ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

Status: IFR

Rev. Date:

CONTRACTOR DOCUMENT:

Page: 1 of 8

APGREID SUBSTATION PROJECT

ELECTRICAL SYSTEM
GROUNDING CALCULATION

REV.

STATU
S

0A

IFR

DATE

REVISION MEMO
Issued For Review

ISSUED

CHECK

APP
R.

COMPANY
APPROVAL

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

CONTRACTOR DOCUMENT:

Status: IFR

Rev. Date:
Page: 2 of 8

REVISION TABLE

PAGES
PAGES

B C D E

REMARKS

ATT

ATTACHMENTS

EXHIBIT

PAGES

REVISIONS

REVISIONS
A

REMARKS

B C D E

REVISIONS
REMARKS
A

B C D E

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL
CONTRACTOR DOCUMENT:

System / Subsystem:

Revision: 0A
Discipline: ELE

Status: IFR

Rev. Date:
Page: 3 of 8

1. GENERAL......................................................................................................................... 4
2. REFERENCES..................................................................................................................4
3. ABBREVIATION................................................................................................................4
4. SCOPE.............................................................................................................................. 5
4.1 Electrical system neutral grounding..........................................................................5
4.2 Electrical safety grounding........................................................................................5
4.3 Electrostatic grounding.............................................................................................5
5. GROUNDING CALCULATION PARAMETER...................................................................5
5.1 Soil resistivity............................................................................................................ 5
5.2 Grounding conductor................................................................................................5
5.3 Grounding electrode.................................................................................................6
5.4 Tolerable step and touch voltage..............................................................................7
6. GROUNDING CALCULATION ANALYSIS RESULT..........................................................7

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

CONTRACTOR DOCUMENT:

Status: IFR

Rev. Date:
Page: 4 of 8

1. GENERAL
The purpose of this document is to give guidance on the design of the grounding and
lightning protection system. The grounding system is provided for the safety of
personnel, equipment and the proper operation of the plant. The project specifications
and the applicable international standards are listed
This calculation will be revised whenever necessary to cope up with the changes on the
system components that may be caused by further engineering.

2. REFERENCES
The grounding and lightning protection system shall be design in accordance with the
applicable sections of the following standards and codes:
IEEE 142

IEEE Recommended Practice for Grounding of Industrial


and Commercial Power Systems

IEEE 80-2000

Guide for Safety in AC Substation Grounding

NFPA 70

National Electrical Code

NFPA 780

Standard for the Installation of Lightning Protection System


Soil Investigation Report

3. ABBREVIATION
kVA
MVA
PF
LF
ACSR
GCB
HV
LV
LVSB
MDB
SDB
DB
Es
E

Kilo Volt Ampere


Mega Volt Ampere
Power Factor
Load Factor
Aluminum conductors steel reinforced
Generator Circuit Breaker
High Voltage
Low Voltage
Low Voltage Switch Board
Main Distribution Board
Sub Distribution Board
Distribution Board
Essential
Emergency

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

CONTRACTOR DOCUMENT:

Status: IFR

Rev. Date:
Page: 5 of 8

4. SCOPE
This document includes the following systems:

4.1 Electrical system neutral grounding


The electrical ground system in medium voltage (>1000V) distribution system shall be
done by either isolation of transformer star point or by grounding the transformer star
point via a resistor.
The electrical ground system in low voltage (<1000V) distribution system shall be
established by direct grounding of the neutral conductor or transformer star point.

4.2 Electrical safety grounding


The safety grounding resistance shall not exceed 1 ohm.

4.3 Electrostatic grounding


To avoid hazardous operating condition because of static charge in the equipment, an
electrostatic grounding is foreseen.
The sources of static charging source in the plant include equipment with a surface
made of metal, steel structures, pipe racks, metal plate and etc. Each of those
equipments will be connected into plant main grounding system.

5. GROUNDING CALCULATION PARAMETER


5.1 Soil resistivity
Table below taken from soil investigation report on attachment 4:
Soil material

Resistivity
(ohm.m)

Depth
(Feet)

Crush rock surface

2500

0.328

Soil

17.28

3.28

Soil

48.55

9.84

Soil

32.9

16.4

Soil

26.67

22.96

Location

Switchyard
Area

5.2 Grounding conductor


Grounding conductor to be used in this project is copper with the size 4/0 AWG lying at
the soil depth 1.64 feet. The conductor grid configuration refers to the drawing Layout
Grounding Line KETIGUL on attachment 1. ETAP drawing model 2D and 3D for the grid
configuration described on attachment 2.

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

Status: IFR

Rev. Date:

CONTRACTOR DOCUMENT:

Page: 6 of 8

5.3 Grounding electrode


The grounding electrode to be used in this project is as shown below..
Length

= 9.84 feet

Diameter

= 3 /4 inch

Total resistance of the grounding grid calculated in accordance with IEEE 80-2000
calculated as follows:
a)

IEEE 80-2000 Equation No. 53

Rg

R1 R 2 R m2
R1 R 2 2 R m

b) IEEE 80-2000 Equation No. 54

R1

LC

2 LC k1 LC
k2

ln
A
a'

c) IEEE 80-2000 Equation No. 55

R2

2 nR L R

2 k1 LR
4 LR
1
ln
A
b

nR 1

d) IEEE 80-2000 Equation No. 56

Rm

2 LC
ln
LC LR

k 2 1
A

k1 LC

Where:
Rg

= total system resistance ()

R1

= ground resistance of grid conductors ()

R2

= ground resistance of all ground rods ()

Rm

= mutual ground resistance between the group of grid conductors, R1,


and group of ground rods, R2 ()

= soil resistivity (.m)

LC

= total length of all connected grid conductors (m)

2a

= diameter of conductor (m)

= area covered by conductors (m2)

k1

= coefficient, taken from IEEE 80 Figure 25 (a)

k2

= coefficient, taken from IEEE 80 Figure 25 (b)

LR

= length of each rod (m)

a 2h for conductors buried at depth h (m)

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

CONTRACTOR DOCUMENT:

Status: IFR

Rev. Date:
Page: 7 of 8

2b

= diameter of rod (m)

nR

= number of rods placed in area A

L AREA

= length area covered by conductor (m)

WAREA

= width area covered by conductor (m)

hC

= depth of ground conductor (m)

5.4 Tolerable step and touch voltage


Tolerable step and touch voltage for standard 70 kg weight person (used for this
analysis) is calculated as follows :
E step 70 (1000 6C s s )

0.157

E touch 70 (1000 1.5C s s )

ts
0.157
ts

Where,
Cs

Surface layer derating factor

Surface layer resistivity crushed rock, 2500 Ohm.m

Ts

Duration of shock for determining allowable body current. Table


10 IEEE 80 2000, 0.5 s
Cs calculated based on formula

0.09 1
s

Cs 1
2hs 0.09

Where

Soil resistivity Ohm.m

Hs

Surface layer thickness in meter

6. GROUNDING CALCULATION ANALYSIS RESULT


Grounding calculation is carried out by using computer program ETAP Power Station
7.0.0 from Operation Technology, Inc. which is follows to the IEEE 80-2000 standards.

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

CONTRACTOR DOCUMENT:

Status: IFR

Rev. Date:
Page: 8 of 8

Below is summary for the grounding calculation report, while complete ETAP calculation
shown on attachment-3
Grounding calculation
Area

Grounding
rod quantity

Total
resistance
Value

Touch
Potential

Tolerable
touch
potential

Step
Potential

Tolerable
step
potential

Switchyard

720

0.64 ohm

584.5

595.9

1090.2

1891.5

Note: Above calculation used L-G short circuit data maximum 13 kA, X/R=8.5%

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

CONTRACTOR DOCUMENT:

Rev. Date:
Page: 9 of 8

ATTACHMENT 1
GROUNDING LAYOUT PLAN

Status: IFR

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

CONTRACTOR DOCUMENT:

Rev. Date:
Page: 10 of 8

ATTACHMENT 2
ETAP 2D AND 3D MODEL

Status: IFR

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL
CONTRACTOR DOCUMENT:

System / Subsystem:

Revision: 0A
Discipline: ELE

Rev. Date:
Page: 11 of 8

ATTACHMENT 3
GROUNDING CALCULATION REPORT

Status: IFR

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

Status: IFR

Rev. Date:

CONTRACTOR DOCUMENT:

Page: 12 of 8

SOIL INVESTIGATION REPORT:


SOIL RESISTIVITY
Project

: Ketigul Substation

Client

: PT.Chevron Pacific Indonesia

Subject

: Soil Resistivity Based on Soil Analysis

Date

: 4 Februari 2010 /Rev.01

Data from soil analysis :


No

Sampl
e ID

Fac Loc,Fac Name,Fac Unit, Sapml


Pt /
UWI,Well Nm/Proc#,Prod
Nm,Sample Nm

Unit
CPI Specification
Method
1
001-01 KETIGUL,POWER
HOLE 03
2
002-01 KETIGUL,POWER
HOLE 03
3
003-01 KETIGUL,POWER
HOLE 03
4
004-01 KETIGUL,POWER
HOLE 03
5
005-01 KETIGUL,POWER
HOLE 04
6
006-01 KETIGUL,POWER
HOLE 04
7
007-01 KETIGUL,POWER
HOLE 04
8
008-01 KETIGUL,POWER
HOLE 04

Time

Conductivity

pH

Umho/cm

PLANT,BORE :

SM2510B
529

SM 4500 H+
3,94

PLANT,BORE :

206

4,52

PLANT,BORE :

304

5,31

PLANT,BORE :

375

5,72

PLANT,BORE :

30,9

4,23

PLANT,BORE :

215

4,91

PLANT,BORE :

82,7

5,65

PLANT,BORE :

n/a

5,89

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

Status: IFR

Rev. Date:

CONTRACTOR DOCUMENT:

Page: 13 of 8

Resistivity based on soil investigation :


No
1
2
3
4
5
6
7
8

Description
BORE HOLE,03
BORE HOLE,03
BORE HOLE,03
BORE HOLE,03
BORE HOLE,04
BORE HOLE,04
BORE HOLE,04
BORE HOLE,04

Depth

Conductivity

(m)
1
3
5
7
1
3
5
7

(mhosicrn)
529
206
304
375
30,9
215
82,7
n/a

Resistivity (.m)
17,28
48,55
32,9
26,67
323,63
46,52
120,92
n/a

Note ; Base on the Bangko Substation soil investigation

Sice data for bore hole 04 are not complete,data from bore hole 03 will be used in
this calculation.

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

Revision: 0A
Discipline: ELE

CONTRACTOR DOCUMENT:

Project

: Ketigul Substation

Client

: PT.Chevron Pacific Indonesia

Subject

: Soil Resistivity Based on Soil Analysis

Date

: 9 November 2009 /Rev.B

Status: IFR

Rev. Date:
Page: 14 of 8

BASED,IEEE STD 80-2000


Annex B
Step 1 Field Data
Symbol

s
3I0
A
Cs
d
D
Dm
Em
Es
Estep50
Lp
Estep70
Etouch50
Etouch70
h
hs
IG

Description
Soil resistivity, m
Surface layer resistivity Crushed rock, m
Symmetrical fault current in substation for
conductor sizing, A
Total area enclosed by ground grid,m2
Surface layer derating factor
Diameter of grid conductor,m
Spacing between parallel conductors,m
Maximum distance between any two points
on the grid ,m
Mesh voltage at the center of the corner mesh
for the simplited method , V
Step voltage between a point above the outer
corner of the grid and a point 1 m diagonally
outside the grid for the simpliled method ,V
Tolerable step voltage for human with 50 kg
body weight ,V
Square area ground
Tolerable step voltage for human with 70 kg
body weight ,V
Tolerable touch voltage for human with 50 kg
body weight, V
Tolerable touch voltage for human with 70 kg
body weight, V
Depth of ground grid conductors, m
Surface layers thickness,
Maximum grid current that flows between
ground grid and surrounding earth ( including

Remark
17,28 m/323,63 m
2500 m
Unknown
Unknown
Unknown
Unknown
7m
Unknown
Unknown
Unknown
66m+77m+66m+77m
Unknown
Unknown
Unknown
0.5 m
Crushed rock
Unknown

Document Number

ELECTRICAL SYSTEM
GROUNDING CALCULATION
Document Type: CAL

System / Subsystem:

CONTRACTOR DOCUMENT:

dc offset),A

Revision: 0A
Discipline: ELE

Rev. Date:
Page: 15 of 8

Status: IFR