POWER-UP
Apply the main power. The control panel first shows the panel
identification data
(If no key is pressed for a few seconds, the display starts to alternate between the
Actual Signal Display and the suggestion on selecting the language.)
or
) and
(The drive loads the selected language into use, shifts back to the Actual Signal
Display and starts to alternate between the Actual Signal Display and the
suggestion on starting the guided motor set-up.)
17
How to perform the limited start-up (covers only the basic settings)
Before you start, ensure you have the motor nameplate data at your hand.
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the
appropriate hardware manual for safety instructions.
Check the installation. See the installation checklist in the appropriate hardware/installation
manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
- there is a risk of damage in case of incorrect direction of rotation, or
- a Standard ID Run needs to be performed during the drive start-up. (ID Run is essential
only in applications which require the ultimate in motor control accuracy.)
POWER-UP
Apply the main power. The control panel first shows the panel
identification data
or
or
or
18
- for multimotor drives when the number of the motors connected to the drive is
variable
- when the nominal current of the motor is less than 1/6 of the nominal current of
the inverter
- when the inverter is used for test purposes with no motor connected.
ABB Motors
3
motor
V
690 Y
400 D
660 Y
380 D
415 D
440 D
Cat. no
6312/C3
IP 55
IA/IN t E/s
6210/C3
380 V
input
voltage
180
IEC 34-1
each of the nominal voltage ranges: 415 VAC for 400 VAC units, 500 VAC for 500
VAC units and 690 VAC for 600 VAC units.)
19
When the motor data has been entered, two displays (warning and
information) start to alternate. Move to next step without pressing
any key.
Note: If you select STANDARD ID Run, the brake is opened when
the Start command is given from the control panel and the brake
remains open until the STANDARD ID Run is completed. If you
select ID MAGN, the brake is kept closed during the ID Run
sequence.
20
forward
direction
reverse
direction
21
Ensure the drive is in external control mode. Press the LOC/REM key to
change between external and local control.
22
23
In general it is recommended not to press any control panel keys during the ID run.
However:
The Motor ID Run can be stopped at any time by pressing the control panel stop
key ( ).
After the ID Run is started with the start key ( ), it is possible to monitor the
actual values by first pressing the ACT key and then a double-arrow key ( ).