
diameters ranging from 5" to 16"
(127-406mm)
t Style B - From 270 to 1390 cfm
airow throughput per air cleaner in
body diameters ranging from 10" to
18" (254-457mm)

FRG Style A

FRG Style B

The FRG Style A series replaces Donaldsons


obsolete FHG series in size and airow capacity.

The FRG Style B series replaces Donaldsons


obsolete FTG series in size and airow capacity.

Ideal for
t$POTUSVDUJPOFRVJQNFOU
t"HSJDVMUVSBMNBDIJOFSZ
t .JOJOHFRVJQNFOU
t0GGIJHIXBZWFIJDMFT

Air Cleaner Features


t5XPTUBHFmMUFSTZTUFNUIFmSTU
stage removes up to 85% of
incoming dust
- The rst stage in the Style A uses
the angled vanes on the primary
lter
-The rst stage in the Style B has a
tangential air inlet
t *OMFUPOTJEF PVUMFUPOFOE (nPX

t "MSFBEZUBQQFEUPBDDFQUmMUFS
service indicator
t7BDVBUPS7BMWFBVUPNBUJDBMMZ
releases the pre-cleaned dust
t %VSBCMF MPOHMBTUJOHmOJTI
- Style A housing is metal and coated
with a black, corrosion- and chemicalresistant polymer paint (service
cover is accessed with clamp and
bolt)
- Style B is comprised of two
NBUFSJBMTJOKFDUJPONPMEFE IJHI
strength polymer service cover and
a metal body (the service cover is
accessed by latches)
t .PVOUJOHUIFVOJUEJSFDUMZUPUIF
engine is not recommended;
excessive engine vibration can
cause premature air cleaner
structural failure

106sEngine Air Filtration

While it looks like an


axial seal air cleaner on
the outside, this new style
housing is equipped with a RadialSeal
style primary lter and an optional safety
lter. Easy to service, one wing-bolt clamp
to undo to access lter(s).

Filter Features
The RadialSeal lter inside
the air cleaner is also
RVJUFEJGGFSFOUGSPNUIF
conventional lters. Its one piece,
molded urethane endcaps encase
the lter media and liners reducing
components, increasing sealing
reliability
The glued-on gasket found on the metal
end cap of conventional lters is gone
the inside surface of the lters open
end is actually the sealing surface. For
added engine protection during lter
service, consider a model with a safety
lter.

Injection-molded endcap, made of


specially-engineered resins for high
strength and durability, serves as
the service cover. Filter change out
is easier than ever just unsnap
the latches to access the lter!

Accessories
Donaldson intake accessories for your
FRG Air Cleaner can help overcome or
QSFWFOUWBSJPVTQSPCMFNT'PSJOTUBODF
t Mounting bands for FRGs must be
ordered separately
t*GUIFJOTUBMMFEBJSDMFBOFSXJMMCF
exposed to rain, snow or debris,
an inlet cap can prevent moisture
ingestion.
t"lter service indicator measures the
airow restriction across the lter
and indicates when to replace the
lter (see Accessories section of this
catalog)

FRG Mounting Bands


t5XPNPVOUJOHCBOETBSFSFRVJSFEGPSQSPQFS'3(
installation (see service parts listing in this section).
t %VSBCMF DPSSPTJPOSFTJTUBOU HBMWBOJ[FETUFFMDPOTUSVDUJPO
t &OHJOFFSFEBOEUFTUFEUPSFTJTUUIFBEWFSTFFGGFDUTPG
vibration.
t.PVOUJOHCBOEGFFUBSFEFTJHOFEUPDPOUJOVPVTMZFOTVSF
NBYJNVNUPSRVFQSFTTVSF
t%JNFOTJPOBMJOGPSNBUJPOGPSNPVOUJOHCBOETDBOCFGPVOE
in the accessories section.
www.buydonaldson.com

Air in the Side, Out the End (standard ow lters)


Initial Airow Restriction

INLE T

FLO W

MEDIUM DUST AIR CLEANERS

FRG Air Cleaners

Airow CFM @
6"H20 8"H20 10"H20

Air Cleaner
Model

Weight
lbs
kg

STYLE A - BOLT/CLAMP SERVICE COVER

82
93
132
152
198
224
268
295
283
328
315
408
486
560
590

OUTLE T

For the 4045


engines
When Selecting an Air Cleaner . . .

95
107
155
195
228
258
315
344
332
388
350
458
570
657
700

107
120
173
232
255
287
357
385
375
435
418
528
644
742
795

G052685
G052686
G065541
G065551
G080582
G080585
G090245
G090250
G100395
G100398
G120415
G120417
G140523
G140526
G160679

5.5
5.2
7.6
7.1
11.0
10.5
13.1
12.1
30.1
28.6
26.5
28.1
34.9
33.3
41.7

2.5
2.4
3.4
3.2
5.0
4.8
5.9
5.5
13.7
13.0
12.0
12.7
15.8
15.1
18.9

12.0
13.1
17.5
20.6
25.0
30.0
44.0

5.4
5.9
8.0
9.3
11.4
13.6
20.0

STYLE B - LATCH SERVICE COVER

270
300
370
440
520
715
1040

%FUFSNJOFUIFBJSnPXSFRVJSFNFOUTPGZPVSFOHJOF UIFO
nd the corresponding cfm airow in the table at right. The
restriction numbers (shown in inches of water) indicate the
approximate initial restriction of each model air cleaner at
that cfm. If there are two air cleaner models that t your
parameters, choosing the one with the lowest restriction will
provide longest lter service life. When calculating total initial
restriction of the entire air intake system, include the restriction
caused by ducting, elbows, and pre-cleaners.

305
360
430
510
590
805
1230

340
400
490
570
655
945
1390

G100297
G110214
G110206
G130107
G130097
G150092
G180031

FRG Air Cleaner Performance Curves (Restriction & Dust Capacity)






$LUIORZ PPLQ


G052686 - Style A







+
























5HVWULFWLRQ







www.buydonaldson.com




$LUIORZ FIP
$LUIORZ FIP







5(675,&7,21 ,1&+(62)+2 $7 6(59,&(,1',&$7253257




'867&$3$&,7<3(5,62 *
*5$062)&2$56('867

5(675,&7,21 ,1&+(62)+2 $7 6(59,&(,1',&$7253257

G052685 - Style A


















$LUIORZ PPLQ

































5HVWULFWLRQ








$LUIORZ FIP
$LUIORZ FIP

Engine Air Filtrations107

continued - FRG Air Cleaner Performance Curves (Restriction & Dust Capacity)






















5HVWULFWLRQ






G080582 - Style A











$LUIORZ FIP
$LUIORZ FIP

$LUIORZ PPLQ





































G090245 - Style A



+







$LUIORZ FIP
$LUIORZ FIP

$LUIORZ PPLQ



































5HVWULFWLRQ










108sEngine Air Filtration



$LUIORZ FIP
$LUIORZ
FIP























5HVWULFWLRQ

















$LUIORZ FIP
$LUIORZ
FIP

$LUIORZ PPLQ




















+
















5HVWULFWLRQ








G090250 - Style A





















5HVWULFWLRQ


$LUIORZ PPLQ








+





G080585 - Style A












5(675,&7,21 ,1&+(62)+2 $76


6(59,&(,1',&$7253257









5(675,&7,21 ,1&+(62)+2 $7 6(59,&(,1',&$7253257




+




'867&$3$&,7<3(5,62 *
*5$062)&2$56('867





5(675,&7,21 ,1&+(62)+2 $76(59,&(,1',&$7253257















$LUIORZ FIP
$LUIORZ
FIP

$LUIORZ PPLQ
























+




















5HVWULFWLRQ








'867&$3$&,7<3(5,62 *
*5$062)&2$56('867



5(675,&7,21 ,1&+(62)+2 $7 6(59,&(,1',&$7253257



'867&$3$&,7<3(5,62 *
*5$062)&2$56('867



'867&$3$&,7<3(5,62 *
*5$062)&2$56('867




G065551 - Style A
$LUIORZ PPLQ




'867&$3$&,7<3(5,62 *
*5$062)&2$56('867

5(675,&7,21 ,1&+(62)+2 $7


76(59,&(,1',&$7253257

G065541 - Style A

5(675,&7,21 ,1&+(62)+2 $76


6(59,&(,1',&$7253257

MEDIUM DUST AIR CLEANERS

FRG Air Cleaners








$LUIORZ FIP
$LUIORZ FIP











www.buydonaldson.com

ECG Konepac Air Cleaner

LIGHT DUST

When specing an
Air Cleaner . . .

Initial Airflow Restriction

Service parts for this axial style air cleaner


may not be available due to newer filtration
technology and housing designs. Donaldson
now recommends one of two other families
- the EPG or PSD.

CFM @ "H20
6"
8"
10"

Air Cleaner
Model

Airflow Pattern G
Air in the side, out the end

Models with bolted service access

775
1100
1200

880
1300
1400

1000
1425
1550

G092001
G112001
G132000

Models with latched service access

800
1200
1200
1200
1200

Deere 6090

Scania 13L

925
1400
1400
1400
1400

1040
1600
1600
1600
1600

G092401
G112404
G1124171
G112501
G112504

1 - No inlet tube, perforated inlet holes on side

ECG Konepac Specification Illustrations


Bolted Service Access

Latched Service Access

ECG Konepac Specifications



Air
Cleaner
Models

Body
Diameter
(A)
in
mm

Inlet
Diameter
(B)
in
mm

Outlet
Diameter
(C)
in
mm

Overall

Length
(D)
(E)
in
mm in
mm

Inlet
Service
Service
Length
Clearance Indicator
(F)
(G)
Tap
in
mm in
mm in
mm

Weight
lbs kg

6.00 152
7.00 178
7.00 178

6.00 152
7.00 178
7.00 178

28.63 727
28.62 727
24.59 625

7.85 199
8.95 227
9.54 242

1.18 30
1.58 40
2.38 60

18.63 473
20.62 524
18.25 464

27.62 702
27.00 686
27.62 702

No
No
No

30
38
36

14
17
16

6.00
7.00
7.00
7.00
7.00

28.70
22.70
28.70
28.30
22.30

7.86
8.97
--
8.97
8.97

1.18
2.00
2.00
2.00
2.00

21.75
12.32
15.11
21.22
12.32

27.62
22.00
28.00
28.00
22.00

No
Yes
Yes
Yes
Yes

30
33
30
23
20

14
15
14
10
9

Bolted Service Access

G092001
G112001
G132000

9.00 229
11.00 279
13.00 330

Latched Service Access

G092401
G112404
G1124171
G112501
G112504

9.00
11.00
11.00
11.00
11.00

229
279
279
279
279

6.00
7.00
--
7.00
7.00

152
178
--
178
178

152
178
178
178
178

729
577
729
719
566

200
228
--
228
228

30
51
51
51
51

553
313
384
539
313

702
559
711
711
559

1 - This model has no inlet tube; inlet consists of


rectangular perforated holes on side of housing.

Side view of G112417

44

Engine Air Cleaners, Accessories & Service Parts

www.donaldson.com/aircleaners

ECG Konepac Air Cleaner


Plastic Nut

Retaining Ring

Cover Gasket

Filter with no Cover

ss

Bolt Service Acce

LIGHT DUST

Housing Body

ss

Latch Service Acce

Filter with no Cove

Access
Covers

Mounting Band

2 required for proper


installation

Spring Latch

Access
Covers

d Cover
Filter with Attache

ECG Konepac Service Parts


G092001

Bolted Cover

filter, primary, no cover, treated..... P148044......1,3


mounting band.................................. P004073......2
nuts, plastic....................................... P119325
retaining ring.................................... P129469

G092401

Latched Cover

filter, primary, no cover................... P150692......3


filter, primary, no cover, treated..... P148044 .....1
filter, primary, attached cover........ P150693 .....6
latch replacement kit...................... X009291

G112001

Bolted Cover

filter, primary, no cover, treated..... P148043 .....1,3


gasket, cover.................................... P155211
mounting band.................................. P004079......2
nuts, plastic....................................... P119325
retaining ring.................................... P129469

G112404

Latched Cover

cover.................................................. P150862
filter, primary, attached cover
- ES & HE..................................... EAF5053
filter, primary, attached cover........ P153551
filter, primary, no cover, treated..... P154575 ...1,3,5
gasket, cover.................................... P536493
latch replacement kit ..................... X009291

G112417

Latched Cover

cover.................................................. P150862
filter, primary, no cover................... P150694......3,5
filter, primary, no cover-ES & HE... EAF5029......5
filter, primary, attached cover........ P150695
filter, primary, attached cover
- ES & HE..................................... EAF5047
gasket, cover.................................... P536493
latch replacement kit ..................... X009291

www.donaldson.com/aircleaners

G112501

Latched Cover

filter, primary..................................... P150694......5


filter, primary, no cover-ES & HE... EAF5029......5
filter, primary..................................... P150695......3,6
filter, primary, attached cover
- ES & HE..................................... EAF5047
filter, primary, treated...................... P148043......1
gasket, cover.................................... P536493
latch replacement kit ..................... X009291

G112504

Latched Cover

cover.................................................. P150862
filter, primary, attached cover
- ES & HE...................................... EAF5053
filter, primary, attached cover........ P153551......6
filter, primary, attached black
cover............................................. P537791......3,6
filter, primary, no cover, treated..... P154575......1,5
gasket, cover.................................... P536493
latch replacement kit ..................... X009291

G132000

Bolted Cover

filter, primary, no cover................... P142100......3


filter, primary, no cover-ES & HE... EAF5027
gasket, cover.................................... P120604
mounting band.................................. P013722......2
nuts, plastic....................................... P119325
retaining ring.................................... P129469

Latch
Replacement Kit
X009291

ECG style air


cleaners have
three cover latches
that need to
perform correctly
to ensure the
filter gasket is
sealing properly.
These latches
should be checked
for tightness and wear. To check for
tightness, close all three latches, then
open and close them one at a time.There
should be good tension and should snap
tightly when closed. If any latches seem
loose or rattle, they should be replaced.

NOTES:

1 = Filter is treated with chemical for carbon


resistance and is not cleanable
2 = Two required for proper installation
3 = Shipped with air cleaner initially
5 = Also requires access cover P150862
6 = Access cover is attached to filter
E S = Extended Service
HE = High Efficiency

Engine Air Cleaners, Accessories & Service Parts

45

Filter Indicators & Gauges


Hand tighten lter service indicators (30-40 lbs./inch maximum).

The lnformer for Graduated, The Mini-lnformer


Continuous Readings
for Light & Medium Trucks

The lnformer
Restriction
Limit

Gauge
Only

Kit

(2/K0A
(2/K0A
(2/K0A

8 8
8 8
8 8

4HE-INI )NFORMER
RESTRICTIONGAUGE
is designed to
MOUNTINTHEPLASTIC
AIRCLEANERSOF
PASSENGERCARS LIGHT
TRUCKS ANDSPORT
UTILITYVEHICLES
)TSANACCURATE
DURABLE EASY TO READhGONOGOv
STYLEINDICATOR SMALLERTHANTHE
ORIGINAL)NFORMER

3MALLENOUGHTOlTJUSTABOUT
ANYWHEREONLYHIGH THE
$ONALDSON3ERVI3IGNALSHOWSA
HIGHLYVISIBLE
BRIGHTREDmAG
INTHEFULL VIEW
WINDOWWHEN
restriction limit
ISREACHED
2ESETSMANUALLY
VIATOPBUTTON
AFTERAIRCLEANER
service.

4HROUGHTHECLEARWINDOW AGREEN
mAGSHOWSWHENAIRlLTERRESTRICTION
ISBELOWTHESERVICEPOINT7HEN
THERESTRICTIONREACHESITSLIMITS AN
ORANGEmAGIMPRINTEDWITHhCHANGE
lLTERvPOPSUP

+ITINCLUDES
.04THREADEDBRASSlTTINGFOR
MOUNTINGONTHEAIRCLEANER&OR
REMOTEMOUNT ALSOORDER0
mANGE(OSESNOTINCLUDED

4HE-INI )NFORMERMOUNTSINTHE
AIRCLEANERDUCTINGINARUBBER
grommet.

The ServiSignal Mini Indicator

(gauge & tting)

The Mini-lnformer
Restriction
Limit

Gauge &
Grommet

Gauge
Only

(2/K0A

8

8

Restriction
Limit

Gauge
Only

Kit

(2/K0A
(2/K0A
(2/K0A
(2/K0A

8
8
8
8

8
8
8
8

(gauge & tting)

Grommet

WWWDONALDSON lLTERSCOM

Engine Air Cleaners, Accessories & Service Partss105

INTAKE ACCESSORIES

4HE)NFORMER WHEN
MOUNTEDONTHE
AIRCLEANERORTHE
DASHBOARD PROVIDES
ACONTINUOUS
READINGWHETHERTHE
ENGINEISRUNNING
ORISSHUTDOWN
2ESETBUTTONISON
TOP+ITINCLUDES
FULLINSTALLATION
INSTRUCTIONSAND
A0SAFETYlLTERlTTING&OR
REMOTEMOUNTING ORDERA0
mANGEANDA0ELBOW

ServiSignal Mini Indicator

RTDs 3
RG Style

High Temperature

Features

General Specifications

High vibration, high temperature (650 C).


Element encased with high density Magnesium

Available in .125 to .250 O.D.


FEP or Fiberglass leadwire insulation available.

Oxide (MgO).

R
Element DIN
Wire
CLASS A
CLASS B

Special requirments
If none, enter 0
if required consult factory

.00385//
//C
wound
Thin film
A
F
B
M

Sheath O.D.
5 - .125

Cold end termination


6 - .188

7 - .250

C - Three Pin Plug


E - Three Pin Jack
W - Plug and Jack
S - Standard 1 1/2 Leads

Tube & Wire M.I. Cable


Max 260 C Max 650 C

Sheath material
316 SS

B
Leadwire length E

Connection

2 Wire

3 Wire

4 Wire

2
D

3
L*

4
F *

100 Ohm Single


100 Ohm Duplex

Enter E Length in
Whole Feet 01 to 99

Leadwire construction
Standard Overbraid
Fiberglass
F
B
FEP
T
E

Sheath length L
Specify Whole Inches

Flex
1
3

*Not available in .125 sheath O.D.

B ase
price

Sheath
Element Circuit Circuit Sheath
Element
diameter
price
w ires
price diameter

Sheath
price
(per inch)

Leadw ire
construction

Leadw ire
price
(per foot)

Leadw ire
duplex
price
(per foot)

Cold end
termination

Cold end
termination
price

Cold end
termination
duplex price

$94.64

5
(650C)

$5.20

2,3

$.11

$.63

$.95

$14.56

$21.84

$89.44

6
(650C)

$2.08

$1.04

6,7

$.31

$.73

$1.10

$18.72

$28.08

$91.52

7
(650C)

$8.32

$.63

$.95

$24.96

$37.44

$8.32

$.73

$1.10

$9.36

$2.18

$3.27

$2.39

$3.58

Eustis Co.

Temperature Measurement, Heating & Control

Page - 39

PRESSURE
Current Output
Pressure Transmitters

100

SERIES

HIGH PERFORMANCE CURRENT OUTPUT PRESSURE TRANSMITTERS


NOSHOK 100 Series Current Output Pressure Transmitters are designed
to provide a previously unequalled level of performance, utilizing diffused
semiconductor and sputtered thin film strain gage technology. 100 Series
transmitters are highly repeatable, shock resistant and are extremely
stable over long periods of time. CE compliance which includes
substantial levels of RFI, EMI and ESD noise protection combined with
reverse polarity and over-voltage protection hardens the product so it
performs well in the most demanding applications.
Advanced manufacturing techniques combined with technologically
advanced standard features allow NOSHOK to offer a level of
performance previously found only on transducers costing hundreds
of dollars more. Final calibration tests performed on all NOSHOK
transmitters prior to shipment ensures 100% out of the box reliability

SPECIFICATIONS
Output signal
Pressure ranges

FEATURES

APPLICATIONS

Accuracy up to 0.25 % Full


Scale (Best Fit Straight Line)

Hydraulic and pneumatic


systems

Welded stainless steel


pressure chamber

Injection molding machines

Advanced diffused semiconductor and sputtered thin film


sensor for maximum stability

HVAC systems

Proof pressure

Compact size
High alternating load
resistance
High overpressure protection
CE compliant to suppress RFI,
EMI and ESD noise
interference
Compatible with NOSHOK
Smart System Indicators

Railroad engine controls


Stamping and forming
presses
Refrigeration controls
Industrial machinery and
machine tools
Pumps and compressors

Burst pressure

Accuracy
Repeatability
Hysteresis
Stability
Response time
Power supply
Load limitations
Wetted materials

Housing material
Adjustment
Pressure cycle limit
Durability
Temperature ranges

Environmental rating
Electromagnetic rating
Electrical protection
Shock
Vibration
Weight

4 mA to 20 mA, 2-wire
Standard gauge ranges from vacuum to 15000 psi; Standard Absolute
ranges from 15 psia to 300 psia
3 times Full Scale for ranges 0 psi to 5 psi through 0 psi to 200 psi
1.75 times Full Scale for ranges 0 psi to 300 psi through 0 psi to 10000 psi
1.5 times Full Scale for 0 to 15000 psi range
3.8 times Full Scale for ranges 0 psi to 5 psi through 0 psi to 200 psi
4 times Full Scale for ranges 0 psi to 300 psi through 0 psi to 10000 psi
3 times Full Scale for 0 to 15000 psi range
0.5 % Full Scale (Best Fit Straight Line); 0.25 % optional
(Includes the combined effects of linearity, hysteresis and repeatability)
 0.05 % Full Scale
 0.1 % Full Scale
 0.2 % Full Scale for 1 year, non-accumulating
 1 ms (between 10 % and 90 % Full Scale)
10 Vdc to 30 Vdc, unregulated
Load in resistance must be  (Vpower supply 10)/.020 Amp
316 stainless steel for vacuum through 300 psi; 17-4PH
stainless steel sensing diaphragm and 316 stainless steel process
connection for higher ranges
316 stainless steel
10 % Full Scale for zero and span
150 Hz
> 100,000,000 Full Scale cycles
Compensated 32 F to 176 F (0 C to 80 C)
Effect 0.017 % Full Scale/F for zero and span
Ambient -22 F to 185 F (-30 C to 85 C)
Media -22 F to 212 F (-30 C to 100 C)
Storage -40 F to 212 F (-40 C to 100 C)
IP65, NEMA 4X according to EN 60529/IEC 529
CE compliant to EMC norm EN 61326:1997/A1:1998
RFI, EMI and ESD protection
Reverse polarity, over-voltage and short circuit protection
1000 gs per IEC 770
30 gs per IEC 770
Approximately 3.5 oz.

SERIES

100

ORDERING INFORMATION
DIMENSIONS
WIRING DIAGRAMS
ELECTRICAL CONNECTIONS

ORDERING INFORMATION
SERIES 100
PRESSURE
RANGES

-30 inHg to 0 psig


-30 inHg to 15 psig
-30 inHg to 30 psig
-30 inHg to 60 psig
-30 inHg to 100 psig
-30 inHg to 150 psig
-30 inHg to 200 psig
-30 inHg to 300 psig

30V
30/15
30/30
30/60
30/100
30/150
30/200
30/300

0 psig to 5 psig
0 psig to 10 psig
0 psig to 15 psig
0 psig to 30 psig
0 psig to 60 psig
0 psig to 100 psig
0 psig to 150 psig

ACCURACY

1 0.5 % Full Scale (Best Fit Straight Line)

OUTPUT

1 4 mA to 20 mA

PROCESS CONNECTION

1 1/8 NPT male

psig = gauge pressure

OPTIONS

0 psig to 200 psig


0 psig to 300 psig
0 psig to 500 psig
0 psig to 600 psig
0 psig to 750 psig
0 psig to 1000 psig
0 psig to 1500 psig

200
300
500
600
750
1000
1500

psia = absolute pressure

0 psig to 2000 psig


0 psig to 3000 psig
0 psig to 5000 psig
0 psig to 6000 psig
0 psig to 7500 psig
0 psig to 10000 psig
0 psig to 15000 psig

2000
3000
5000
6000
7500
10000
15000

0 psia to 15 psia
0 psia to 30 psia
0 psia to 60 psia
0 psia to 100 psia
0 psia to 150 psia
0 psia to 200 psia
0 psia to 300 psia

15A
30A
60A
100A
150A
200A
300A

Other ranges available on special request ranges

2 0.25 % Full Scale (Best Fit Straight Line)

2 1/4 NPT male

1 36 cable (connected to option 7)


7 Mini-Hirschmann (DIN 43650C with mate)

ELECTRICAL CONNECTION

5
10
15
30
60
100
150

3 7/16 -20 UNF #4 SAE J-514 male

2 4-pin bendix

3
25

6 1/2 NPT conduit ( with 36 cable)

6-pin bendix
M12 x 1 4-pin

ORF Threaded orifice (.3mm)

Please consult your local NOSHOK Distributor or NOSHOK, Inc. for availability and delivery information.

EXAMPLE

100

Series
Pressure Range
Accuracy
Output Signal
Process Connection
Electrical Connection
Option

500

ORF

100
0 psig to 500 psig
0.50 % Full Scale
4 mA to 20 mA
1/4 NPT male
Mini-Hirschmann
Orifice

Outline Dimensions
Red
Power
Supply

1/2 NPT Conduit


with 36 jacketed
cable

4 and 6 pin Bendix


(mate supplied
separately or
customer supplied)

M12 x 1
(mate supplied
separately or
customer supplied)

4.17
(106mm)

1.06
(27mm)

3.15
(80mm)

4-pin or 6-pin

MiniHirschmann

+ Supply

pin A

+ Output

pin B

Wire

Bendix

Cable

M12 x 1

pin 1

Red

pin 1

pin 2

Black

pin 3

.69
(17mm)

.59
(15mm)

Black
Output

Te m p e r a t u r e

Platinum Resistance Temperature Transmitters

800

SERIES

HIGH PERFORMANCE PLATINUM RESISTANCE


TEMPERATURE TRANSMITTERS
The NOSHOK Series 800 temperature transmitter provides an unbeatable
level of performance at an economical price. Using the proven reliability and
stability of 100 ohm platinum resistance technology, this transmitter offers
a broad array of choices for the OEM and user alike.
A rigorous test and inspection process is performed on all NOSHOK
temperature transmitters prior to shipment to further ensure 100%
out of the box reliability.

SPECIFICATIONS

FEATURES

 Proven platinum 100 ohm


sensor
 Maximum reliability

 Wide variety of temperature


ranges and connections
 CE compliant

 Quick response time

APPLICATIONS

 Water systems
 Storage tanks

 Industrial machinery and


machine tools
 HVAC systems

Output signals

4 mA to 20 mA 2-wire, 0 Vdc to 5 Vdc 3-wire


0 Vdc to 10 Vdc 3-wire, 1 Vdc to 5 Vdc 3-wire

Temperature ranges

Standard ranges from -40 F to 1000 F

Accuracy
Measuring Element
Output

Class B per EN 60751 (IEC 751)


[0.30 +0.005*ltl] C
0.5% Full Scale

Sensor protection

Burnout protected from 3.3 mA to 23 mA

Power supply

10 Vdc to 30 Vdc for 4 mA to 20 mA, 0 Vdc to 5 Vdc, unregulated,


1 Vdc to 5 Vdc 12 Vdc to 30 Vdc for 0 Vdc to 10 Vdc, unregulated

Load limitations

(VPower -10)/0.020 Amp for 4 mA to 20 mA output


5,000 for 1 Vdc to 5 Vdc output
10,000 for 0 Vdc to 10 Vdc output
4,500 for 0.5 Vdc to 4.5 Vdc output

Wetted materials

316 stainless steel

Housing material

316 stainless steel

Ambient Temperature

-40 F to 185 F (-40 C to 85 C)

Storage Temperature

-40 F to 185 F (-40 C to 85 C)

Environmental rating

IP65 according to EN 60529/IEC 529

Electromagnetic rating

CE compliant to EMC norm EN 61326:1997/A1:1998


RFI, EMI and ESD protection

Electrical protection

Reverse polarity, over-voltage and short circuit protection

Weight

Approximately 4 oz.

 Refrigeration systems

Also available with our 1800 Series


Attachable Loop Indicator.
See page 42 for more information.
Optional USB programmable output

34

800

SERIES

ORDERING INFORMATION
DIMENSIONS
WIRING DIAGRAMS
ELECTRICAL CONNECTIONS

ORDERING INFORMATION
SERIES 800
TEMPERATURE
RANGES

-40/120F
25/125F
0/140F

ACCURACY

-40/120
0/200F
25/125
20/240F
0/140
0/250F
Other ranges available on special request

0/200
20/240
0/250

0/300F
50/300F
50/500F

0/300
50/300
50/500

0/750F
0/1000F

0/750
0/1000

1 Class B + (0.5 % BFSL)

OUTPUT SIGNALS

1 4 mA to 20 mA, 2-wire 2 0 Vdc to 5 Vdc, 3-wire 3 1 Vdc to 5 Vdc, 3-wire 5 0 Vdc to 10 Vdc, 3-wire 34 4 mA to 20 mA, 2-wire, USB programmable
2 1/4 NPT male
8 1/2 NPT male
48 1/2 NPT male w/Adjustable Compression Fitting

PROCESS CONNECTIONS
ELECTRICAL CONNECTIONS
STEM LENGTH

1 36 cable (connected to option 8)


025 2.5 inch
040 4 inch

STEM DIAMETER

8 Hirschmann (DIN EN 175301-803 Form A)


060 6 inch
090 9 inch

3 Tapered from 6mm - 3mm tip

14 Hirschmann connection w/ISO 4400 1/2 NPT conduit

120 12 inch

6 6 mm

8 8 mm

Please consult your local NOSHOK Distributor or NOSHOK, Inc. for availability and delivery information.
EXAMPLE

800 50/300 1 1 8

8 040 6

Series . . . . . . . . . . . . . . . . . . . . . . . . .800
Temperature Range . . . . .50 F to 300 F
Accuracy . . . . . . . . . . . . . . .0.25% BFSL
Output Signal . . . . . . . . . .4 mA to 20 mA
Process Connection . . . . .1/2 NPT male
Electrical Connection . . . . . . .Hirschmann
Stem length . . . . . . . . . . . . . . . . . . .4 inch
Stem diameter . . . . . . . . . . . . . . . . .6 mm
1.10
(28mm)

Outline Dimensions

1.65
(42mm)
2.05
extension

1.06 sq
(27mm)

1.85
(47mm)
1.06 sq
(27mm)

2.16
(55mm)

Stem
length

1.06 HEX
(27mm)
Adjustable
stem length

Hirschmann with
1/2 NPT female
ISO 4400 conduit

Stem
length

1/2 NPT

0.75
(19mm)

* For temperature ranges above


400F a 2.05 (50mm) extention
must be added to this dimension

Adjustable
Compression Fitting

2-WIRE WIRING

3-WIRE WIRING

Wiring

Hirschmann

Cable

Wiring

Hirschmann

Cable

+ Supply

Red

+ Supply

Red

+ Output

Black

Common

Black

+ Output

White

Stem Diameter
(6mm standard)

Hirschmann

1.06
(27mm)

Optional thermowells available in 316 SS, 304 SS and Brass.

35

NAPA AUTO PARTS

http://www.napaonline.com/Catalog/CatalogItemDetail.aspx?R=FIL401...

Fuel Filter Base

Add New Vehicle

Purchase Item
Part Number: FIL 4019
Product Line: NAPA Gold Filters

Enter zip and select a store for


pricing

Attributes:
Fits Part #(s) : 4069, 4070, 4083, 4084, 4071, 4072, 4073, 4074,
4082, 4088

Not in a rush?
BUY IT ONLINE

and ship it to me.

Contents : Base

Warranty:
NAPA Filters are Covered by a Comprehensive Limited Product
Warranty. NAPA Filters May Pay the Reasonable Cost for Parts &
Labor to Repair any System Damaged by NAPA Filters Due to a
Defect in Design or Material.
Warranty PDF

Material Safety Data Sheet:


C5-A Copper Based Anti-Seize

Have questions about this item?


Call your local NAPA AUTO PARTS Store at 800-LET-NAPA
(800-538-6272)

Buyer's Guide:
For a list of specific cars that this part is compatible with, please
visit our Buyer's Guide.

Reserve & Pick Up FAQs


What is Reserve & Pick Up?
Why Reserve Your Items Online?
How Reserve & Pick Up Works
Out-of-Stock or Unavailable Items

Buy Online FAQs


Delivery Time
Shipping and Handling Charges
Where We Ship
Tracking Your Order
Hazardous Materials

Close

1 of 1

2/16/2013 8:20 AM

NAPA AUTO PARTS

http://www.napaonline.com/Catalog/CatalogItemDetail.aspx?R=FIL406...

Cooling System Filter, Spin-on Coolant Filter

Add New Vehicle

Purchase Item
Part Number: FIL 4069
Product Line: NAPA Gold Filters

Enter zip and select a store for


pricing

Attributes:
Cooling System Filter Style : Spin-On Coolant Filter
Filter Style : Spin-on Coolant Filter

Not in a rush?
BUY IT ONLINE

and ship it to me.

Gasket I.D. (Inches) : 2.462"


Gasket O.D. (Inches) : 2.834"

Reserve & Pick Up FAQs

Gasket Thickness (Inches) : .2"


Height (Inches) : 4.317"
O.D. (Inches) : 3.694"
Thread Size (Inches) : 11/16-16
Gasket I.D. (mm) : 63 mm
Gasket O.D.(mm) : 72 mm
Gasket Thickness (mm) : 5 mm
Height (mm) : 110 mm
O.D. (mm) : 94 mm

Warranty:
NAPA Filters are Covered by a Comprehensive Limited Product
Warranty. NAPA Filters May Pay the Reasonable Cost for Parts &
Labor to Repair any System Damaged by NAPA Filters Due to a
Defect in Design or Material.
Warranty PDF

Have questions about this item?


Call your local NAPA AUTO PARTS Store at 800-LET-NAPA
(800-538-6272)

What is Reserve & Pick Up?


Why Reserve Your Items Online?
How Reserve & Pick Up Works
Out-of-Stock or Unavailable Items

Buy Online FAQs


Delivery Time
Shipping and Handling Charges
Where We Ship
Tracking Your Order
Hazardous Materials

Buyer's Guide:
For a list of specific cars that this part is compatible with, please
visit our Buyer's Guide.

Close

1 of 1

2/16/2013 8:21 AM

Tab 3
Controls and Instrumentation

Single-Door Type 4 Enclosures

Application

Finish

For use in housing electrical and electronic


controls, instruments, components, and
associated wiring, these enclosures incorporate
hinged doors that provide convenient access.
Designed for indoor or outdoor use in
protecting components from dust, dirt, oil, and
hose-directed water.

ANSI 61 gray polyester powder paint inside


and out over phosphatized surfaces. Optional
panels are white.

You can customize this product to your unique


requirements by specifying from these options:

Industry Standards

Construction
16 or 14 gauge steel (see table)
Seams continuously welded and ground
smooth, no holes or knockouts
External wall-mounting brackets
Rolled flanges exclude liquids and
contaminants
Stainless steel door clamps on three sides of
door for watertight seal
Removable heavy gauge stainless steel
continuous hinge pin
Hasp and staple provided for padlocking
Data pocket is high-impact thermoplastic
Oil-resistant door gasket attached with oil
resistant adhesive
Collar studs provided for mounting
optional panels
Bonding provision on door

4.44

Modification Services Program

UL 508A, 508, File No. E61997:Type 4,Type 12,


and Type 13
NEMA/EEMAC Type 3,Type 4,Type 12, and
Type 13
JIC standard EGP-1-1967 (14 gauge only)
CSA, File No. LR42186,Type 4 and Type 12
IEC 60529, IP66

Accessories
See Chapter 12, General Accessories.

Clamp Kit
Corrosion Inhibitors
Door Stop Kit
Drip Shield Kit
Electrical Interlocks
Enclosure Stabilizer
Fast Operating Clamp Assembly
Floor Stand Kit
Lighting Kit
Lock Kit
Panel Support Kit
Panels (see table)
Rack Mounting Angle Kit
Swing-Out Panel Kit
Terminal Block Kit Assembly
Touch-Up Paint (ATPPY61)
Window Kit
Wiring Duct

Data subject to change without notice

763 422 2211

Enclosure height, width, depth


Over 100 standard finish colors and textures
Holes and cutouts in body, doors, subpanels
Tapped holes, fasteners in enclosure or
subpanel
Mounting
Doors
Subpanels
Structural changes
Environmental control (louvers, fans, filters)
Windows
Standard accessories

For details, see Modification Services at


www.hoffmanonline.com.
To order, contact your local Hoffman
sales representative.
NOTE: For information about modifications
outside the scope of the Modification Services
program, contact your Hoffman sales
representative.

FAX 763 422 2600

2003 Hoffman Enclosures Inc.

Bulletin

A4

Enclosure
Catalog Number

Body
Gauge

Enclosure Size
AxBxC

A16H12ALP

16

16.00 x 12.00 x 6.00


(406 x 305 x 152)

A16H16ALP

16

A16H20ALP

* Panel
Catalog
Number

Number
of Clamps

Data
Pocket

A16P12

13.00 x 9.00
(330 x 229)

1.25
(32)

Small

16.00 x 16.00 x 6.00


(406 x 406 x 152)

A16P16

13.00 x 13.00
(330 x 330)

3.00
(76)

Small

16

16.00 x 20.00 x 6.00


(406 x 508 x 152)

A20P16

17.00 x 13.00
(432 x 330)

3.00
(76)

Small

A20H16ALP

16

20.00 x 16.00 x 6.00


(508 x 406 x 152)

A20P16

17.00 x 13.00
(432 x 330)

3.00
(76)

Small

A20H20ALP

16

20.00 x 20.00 x 6.00


(508 x 508 x 152)

A20P20

17.00 x 17.00
(432 x 432)

3.00
(76)

Small

A24H12ALP

16

24.00 x 12.00 x 6.00


(610 x 305 x 152)

A12P24

9.00 x 21.00
(229 x 533)

1.25
(32)

Small

A24H16ALP

16

24.00 x 16.00 x 6.00


(610 x 406 x 152)

A24P16

21.00 x 13.00
(533 x 330)

3.00
(76)

Small

A24H20ALP

16

24.00 x 20.00 x 6.00


(610 x 508 x 152)

A24P20

21.00 x 17.00
(533 x 432)

3.00
(76)

Small

A24H24ALP

16

24.00 x 24.00 x 6.00


(610 x 610 x 152)

A24P24

21.00 x 21.00
(533 x 533)

3.00
(76)

Small

A30H20ALP

14

30.00 x 20.00 x 6.00


(762 x 508 x 152)

A30P20

27.00 x 17.00
(686 x 432)

3.00
(76)

Small

A30H24ALP

14

30.00 x 24.00 x 6.00


(762 x 610 x 152)

A30P24

27.00 x 21.00
(686 x 533)

3.00
(76)

Large

A36H24ALP

14

36.00 x 24.00 x 6.00


(914 x 610 x 152)

A36P24

33.00 x 21.00
(838 x 533)

3.00
(76)

Large

A16H12BLP

16

16.00 x 12.00 x 8.00


(406 x 305 x 203)

A16P12

13.00 x 9.00
(330 x 229)

1.25
(32)

Small

A20H16BLP

16

20.00 x 16.00 x 8.00


(508 x 406 x 203)

A20P16

17.00 x 13.00
(432 x 330)

3.00
(76)

Small

A20H20BLP

16

20.00 x 20.00 x 8.00


(508 x 508 x 203)

A20P20

17.00 x 17.00
(432 x 432)

3.00
(76)

Small

A20H24BLP

16

20.00 x 24.00 x 8.00


(508 x 610 x 203)

A24P20

21.00 x 17.00
(533 x 432)

3.00
(76)

Small

A24H20BLP

16

24.00 x 20.00 x 8.00


(610 x 508 x 203)

A24P20

21.00 x 17.00
(533 x 432)

3.00
(76)

Small

A24H24BLP

16

24.00 x 24.00 x 8.00


(610 x 610 x 203)

A24P24

21.00 x 21.00
(533 x 533)

3.00
(76)

Small

A24H30BLP

14

24.00 x 30.00 x 8.00


(610 x 762 x 203)

A30P24

27.00 x 21.00
(686 x 533)

3.00
(76)

Small

A30H20BLP

14

30.00 x 20.00 x 8.00


(762 x 508 x 203)

A30P20

27.00 x 17.00
(686 x 432)

3.00
(76)

Small

A30H24BLP

14

30.00 x 24.00 x 8.00


(762 x 610 x 203)

A30P24

27.00 x 21.00
(686 x 533)

3.00

Large

4
Wall-Mount

Panel Size
DxE

Industrial Enclosures

Standard Sizes Single-Door Type 4 Enclosures

(76)

Continued on next page

Data subject to change without notice

763 422 2211

FAX 763 422 2600

2003 Hoffman Enclosures Inc.

4.45

Bulletin

A4
Rev. A October 2004

Industrial Enclosures

4
>31.00
(787)
Any

Any

>31.00
(787)

NOTE: Maximum spacing between door clamps is 15.00 in. (382mm).

Data subject to change without notice

763 422 2211

FAX 763 422 2600

2003 Hoffman Enclosures Inc.

4.47

Wall-Mount

Number of Body Studs


Enclosure Size
Qty of
A
B
Studs

Terminal Blocks

BNH/BN Terminal Blocks


BNH/BN Series
Key features of the BNH/BN series include:
Touch-down terminals with spring-loaded captive screws
available
Jumpers available up to 30A model
Fuse block with or without blown-fuse indicator in neon or
LED
Mount on 35mm standard DIN rail

File No. R9551701


J9551516 (power blocks)
R9650688 (dual-deck blocks)

CSA Certified
File No. LR64803

UL Recognized
File No. E78117

Specifications
Part Numbers

BNH10W

BNH15MW

BNH15LW

BNH30W

Appearance

Width

0.275" (7mm)

0.315" (8mm)

0.413" (10.5mm)

0.472" (12mm)

Approvals

UL, CSA, TUV

UL, CSA, TUV

UL, CSA, TUV

UL, CSA, TUV

No. of Poles

Specifications

Wire Sizes
Current
Terminals

1
2

1
2

1
2

22 to 16 AWG (2mm )

22 to 14 AWG (2mm )

22 to 14 AWG (2mm )

18 to 10 AWG (5.5mm2)
600V / 30A

600V / 10A

600V / 10A

600V / 15A

Size

M3

M3

M3.5

M4

Type

Touch-down

Touch-down

Touch-down

Touch-down
35mm DIN rail

Mounting

35mm DIN rail

35mm DIN rail

35mm DIN rail

(N-m)

0.6 - 1.0

0.6 - 1.0

1.0 - 1.3

1.4 - 2.0

(in-lbs.)

5.3 - 8.9

5.3 - 8.9

8.9 - 11.5

12.4 - 17.8

End Plate

BNE15W

BNE15W

BNE15W

BNE30W

DIN Rail Stop

BNL-5

BNL-5

BNL-5

BNL-5

Dust Cover

BNC230

BNC230

BNC230

BNC230

Terminal Torque

PVC

BNM7

BNM7

BNM7

BNM7

Fiberglass

BNM9

BNM9

BNM9

BNM9

End clip

BNM3

BNM3

BNM3

BNM3

Ring Terminal Jumpers

BNJ16

BNJ26W

BNJ46

BNJ56

Fork Terminal Jumpers

BNJ16F

BNJ26FW

BNJ46F

BNJ56F

Terminal Blocks

Marking Strip

1. BNDN1000 aluminum DIN rails are available in 1 meter lengths.


2. Marking strips are available in 1 meter lengths.
3. Jumpers are available in groups of six.
4. Remove the H in the terminal block part number for standard screw type.

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC

P-3

Terminal Blocks

BNH/BN Terminal Blocks


Specifications cont

Part Numbers

BNH50W

BN75W

BN150W

BNDH15W

Appearance

Width

0.787" (20mm)

0.787" (20mm)

1.024" (26mm)

0.315" (8mm)

Approvals

UL, CSA, TUV

UL, CSA, TUV

UL, CSA, TUV

UL, CSA, TUV

No. of Poles

Wire Sizes
Current
Specifications

1
2

1
2

2
2

16 to 6 AWG (14mm )

16 to 4 AWG (22mm )

16 to 0 AWG (38mm )

22 to 14 AWG (2mm2)
600V / 10A

600V / 50A

600V / 75A

600V / 150A

Size

M5

M6

M8

M3

Type

Touch-down

Hex bolt

Hex bolt

Touch-down

35mm DIN rail

35mm DIN rail

35mm DIN rail

35mm DIN rail, surface

(N-m)

2.6 - 3.7

3.9 - 5.4

10 - 13.5

0.6 - 1.0

(in-lbs.)

23.1 - 32.8

34.6 - 47.9

88.8 - 119.8

5.3 - 8.9

End Plate

BNE50W

BNE75W

BNE150W

BNDE15W

DIN Rail Stop

BNL-5

BNL-6

BNL-6

BNL-8

Dust Cover

BNC320

BNC420

BNC520

BNC230 (top level)


BNC240 (bottom Level)

Terminals
Mounting
Terminal Torque

Marking Strip

PVC

BNM7

BNM7

BNM7

BNM7

Fiberglass

BNM9

BNM9

BNM9

BNM9

End clip

BNM3

BNM3

BNM3

BNM3

BNR1 10.34" (265mm)


BNR2 19.69" (500mm)

Connecting Rods
Connecting Nuts

BNN1 (2 pieces)

Base Mount Brackets

BNDL2

Ring Terminal Jumpers

BNJ26

Fork Terminal Jumpers

BNJ26FW

1. BNDN1000 aluminum DIN rails are available in 1 meter lengths.


2. Marking strips are available in 1 meter lengths.
3. Jumpers are available in groups of six.
4. Remove the H in the terminal block part number for standard screw type.

Terminal Blocks

P-4

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC

Tab 4
6KLS/RRVH Accessories

CriticalDCK2

Page 1 of 2

FAQs | Site Map | Product Inquiry | Send to a Friend |

Search:

Home

About Us

Our Capabilities

Our Products

Catalogs

Market Applications

Careers

Customer Service

Home > Silencing/Emission Technology > Silencing > EMDisk > CriticalDCK2

Call Now
View phone list

Disk Critical Grade - DCK2 Series


Typical Reduction 22-36 dB

Request Info

Low-profile critical grade series silencer is

Fill out form

specifically designed for use in enclosures,


trailers, marine, and other size restricted areas.

Headquarters

Provides effective noise reduction in critical

9700 West 74th Street

areas. Silencer is insulated to reduce external

Eden Prairie, MN 55344

surface temperature.

Description

Technical Specs

Accessories

http://phillipsandtemro.com//silencing-disk/criticaldck2.asp

Literature

11/29/2012

CriticalDCK2

Page 2 of 2

7 each
10 each
1 each

Phillips & Temro

Markets & Applications

Products

Home
About Us

Hybrid/Electric Vehicles
Heavy Duty

Air Intake Heaters


Coolant/Oil Heating

Our Capabilities
Our Products

Construction/Agriculture
Light Duty

Hybrid Fans
Spider Fans

Catalogs
Careers

Power Generation
Aftermarket

EM/Cowl Silencers
Emission/Catalyst Silencers

Customer Service

Automotive
Search:

Headquarters

Call Now

Request Info

9700 West 74th Street


Eden Prairie, MN 55344

View phone list

Fill out form

http://phillipsandtemro.com//silencing-disk/criticaldck2.asp

Copyright 2011 Phillips & Temro Industries


website designers: cazarin interactive

11/29/2012

4 each for the


4045's.

4 each for the 6090


Deere

4 each for the


Scania

NRG

Intelligent Engine Start Battery Charger

The Smart Choice for Mission-Critical Engine Starting


Fast, accurate, mission-critical charging gives best starting reliability
4-rate, temperature-compensated output offers longest battery life
Replace nearly any charger without planning ahead
Industry-first battery-fault alarm helps dispatch service early
Lasting reliability field MTBF > 1 million hours with industry-best warranty
IBC seismic certification meets latest building codes, no installation delays
Optional OSHPD pre-approval already approved for California hospital projects

SMI
2 00

0
00

EI
2

IBC
2006

t
t
t
t
t
t
t

RTIFIE

STORED ENERGY SYSTEMS

XXXTFOTVTBDPNtJOGP!TFOTVTBDPNt5PMMGSFFt

NRG Battery Charger Benefits and Features

Failure to start due to battery problems is the


leading cause of inoperable engine generator sets.

SENS NRG battery charger maximizes starting system reliability while slashing genset servicing costs:
One NRG replaces almost any charger without extra site visits. Installers can select or change at
any time 120, 208 or 240 volts AC input, 12 or 24-volt battery and output settings optimized for nearly
any lead-acid or nickel cadmium battery.
Easy to understand user interface provides state-of-the-art system status including digital
metering, NFPA 110 alarms and a battery fault alarm that can send service personnel to the site
before failure to start.
Batteries charged by NRG give higher performance and last longer. In uncontrolled environments
precision charging by SENS increases battery life and watering intervals 400% or more.
NRG meets all relevant industry standards including UL, NFPA 110 and CE. Seismic Certification
per International Building Code (IBC) 2000, 2003, 2006. All units are C-UL listed. 50/60 Hz units
add CE marking to UL agency marks.
EnerGenius reliability technology built into every charger includes:
t"MMFMFDUSPOJDPQFSBUJPOXJUIHFOFSPVTDPNQPOFOUEFSBUJOH
t%JTDPOOFDUFESFWFSTFEJODPSSFDUWPMUBHFCBUUFSZBMBSNBOEQSPUFDUJPO
t1SPUFDUJPOPGDPOOFDUFEFRVJQNFOUBHBJOTUMPBEEVNQUSBOTJFOUT
t8JEFTUUFNQFSBUVSFSBUJOH BOEPWFSUFNQFSBUVSFQSPUFDUJPO
t4VQFSJPSMJHIUOJOHBOEWPMUBHFUSBOTJFOUQSPUFDUJPO
t%FNPOTUSBUFEmFME.5#'NJMMJPOIPVST
t4UBOEBSEZFBSXBSSBOUZ ZFBSTNBHOFUJDTBOEQPXFSTFNJDPOEVDUPST

and available 10-year complete warranty with reimbursement of field service costs

Earn the best return on your charger


investment choose SENS NRG

NRG Specifications
AC Input

Voltage
Input current
Frequency
Input protection

Charger Output

Nominal voltage ratings


Optional voltage rating
Battery settings

Regulation
Current
Electronic current limit
Charge characteristic
Temperature compensation
Output protection

110-120/208-240 VAC, +10%, single phase, field selectable


10A charger: 6.6/3.3 amps maximum
20A charger: 12.6/6.3 amps maximum
60 Hz +5% standard; 50/60 Hz +5% optional
1-pole fuse, soft-start, transient suppression

12 or 24 volt nominal
12/24 volt, field selectable
Six discrete battery voltage programs
- Low or high S.G. flooded
- Low or high S.G. VRLA
- Nickel cadmium 9, 10, 18, 19 or 20 cells
+0.5% (1/2%) line and load regulation
10 or 20 amps nominal
105% rated output typical no crank disconnect required
Constant voltage, current limited, 4-rate automatic equalization
Enable or disable anytime, remote sensor optional
Current limit, 1-pole fuse, transient suppression

Standard
4-rate charging

User Interface, Indication and Alarms


Digital meter
Accuracy
Alarms

Automatic meter alternately displays output volts, amps4


+2% volts, +5% amps
LED and Form C contact(s) per table:

Front panel
status display
1. Alarms 1 available only on 10A charger
2. Form C contact provides summary alarm of these conditions. BBHH
chargers include this alarm configuration. Contacts rated 2A @ 30 VDC resistive
3. Battery fault alarm indicates these fault conditions:
- Battery disconnected - Battery polarity reversed - Mismatched charger
battery voltage - Open or high resistance charger to battery connection
- Open battery cell or excessive internal resistance
4. Three-position jumper allows user to select from three display settings:
alternating volts / amps (normal), constant volts, or constant amps

Controls

AC input voltage select


Optional 12/24-volt output select
Battery program select
Meter display select
Fast charger enable/disable
Temp compensation enable
Remote temp comp enable

Environmental

Operating temperature
Over temperature protection
Humidity
Vibration (10A unit)
Transient immunity
Seismic Certification

Agency Standards
Safety

Agency marking
EMC
NFPA standards
Optional agency compliance

Construction

Housing/configuration


Packaging
Dimensions
Printed circuit card
Cooling
Protection degree
Damage prevention
Electrical connections

Warranty

Standard warranty
Optional warranty

Optional features

Input
Remote temp comp sensor
Drip shield meets s/b (IP21)
NEMA 3R housing
UL BBHH listing
Field service warranty

Field-selectable switch
Field-selectable two-position jumper
Field-selectable six-position jumper
Field-selectable three-position jumper
Field-selectable two-position jumper
Standard. Can be disabled or re-enabled in the field
Connect optional remote sensor to temp comp port

Simple field
adjustments

-20C to +60C, meets full specification to +45C


Gradual current reduction to maintain safe power device temperature
5% to 95%, non-condensing
UL 991 Class B (2G sinusoidal)
ANSI/IEEE C62.41, Cat. B, EN50082-2 heavy industrial, EN 61000-6-2
IBC 2000, 2003, 2006, 2009 Maximum Sds of 2.28 g, Optional OSHPD pre-approval

C-UL listed to UL 1236 (required for UL 2200 gensets), UL Category BBGQ,


CSA standard 22.2 no. 107.2-M89
CE: 50/60 Hz units DOC to EN 60335
60 Hz: C-UL-US listed
50/60 Hz: C-UL-US listed plus CE marked
Emissions: FCC Part 15, Class B; EN 50081-2
Immunity: EN 61000-6-2
NFPA 70, NFPA 110. (NFPA 110 requires Alarms C)
Units with Alarms 1 configuration available with additional compliance to
UL Categories BBHH, QWIR, and NFPA 20
OSHPD pre-approval

Material: Non-corroding aluminum. Configuration options:


t'VMMZFODMPTFE$6-MJTUFEFODMPTVSF
t0QFOGSBNF$6-SFDPHOJ[FE
Open-frame and Slimline configurations only available in bulk OEM quantities and packaging
See Drawings and Dimensions page for details
Surface mount technology, conformal coated
Natural convection
Listed housing: NEMA-1 (IP20). Optional IP21 drip shield. Optional NEMA 3R enclosure
Fully recessed display and controls
Compression terminal blocks

Three year parts and labor warranty (10 years magnetics and power semiconductors) from
date of shipment
If specified at time of order, warranty coverage can be increased to reimburse customers documented
field service costs up to the original charger price or increased to 5 or 10 years with field service cost
reimbursement. Contact the factory for full details

Input frequency, 50/60 Hz


Recommended where battery and charger are in different locations
Protects from dripping water
Enables outdoor installation (remote temp sensor recommended)
Available in 10A units with Alarms 1
Reimbursement of customer field service expenses up to charger price for 3, 5, or 10 years

Drawings and Dimensions


10A Chargers

20A Chargers

111009 G

All models offer field-selectable input 120/


208-240 volts. 60 Hz input is standard
with C-UL listing. Optional 50/60 Hz input
includes C-UL listing and adds CE mark.

Option code
E: OSHPD Pre-Approved

Model Output voltage


Output current
10: 10 amps
12: 12 volts
20: 20 amps
24: 24 volts
22: 12/24-volt
field selectable

AC input
R: 120/208-240 VAC, 60 Hz
H: 120/208-240 VAC, 50/60 Hz

UL category code
S: UL category BBGQ (standard)
P: UL categories BBHH, QWIR (Alarms 1 only)

Alarm system code


1: LED and single Form C contact
C: LEDs and Form C contacts to meet
NFPA 110

Housing/Agency
L: Enclosed: C-UL listed

5IF4NBSU$IPJDFGPS.JTTJPO$SJUJDBM&OHJOF4UBSUJOH
"EEJUJPOBM*OGPSNBUJPO

Contact SENS or your local sales representative for additional


specification, engineering and installation information. Check the
SENS web site for latest available data. Specification is subject to
change without notice.

2 00

SMI

0
00

EI

IBC
2006

RTIFIE

Contact Information

For information and service on any SENS product, please contact us at:
4BMFTtt'BY
XXXTFOTVTBDPNtJOGP!TFOTVTBDPN
*OEVTUSJBM$JSDMF -POHNPOU $064"

STORED ENERGY SYSTEMS

Tab 5
Drawings

Page 32 of 44

Page 33 of 44

Page 34 of 44

Page 35 of 44

Page 36 of 44

Page 37 of 44

Page 38 of 44

Page 39 of 44

Page 40 of 44

TVA Model Request Sheet - OEM Gen Set Engine Application

TVA Model Request Sheet Version 3.0

TVA Model Request Date


TVA Model Completion Date

5-Mar-13
15-Mar-13

Requester
Location
Office Phone #
Cell Phone #
PEC Account # to Charge (XXX)

Karl Schmid
JDPS OEM
319-292-6697

OEM Engine Customer


Location (City, State)
OEM Distributor Involved
Location (City, State)

Marsh Creek
Anchorage, AK
Caccade Engine Center
Tukwila, WA

Gen Set Make and Model


Power Rating
Electrical Frequency (Hz)
Power Unit Type

Marsh Creek
117 kWe
60 Hz
Prime

kWe or KVA
Hz
Standby, Prime, or Continuous

Alternator Make
Alternator Model
Alternator Drawing #
Is Drawing already On-file ?
Will PMG Option be Used ?

Newage
UCI-274F
DL15-12647a
Yes
Yes

I = 1.597 kg-m^2, K-flywheel to rotor = 2.24E+06 Nm/radian.


Marathon drawings must include 'Dash Number'
Yes, No
Yes, No

Engine Model
Emission Type (Tier__)
Engine Performance Curve Sheet
Standby Power Rating (kW)
Prime Power Rating (kW)
Rated Speed (RPM)
Governor Type
Speed Regulation
Droop Percentage

4045HF485
T3
4045HFG85_E
147
134
1800
Electronic
Isocchronous
0%

kW
197
kW
180
RPM
Electronic or Mechanical
Isochronous or Droop
%

Crank Pulley Option


Damper Option
Flywheel Housing Option
Flywheel Option
Add-On Crank Pulley Option

1328

Any Other Comments:

REP SN PE4045L234474
SOLICITATION 2013019

255

1403
1503
4199

REF: TVR-2013-018
STATUS: This genset application is torsionally
approved as modelled
Vishal Edake ( 15March2013)

AGIRX381XXX

Hp
Hp

Allow 20 work days for normal processing


Allow 10 work days for rapid processing
Aaron Ison
Engineering Mgr
Cascade Diesel
Tukwila, WA
tel: 253-867-2020

TVA Model Request Sheet - OEM Gen Set Engine Application


TVA Model Request Date
TVA Model Completion Date

5-Apr-13
8-Apr-13

Requester
Location
Office Phone #
Cell Phone #
PEC Account # to Charge (XXX)

Adam Paul
JDPS Marine
319-292-8645

OEM Engine Customer


Location (City, State)
OEM Distributor Involved
Location (City, State)

Marsh Creek
Anchorage, AK
Cascade Diesel
Tukwila, WA

Gen Set Make and Model


Power Rating
Electrical Frequency (Hz)
Power Unit Type

Marsh Creek
67 kWe
60 Hz
Prime

Alternator Make
Alternator Model
Alternator Drawing #
Is Drawing already On-file ?
Will PMG Option be Used ?

Newage
UCI-274C
DL15-12644a
Yes
Yes

Engine Model
Emission Type (Tier__)
Engine Performance Curve Sheet
Standby Power Rating (kW)
Prime Power Rating (kW)
Rated Speed (RPM)
Governor Type
Speed Regulation
Droop Percentage

4045TFM75
T2 Marine
4045TFM7598MG
80
73
1800
Electronic
Isochronous
0%

Crank Pulley Option


Damper Option
Flywheel Housing Option
Flywheel Option
Add-On Crank Pulley Option

1333

Any Other Comments:

REP SN PE4045T905079
SOLICITATION 2013019

350

1406
1597
4199

TVA Model Request Sheet Version 3.0


REF: TVR-2013-041
STATUS: This marine gen set application is
torsionally approved as modelled
Vishal Edake
8-Apr-13

Allow 20 work days for normal processing


Allow 10 work days for rapid processing
Aaron Ison
Engineering Manager
Cascade Diesel
Tel: 206-914-6457

AGIRX381XXX

kWe or KVA
80 kWe standby
Hz
Standby, Prime, or Continuous
I = 1.071 kg-m^2, K-fywheel to rotor centerline = 2.50E_06 Nm/radian
Marathon drawings must include 'Dash Number'
Yes, No
Yes, No

kW
98
kW
107
RPM
Electronic or Mechanical
Isochronous or Droop
%

Hp
Hp

TVA Model Request Sheet - OEM Gen Set Engine Application

TVA Model Request Sheet Version 3.0

TVA Model Request Date


TVA Model Completion Date

1-Mar-13

REF: TVR-2013-034
STATUS: This genset application is torsionally
approved as modelled.
Vishal Edake ( 28 March 2013)

Requester
Location
Office Phone #
Cell Phone #
PEC Account # to Charge (XXX)

CASCADE ENGINE
TUKWILA, WA
253 867 2020
206 914 6457

OEM Engine Customer


Location (City, State)
OEM Distributor Involved
Location (City, State)

MARSH CREEK
ANCHORAGE, AK
CASCADE ENGINE CENTER
TUKWILA, WA

Gen Set Make and Model


Power Rating
Electrical Frequency (Hz)
Power Unit Type

MARSH CREEK
200 kWe
60
PRIME

Alternator Make
Alternator Model
Alternator Drawing #
Is Drawing already On-file ?
Will PMG Option be Used ?

NEWAGE-STAMFORD
HCI434D
TBD
YES

Marathon drawings must include 'Dash Number'


Yes, No
Yes, No

Engine Model
Emission Type (Tier__)
Engine Performance Curve Sheet
Standby Power Rating (kW)
Prime Power Rating (kW)
Rated Speed (RPM)
Governor Type
Speed Regulation
Droop Percentage

6090AFM75
T2 MARINE
6090AFM75_E
244
222
1800
ELECTRONIC
ISSOC
0

kW
327
kW
297
RPM
Electronic or Mechanical
Isochronous or Droop
%

Crank Pulley Option


Damper Option
Flywheel Housing Option
Flywheel Option
Add-On Crank Pulley Option

1350
6899
1435
1550
4199

Any Other Comments:

REP SN RG6090G011580
SOLICITATION 2013019

Allow 20 work days for normal processing


Allow 10 work days for rapid processing

AGIRX381XXX

kWe or KVA
Hz
Standby, Prime, or Continuous

Hp
Hp

REQUESTED FROM NEWAGE 3/1/2013

Approved by:

KEPS, Torben Johansson


Handled by:

KEPS, Hanna, Johnny

Date:

8 April 2013

CASCADE ENGINE CENTER, LLC


18435 OLYMPIC AVE S, TUKWILA, WA, USA
aison@cascadeengine.com
COMMENTS TO THE TORSIONAL VIBRATION CALCULATION 2357 A

General data
1a. End User /Name of
Customer
1b.
Scania Order No
Yard
1c. New built No
1d. Classification
society

MARSH CREEK
TBD
STATE OF ALASKA, USA
RFI 04-13 (CASCADE RFI #)
UL

System description:
Engine No
Engine type
Output
Rated speed
Operating range (min-max)

DI13 75M GEN DRIVE, SN# TBD (ordered)


DI13 75M GEN DRIVE
426
1800
+/- 30 RPM

Summary:
The TVC was performed to evaluate the feasibility of DI13 075M with Stamford
alternator. The vibratory torque levels for the main bearings does not exceed
designed limits during normal operation and misfire. The heat dissipation for the
crankshaft damper does not exceed designed limits during normal operation and
misfire. The vibratory torque levels for the alternator should be verified by the
manufacturer.
Scania Engines approves the installation regarding torsional vibrations for
Scania components.

Scania CV AB
Scania Engines

Johnny Hanna

Page 1 of 10

TVC 2357

Approved by:

KEPS, Torben Johansson


Handled by:

KEPS, Hanna, Johnny

Date:

8 April 2013

Page 2 of 10

TVC 2357

Torsional Vibration Calculation made by Scania


The Scania torsional vibration calculation (TVC) is made with the Matrix method.
The calculation is based on the technical data supplied to Scania by the customer or the
manufacturer for items involved in the secondary system that are not manufactured by Scania.
An approved calculation is valid for and constitutes a guarantee, with reference to the general
Scania guarantee conditions, for all Scania engine products in the subjected set in respect of
torsional vibration. The approval as such is thus not to be construed as a general system
guarantee in other respects.
For non-Scania products no responsibility will be taken, but a warning can be given for
components exposed for high vibratory nominal stresses. The supplier of the complete set,
diesel engine + driven equipment, ought to confirm the torsional capability of respective
components on basis of the torsional vibration calculation.
ISO 3046/V is valid, where applicable.
We can not on basis of the torsional vibration calculation give any statement nor guarantee
concerning speed-hunting.

Approved by:

KEPS, Torben Johansson


Handled by:

KEPS, Hanna, Johnny

Date:

8 April 2013

Page 3 of 10

TVC 2357

Detailed System Description


Name of object
Front system
Engine data
Scania engine type:
Output power [kW]:
Rated speed [rpm]:
No of cylinders:
Firing orders:
Bore of cylinders [mm]:
Stroke [mm]:
Flywheel
Flywheel moment of inertia [kgm2]:
Crank shaft drawing no:
Viscous damper drawing no:
Normal operation

DI13 075M
426
1800
6
1-5-3-6-2-4
130
160
14
2.029
1775228
1805513

Rear system
Coupling
Alternator
Running condition

Flexplate
Stamford HC534 1D
Normal maximum power, genset load curve

Approved by:

KEPS, Torben Johansson


Handled by:

Date:

KEPS, Hanna, Johnny

Page 4 of 10

8 April 2013

TVC 2357

Mass-Elastic Tabulation
The simplified system was used.
Element
Node

Moment of
Stiffness
inertia [kgm2] [Nm/rad]

Floating ring

0,211
See below

Damper
0,131

Driver + damper house


Main Bearing 1

5.034e6
0,096

Cylinder 1
Main Bearing 2

3.089e6
0,06

Cylinder 2
Main Bearing 3

3.089e6
0,086

Cylinder 3
Main Bearing 4

3.089e6
0,086

Cylinder 4
Main Bearing 5

3.089e6
0,06

Cylinder 5
Main Bearing 6

3.089e6
0,102

Cylinder 6
Main Bearing 7

4,94e6
2,029

Flywheel
Flex plate

Rigid
1,0995

Hub + Fan + shaft


K1 torsional stiffness
fan to main rotor

60,33e6
6,553

Main rotor
K2 torsional stiffness
main rotor to ex rotor

2.24e6
0,51

Ex rotor

Crankshaft vibration damper characteristics


Floating Ring inertia
Stiffness
Damping

0,211
13240 * f0,4831
7732,0 * f0,8384

kgm2
Nm/rad
Nms/rad

The torsional stiffness values has been calculated from the indata form, the values should
be verified by the alternator manufacturer.

Approved by:

KEPS, Torben Johansson


Handled by:

Date:

KEPS, Hanna, Johnny

Page 5 of 10

8 April 2013

TVC 2357

Eigen frequencies for the system


The eigen frequencies below 500 Hz are shown in the table below.
116,9

216,4

341,2

0,773

0,013

Driver+damperhouse

0,335

-0,988

-0,061

Cylinder 1

0,308

-1

-0,056

Cylinder 2

0,256

-0,936

-0,037

Cylinder 3

0,199

-0,815

-0,012

Cylinder 4

0,137

-0,627

0,016

Cylinder 5

0,073

-0,393

0,041

Cylinder 6

0,007

-0,134

0,059

Flywheel

-0,034

0,035

0,062

Hub + Fan + shaft

-0,034

0,035

0,062

Main rotor

-0,037

0,045

0,046

Ex rotor

-0,042

0,078

-1

Hz
Node
Floating ring

Approved by:

KEPS, Torben Johansson


Handled by:

KEPS, Hanna, Johnny

Date:

8 April 2013

Eigen modes for the system


The eigen modes for the system is shown below.

Page 6 of 10

TVC 2357

Approved by:

KEPS, Torben Johansson


Handled by:

Date:

KEPS, Hanna, Johnny

Page 7 of 10

8 April 2013

TVC 2357

Results Load curve, normal operation 426kW.


The load curve is shown below.
Load curve
450

400

350

L o a d [k W ]

300

250

200

150

100

50

0
600

800

1000

1200
rpm

1400

1600

1800

Approved by:

KEPS, Torben Johansson


Handled by:

Date:

KEPS, Hanna, Johnny

Page 8 of 10

8 April 2013

TVC 2357

Results Vibratory Torque amplitudes, normal operation 426kW.


The vibratory torque amplitude in the crankshaft as percent of permitted amplitude below.
Vibratory Torque in main bearings
100

90
MB1
MB2

80

MB3

[% o f p e rm is s ib le v ib ra to ry to rq u e ]

MB4
MB5

70

MB6
MB7
60

50

40

30

20

10

0
600

800

1000

1200
rpm

1400

1600

1800

Approved by:

KEPS, Torben Johansson


Handled by:

Date:

KEPS, Hanna, Johnny

Page 9 of 10

8 April 2013

TVC 2357

Results Vibratory Torque, Secondary system, normal operation.


The vibratory torque levels for the alternator are shown below in the figure.
Vibratory Torque in Secondary system
7000

6000

Rigid Flywheel-to-Flexplate element


Main rotor
Ex rotor

V ib ra t o ry t o rq u e [ N m ]

5000

4000

3000

2000

1000

0
600

800

1000

1200
rpm

1400

1600

1800

Approved by:

KEPS, Torben Johansson


Handled by:

Date:

KEPS, Hanna, Johnny

Page 10 of 10

8 April 2013

TVC 2357

Results Heat dissipation, crankshaft damper, normal operation.


The heat dissipation for the crankshaft damper is shown below.

Heat dissipation damper


1500

Heat dissipation damper

W att

1000

500

0
600

800

1000

1200
rpm

1400

1600

1800

Approved by:

KEPS, Torben Johansson


Handled by:

KEPS, Hanna, Johnny

Date:

8 April 2013

Detailed System Description


Name of object
Front system
Engine data
Scania engine type:
Output power [kW]:
Rated speed [rpm]:
No of cylinders:
Firing orders:

DI13 075M
426
1800
5
1-2-4-5-3

Bore of cylinders [mm]:


Stroke [mm]:
Flywheel
Flywheel moment of inertia [kgm2]:
Crank shaft drawing no:
Viscous damper drawing no:
Misfire, pressure loss:

130
160
14
2,029
1775228
1805513
70% pressure drop

Rear system
Coupling
Alternator
Running condition
Misfire, pressure loss:

Mass-Elastic Tabulation
See TVC2357 A
Eigenfrequencies
See TVC2357 A
Eigenmodes
See TVC2357 A
Load curve
See TVC2357 A

Flexplate
Stamford HC534 1D
70% pressure drop in cyl 5

Page 1 of 4

TVC 2357

Approved by:

KEPS, Torben Johansson


Handled by:

Date:

KEPS, Hanna, Johnny

Page 2 of 4

8 April 2013

TVC 2357

Results Vibratory Torque amplitudes, (B).


The torque amplitude as a percentage of permitted level for positions in the crankshaft
corresponding to each main bearing (MB) is presented below. There is no remarkable
difference in comparison to normal operation.

Vibratory Torque in main bearings


100

90
MB1
MB2

80

MB3
[ % o f p e rm is s ib le v ib ra t o ry t o rq u e ]

MB4
70

MB5
MB6
MB7

60

50

40

30

20

10

0
600

800

1000

1200
rpm

1400

1600

1800

Approved by:

KEPS, Torben Johansson


Handled by:

Date:

KEPS, Hanna, Johnny

Page 3 of 4

8 April 2013

TVC 2357

Results Heat dissipation, (B).


The power dissipation in the crankshaft damper is shown below. There is no remarkable
difference compared to normal operation.
Heat dissipation damper
1500

Heat dissipation damper

Watt

1000

500

0
600

800

1000

1200
rpm

1400

1600

1800

Approved by:

KEPS, Torben Johansson


Handled by:

Date:

KEPS, Hanna, Johnny

Page 4 of 4

8 April 2013

TVC 2357

Result secondary system (B).


The vibratory torque level for the alternator are shown below.
Vibratory Torque in Secondary system
7000

6000

5000

Rigid Flywheel-to-Flexplate element

V ib ra to ry torqu e [N m ]

Main rotor
Ex rotor
4000

3000

2000

1000

0
600

800

1000

1200
rpm

1400

1600

The vibratory torque levels must be verified by the alternator manufacturer.

1800