GS3BA Series
High Efficiency Air Conditioner
10 SEER
1-1/2 5 Ton Capacity
The GS3BA Series of air conditioners offers
exceptional performance from a small, compact
package. The unit, when combined with our
engineered coils or air handlers, offers a full line
of quality, split system cooling equipment. Units
are ideally sized for slab or rooftop mounting in
single, multifamily, and light commercial
applications.

FEATURES and BENEFITS


Designed using galvanized steel with a polyester
urethane coat finish. The 950 hour salt spray finish resists
corrosion 50% better than comparable units.

Removable Top Grille Assembly Allows ease of


service from the top without disconnecting fan motor
leads.

Copper Tube / Aluminum Fin Coils Both indoor and


outdoor coils are designed to optimize heat transfer,
minimize size and cost, and increase durability and
reliability.

One Piece Top/Orifice Designed for maximum airflow


and quiet operation.

2-1/2" Pedestal Base The sturdy base keeps the


bottom of the coil out of harms way. Secondly, the base
has weep holes along the edge to allow the water from
rain to flow away from the unit.

Easy Compressor and Control Access Designed to


make servicing easier for the contractor, access panels
are provided to all controls and the compressor from the
side of the unit.

Warranty Five year limited parts and compressor.

Permanently Lubricated Motor A heavy duty PSC


motor for long lasting reliability and quiet operation.
Requires no maintenance and is completely protected
from rain and snow.
Full Service Valves These brass valves are easily
accessible and simplify servicing of the refrigeration
system.
Plastic Mesh Hail Guard A guard that will never rust
and protects the units coil from being damaged.

MODEL IDENTIFICATION CODES


EX: GS3BA-036K

GS 3

GS - Air Conditioner
GT - Heat Pump

A -

036

A
Style
A, B, etc.

Nominal
Capacity
(000) BTU

Product
Identifier

Electrical Code
K = 208/230-60-1

Generation 1, 2, 3. etc.
BA = Braze 10 SEER
BC = Braze 12 SEER
BD = Braze 13 SEER

DIMENSIONS
OUTDOOR SECTION
GS3BAH
W
D

18KA
22-1/2
22-1/2
22-1/2

024KA
22-1/2
22-1/2
22-1/2

030KA
22-1/2
22-1/2
22-1/2

036KA
22-1/2
22-1/2
22-1/2

042KA
30-1/2
22-1/2
22-1/2

048KA
34-1/2
22-1/2
22-1/2

060KB
30-1/2
30-1/2
30-1/2

Air Discharge
Allow Adequate
Clearance for Airflow

;
y
;
y
;
y
;
y
D

;;
yy
;;
yy
;;
yy
;;
yy
W

PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS


10 SEER High Efficiency Single Phase
Model No. GS3BAElectrical

Volts-Cycles-Phase (1)

Data

Total Amps
Delay Fuse Max. (2)
Min. Circuit Ampacity

Component

Coil

Data

Area
Rows-FPI
Tube Dia.

Fan

Type

Motor

Amps
HP

Fan

Dia.-#Blades

Blade

SCFM

Compressor RLA
Data*

LRA

Refrigerant Suction Line-Length/O.D.

0-24 ft.

(Liq. Line All Lengths - 3/8"O.D.)

25-39 ft.
40-75 ft.

Refrigerant Charge

(Outdoor unit, Indoor Unit

R-22 Ounces

15' Line Set)

Weight

Net

Approximate (lbs.)

Ship

018KA

024KA

030KA

036KA

042KA

048KA

060KB

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

9.2
15
11.4
8.3
1-14
3/8 O.D.
PSC
0.67
1/10
18 in. - 3
2100
8.6
49
5/8" (3)
5/8" (3)
3/4"

10.5
20
12.9
8.3
1-14
3/8 O.D.
PSC
0.67
1/10
18 in. - 3
2100
9.8
56
5/8" (3)
3/4"
3/4"

14.8
30
18.2
8.3
1-18
3/8 O.D.
PSC
1.13
1/8
18 in. - 3
2500
13.7
75
3/4"
3/4"
3/4"

15.9
30
19.7
8.3
1-22
3/8 O.D.
PSC
1.13
1/8
18 in. - 3
2500
14.8
96
3/4"
3/4"
7/8" (4)

18.1
35
22.4
11.5
1-20
3/8 O.D.
PSC
1.13
1/8
18 in. - 3
2500
17.0
105
3/4"
7/8" (4)
7/8" (4)

19.6
40
24.2
14.8
1-18
3/8 O.D.
PSC
1.4
1/4
18 in. - 4
3000
21.8
131
7/8"
7/8"
7/8"

28.5
60
35.3
17.7
1-22
3/8 O.D.
PSC
1.5
1/4
24 in. - 3
4000
27.0
144
7/8"
1-1/8" (5)
1-1/8" (5)

63
116
122

64
118
124

68
124
130

69
128
134

87
133
140

115
166
162

114
190
202

COPPER WIRE SIZE AWG


(1% Voltage Drop)
Supply Wire Length-Feet Supply Circuit
200
150
100
50
Ampacity

6
4
4
4
3
3
2
2

8
6
6
4
4
4
3
3

10
8
8
6
6
6
4
4

14
12
10
10
8
8
6
6

15
20
25
30
35
40
45
50

Wire Size based on N.E.C. for 60 type copper


conductors.
* Values shown are most severe and may vary slightly depending on the make of the compressor supplied.
(1) Operating Voltage Range: 198v min. 253v max.
(2) HACR Type Circuit Breakers or Time Delay Fuse
(3) Requires 3/4" to 5/8" reducer from unit to line.
(4) Requires 7/8" to 3/4" reducer from line to unit.
(5) Requires 7/8" to 1-1/8" reducer from line to unit.

SYSTEM HEATING & COOLING CAPACITIES


10 SEER High Efficiency Single Phase
Outdoor Unit
Model Number
GS3BA018KA
024KA
030KA
030KA
036KA
036KA
042KA
048KA
048KA
060KB

With This Coil


Coil
C3BA024C/U-A (2)
024C/U-A (2)
030C/U-B
036C/U-A (2)
036C/U-B (2)
036C/U-A (2)
042C/U-B (2)
048C/U-B (2)
048C/U-C
060C/U-C (2)

Outdoor Unit

Cooling
Btuh

SEER

Nominal
CFM

18,000
22,800
28,600
29,000
34,600
34,000
40,000
46,000
46,000
58,000

10
10
10
10
10
10
10
10
10
10

675
900
1125
1125
1350
1150
1500
1500
1500
1800

Required
Orifice
Size (1)
.051
.060
.063
.063
.067
.067
.075
.080
.080
.093

With This Air Handler

Model Number
GS3BA-

Air Handler
GB3B(M,V)-

Cooling
Btuh

SEER

Nominal
CFM

Required
Orifice
Size (1)

018KA

024K-A

18,000

10

675

.051

024KA

024K-A

23,000

10

900

.060

030KA

030K-A

28,600

10

1125

.063

030KA

030K-B

28,600

10

1125

.063

036KA

036K-B

34,600

10

1350

.067

042KA

042K-B

40,000

10

1500

.075

048KA

048K-B

46,000

10

1600

.080

060KB

060K-C

57,000

10

1700

.093

(1) Orifice supplied with indoor section.


(2) Also available as C3BH Horizontal Case Coil
See current ARI Directory for certified combinations and ratings.

ACCESSORIES - Condensing Unit


Start Assist Kit - 912933
Provides additional starting torque for the compressor
motor when operating with low line voltage or high
operating temperatures.

CERTIFICATION APPLIES
ONLY WHEN THE
COMPLETE SYSTEM
IS LISTED WITH ARI

774A-0105 (Replaces 774A-0803)

O'Fallon, MO

Before purchasing this appliance, read important energy cost and


efficiency information available from your retailer. Specifications
and illustrations subject to change without notice and without
incurring obligations.
Printed in U.S.A. (01/05)

Вам также может понравиться