WATER AND POWER DEVELOPMENT AUTHORITY
SPECIFICATION P-90: 1982
AMENDMENT NO.1 DATED 27.11.1983
1.
2.
3.
4.
5.
C O N T E N T S
0.
Foreword
1.
Scope
2.
Reference Specification
3.
Climatic Conditions
4.
Ratings
5.
Construction Requirements
6.
Terminal Marking
7.
8.
Tests
9.
PRINTING HISTORY
First approved on 15th March,1975
Second edition 27th November, 979
Third edition October, 1982
First amendment on 27th November, 1983
SPECIFICATION P-90:82
CURRENT TRANSFORMERS (33KV TO 132 KV)
0.
FOREWORD
Type
Designation
A
B
C
D
E
F
4
2.
REFERENCE SPECIFICATION
CLIMATIC CONDITIONS
3.1
3.2
Ambient Temperature
Maximum
500C
450C
300C
Minimum
-100C
3.3
3.4
Altitude
Atmospheric condition
3.5.1 It may be assumed that the air is not normally heavily polluted
by dust, smoke, aggressive gases, vapors or salt spray.
However, at certain times of the year severe dust storms may be
experienced.
5
RATINGS
4.1
v)
vi)
vii)
Type
A
B
C
D
E
F
designation
Normal system
132
132
132
132
66
33
voltage, kV
Rated voltage,kV 145
145
145
145 72.5
36
Rated normal
1600/ 200/ 1200/ 200/ 600/ 300/
primary
800/
100
600
100 300/ 150/
current, Amps
400
300
150
75
Rated
Secondary
Current, Amps
Rated
frequency, Hz
Rated
Secondary
Output, VA:
a) Measuring
Core 1
b) Protective
Core 2
c) Protective
Core 3
d) Protective
Core 4
viii) Accuracy
Class:
a)Measuring
Core
b)Protective
Core
ix)
x)
Maximum
temperature
rise 0C
Accuracy limit
factory for
50
50
50
15
15
15
15
15
15
60
60
60
60
60
60
30
30
30
30
30
30
30
30
30
0.5
o.5
0.5
0.5
0.5
0.5
10P
10P
10P
10P
10P
10P
55
55
55
55
55
55
20
20
20
20
20
20
50
5
50
5
50
protective core
xi)
Short time
current Rating,
kA
a) Thermal,
Ith
b) Dynamic,
Idyn
xii) One minute
Power
frequency
withstand
voltage, kV rms
xiii) Impulse
withstand
voltage, kV peak
xiv) One minute
power
frequency
withstand
voltage, kV rms
Secondary
Windings
5.
5.1
5.1.1
5.1.2
40
40
20
20
20
20
100
100
50
50
50
50
275
275
275
275
140
70
650
650
650
650
325
170
CONSTRUCTION REQUIREMENTS
General
The current transformers shall be single pole, oil filled, and selfcontained outdoor type. Oil level indicator marked for 250C
shall be provided. The oil shall be class-I oil conforming to IEC296.
The current transformers shall be hermetically sealed.
If
bellows are used to accommodate oil expansion, they shall be
made of a suitable grade of stainless steel. A suitable device for
indicating the position of the bellows shall be provided.
5.1.3
5.2
Temperature Rise
Painting
5.3.1
5.3.2
5.3.3
5.4
5.4.2
5.5.
Bushings.
5.5.1
5.5.2
5.6
Rated Voltage
Min. Normal
Creepage Distance
132kV
66kV
33kV
2400 mm
1100 mm
550 mm
Extended
Creepage
Distance
38 mm
1800 mm
900 mm
Primary Terminals
The size of primary terminals for type A and C current
transformers shall be 125 mm in length x 40 mm dia. For type
B, D, E and F the terminals shall be 80 mm in length x 30
mm in dia.
5.7
Secondary Terminals
All secondary leads shall be brought to an outlet box near each
bushing and terminated in non split, current shorting type,
terminal block located in a weather proof case near the current
transformer base.
Provision shall be made for entry and
connection with 4 Core, 6 mm2, Copper Control Cables.
5.8
Earthing Terminals
Two number earthing terminals at diagonally opposite position
shall be provided. Each terminal shall be capable of carrying
full short circuit current and be suitable for accommodating 95
to 120 sq mm copper earthing lead.
6.
TERMINAL MARKING
The terminal marking for the current transformers shall be in
accordance with clause 22 of the IEC Publication 185 (1966).
7.
8.
TESTS
8.1
Routine Tests.
The following routine tests shall be made in accordance with the
IEC Publication 185 (1966) for all ratios and at all taps:
i)
ii)
iii)
iv)
v)
8.2
Type Tests.
The following type tests shall be carried out in accordance with
the IEC Publication 185 (1966).
i)
ii)
iii)
iv)
v)
vi)
9.1
Tender Drawings.
The following information shall be furnished with the bid:
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)
ix)
x)
xi)
xii)
Approval Drawings
9.2.1
i)
ii)
iii)
iv)
v)
vi)
vii)
9.3
1)
2)
3)
4)
Designation
Type
Manufacturer
Design test Certificate
i) Issuing Institute
ii)Number and date
5) Rated Voltage
6) Rated frequency
7) Rated normal primary current
8) Rated Secondary current
9) Rate secondary output:
i) Measuring core (1)
ii) Protective core (2)
iii) Protective core (3)
iv)
Protective core (4)
10) Ac curacy Class:
i) Measuring core
ii) Protective core
11) Accuracy limit factor
12) Continuous thermal
Current rating
13) Short time current ratings:
i) Thermal (Ith)
ii) Dynamic (Idyn)
14) The minimum guaranteed
instrument security factor
for metering current
transformer
15) Power frequency withstand
voltage
16) Impulse withstand
voltage
17) Impulse wave
18)
19)
Resistance of secondary
winding
______________________
______________________
______________________
______________________
______________________
kV______________________
Hz______________________
A______________________
A ______________________
VA______________________
VA ______________________
VA______________________
VA______________________
_______________________
_______________________
_______________________
A_______________________
kA _______________________
kA_______________________
_______________________
kV_____________________
kV____________________
Sec____________________
Ohm ___________________
Mechanical loads of
Primary Terminals:
i) Dynamic load
ii) Static load
N____________________
N____________________
12
_____________________
mm _____________________
mm ____________________
mm _____________________
mm ____________________
mm ____________________
kg
___________________
kg
___________________
___________________
gm/ml.
cs
__________________
__________________
13