Академический Документы
Профессиональный Документы
Культура Документы
P631/P632/P633/P634
Transformer Differential Protection Devices
P63x/EN M/Aq6
Version
P631
P632
P633
P634
-305/306/307/308
-403/404/405/406/407/408
-610/611/620/621/622/630
-305/306/307/308
-403/404/405/406/407/408
-610/611/620/621/622/630
-305/306/307/308
-404/405/406/407/408/409/410/411/412
-610/611/620/621/622/630
-305/306/307/308
-403/404/405/406/407/408
-610/611/620/621/622/630
Technical Manual
Content
P63x/EN M/Ca4
P63x/EN AD/Ak6
P63x/EN AD/Am6
P63x/EN AD/An6
P63x/EN AD/Aq6
Volume 1 of 2
(-610)
(-611/620)
(-621)
(-622)
(-630)
MiCOM
P631/P632/P633/P634
Transformer Differential Protection Devices
P63x/EN M/Ca4
(AFSV.12/09701 D)
Version
P631
P632
P633
P634
-305
-305
-305
-305
Technical Manual
-403/404
-403/404
-404/405/406
-403/404
-610
-610
-610
-610
Warning
When electrical equipment is in operation, dangerous voltage will be present in certain parts of the
equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the device must be isolated. Where stranded conductors
are used, wire end ferrules must be employed.
Proper and safe operation of this device depends on appropriate shipping and handling, proper
storage, installation and commissioning, and on careful operation, maintenance, and servicing.
For this reason only qualified personnel may work on or operate this device.
Any modifications to this device must be in accordance with the manual. If any other modification
is made without the express permission of Schneider Electric, it will invalidate the warranty, and
may render the product unsafe.
Qualified Personnel
are individuals who
are familiar with the installation, commissioning and operation of the device and of the system to which it is being
connected;
are able to perform switching operations in accordance with safety engineering standards and are authorized to
energize and de-energize equipment and to isolate, ground, and label it;
are trained in the care and use of safety apparatus in accordance with safety engineering standards;
are trained in emergency procedures (first aid).
Note:
The operating manual for this device gives instructions for its installation, commissioning, and operation.
However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In
the event of questions or specific problems, do not take any action without proper authorization. Contact the
appropriate Schneider Electric technical sales office and request the necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric,
including settlement of warranties, result solely from the applicable purchase contract, which is not affected by the
contents of the operating manual.
11
12
Contents
1-1
2
2.1
2.2
2.3
2.3.1
2.3.2
2.4
2.5
2.6
2.7
2.8
2.9
2.9.1
2.9.2
2.9.3
2.10
2.11
2.12
Technical Data
Conformity
General Data
Tests
Type tests
Routine Tests
Environmental Conditions
Inputs and Outputs
Interfaces
Information Output
Settings
Deviations
Deviations of the Operate Values
Deviations of the Timer Stages
Deviations of Measured Data Acquisition
Recording Functions
Power Supply
Current Transformer Specifications
2-1
2-1
2-1
2-2
2-2
2-5
2-5
2-6
2-8
2-11
2-11
2-12
2-12
2-13
2-14
2-15
2-16
2-17
13
Contents
(continued)
3
3.1
3.2
3.3
3.4
3.4.1
3.4.2
3.4.3
3.4.4
3.4.5
3.4.5.1
3.4.5.2
5.4.5.3
3.5
3.6
3.7
3.7.1
3.7.2
3.8
3.9
3.9.1
3.9.2
3.9.3
3.10
3.11
3.11.1
3.11.2
3.11.3
3.11.4
3.11.5
3.11.6
3.11.7
3.11.8
3.11.9
3.11.10
3.11.11
3.11.12
3.11.13
14
Operation
Modular Structure
Operator-Machine Communication
Configuration of the Measured
(Function Group LOC)
Value Panels
Serial Interfaces
PC interface
(Function Group PC)
Communication Interface
(Function Group COMM1)
3-1
3-1
3-3
3-4
Communication Interface 2
UCA2 Communication Interface
IEC 61850 Communication
Interface
IEC 61850 Communication
Interface
Generic Object Oriented
Substation Event
Generic Substation State Event
IRIG-B Clock Synchronization
Configuration and Operating Mode
of the Binary Inputs
Measured data input
Direct Current Input
Input for Connection of a
Resistance Thermometer
Configuration, Operating Mode,
and Blocking of the Output Relays
Measured data output
BCD Measured Data Output
Analog Measured Data Output
Output of External Measured
Data
Configuration and Operating Mode
of the LED Indicators
Main Functions of the P63x
Conditioning of the Measured
values
Phase Reversal Function
Selection of the Residual Current
to be Monitored
Forming a Virtual Transformer End
Operating Data Measurement
Configuring and Enabling the
Protection Functions
Activation of Dynamic Parameters
Multiple Blocking
Multiple Signaling of the
Measuring Circuit Monitoring
Function
Blocked / Faulty
Starting Signals and Tripping
Logic
Time Tagging and Clock
Synchronization
Resetting Mechanisms
3-18
3-21
3-22
3.25
3-27
3-29
3-30
3-31
3-32
3-36
3-37
3-40
3-43
3-45
3-51
3-52
3-56
3-56
3-7
3-7
3-9
3-22
3-60
3-62
3-64
3-66
3-79
3-81
3-82
3-84
3-85
3-86
3-90
3-92
Contents
(continued)
3.11.14
3-24
Assigning Communications
Interfaces to Physical
Communications Channels
Test mode
Parameter Subset Selection
Self-Monitoring
Operating Data Recording
Monitoring Signal Recording
Overload Data Acquisition
Overload Recording
Fault Data Acquisition
Fault Recording
Differential Protection
Ground Differential Protection (Br:
Restricted earth fault protection)
Definite-Time Overcurrent
Protection
Inverse-Time Overcurrent
Protection
Thermal Overload Protection
3.25
3.26
3.27
3.28
3.29
Time-Voltage Protection
Over-/Underfrequency Protection
Overfluxing Protection
Current Transformer Supervision
Measuring-Circuit Monitoring
3.30
3.31
3.11.15
3.12
3.13
3.14
3.15
3.16
3.17
3.18
3.19
3.20
3.21
3.22
3.23
3.32
3-93
3-94
3-95
3-97
3-100
3-101
3-102
3-105
3-108
3-116
3-122
3-145
3-157
3-167
3-183
3-193
3-196
3-202
3-210
3-218
3-221
3-224
3-227
15
Contents
(continued)
16
4
4.1
4.2
Design
Designs
Modules
4-1
4-1
4-9
5
5.1
5.2
5.3
5.4
5.5
5.6
5.6.1
5.6.2
5.6.3
5-1
5-1
5-1
5-2
5-3
5-14
5-15
5-15
5-18
5-18
6
6.1
6.2
6.3
6.4
6.5
6.5.1
6.5.2
6.5.3
6.5.4
6.5.5
6.5.6
6.5.7
6.5.8
6.5.9
6-1
6-2
6-6
6-7
6-7
6-8
6-8
6-9
6-10
6-13
6-14
6-15
6-19
6-20
6-21
7
7.1
7.1.1
7.1.2
7.1.3
7.1.3.1
7.1.3.2
7.1.3.3
Settings
Parameters
Device Identification
Configuration Parameters
Function Parameters
Global
General Functions
Parameter Subsets
7-1
7-1
7-2
7-6
7-50
7-50
7-55
7-67
Contents
(continued)
8
8.1
8.1.1
8.1.1.1
8.1.1.2
8.1.1.3
8.1.2
8.1.3
8.2
8.2.1
8.2.2
8.2.3
8-1
8-1
8-1
8-1
8-8
8-15
8-33
8-37
8-38
8-38
8-39
8-42
9
9.1
9.2
Commissioning
Safety Instructions
Commissioning Tests
9-1
9-1
9-3
10
Troubleshooting
10-1
11
Maintenance
11-1
12
Storage
12-1
13
13-1
14
14.1
14.2
14.3
14.4
Order Information
Order Information for P631 in 40TE case
Order Information for P632 in 40TE case
Order Information for P633 in 40TE or 84TE case
Order Information for P634 in 84TE case
14-1
14-1
14-2
14-3
14-4
Appendix
A Glossary
B Signal List
C Terminal connection diagrams
D Overview of Changes
Address list:
See chapters 7, 8 and 10, as well as the MiCOM S1 / S&R-103
support software.
17
18
The P63x differential protection devices are designed for the fast and selective shortcircuit protection of transformers, motors and generators and of other two-, three- or
four-winding end arrangements.
The MiCOM P63x range features fast three-stage differential protection by applying a
tripping characteristic with two knee points and two high value settable differential
current thresholds to enable rapid tripping in conjunction with inrush, overfluxing and
through-stabilization. Amplitude and vector group matching is made by just entering the
nominal values of each transformer end and the associated current transformers.
A new (optional) overreaching current measuring circuit monitoring function will prevent
unwanted tripping by differential protection for faults in the CT's secondary circuit.
When considering 1 circuit breaker arrangements and ring busbar arrangements it is
also possible to define a virtual end, where phase currents and the residual current from
two freely-selectable ends may be added geometrically (vector sum).
A phase reversal function is available for applications in pumped storage power stations.
In a device type where protection functions are available more than once they may each
be freely assigned to individual winding ends.
Moreover there are numerous backup protection and automatic control functions
available.
The relevant protection parameters can be stored in four independent parameter
subsets in order to adapt the protection device to different operating and power system
management conditions.
1-1
General functions
General functions are complete function groups, which may be individually configured or
cancelled, depending on the application (e.g. included in or excluded from the devices
configuration).
An exception is the M A I N function, which is always visible.
A function is selected by a mouse click in the support software:
Unused or cancelled function groups are hidden to the user, thus simplifying the menu.
Communication functions and measured value functions may also be configured or
excluded.
This concept provides a wide choice of functions and makes wide-ranging application of
the protection device possible, with just one model version. On the other hand simple
and clear parameter settings and adaptations to each protection scheme can be made.
The powerful programmable logic provided by the protection device also makes it
possible to accommodate special applications.
1-2
General Functions
87
DIFF
Differential protection
P631
P632
P633
P634
2 ends
2 ends
3 ends
4 ends
REF_x
50
DTOCx
51
IDMTx
49
THRMx
27 / 59
V<>
Time-voltage protection
81 O/U
f<>
Over-/underfrequency protection
24
U_f
Overfluxing protection
CTS
optional
optional
optional
optional
MCM_x
Measuring-circuit monitoring
LIMIT, LIM_x
LOGIC
Programmable logic
Communication Functions
COMM1, COMM2
2 information interfaces
IRIGB
IRIG-B
Input/output functions
INP / OUTP
Measuring inputs
Phase currents
Resultant current and neutral-point current
Voltage
P63x
options
P631
P632
P633
P634
4 / 14
34 / 22
40 / 30
34 / 22
P631
P632
P633
P634
optional
optional
optional
P631
P632
P633
P634
2x3
-
2x3
2
1
3x3
3
1
4x3
3
1
1-3
Global functions
In addition to the listed features and extensive self-monitoring, the P63x offers the
following global functions:
Global functions
PSS
OP_RC
OL_DA
OL_RC
FT_DA
FT_RC
Further functions
Further functions
1-4
MAIN
DVICE
Main function
Device
LED
LOC
PC
LED indicators
Local control panel
PC link
SFMON
MT_RC
Comprehensive self-monitoring
Monitoring Signal Recording
Functional diagram
Communication
Iph
COMM1
COMM2
Inter
MiCOM
IEC
IRIG-B
Self
Monitoring
LOGIC
LIM-3
LIM-2
LIM-1
Recording
and
Data
Acquisition
Metering
Overload rec.
Fault rec.
V
IY,a
27, 59
V<>
81
f<>
24
V/f
IY,b
Iph
IY,c
87
DIFF
87G
REF_3
50
DTOC-3
51
IDMT-3
87G
REF_2
50
DTOC-2
51
IDMT--2
49
THRM2
BC _3
87G
REF_1
50
DTOC-1
51
IDMT--1
49
THRM1
BC_2
BC_4
BC_1
Iph
Iph
Ivirtual
RTD,mA
mA_OP
always available
optional or specific
Transformer Differential
Protection P63x
1-5
Design
The MiCOM P631, P632, P633 and P634 protection devices are modular in design.
The plug-in modules are housed in a robust aluminum case and electrically
interconnected via one analog p/c board and one digital p/c board.
The nominal current and voltage values of the measuring inputs on the P63x can be set
with the function parameters.
The nominal voltage range of the optical coupler inputs is 24 to 250 V DC. As an option
binary signal input modules with a higher operate threshold are available.
The auxiliary voltage input for the power supply is also designed for an extended range.
The nominal voltage ranges are 48 to 250 V DC and 100 to 230 V AC. A 24 VDC
version is also available.
All output relays can be utilized for signaling and command purposes.
The optional PT 100 input is lead-compensated, balanced and linearized for PT 100
resistance thermometers as per IEC 751.
The optional 0 to 20 mA input provides open-circuit and overload monitoring, zero
suppression defined by a setting, plus the option of linearizing the input variable via
20 adjustable interpolation points.
Two selectable measured values (cyclically updated measured operating data and
stored measured fault data) can be output as a burden-independent direct current via
the two optional 0 to 20 mA outputs. The characteristics are defined via 3 adjustable
interpolation points allowing a minimum output current (4 mA, for example) for slave-side
open-circuit monitoring, knee-point definition for fine scaling, and a limitation to lower
nominal currents (10 mA, for example). Where sufficient output relays are available,
a selectable measured value can be output in BCD-coded form by contacts.
1-6
Information interfaces
Information is exchanged through the local control panel, the PC interface, or two
optional communication interfaces (channel 1 and channel 2).
Using the first communication interface, the numerical protection device can be wired
either to the substation control system or to a telecontrol system.
The first communication interface is optionally available with a switcheable protocol
(per IEC 60870-5-103, IEC 870-5-101, DNP 3.0, MODBUS or Courier) or as an
IEC 61850 interface.
The second communication interface (communication protocol per IEC 60870-5-103
only) is designed for remote control.
External clock synchronization can be accomplished by using the optional IRIG-B input.
1-7
Overview of all
function groups
IDMT1:
IDMT2:
IDMT3:
OUTP:
OP_RC:
DIFF:
REF_1:
REF_2:
REF_3:
INP:
f<>:
DVICE:
GOOSE:
LIMIT:
MAIN:
LIM_1:
LIM_2:
LIM_3:
GSSE:
IEC:
IRIGB:
COMM1:
COMM2:
LED:
LOGIC:
MEASO:
MEASI:
MCM_1:
MCM_2:
MCM_3:
MCM_4:
PC:
PSS:
SFMON:
CTS:
FT_RC:
FT_DA:
THRM1:
THRM2:
V<>:
V/f:
OL_RC:
OL_DA:
DTOC1:
DTOC2
DTOC3:
MT_RC:
UCA2:
LOC:
1-8
P631
P632
P633
P634
9
9
9
9
9
-
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
2 Technical Data
2
2.1
Notice
Declaration of conformity
Conformity
Technical Data
General Data
Design
Surface-mounted case suitable for wall installation or flush-mounted case for
19" cabinets and for control panels.
Installation Position
Vertical 30
Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.
IP 52; IP 20 for rear connection space with flush-mounted case
(IP 10 for ring-terminal connection)
Weight
40TE case: Approx. 7 kg; 84TE case: Approx. 11 kg
Dimensions and Connections
See dimensional drawings (Chapter 4) and terminal connection diagrams (Chapter 5).
Terminals
PC interface (X6):
EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin.
Communication Interface:
Optical fibers (X7 and X8):
or
Leads (X9 and X10):
BNC plug.
2-1
2 Technical Data
(continued)
Tests
Type Tests
For this EN, ENV or IEC standard, the DIN EN, DINV ENV or DIN IEC edition,
respectively, was used in the test.
2-2
2 Technical Data
(continued)
Voltage Test
Per EN 61010-1 and IEC 255-5.
2 kV AC, 60 s.
Only direct voltage (2.8 kV DC) must be used for the voltage test on the power supply
inputs. The PC interface must not be subjected to the voltage test.
Impulse Voltage Withstand Test
Per IEC 255-5.
Front time: 1.2 s
Time to half-value: 50 s
Peak value: 5 kV
Source impedance: 500 W
2-3
2 Technical Data
(continued)
Mechanical robustness
1(**)
Vibration Test
Per EN 60255-21-1 or IEC 255-21-1, test severity class 1
Frequency range in operation:
10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Frequency range during transport: 10 to 150 Hz, 1 g
Shock Response and Withstand Test, Bump Test
Per EN 60255-21-2 or IEC 255-21-2,
acceleration and pulse duration:
Shock Response tests are carried out to verify full operability (during operation),
test severity class 1 ,
5 g for 11 ms,
Shock Withstand tests are carried out to verify the endurance (during transport),
test severity class 1 ,
15 g for 11 ms
Seismic Test
Per EN 60255-21-3 or IEC 60255-21-3, test procedure A, class 1
Frequency range:
5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s2, 3 x 1 cycle.
Mechanical robustness
2(**)
Vibration Test
Per EN 60255-21-1 or IEC 255-21-1, test severity class 2
Frequency range in operation:
10 to 60 Hz, 0.075 mm and 60 to 150 Hz, 1.0 g
Frequency range during transport: 10 to 150 Hz, 2 g
Shock Response and Withstand Test, Bump Test
Per EN 60255-21-2 or IEC 255-21-2,
acceleration and pulse duration:
Shock Response tests are carried out to verify full operability (during operation),
test severity class 2,
10 g for 11 ms;
Shock Withstand tests are carried out to verify the endurance (during transport),
test severity class 1,
15 g for 11 ms
Shock bump tests are carried out to verify permanent shock (during transport),
test severity class 1,
10 g for 16 ms
Seismic Test
Per EN 60255-21-3 or IEC 60255-21-3, test procedure A, class 2
Frequency range:
5 to 8 Hz, 7.5 mm / 3.5 mm, 8 to 35 Hz, 20 / 10 m/s2, 3 x 1 cycle.
(**)
Mechanical robustness 2:
Valid for with delivery date as of May 2005, if one of the following case variants is
used:
Flush mounted case, flush-mounting method 2 (with angle brackets and frame)
Surface-Mounted Case
2-4
2 Technical Data
(continued)
2.3.2
Routine Tests
Environmental Conditions
Temperatures
Recommended temperature range: -5C to +55C (23F to 131F)
Storage and transit: -25 C to +70 C (-13 F to +158 F)
Ambient Humidity Range
75 % relative humidity (annual mean),
56 days at 95 % relative humidity and 40 C (104F), condensation not permitted.
Solar Radiation
Direct solar radiation on the front of the device must be avoided.
2-5
2 Technical Data
(continued)
2.5
Measuring inputs
Current
Rated current: 1 or 5 A AC (settable).
Nominal burden per phase: < 0.13 VA at Inom
Load rating:
continuous: 4 Inom
for 10 s: 30 Inom
for 1 s: 100 Inom
Nominal surge current: 250 Inom
Voltage
Nominal voltage Vnom: 50 to 130 V AC (adjustable)
Nominal burden per phase: < 0.3 VA at Vnom = 130 V AC
Load rating: continuous 150 V AC
Frequency
Nominal frequency fnom: 50 Hz and 60 Hz (adjustable)
Operating range: 0.95 to 1.05 fnom
Frequency protection: 40 to 70 Hz
All other protection functions:
Operating range: 0.95 to 1.05 fnom
Overfluxing protection: 0.5 to 1.5 fnom
2-6
2 Technical Data
(continued)
IRIG-B interface
Resistance thermometer
inputs
Output relays
2-7
2 Technical Data
(continued)
2.6
Local control panel
Interfaces
Input or output:
via seven keys and a 4 x 20 character-LCD display
State and fault signals:
17 LED indicators (13 permanently assigned, 4 freely configurable)
PC interface
Communication interfaces
1 and 2
Communication Protocol
BA-no. -910
(one channel)
IEC 60870-5-103
BA-no. -921
(two channels)
1)
Distance to be bridged given for identical optical outputs and inputs at both ends, a
system reserve of 3 dB, and typical fiber attenuation.
2-8
2 Technical Data
(continued)
Communication Protocol
BA-no. -910
(one channel)
IEC 60870-5-103
BA-no. -922
(two channels)
Communication Protocol
BA-no. -910
(one channel)
IEC 60870-5-103
BA-no. -924
(two channels)
1)
Distance to be bridged given for identical optical outputs and inputs at both ends, a
system reserve of 3 dB, and typical fiber attenuation.
2-9
2 Technical Data
(continued)
IRIG-B interface
B122 format
Amplitude modulated signal
Carrier frequency: 1 kHz
BCD-coded variation data (daily)
2-10
2 Technical Data
(continued)
2.7
Information Output
Settings
Main function
Minimum output pulse duration for a trip command:
0.1 to 10 s (adjustable)
Differential Protection
Operate time at Id = 10 Idiff> with inrush restraint disabled, or at Id > Idiff>>>:
at least 13 ms, typically 15 ms.
Operate time at Id = 2.5 Idiff> with inrush restraint disabled:
at least 19 ms, typically 21 ms.
Operate time at Id = 2.5 Idiff> with inrush restraint enabled:
at least 30 ms, typically 33 ms.
Definite-time and inverse-time overcurrent protection
Operate time including output relay (measured value from 0 to 2-fold operate value):
40 ms, approx. 30 ms
Reset time (measured value drops from 2-fold operate value to 0):
40 ms, approx. 30 ms
Starting resetting ratio: Approx. 0.95
Time-Voltage Protection
Operate time including output relay (measured value from nominal value to 1.2-fold
operate value or measured value from nominal value to 0.8-fold operate value):
40 ms, approx. 30 ms
Reset time (measured value from 1.2-fold operate value to nominal value
or measured value from 0.8-fold operate value to nominal value):
45 ms, approx. 30 ms
Resetting ratio for V<>: 1 to 10 % (adjustable)
Overfluxing protection
Starting and measurement resetting ratio (hysteresis): 0.95
2-11
2 Technical Data
(continued)
2.9
2.9.1
Definitions
Deviations
Deviations of the Operate Values
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambient
temperature 20C (68F), and nominal auxiliary voltage VA,nom
Deviation
Deviation relative to the setting under reference conditions.
Differential Protection
Measuring system
Deviation for Idiff : 0.2 Iref: 5 %
Harmonic blocking: 10 %
Inrush Stabilization (Harmonic Restraint)
Deviation: 10 %
Ground differential
protection (Br: Restricted earth
fault protection)
Frequency protection
df/dt protection
Time-Voltage Protection
Overfluxing protection
Resistance thermometer
2-12
Measuring system
Deviation for Idiff : 0.2 Iref: 5 %
Deviation: 5 %
Deviation: 5 %
Operate Values
fnom = 50 Hz: Deviation: 30 mHz
fnom = 60 Hz: Deviation: 40 mHz
Operate Values
fnom = 50 Hz: Deviation: 0.1 Hz/s
fnom = 60 Hz: Deviation: 0.1 Hz/s
Deviation: 3 %
Deviation: : 3 %
Deviation: 1 %
Deviation: 2 or 1 %
2 Technical Data
(continued)
Deviation: 1 %
Output residual ripple with max. load: 1 %
2.9.2
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambient
temperature 20 C (68F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Definite-time stages
Deviation: 1 % or + 20 ms to 40 ms
Inverse-time stages
Deviation when I 2 Iref: 5 % + 10 to 25 ms
or for IEC 'Extremely Inverse', thermal overload and V/f characteristics:
7.5 % + 10 to 20 ms
Limit Value Monitoring
2-13
2 Technical Data
(continued)
2.9.3
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambient
temperature 20 C (68F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Fault data
Internal clock
2-14
2 Technical Data
(continued)
Overload memory
Fault memory
Depth:
Depth:
Up to 30 signals
Depth:
Signals:
All fault-relevant signals from a total of 1024 different
logic state signals
Depth for fault values:
Sampled values for all measured currents and voltages
2-15
2 Technical Data
(continued)
Fault values
Voltage
Time resolution: 1 ms
Time resolution: 20 sampled values per period
Dynamic range:
Amplitude resolution
33 Inom
at Inom = 1 A: 2 mA r.m.s.
at Inom = 5 A: 10.1 mA r.m.s.
Dynamic range:
Amplitude resolution:
150 V AC
9.2 mVrms
40TE
84TE
Relays de-energized,
approx.:
13 W
13 W
Relays energized
approx.:
29 W
37 W
2-16
2 Technical Data
(continued)
'
Vsat = (R nom + R i ) n Inom R op + R i k I1,
max
with:
Vsat:
I'1,max:
Inom:
n:
k:
Rnom:
Rop
Ri
The specifications of a current transformer can then be calculated for the minimum
required saturation voltage Vsat as follows:
'
Vsat R op + R i k I1,
max
(R op + R i )
(R nom + R i )
'
I1,
max
Inom
(Pop + Pi )
(Pnom + Pi )
'
I1,
max
Inom
With
2
Pnom = R nom Inom
2
Pop = R op Inom
2
Pi = R i Inom
Theoretically, the specifications of the current transformer could be calculated for lack of
saturation by inserting instead of the required over-dimensioning factor k its maximum
value:
k max 1 + T1
with:
:
T1:
2-17
2 Technical Data
(continued)
However, this is not necessary. Instead, it is sufficient to calculate the overdimensioning factor k such that the normal behavior of the analyzed protective function
is guaranteed under the given conditions.
The transformer differential protection device is equipped with a saturation discriminator.
This function will generate a stabilizing blocking signal if a differential current occurs as a
consequence of transformer saturation with an external fault (in contrast to an internal
fault). For the passing maximum fault current in the case of an external fault,
overdimensioning is, therefore, obviated.
For the maximum fault current with an internal fault, static saturation up to a maximum
saturation factor fS of 4 is permissible. This corresponds to an overdimensioning
factor k of 0.25.
The implementation of these requirements is comparatively unproblematic as
transformer differential protection would require overdimensioning in accordance with the
total fault clearing time, which includes the total circuit-breaker open time for an external
fault.
Current transformers should observe the error limit values for class 5P.
2-18
3 Operation
3
3.1
Operation
Modular Structure
The P63x, a numeric device, is part of the MiCOM P 30 family of devices. The device
types included in this family are built from identical uniform hardware modules.
Figure 3-1 shows the basic hardware structure of the P63x.
3-1
3-1
3 Operation
(continued)
The external analog and binary quantities electrically isolated are converted to the
internal processing levels by the peripheral modules T, Y, and X. Commands and
signals internally generated by the device are connected to the external plant via
contacts through the binary I/O modules X. The external auxiliary voltage is applied to
the power supply module V, which supplies the auxiliary voltages that are required
internally.
Analog data is transferred from the transformer module T via the analog bus module B to
the processor module P. The processor module contains all the elements necessary for
the conversion of measured analog variables, including multiplexers and analog/digital
converters. The analog data conditioned by the analog I/O module Y is transferred to
the processor module P via the digital bus module. Binary signals are fed to the
processor module by the binary I/O modules X via the digital bus module.
The processor handles the processing of digitized analog variables and of binary signals,
generates the protective trip and signals, and transfers them to the binary I/O modules X
via the digital bus module. The processor module also handles overall device
communication. As an option, communication module A can be mounted on the
processor module to provide serial communication with substation control systems.
The control and display elements of the integrated local control panel and the integrated
PC interface are housed on control module L.
3-2
3 Operation
(continued)
3.2
Operator-Machine Communication
The following interfaces are available for the exchange of information between the user
and the device:
PC interface
Communication interface
All settings and signals as well as all measurements and control functions are arranged
within the branches of the menu tree following a scheme that is uniform throughout the
device family. The main branches are:
Parameters branch
Operation branch
Events branch
All settings are contained in this branch. This branch carries all settings, including the
device identification data, the configuration parameters for adapting the device interfaces
to the system, and the function parameters for adapting the device functions to the
process. All values in this group are stored in non-volatile memory, which means that
the values will be preserved even if the power supply fails.
This branch includes all information relevant for operation such as measured operating
data and binary signal states. This information is updated periodically and consequently
is not stored. In addition, various controls are grouped here, for example those for
resetting counters, memories and displays.
The third branch is reserved for the recording of events. All information in this group is
therefore stored. In particular, the start/end signals during a fault, the measured fault
data, and the sampled fault waveforms are stored here and can be read out when
required.
Settings and signals are displayed either in plain text or as addresses, in accordance
with the users choice. Chapters 7, 8 and 10 describe the settings, signals and
measured values available with the P63x. The possible setting values can be found in
the P63x's data model file associated with the PC operating program (MiCOM S1).
The configuration of the local control panel also permits the installation of Measured
Value 'Panels on the LCD display. Different Panels are automatically displayed for
specific system operating conditions. Priority increases from normal operation to
operation under overload conditions and finally to operation following a short circuit in
the system. Thus the P63x provides the measured data relevant for the prevailing
conditions.
3-3
3 Operation
(continued)
3.3
The P63x offers Measured Value Panels, which display the measured values relevant at
a given time.
During normal power system operation, the Operation Panel is displayed. As an event
occurs, the display switches to the appropriate Event Panel - provided that measured
values have been selected for the Event Panels. In the event of overload event, the
display will automatically switch to the Operation Panel at the end of the event. In the
event of a fault, the Fault Panel remains active until the LED indicators or the fault
memories are reset.
Operation Panel
The Operation Panel is displayed after the set return time has elapsed, provided that at
least one measured value has been configured.
The user can select which of the measured operating values will be displayed on the
Operation Panel by means of an m out of n parameter. If more measured values are
selected for display than the LC display can accommodate, then the display will switch to
the next set of values at intervals defined by the setting at L O C : H o l d - T i m e fo r
P a n e l s or when the appropriate key on the local control panel is pressed.
3-2
3-4
Operation Panel
3 Operation
(continued)
Fault panel
The Fault Panel is displayed in place of another data panel when there is a fault,
provided that at least one measured value has been configured. The Fault Panel
remains on display until the LED indicators or the fault memories are cleared.
The user can select the measured fault values that will be displayed on the Fault Panel
by setting an 'm out of n' parameter. If more measured values are selected for display
than the LC display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at L O C : H o l d - T i m e fo r P a n e l s or when
the appropriate key on the local control panel is pressed.
3-3
Fault panel
3-5
3 Operation
(continued)
Overload Panel
The Overload Panel is automatically displayed in place of another data panel when there
is an overload, provided that at least one measured value has been configured.
The Overload Panel remains on display until the overload ends, unless a fault occurs.
In this case the display switches to the Fault Panel.
The user can select the measured values that will be displayed on the Overload Panel
by setting a 'm out of n' parameter. If more measured values are selected for display
than the LC display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at L O C : H o l d - T i m e fo r P a n e l s or when
the appropriate key on the local control panel is pressed.
3-4
3-6
Overload Panel
3 Operation
(continued)
3.4
Serial Interfaces
Communication between the device and a PC is through the PC interface. In order for
data transfer between the P63x and the PC to function, several settings must be made in
the P63x.
There is a support software available as an accessory for P63x control (see Chapter 13).
3-7
3 Operation
(continued)
3-5
3-8
PC interface settings
3 Operation
(continued)
3.4.2
Communication between the P63x and the control stations computer is done through
the communication interface. Depending on the design version of communications
module A (see "Technical Data") there are several interface protocols available.
The IEC 60870-5-103 protocol is always supported. The following user-selected
interface protocols are available for use with the P63x:
MODBUS
DNP 3.0
COURIER
In order for data transfer to function properly, several settings must be made in the P63x.
Communication interface 1 can be blocked through a binary signal input. In addition,
a signal or measured-data block can also be imposed through a binary signal input.
3-9
3 Operation
(continued)
3-6
3-10
3 Operation
(continued)
3-7
3-11
3 Operation
(continued)
3-8
3-12
3 Operation
(continued)
3-9
3-13
3 Operation
(continued)
3-10
3-14
3 Operation
(continued)
3-11
3-15
3 Operation
(continued)
3-12
3-16
3 Operation
(continued)
Checking spontaneous
signals
3-13
3-17
3 Operation
(continued)
3.4.3
3-18
3 Operation
(continued)
3-14
3-19
3 Operation
(continued)
Checking spontaneous
signals
It is possible to select a signal for test purposes. The transmission of this signal to the
control station as sig. start or sig. end can then be triggered via setting parameters.
Spontan.
signal start
Spontan.
signal end
3-15
3-20
3 Operation
(continued)
3.4.4
This function group is available only with the P63x -604/-605/-606 device.
(As of device version P63x 610, the IEC 61850 communication interface is available:
it uses function groups IEC, GOOSE and GSSE. A description is provided in the
following section).
The communication protocol Utility Communication Architecture 2.0 is implemented with
the UCA2 function group and the Ethernet module (in the 10 MHz and 100 MHz
variants).
Function group UCA2 is only available as an alternative to function group COMM1
(hardware ordering option!). Pending the implementation of the IEC 61850 protocol,
the use of UCA2 is reserved for specific projects.
The UCA2 addresses for setting, information and control functions are described in
chapters 7 and 8.
(See also the detailed description of the UCA2 protocol implementation:
P54x_EN_UC_B42.pdf).
3-21
3 Operation
(continued)
3.4.5
These function groups are available only with the P63x -610 device.
The IEC 61850 communication protocol is implemented by these function groups and the
Ethernet module.
Note:
Function group IEC is only available as an alternative to function group COMM1
(hardware ordering option!).
3.4.5.1 IEC 61850 Communication Interface (Function Group IEC)
IEC 61850
IEC 61850 was created jointly by users and manufacturers as an international standard.
The main target of IEC 61850 is interoperability of devices. This includes the capability
of two or more intelligent electronic devices (IED), manufactured by the same company
or different companies, to exchange data for combined operation.
Now this new communication standard IEC 61850 has created an open and common
basis for communication from the process control level down to the network control level,
for the exchange of signals, data, measured values and commands.
For a standardized description of all information and services available in a field device a
data model, which lists all visible functions, is created. Such a data model, specifically
created for each device, is used as a basis for an exchange of data between the devices
and all process control installations interested in such information. In order to facilitate
engineering at the process control level a standardized description file of the device,
based on XML, is created with the help of the data model. This file can be imported and
processed further by the relevant configuration program used by the process control
device. This makes possible an automated creation of process variables, substations
and signal images.
The following documentation with the description of the IEC 61850 data model, used with
the P63x, is available:
3-22
IDC file based on XML in the SCL (Substation Configuration Description Language)
with a description of data, properties and services, available from the device, that are
to be imported into the system configurator.
3 Operation
(continued)
Ethernet Module
The optional Ethernet module provides an RJ45 connection and a fiber optic interface
where an Ethernet network can be connected. The selection which of the two interfaces
is to be used to connect to the Ethernet network is made by setting the parameter
I E C : E t h e r n e t m e d i a . The optical interface of the Ethernet module is currently
available with an SC connector (100 Mbit/s and 1300 nm). A variant with an ST
connector is being developed. The RJ45 connector supports 10 Mbit/s and 100 Mbit/s.
The optional Ethernet module additionally provides an RS485 interface for remote
access with the operating program MiCOM S1 (function group COMM2).
Notes:
The P63x may only be equipped with the optional Ethernet module as an
alternative to the standard optional communication module. Therefore the
Ethernet based communication protocol IEC 61850 is only available as an
alternative to function group COMM1.
The Ethernet module can only be applied in conjunction with the processor
module P (included in current hardware version) with the item number 9650
135 or other processor modules available in the near future. When upgrading
older P63x hardware versions with an Ethernet module, which is technically
possible, it must be kept in mind that such units are usually equipped with the
processor module P, item number 0337 875. But this processor module P
does not support the Ethernet module and therefore the communications
protocol per IEC 61850 is also not supported. If such an upgrade is carried
out the processor module P must be exchanged. The processor module item
number can be checked by reading the device identification setting at
DVICE: Module var. slot 1.
Client Log-on
3-23
3 Operation
(continued)
Clock Synchronization
With IEC 61850 clock synchronization occurs via the SNTP protocol, defined as standard
for Ethernet. Here the P63x functions as a SNTP client.
For clock synchronization one can select between the operating modes Broadcast from
SNTP Server or Request from Server. With the first operating mode synchronization
occurs by a broadcast message sent from the SNTP server to all devices in the network,
and in the second operating mode the P63x requests the device specific time signal
during a settable cycle.
Fault Transmission
Transmission of "Goose
Messages"
Direct access by the operating program MiCOM S1 via the Ethernet interface on the
device may occur through the "tunneling principle". Transmission is carried out by an
Ethernet Standard Protocol, but this is only supported by the associated operating
program MiCOM S1 (specific manufacturer solution). Such transmission is
accomplished over the same hardware for the network, which is used for server-client
communication and "Goose Messages".
Available are all the familiar functions offered by the operating program MiCOM S1 such
as reading/writing of setting parameters or retrieving stored data.
The various settings, measured values and signals for function group IEC are described
in chapters 7 and 8.
3-24
3 Operation
(continued)
Sending GOOSE
With GOOSE the P63x can transmit up to 32 logic binary state signals. Selection of
binary state signals is made by setting
G O O S E : O u t p u t n f c t . a s s i g . (n = 1 to 32). The assignment of data object
indexes to logic state signals is made in the range from 1 to 32 according to the
assignment to GOOSE outputs.
GOOSE is automatically sent with each new state change of a configured binary state
signal or an external device. There are numerous send repetitions in fixed ascending
time periods (10 ms, 20 ms, 50 ms, 100 ms, 500 ms, 1000 ms, 2000 ms). If after
2 seconds there is no further state change apparent, GOOSE is then sent cyclically at
2-second intervals.
3-25
3 Operation
(continued)
GOOSE-DataSet: LLN0$GooseST
Identification:
Data range:
Server nameSYSTEM/GosGGI01/Out1/stVal
Server nameSYSTEM/GosGGI01/Out2/stVal
Server nameSYSTEM/GosGGI01/Out32/stVal
64Z6090A_EN
3-16
3-26
3 Operation
(continued)
With GOOSE up to 16 logic binary state signals can be received. Configuration of the
logic state signals received (G O O S E : I n p u t n f c t . a s s i g . , where n = 1 to 16) is
made on the basis of the selection table of the binary inputs (opto coupler inputs).
For each state signal to be received from an external device the "Goose Message" must
be selected that includes the information wanted by setting the Goose ID, the Application
ID and the 'Dataset Reference'. With the further setting of the data object index and the
data attribute index through parameters, the required information from the chosen
GOOSE will be selected. The device will not evaluate the identification features VLAN
identifier and Dataset Configuration Revision that are also included in the GOOSE
received.
Each GOOSE includes time information on the duration of validity of its information.
This corresponds to the double time period to the next GOOSE repetition. If the duration
of validity has elapsed without having received this GOOSE again (i.e. because of a
communications fault), the received signals will automatically be set to their respective
default values G O O S E : I n p u t n d e f a u l t o r G O O S E : E x t . D e v . n d e f a u l t
(n = 1 to 16).
The various settings, measured values and signals for function group GOOSE are
described in chapters 7 and 8.
3.4.5.3 Generic Substation State Event (Function Group GSSE)
For high-speed exchange of information between individual IEDs (intelligent electronic
devices) in a local network, the P63x provides, as an additional functionality, the function
group GSSE (UCA2.0-GOOSE) as defined in the IEC 61850 standard. GSSE features
high-speed and secure transmission of logic binary state signals such as trip commands,
blocking, enabling and other signals.
Activating and Enabling
3-27
3 Operation
(continued)
Sending GSSE
With GSSE up to 32 logic binary state signals can be sent. Selection of binary state
signals is made by setting
G S S E : O u t p u t n f c t . a s s i g . (n = 1 to 32). Each state signal selected is to be
assigned to a bit pair in GSSE (G S S E : O u t p u t n b i t p a i r (n = 1 to 32)), which
will transmit this state signal.
GSSE is automatically sent with each state change of a selected state signal. There will
be multiple send repetitions at ascending time periods. The first send repetition occurs
at the given cycle time set with the parameter G S S E : M i n . c y c l e . The cycles for
the following send repetitions result from a conditional equation with the increment set
with the parameter G S S E : I n c r e m e n t . Should no further state changes occur up to
the time when the maximum cycle time has elapsed (G S S E : M a x . c y c l e ) , then
GSSE will be sent cyclically at intervals as set for the max. cycle time.
In order to have unambiguous identification of a GSSE sent, the IED name is used which
was set in function group IEC.
Receiving GSSE
With GSSE up to 32 logic binary state signals can be received. Configuration of the logic
binary state signals received (G S S E : I n p u t n f c t . a s s i g . , where n = 1 to 32) is
made on the basis of the selection table of the binary inputs (opto coupler inputs).
For each state signal to be received, the GSSE message, which will include the required
information, must be selected by setting the IED name (G S S E : I E D n a m e ) .
Selection of information wanted from the selected GSSE will occur by setting the bit pair
(G S S E : b i t p a i r ) .
Each GSSE includes time information on the duration of validity of its information.
This corresponds to the double time period to the next GSSE repetition. If the duration
of validity has elapsed without having received this GSSE again (i.e. because of a
communications fault), the signals received will automatically be set to their respective
default value ( G S S E : I n p u t n d e f a u l t (n = 1 to 32)).
The various settings, measured values and signals for function group GSSE are
described in chapters 7 and 8.
3-28
3 Operation
(continued)
3.5
If, for example, a GPS receiver with IRIG-B connection is available, the internal clock of
the P63x can be synchronized to run on GPS time using the optional IRIG-B interface.
It should be noted that the IRIG-B signal holds information on the day only (day of the
current year). Using this information and the year set at the P63x, the P63x calculates
the current date (DD.MM.YY).
Disabling or enabling the
IRIG-B interface
Synchronization readiness
3-17
IRIG-B interface
3-29
3 Operation
(continued)
3.6
Configuration and Operating Mode of the Binary Inputs (Function Group INP)
The P63x has opto coupler inputs for processing binary signals from the substation.
The functions that will be activated in the P63x by triggering these binary signal inputs
are defined by the configuration of the binary signal inputs. The typical response time is
< 10 ms, although for reliability it is recommended that the initiating signal is maintained
for at least 30 ms.
Configuring the binary
inputs
One function can be assigned to each binary signal input by configuration. The same
function can be assigned to several signal inputs. Thus one function can be activated
from several control points having different signal voltages.
In this manual, we assume that the required functions (marked 'EXT' in the address
description) have been assigned to binary signal inputs by configuration.
It should be noted that time-critical applications such as time synchronization commands
should not be mapped to the binary signal inputs of the analog I/O module as these have
an increased reaction time due to internal processing.
3-18
3-30
The operating mode for each binary signal input can be defined. The user can specify
whether the presence (active 'high' mode) or the absence (active 'low' mode) of a
voltage should be interpreted as the logic '1' signal. The display of the state of a binary
signal input 'low' or 'high' is independent of the setting for the operating mode of the
signal input.
3 Operation
(continued)
3.7
The P63x has a measured data input function involving two inputs. Direct current is fed
to the P63x through one of the inputs. The other input is designed to connect a
resistance thermometer.
The input current IDC is displayed as a measured operating value. The current that is
conditioned for monitoring purposes (IDC,lin) is also displayed as a measured operating
value. In addition, it is monitored by the Limit Value Monitoring function to determine
whether it exceeds or falls below set thresholds (see "Limit Value Monitoring").
The measured temperature is also displayed as a measured operating value and
monitored by the limit value monitoring function to determine whether it exceeds or falls
below set thresholds (see "Limit Value Monitoring").
Disabling or enabling the
measured data input
function
3-19
The measured data input can be disabled or enabled via a setting parameter.
3-31
3 Operation
(continued)
3.7.1
IDClin / IDC,nom
1.2
1.1
IDClin20
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
IDClin1
0
0
0.1
0.2
IDC1
0.25
0.3
0.35
0.4
0.45
0.5
0.6
IDC/ IDC,nom
IDC20
D5Z52KDA
19Z5266A_EN
3-20
3-32
3 Operation
(continued)
IDClin / IDC,nom
0.8
Interpolation points
IDC,lin20
0.7
0.6
IDC,lin4
0.5
0.4
IDC,lin3
0.3
IDC,lin2
0.2
IDC,lin1
0.1
0
0
0.1
0.2
IDC1
0.3
0.4
0.5
IDC2
0.6
IDC3
0.7
0.8
0.9
IDC4
1.1
IDC20
3-21
1.2
IDC / IDC,nom
D5Z52KEB
D5Z52KEB _EN
Example of a characteristic with five interpolation points (characteristic with zero suppression setting of 0.1 IDC,nom is shown as a broken
line)
Zero suppression
The device is equipped with an open-circuit monitoring function. If current IDC falls below
the set threshold, M E A S I : I D C < o p e n c i r c u i t , the M E A S I : O p e n c i r c .
2 0 m A i n p . signal is issued.
The input current is monitored in order to protect the 20 mA input against overloading.
If it exceeds the fixed threshold of 24.8 mA, the M E A S I : O v e r l o a d 2 0 m A i n p u t
signal is issued.
3-33
3 Operation
(continued)
3-22
3-34
3 Operation
(continued)
Beyond the linearization described above, the user has the option of scaling the
linearized values. Thereby negative values, for example, can be displayed as well and
are available for further processing by protection functions.
3-23
3-35
3 Operation
(continued)
3.7.2
3-24
3-36
3 Operation
(continued)
3.8
The P63x has output relays for the output of binary signals. The binary signal
assignment is freely-configured by the user.
Configuration of the output
relays
One binary signal can be assigned to each output relay. The same binary signal can be
assigned to several output relays by configuration.
The user can set an operating mode for each output relay that determines whether the
output relay operates in a normally open arrangement (NO) or normally closed
arrangement (NC) and whether it operates in latching mode. Latching can be disabled
either manually via a setting parameter, or by an appropriately configured binary signal
input, at the onset of a new fault or of a new system disturbance, depending on the
selected operating mode.
The P63x offers the option of blocking all output relays via a setting parameter or by way
of an appropriately configured binary signal input. The output relays are likewise
blocked if the device is disabled via appropriately configured binary inputs.
In these cases the relays are treated according to their set operating mode, i.e. relays in
a normally open arrangement (NO) are not triggered, whereas relays in a normally
closed arrangement (NC) are triggered.
This does not apply to the relays associated with the signals
SF M O N : W a r n i n g ( r e l a y) or M AIN : Bl o c k e d /fa u l ty. Self-monitoring alarms are
thus correctly indicated.
If the self-monitoring detects a serious hardware fault (see error messages in chapter 10,
which will lead to a blocking of the protection), all output relays are reset regardless of
the set operating mode or signal configuration.
3-37
3 Operation
(continued)
3-25
3-38
Configuration, setting the operating mode, and blocking the output relays
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
3 Operation
(continued)
For testing purposes, the user can select an output relay and trigger it via a setting
parameter. Therefore the device must be switched to 'off-line'. Triggering persists for
the duration of the set hold time.
MAIN: Protection
enabled
No (off)
47Z1050A_EN
3-26
3-39
3 Operation
(continued)
3.9
Measured values made available by the P63x can be provided in BCD (binary coded
decimal) form through output relays or in analog form as direct current output. Output as
direct current can only occur if the device is equipped with analog module Y. BCD
output is always possible, whether the device is equipped with analog module Y or not.
Disabling or enabling the
measured data output
function
3-27
3-40
The measured data output can be disabled or enabled via a setting parameter.
3 Operation
(continued)
3-28
The measured data output can be enabled through a binary signal input, provided that
the function M E A S O : O u t p . e n a b l e d E X T has been configured. If the function
M E A S O : O u t p . e n a b l e d E X T has not been configured to a binary signal input, then
the measured data output is always enabled.
3-41
3 Operation
(continued)
3-29
Scaling
3-42
BCD or analog output of measured values is terminated for the duration of the hold time
if one of the following conditions is met:
The measured data output is reset either via a setting parameter or via an
appropriately configured binary signal input.
Scaling is used to map the physical measuring range to the device's inherent setting
range.
3 Operation
(continued)
3.9.1
The user can select a measured value for output in BCD form by assigning output relays.
The selected measured value is available in BCD form for the duration of the set hold
time M E A S O : H o l d T i m e O u t p u t B C D . If the selected variable was not measured,
then there is no output of a measured value.
Output of measured event
values
Output of measured
operating values
If the measured event value is updated during the hold time, the measured value output
memory is cleared and the hold time is re-started. This leads to an immediate availability
at the output of the updated value.
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is restarted. If the hold time has been set to 'blocked', the measured operating value that has
been output will be stored until the measured data output function is reset.
The resolution for measured data output is defined by setting the scaling factor.
The scaling factor should be selected so that the value 399 is not exceeded by the
maximum measured value to be output. If this should occur or if the measured value is
outside the acceptable measuring range, then the value for "Overflow" (all relays
triggered) is transmitted.
Mx,scal =
Mx,max
scaling factor
where:
Mx,scal : scaled measured value
Mx,max : maximum transmitted value for the selected measured value
3-43
3 Operation
(continued)
3-30
3-44
3 Operation
(continued)
3.9.2
Output of measured
operating values
Configuration of output
relays assigned to the
output channels
If the measured event value is updated during the hold time, the measured value output
memory is cleared and the hold time is re-started. This leads to an immediate availability
at the output of the updated value.
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is
re-started. If the hold time has been set to "blocked", the measured operating value that
has been output will be stored until the measured data output function is reset.
The user must keep in mind that direct current output only occurs when the output relays
assigned to the output channels are configured for M E A S O : V a l u e A - x o u t p u t ,
since the output channels would otherwise remain short-circuited (see terminal
connection diagrams).
3-45
3 Operation
(continued)
In order to define the resolution for measured data output the measured value range in
scaled form and the associated display range have to be set. One additional value for
the knee point must also be defined. In this way the user can obtain an analog output
characteristic similar to the characteristic shown in Figure 3-31.
The measured value range to be output is (Mx,min ... Mx,knee ... Mx,max),
with:
Mx,min:
minimum value to be output
Mx,knee: Knee point value for the measured value range to be output
Mx,max:
maximum value to be output
This measured value range to be output is defined by setting the following parameters:
Scaling is made with reference to the complete range of values for the selected
measured value (variable Mx). The complete range of values is defined by their end
values Mx,RL1 and Mx,RL2. (Mx,RL1 and Mx,RL2 are listed in the S&R-103 - PC MiCOM S1
Support Software - under "minimum" and "maximum".)
Measured values
Range
0 ... 1
Measured value to be
output
Range
3-46
3 Operation
(continued)
Measured values
Measured values:
Mx,RL1 = Mx = Mx,min
3-47
3 Operation
(continued)
Range
0 V ... 150 V
0 ... 1
Measured values to be
output
Range
Measured values
4 mA ... 16 mA ... 18 mA
3-48
Address
Description
Current value
056 020
031 074
053 000
010 114
037 104
037 105
037 106
037 107
037 108
037 109
With
Yes
MAIN:
Voltage A-B PU
1.00 s
0.013 (corresponds with
0.02 Vnom)
0.067 (corresponds with
0.10 Vnom)
0.667 (corresponds with
1.00 Vnom)
4 mA
16 mA
18 mA
3 Operation
(continued)
Ia / mA
20
Max.
output value18
Knee point
16
output value
14
12
10
8
6
Min.
output value 4
2
0
0
0.02
0.1
0,013
0,067
1.2
1.3
1.4
0,667
1.5 Vnom
1,0Mx,scal
D5Z52KFA
19Z5265A_EN
3-31
Example of a characteristic curve for analog measured data output . In this example the range starting value is = 0; also possible is
directional-signed output (see corresponding example in section BCD Measured Data Output).
3-49
3 Operation
(continued)
3-32
3-50
3 Operation
(continued)
3.9.3
Measured data from external devices, which must be scaled to 0 ... 100%, can be written
to the following parameters of the P63x via the communications interface.
These "external" measured values are output by the P63x either in BCD data form or as
load-independent direct current, provided that the BCD measured data output function or
the channels of the analogue measured data output function are configured accordingly.
3-51
3 Operation
(continued)
The P63x has 17 LED indicators for the indication of binary signals. Four of the LED
indicators are permanently assigned to fixed functions. The other LED indicators are
freely configurable.
One binary signal can be assigned to each of the freely configurable LED indicators
(example for H 5 : L ED : F c t. a s s i g n m . H 5 ). The same binary signal can be assigned
to several LED indicators, if required.
LED indicator
Label
Configuration
H1
'HEALTHY'
H 17
'EDIT MODE'
Not configurable. H 17 indicates the input (edit) mode. Only when the
device is in this mode, can parameter settings be changed by pressing
the and keys. (See Chapter 6, section 'Display and Keypad')
H2
'OUT OF SERVICE'
H3
'ALARM'
H4
'TRIP'
H 5 to H 16
----
The drawing below shows the layout of the LED indicators situated on the local control
panel.
3-52
3 Operation
(continued)
H4
TRIP
H5
H3
ALARM
H6
H2
OUT OF SERVICE
H7
H1
HEALTHY
H8
H17
EDIT MODE
H9
= CLEAR
= READ
= ENTER
H10
H11
H12
H13
H14
H15
H16
64Z6000A_EN
3-33
3-53
3 Operation
(continued)
3-54
The mode determines whether a logic "1" will light the LED, defined as a follower mode,
or whether the binary signal is inverted such that a logic zero will light the LED. Latching
is disabled either manually via a setting parameter or by an appropriately configured
binary signal input (see "Main Functions of the P63x"), at the onset of a new fault or of a
new system disturbance, depending on the selected operating mode.
3 Operation
(continued)
3-34
3-55
3 Operation
(continued)
3-56
3 Operation
(continued)
3-35
Connection of the measured values to the P63x, connection of the fourth current transformer set to the transformers of the
neutral-point-to-ground connections
3-57
3 Operation
(continued)
3-36a
3-58
Connection of the measured values to the P63x, looping of the fourth current transformer set into the ground connections of the phase
current transformers, Part 1 of 2
3 Operation
(continued)
3-36b
Connection of the measured values to the P63x, looping of the fourth current transformer set into the ground connections of the phase
current transformers, Part 2 of 2
3-59
3 Operation
(continued)
Range of Values
PS1
PS2
PS3
PS4
010 200
010 201
010 202
010 203
010 204
010 205
010 206
010 207
010 208
010 209
010 210
010 211
010 212
010 213
010 214
010 215
No swap
A-B swapped
B-C swapped
C-A swapped
Using parameter subsets readily allows phase reversal to be activated via any control
interface (LOC, PC, COMMx) or via appropriately configured binary signal inputs.
Since the currently active parameter subset is shown on the LC-display and may be
recalled from the recordings, phase reversal information is accessible. There are
however applications where an additional display of a phase reversal may be useful.
Such would be the case when recordings by a P63x are to be compared with those by
other devices not featuring phase reversal (e.g. Backup overcurrent-time protection
device) and without knowledge of the P63x setting file. For this the following display is
used:
Description
036 220
Range of Values
No
Yes
Phase reversal is active (Yes) when at least one of the setting parameters in the active
parameter subset has a value other than No swap.
The setting file must be viewed to determine which phases are swapped.
3-60
3 Operation
(continued)
MAIN: Phase
reversal activ
[ 036 220 ]
*1
Parameter
set
set
set
set
0: without
1: a-b
2: b-c
1
2
3
4
MAIN: Phase
reversal a PSx
010 200
010 201
010 202
010 203
3: c-a
*2
set
set
set
set
Parameter
*3
Parameter
set
set
set
set
1
2
1
2
3
4
1
2
3
4
MAIN: Phase
reversal b PSx
010 204
010 205
010 206
010 207
MAIN: Phase
reversal c PSx
010 208
010 209
010 210
010 211
3
0: without
1: a-b
2: b-c
3: c-a
*4
Parameter
set
set
set
set
1
2
3
4
MAIN: Phase
reversal d PSx
010 212
010 213
010 214
010 215
64Z6001 A_EN
3-37
3-61
3 Operation
(continued)
3-62
3 Operation
(continued)
3-38
3-63
3 Operation
(continued)
3-64
3 Operation
(continued)
3-39
Forming the sum of the phase currents or of the residual currents, options 1 to 6
3-65
3 Operation
(continued)
3-66
3 Operation
(continued)
The measured values for the current are displayed both as per unit quantities referred to
the nominal current of the P63x and as primary quantities. To allow display in primary
values, the primary nominal current of the transformers connected to the P63x needs to
be set.
3-67
3 Operation
(continued)
3-68
The P63x offers the option of a delayed display of the maximum value of the three phase
currents (thermal ammeter function). The delayed maximum phase current display is
an exponential function of the maximum phase current IP,max (see upper curve in Figure
3-40). The time after which the delayed maximum phase current display will have
reached 95 % of maximum phase current IP,max is set at M A I N : S e t t l . t . I P , m a x , d e l .
The stored maximum phase current follows the delayed maximum phase current. If the
value of the delayed maximum phase current is declining, then the highest value of the
delayed maximum phase current remains stored. The display remains constant until the
actual delayed maximum phase current exceeds the value of the stored maximum phase
current (see middle curve in Figure 3-40). The stored maximum phase current is set to
the actual value of the delayed maximum phase current at
M A I N : R e s e t I P , m a x , s t o r e d (see lower curve in Figure 3-40).
3 Operation
(continued)
3-40
Operation of delayed and stored maximum phase current display, end d (P634 only)
3-69
3 Operation
(continued)
3-41
3-70
3 Operation
(continued)
3-42
3-71
3 Operation
(continued)
3-43
3-72
Measured operating data for the residual current, end d (P634 only)
3 Operation
(continued)
3-44
Measured operating data for the phase currents and the residual current for the virtual end (formed by current summation,
P633 and P634 only, see Figure 3-39)
3-73
3 Operation
(continued)
As of version P63x -606 the positive- and negative-sequence current measured values
of all ends (primary and per unit values) are determined continuously and displayed as
measured operating data:
z: End a
z: End b
z: End c
z: End d
005 125
005 129
005 136
005 140
M AIN : C u r r e n t Ip o s z p r i m .
005 127
005 134
005 138
005 146
005 126
005 130
005 137
005 145
M AIN : C u r r e n t Ip o s z p .u .
005 128
005 135
005 139
005 147
As of version P63x -606 the positive- and negative-sequence current measured values
of the virtual end, formed by summation or subtraction of current values (primary and per
unit values), are also continuously determined and displayed as measured operating
data:
MAIN: Curr. Ineg,add p.u.
005 149
005 150
When the CB's contacts are open, it is also possible to force to zero the setting of small
positive- and negative-sequence current measured values if such measured values are
below additionally created settable thresholds.
3-74
011 048
M AIN : M e a s .va l u e r e l . Ip o s
011 049
3 Operation
(continued)
3-45
Frequency
3-46
The measured voltage value is displayed both as a per unit quantity referred to the
nominal voltage of the P63x and as a primary quantity. To allow a display in primary
values, the primary nominal voltage of the system transformer connected to the P63x
must be set.
The P63x determines the frequency from the voltage. This voltage needs to exceed a
minimum threshold of 0.65 Vnom in order for frequency to be determined.
Frequency measurement
3-75
3 Operation
(continued)
Angle determination
The P63x determines the angle between the following currents if the associated currents
exceed the minimum threshold of 0.033 Inom:
Angle between the phase currents for each end of the transformer
Angle between the currents of the same phase between two ends of the transformer
Angle between the derived residual current and the current measured at the
transformer -Tx4 (x: 1, 2 or 3) for each end of the transformer
3-47
3-76
3 Operation
(continued)
3-48
Determination of the angle between the phase currents of the transformer ends
3-77
3 Operation
(continued)
3-49
3-78
Determination of the angle between the derived residual current and the current measured at transformer -Tx4
3 Operation
(continued)
The following conditions must be met before a protection function can be cancelled:
The protection function in question must be disabled.
None of the elements of the protection function being cancelled may be assigned to a
binary input.
None of the signals of the protection function may be assigned to a binary output or
an LED indicator.
No functions of the device function being cancelled can be selected in a list setting.
If the above conditions are met, proceed through the 'Configuration' branch of the menu
tree to access the setting relevant for the device function to be cancelled. If, for
example, the "LIMIT" function group is to be cancelled, the setting L IM IT : F u n c ti o n
g r o u p L I M I T is accessed and its value is set to 'Without'. To re-include the "LIMIT"
function in the device configuration, the same setting is accessed and its value is
changed to 'With'.
The protection function to which a setting, a signal, or a measured value belongs is
defined by the function group designation (example: In the following description of the
protection functions, it is presumed that this protection function is included in the
configuration.
3-79
3 Operation
(continued)
Protection functions that are included in the configuration may still be disabled via a
function setting or via binary signal inputs. Protection can only be disabled or enabled
through binary signal inputs if the M A I N : D i s a b l e P r o t e c t . E X T and
M A I N : E n a b l e p r o t e c t . E X T functions are both configured. When neither or only
one of the two functions is configured, the condition is interpreted as "Protection
externally enabled". If the triggering signals of the binary signal inputs are implausible
i.e. both are at logic level = "1" then the last plausible state remains stored in memory.
Note:
3-50
3-80
If the protection is disabled via a binary signal input that is configured for
M A I N : D i s a b l e p r o t e c t . E X T , the signal M A I N : B l o c k e d / f a u l t y
is not issued.
3 Operation
(continued)
3-51
3-81
3 Operation
(continued)
3-82
3 Operation
(continued)
3-52
Multiple Blocking
3-83
3 Operation
(continued)
3-53
3-84
3 Operation
(continued)
3-54
"Blocked/Faulty" signal
3-85
3 Operation
(continued)
3.11.11
Tripping signals for
autotransformers
Starting signals
As of version P63x -603 the following new tripping signals are available for applications
with autotransformers:
MAIN: Trip sig.REF1 & REF2
036 174
036 175
036 176
The trip signals of differential protection and ground differential protection plus the
general starting signals of the definite-time and inverse-time overcurrent protection
functions are combined into one common general starting signal.
DTOC1: General
starting
[ 035 128 ]
DTOC2: General
starting
[ 035 234 ]
DTOC3: General
starting
[ 035 244 ]
IDMT1: General
starting
[ 038 115 ]
IDMT2: General
starting
[ 038 135 ]
IDMT3: General
starting
[ 038 155 ]
DIFF: Starting
[ 041 106 ]
REF_1: Trip
signal
[ 041 005 ]
REF_2: Trip
signal
[ 041 016 ]
REF_3: Trip
signal
[ 041 067 ]
MAIN: General
starting
[ 036 000 ]
64Z6002 A_EN
3-55
3-86
3 Operation
(continued)
3-56
The general starting signals are counted. The counter can be reset individually.
Trip command
The P63x has four trip commands. The functions to effect a trip can be selected by
setting a m out of n parameter independently for each of the four trip commands.
The minimum trip command time may be set. The trip signals are present only as long
as the conditions for the signal are met.
A manual trip command may be issued via a parameter or a binary signal input
configured accordingly, but it is not executed unless the manual trip is included in the
selection of possible functions to cause a trip.
For each of the four trip commands, the user can specify by way of the appropriate
setting whether it will operate in latching mode. The trip command, set to latch mode,
will remain active until reset by parameters or reset through an appropriately configured
binary signal input.
The trip commands can be blocked via parameters or an appropriately configured binary
signal input. This blocking is then effective for all four trip commands. The trip signals
are not affected by this blocking. If the trip commands are both blocked, it is indicated by
the continuously illuminated amber LED indicator H 2 on the local control panel and by a
signal from an output relay configured to "Blocked/Faulty". (To identify H2, see the
dimensional drawings in the Chapter entitled Design.)
3-87
3 Operation
(continued)
3-57
3-88
3 Operation
(continued)
3-58
The number of trip commands is counted. The counters can be reset either individually
or as a group.
3-89
3 Operation
(continued)
3.11.12
The data stored in the operating data memory, the monitoring signal memory and the
event memories are date- and time-tagged. For correct tagging, the date and time need
to be set in the P63x.
The time of different devices may be synchronized by a pulse given to an appropriately
configured binary signal input. The P63x evaluates the rising edge. This will set the
clock to the nearest full minute, rounding either up or down. If several start/end signals
occur (bouncing of a relay contact), only the last edge is evaluated.
3-59
3-90
Date/time setting and clock synchronization with minute pulses presented at a binary signal input
3 Operation
(continued)
The protection device provides several ways of synchronizing the internal clock:
o
Telegram with the time of day via the communication interface COMM1/IEC (full time)
Telegram with the time of day via the communication interface COMM2/PC (full time)
Impulse every minute via a binary signal input (MAIN), see Figure 3-59 and previous
section.
Up to device version P63x -605 these interfaces were of equal priority, i.e. clock
synchronization was carried out irrespective of the source. No conflicts have to be taken
into account as long as synchronization sources (communication master, IRIG-B and
minute impulse source) operate at the same time of day. Should the synchronization
sources operate with a different time basis unwanted step changes in the internal clock
may occur. On the other hand a redundant time of day synchronization is often used so
as to sustain time synchronization via IRIG-B interface even if and while the SCADA
communication is out of service.
As of device version P63x -606 a primary and a backup source for time of day
synchronization may now be set, where both provide the four options listed in the above.
MAIN: Prim.Source TimeSync
MAIN: BackupSourceTimeSync
With this feature synchronization occurs continuously from the primary source as long as
time synchronization telegrams are received within a time-out period set at
M A I N : T i m e s yn c . t i m e - o u t .
When selecting the time telegram via IEC as the primary source the device will expect
time synchronization telegrams from server SNTP2 after server SNTP 1 has become
defective, before it will switch over to the backup source.
Time synchronization occurs solely from the primary source when the time-out stage is
blocked.
3-91
3 Operation
(continued)
3.11.13
Resetting Mechanisms
Stored data such as event logs, measured fault data etc, can be cleared in several ways.
The following mechanisms are available:
Automatic resetting of the event signals provided by LED indicators (given that the
LED operating mode has been set accordingly) and of the display of measured event
data on the local control panel LCD whenever a new event occurs.
Resetting of LED indicators and measured event data displayed on the local control
panel LCD by pressing the "Clear" key C located on the local control panel.
Selective resetting of a particular memory type (e.g. only the fault memory) via setting
parameters or through appropriately configured binary signal inputs
General reset
In the first two cases listed above only the displays on the local control panel LCD are
cleared but not the internal memories such as the fault memory.
In the event of a cold restart, namely simultaneous failure of both internal battery and
substation auxiliary supply, all stored signals and values will be lost.
3-60
3-92
General reset, LED reset and measured event data reset from the local control panel
3 Operation
(continued)
3.11.14
3-61
3-93
3 Operation
(continued)
3.11.15
Test mode
If tests are run on the P63x, the user is advised to activate the test mode so that all
incoming signals via the serial interfaces will be marked accordingly.
3-62
3-94
3 Operation
(continued)
The control path determining the active parameter subset (function setting or binary
signal input) may be selected via the function setting P S S : C o n t r o l v i a U S E R or via
the external signal P S S : C o n t r o l v i a u s e r E X T . Correspondingly, the parameter
subset is selected either in accordance with the pre-set function setting
P S S : P a r a m . s u b s . s e l . U S E R or in accordance with external signals.
The parameter subset actually active at a particular time may be determined by scanning
the logic state signals P S S : A c t u a l p a r a m . s u b s e t or P S S : P S x a c t i v e .
If the binary signal inputs are to be used for parameter subset selection, then the P63x
first checks to determine whether at least two binary inputs are configured for parameter
subset selection. If this is not the case, then the parameter subset selected via the
function setting will be active. The P63x also checks whether the signals present at the
binary signal inputs allow an unambiguous parameter subset selection. This is only true
when only one binary signal input is set to a logic level of "1". If more than one signal
input is set to a logic level of "1", then the parameter subset previously selected remains
active. Should a dead interval occur while switching between parameter subsets (this is
the case if all binary signal inputs have a logic level of "0"), then the stored hold time is
started. While this timer stage is running, the previously selected parameter subset
remains active. As soon as a signal input has a logic level of "1", the associated
parameter subset becomes active. If, after the stored time has elapsed, there is still no
signal input with a logic level of "1", the parameter subset selected via the function
parameter becomes active.
If, after the supply voltage is turned on, no logic level of "1" is present at any of the binary
signal inputs selected for the parameter subset selection, then the parameter subset
selected via the function parameter will become active once the stored time has elapsed.
The previous parameter subset remains active while the stored hold timer stage is
running.
Parameter subset selection may also occur during a starting condition. When subset
selection is handled via binary signal inputs, a maximum inherent delay of approximately
100 ms must be taken into account.
Settings for which only one address is given in the following sections are equally
effective for all four parameter subsets.
3-95
3 Operation
(continued)
3-63
3-96
3 Operation
(continued)
Cyclic tests
After the supply voltage has been turned on, various tests are carried out to verify full
operability of the P63x. If the P63x detects a fault in one of the tests, then start-up is
terminated. The display shows which test was running when termination occurred.
No control actions may be carried out. A new attempt to start up the P63x can only be
initiated by turning the supply voltage off and then on again.
After start-up has been successfully completed, cyclic self-monitoring tests will be run
during operation. In the event of a positive test result, a specified monitoring signal will
be issued and stored in a non-volatile memory the monitoring signal memory along
with the assigned date and time (see also Monitoring Signal Recording).
The self-monitoring function monitors the built-in battery for any drop below the minimum
acceptable voltage level. If the associated monitoring signal is displayed, then the
battery should be replaced within a month, since otherwise there is the danger of data
loss if the supply voltage should fail. Chapter 11 gives further instructions on battery
replacement.
Signals
3-64
The monitoring signals are also signaled via the output relay configured to
S F M O N : W a r n i n g . The output relay operates as long as an internal fault is
detected.
Monitoring signals
3-97
3 Operation
(continued)
Device response
3-98
The response of the P63x depends on the type of monitoring signal. The following
responses are possible:
Signaling Only
If there is no malfunction associated with the monitoring signal, then only a signal is
issued, and there are no further consequences. This situation exists, for example,
when internal data acquisition memories overflow.
Selective Blocking
If a fault is diagnosed solely in an area that does not affect the protective functions,
then only the affected area is blocked. This would apply, for example, to the
detection of a fault on the communication module or in the area of the PC interface.
Warm Restart
If the self-monitoring function detects a fault that might be eliminated by a system
restart such as a fault in the hardware , then a procedure called a warm restart is
automatically initiated. During this procedure, as with any start-up, the computer
system is reset to a defined state. A warm restart is characterized by the fact that no
stored data and, in particular, no setting parameters are affected by the procedure.
A warm restart can also be triggered manually by control action. During a warm
restart sequence the protective functions and the communication through serial
interfaces will be blocked. If the same fault is detected after a warm restart has been
triggered by the self-monitoring system, then the protective functions remain blocked
but communication through the serial interfaces will usually be possible again.
Cold Restart
If a corrupted parameter subset is diagnosed during the checksum test, which is part
of the self-monitoring procedure, then a cold restart is carried out. This is necessary
because the protection device cannot identify which parameter in the subset is
corrupted. A cold restart causes all internal memories to be reset to a defined state.
This means that all the protection device settings are also erased after a cold restart.
In order to establish a safe initial state, the default values have been selected so that
the protective functions are blocked. Both the monitoring signal that triggered the
cold restart and the value indicating parameter loss are entered in the monitoring
signal memory.
3 Operation
(continued)
Depending on the type of internal fault detected the device will respond by trying to
eliminate the problem with a warm restart. (See above; for further details read also about
device behavior with problems in Chapter 10 ,Troubleshooting.) Whether or not this
measure will suffice can only be determined if the monitoring signal has not already been
stored in the monitoring signal memory because of a previous fault. If it was already
stored and a second fault is detected then, depending on the type of fault detected, the
device will be blocked after the second warm restart. Previously this occurred
independently of the time duration that had passed since the first monitoring signal was
issued.
The behavior caused by sporadic faults could lead to an unwanted blocking of the device
if the monitoring signal memory has not been reset in the interim, for example, because
the substation is difficult to reach in wintertime or reading-out and clearing of the
monitoring signal memory via the communication interfaces was not enabled. A
"memory retention time" timer stage has been introduced to defuse this problem.
SFMON: Mon.sig. retention
Now device blocking only occurs, when the same internal device fault is detected twice
during this time duration. Otherwise, the device will continue to operate normally after a
warm restart. In the default setting this timer stage is blocked so that, when an internal
fault is detected, the device will operate in the same way as the previous versions.
Because of these changes the significance of the time tag for entries to the monitoring
signal memory has been re-defined. The time when the device fault occurred first was
previously recorded. As of version P63x 605 the time when the device fault occurred
last is now recorded.
3-99
3 Operation
(continued)
3-65
3-100
Operating data recording and counter for signals relevant to system operation
3 Operation
(continued)
3-66
The number of entries stored in the monitoring signal memory is displayed on the
monitoring signal counter (MT_RC: N o . m o n i t . s i g n a l s ).
3-101
3 Operation
(continued)
3-102
Overload duration
Measured overload data derived from the measured operating data of the thermal
overload protection functions THRM1 and THRM2. The following values are
determined for each of the two functions:
Load current
Object temperature
Coolant temperature
3 Operation
(continued)
3-67
The overload duration is defined as the time between the start and end of the
OL_ R C : R e c o r d . i n p r o g r e s s signal.
Overload duration
3-103
3 Operation
(continued)
Acquisition of the
measured overload data
from the thermal overload
protection
3-68
3-104
Measured overload values are derived from the measured operating data of the thermal
overload protection function. They are stored at the end of an overload event.
3 Operation
(continued)
The following description refers to the thermal overload protection 1 (THRM1) function
and can be applied similarly to THRM2.
An overload exists and consequently overload recording begins if at least the
T H R M 1 : Sta r ti n g k * Ir e f> signal is issued.
3-69
3-105
3 Operation
(continued)
Time tagging
Overload logging
The date of each overload event is stored. The overload start or end signals are likewise
time-tagged by the internal clock. The date and time assigned to an overload event
when the event begins can be read out from the overload memory on the local control
panel or through the PC and communication interfaces. The time information (relative to
the onset of the overload) that is assigned to the signals can be retrieved from the
overload memory or through the PC or communication interfaces.
Protection signals during an overload event are logged in chronological order with
reference to the specific event. A total of eight overload events, each involving a
maximum of 200 start or end signals, can be stored in the non-volatile overload
memories. After eight overload events have been logged, the oldest overload log will be
overwritten, unless memories have been cleared in the interim. If more than 199 start or
end signals have occurred during a single overload event, then O L _ R C : O v e r l .
m e m . o v e r f l o w will be entered as the last signal.
In addition to the signals, the measured overload data will also be entered in the
overload memory.
The overload logs can be read from the local control panel or through the PC or
communication interfaces.
3-106
3 Operation
(continued)
3-70
Overload memory
3-107
3 Operation
(continued)
3-71
3-108
Running time
Fault duration
Fault currents
The running time is defined as the time between the start and end of the general starting
signal that is generated within the P63x, and the fault duration is defined as the time
between the start and end of the F T _ R C : R e c o r d . i n p r o g r e s s signal.
3 Operation
(continued)
The P63x determines the measured fault data for a particular point in time during a fault.
Depending on the protection function that recognizes a fault, the criterion for the
determination of the recording start time is selected by the P63x. If, for example, the
differential protection function detects a fault then the P63x determines the measured
fault data at the time during the fault when the maximum differential current was
measured. The measured fault data are displayed at the end of the fault. If several
protection functions detect a fault then the criterion is selected on the basis of the
priorities given in the table below. The selected criterion is displayed at the P63x.
Priority
End of fault
The difference in time between the start of the fault and the fault data acquisition time is
determined by the P63x and displayed.
3-109
3 Operation
(continued)
3-72
3-110
3 Operation
(continued)
The P63x stores the fault currents data determined at the acquisition time. The following
fault currents are stored:
3-111
3 Operation
(continued)
3-73
3-112
3 Operation
(continued)
Acquisition of the
differential and restraining
currents
The P63x stores the differential and restraining current data determined at the
acquisition time by the differential protection and ground differential protection functions.
Moreover, the values for the second and fifth harmonics of the differential current are
stored.
Differential and restraining currents are stored as per-unit quantities referred to Iref.
3-113
3 Operation
(continued)
3-74
3-114
3 Operation
(continued)
3-75
After pressing the reset key C on the local control panel, the fault data value is
displayed as 'Not measured'. However, the values are not erased and can continue to
be read out through the PC and communication interfaces.
3-115
3 Operation
(continued)
Fault counting
3-116
A fault exists and therefore fault recording begins if at least one of the signals selected
through an m out of n parameter is present. Moreover, fault recording is started if the
Id> and IR> triggers operate. In addition fault recording may also be started manually
using setting parameters or externally through an appropriately configured binary signal
input.
Faults are counted and identified by sequential numbers.
3 Operation
(continued)
3-76
3-117
3 Operation
(continued)
Time tagging
Fault recordings
The date that is assigned to each fault by the internal clock is stored. A faults individual
start or end signals are likewise time-tagged. The date and time assigned to a fault
when the fault begins can be read out from the fault memory on the local control panel or
through the PC and communication interfaces. The time information (relative to the
onset of the fault) that is assigned to the signals can be retrieved from the fault memory
or through the PC or communication interfaces.
Protection signals, including the signals during the settable pre-fault and post-fault times,
are logged in chronological order with reference to the specific fault. A total of eight
faults, each involving a maximum of 200 start or end signals, can be stored in the nonvolatile fault memories. After eight faults have been recorded, the oldest fault recording
will be overwritten, unless memories have been cleared in the interim. If more than
199 start or end signals have occurred during a single fault, then
F T _ R C : F a u l t m e m . o v e r f l o w will be entered as the last signal. If the time and
date are changed during the pre-fault time, the signal F T _ R C : F a u l t y t i m e t a g is
generated.
In addition to the fault signals, the measured RMS fault data will also be entered in the
fault memory.
The fault recordings can be read from the local control panel or through the PC or
communication interfaces.
3-118
3 Operation
(continued)
3-77
Fault memory
3-119
3 Operation
(continued)
Voltage
The signals are recorded before, during and after a fault. The window length for
oscillography recording before and after the fault can be set. A maximum time period of
16.4 s (for 50 Hz) or 13.7 s (for 60 Hz) is available for recording. This period can be
divided among a maximum of eight faults. The maximum recording time per fault can be
set. If a fault, including the set pre-fault and post-fault times, lasts longer than the set
maximum recording time, then recording will terminate when the set maximum recording
time is reached.
The pre-fault time is exactly adhered to if it is shorter than the set maximum recording
time. Otherwise the pre-fault time is set to the maximum recording time minus a
sampling increment, and the post-fault time is set to zero.
If the maximum recording time is exceeded, the analog values for the oldest fault are
overwritten, but not the binary values. If more than eight faults have occurred since the
last reset, then all data for the oldest fault are overwritten.
The analog oscillography data of the fault record can only be read out through the PC or
communication interfaces.
When the supply voltage is interrupted or after a warm restart, the values of all faults
remain stored.
3-120
3 Operation
(continued)
3-121
3 Operation
(continued)
3-122
3 Operation
(continued)
Enabling or disabling
differential protection
3-123
3 Operation
(continued)
Amplitude matching
In order to set the amplitude matching for the protected object, a reference power identical for all windings - needs to be defined. For two-end arrangements, the nominal
power will usually be the transformers reference power. For three- or four-end
transformers, the nominal power of the winding with the highest-power should be set as
the reference power. The individual reference currents for each end of the protected
object are then calculated by the P63x on the basis of the set reference power and the
set primary nominal voltages of the transformer.
I ref ,a =
I ref ,c =
Sref
I ref ,b =
3 Vnom ,a
Sref
I ref ,d =
3 Vnom ,c
Sref
3 Vnom ,b
Sref
3 Vnom ,d
reference power
reference current of end a, b, c or d
nominal voltage of end a, b, c or d
Sref:
:
Iref,a to d
Vnom,a to d:
The P63x calculates the matching factors on the basis of the reference currents and the
set primary nominal currents of the system transformers.
k am ,a =
I nom ,a
k am ,c =
I nom ,c
I ref ,a
I ref ,c
k am ,b =
I nom ,b
k am ,d =
I nom ,d
I ref ,b
I ref ,d
with
kam,a to d:
Inom,a to d:
3-124
The value for the second highest matching factor (kam,mid) must always be 0.5.
3 Operation
(continued)
In three- or four-end protection, the weakest end, that is the end with the smallest
primary nominal transformer current, is thus not under any restrictions pertaining to the
settings for the amplitude matching.
Should the P63x calculate reference currents or matching factors not satisfying the
above conditions then an alarm will be issued and the P63x will be blocked
automatically.
The measured values of the phase currents of the windings of the protected object are
multiplied by the relevant matching factors and are then available for further processing.
Consequently, all threshold values and measured values always refer back to the
relevant reference currents rather than to the transformer nominal currents or the
nominal currents of the device.
3-125
3 Operation
(continued)
MAIN: Vnom
prim., end a
[ 019 017 ]
MAIN: Vnom
prim., end b
[ 019 018 ]
MAIN: Vnom
prim., end c
[ 019 019 ]
MAIN: Vnom
prim., end d
[ 019 037 ]
DIFF: Reference
power Sref
[ 019 016 ]
SFMON: Iref, a
inval. range
[ 091 007 ]
SFMON: Iref, b
inval. range
[ 091 008 ]
SFMON: Iref, c
inval. range
[ 091 009 ]
SFMON: Iref, d
inval. range
[ 091 016 ]
DIFF:
fact.
[ 004
DIFF:
fact.
[ 004
DIFF:
fact.
[ 004
DIFF:
fact.
[ 004
MAIN: Inom
C.T.prim.,end a
[ 019 020 ]
MAIN: Inom
C.T.prim.,end b
[ 019 021 ]
Matching
kam,a
105 ]
Matching
kam,b
106 ]
Matching
kam,c
127 ]
Matching
kam,d
168 ]
MAIN: Inom
C.T.prim.,end c
[ 019 022 ]
kam,a > 16
SFMON: Matching
fail. end a
[ 091 000 ]
MAIN: Inom
C.T.prim.,end d
[ 019 026 ]
kam,b > 16
SFMON: Matching
fail. end b
[ 091 001 ]
kam,c > 16
SFMON: Matching
fail. end C
[ 091 002 ]
kam,d > 16
kam,a=Inom,a/Iref,a
SFMON: Matching
fail. end D
[ 091 017 ]
kam,b=Inom,b/Iref,b
kam,c=Inom,c/Iref,c
kam,d=Inom,d/Iref,d
kam,pos
SFMON: 2nd
match.fact. inv.
[ 091 006 ]
DIFF: Sound match
303 310
64Z6013 A_EN
3-126
3 Operation
(continued)
MAIN: Protection
active
306 001
DIFF: Matching
fact. kam,a
[ 004 105]
kam,a*IA,a
Iam,A,a
kam,a*IB,a
Iam,B,a
kam,a*IC,a
Iam,C,a
kam,b*IA,b
Iam,A,b
kam,b*IB,b
Iam,B,b
kam,b*IC,b
Iam,C,b
kam,c*IA,c
Iam,A,c
kam,c*IB,c
Iam,B,c
kam,c*IC,c
Iam,C,c
kam,d*IA,d
Iam,A,d
kam,d*IB,d
Iam,B,d
kam,d*IC,d
Iam,C,d
IA,a
IB,a
IC,a
DIFF: Matching
fact. kam,b
[ 004 106]
IA,b
IB,b
IC,b
DIFF: Matching
fact. kam,c
[ 004 127]
IA,c
IB,c
IC,c
DIFF: Matching
fact. kam,d
[ 004 168]
IA,d
IB,d
IC,d
64Z5004 B_EN
3-127
3 Operation
(continued)
Vector group matching indicates that the low voltage-side currents are rotated with
respect to the high voltage-side currents according to the vector group of the transformer
to be protected. Thereby, phase coincidence with the high voltage-side currents is
restored. With the P63x, this is achieved by calculating the relevant vector difference or
where appropriate, by sign inversion for the low voltage-side phase currents (end b, c
or d). Care must be taken to avoid distortion of the amplitude matching by this
operation. For all odd vector groups, this is achieved by means of the factor 1/ 3 .
Using vector diagrams, it can be shown that the operations listed in the following table
will lead to phase coincidence of the high and low voltage-side currents while
maintaining the amplitude matching. In Figure 3-82, such a vector diagram is depicted
for a transformer having the vector group Yd5 as an example. By subtraction of each
phase current from the cyclically leading phase current and subsequent multiplication by
the factor 1/ 3 , the desired matching is achieved.
3-128
3 Operation
(continued)
3-82 Vector diagram for vector group matching with a transformer having the vector group Yd5
3-129
3 Operation
(continued)
Zero-sequence current
filtering
The table shows that the zero-sequence current is subtracted from the phase currents of
end a and, for all even vector groups, from the phase currents of ends b, c and d.
According to the theory of symmetrical components, the zero-sequence current is
calculated by dividing by 3 the vector sum of the phase currents:
I am ,0,z =
1
I am ,A ,z + I am ,B ,z + I am ,C ,z
3
z:
Iam:
end a, b, c or d
amplitude-matched current
3-130
amplitude-matched
amplitude- and vector group-matched
phase A, B or C
measuring system 1, 2 or 3
end b, c or d
cyclically trailing phase
cyclically leading phase
3 Operation
(continued)
End
ID of the
vector group
a
0 = 12
1
b, c or d
Setting:
With zero-sequence filtering
Is,y ,z =
Setting:
Without zero-sequence filtering
Is,y ,z =
I am ,x,a I am ,0,a
I am ,x,a
I am ,x,z I am ,0,z
I am ,x,z
I am ,0,z I am ,x ,+1,z
[I
amp ,x 1,z
I am ,x 1,z I am ,0,z
I am ,0,z I am ,x ,z
amp ,x 1,z
I am ,x +1,z
+ I am ,0,z
1
3
+ I am ,0,z
I am ,x ,z
1
3
[I
11
I am ,x +1,z I am ,0,z
I am ,0,z I am ,x 1,z
+ I am ,0,z
I am ,x 1,z
10
I am ,x +1,z
I am ,x +1,z
1
3
+ I am ,0,z
I am ,x +1,z
1
3
1
3
+ I am ,0,z
I am ,x -1,z
1
3
1
3
+ I am ,0,z
Vector group matching is via a straight-forward input of the vector group identification
number provided that the phase currents of the high and low voltage side(s) are
connected in standard configuration (see section 'Conditioning of the measured values').
For other configurations, special considerations apply (see Chapter 7). A reverse phase
rotation (A-C-B) needs to be taken into account by making the appropriate setting at the
P63x. The P63x will then automatically form the complementary value of the set vector
group ID to the number 12 (vector group ID = 12 set ID).
3-131
3 Operation
(continued)
Is,1,a
Is,y,a
Is,2,a
Is,3,a
DIFF: 0-seq.
filt.a en.PSx
Parameter
set
set
set
set
0: no
1: yes
DIFF: 0-seq.
filt.b en.PSx
1
2
3
4
Parameter
set
set
set
set
1
2
3
4
DIFF: 0-seq.
filt.a en.PSx
072 155
073 155
074 155
075 155
DIFF: 0-seq.
filt.b en.PSx
072 156
073 156
074 156
075 156
DIFF: Vec.gr.
ends a-b PSx
019 010
019 040
019 041
019 042
0: no
1: yes
Iam,A,a
Iam,B,a
Iam,0,a
Iam,C,a
Iam,A,b
Iam,B,b
Iam,0,b
Iam,C,b
Iam,A,c
Iam,B,c
Iam,0,c
Iam,C,c
Is,1,b
Is,y,b
Is,2,b
Is,3,b
Iam,A,d
DIFF: 0-seq.
filt.c en.PSx
Parameter
set
set
set
set
Iam,B,d
1
2
3
4
DIFF: 0-seq.
filt.c en.PSx
072 157
073 157
074 157
075 157
DIFF: Vec.gr.
ends a-c PSx
019 011
019 043
019 044
019 045
0: no
Iam,C,d
1: yes
MAIN: Phase
sequence
[ 010 049 ]
Is,1,c
Is,y,c
Is,2,c
Is,3,c
64Z6010 A_EN
3-132
3 Operation
(continued)
Parameter
set
set
set
set
1
2
3
4
Iam,A,d
Iam,B,d
Iam,0,d
Iam,C,d
Is,1,d
Is,y,d
Is,2,d
Is,3,d
64Z6011 A_EN
3-133
3 Operation
(continued)
Tripping characteristics
The differential and restraining current values for each measurement system are
calculated from the current values after amplitude and vector group matching.
The formation of the restraining values differs between two- and three-winding protection
The following equations are valid for uniformly defined current arrows relative to the
protected equipment, e.g. all the current arrows of all windings point either towards the
protected object or away from it.
Calculation of differential and restraining currents for two-winding protection:
I d ,y = I s ,y ,a + I s ,y ,b
I R ,y = 0.5 I s ,y ,a I s ,y ,b
IR ,y = 0.5 I s ,y ,a + I s ,y ,b + I s ,y ,c + I s ,y ,d
The tripping characteristic of the P63x line differential protection device has two knee
points. The first knee-point depends on the setting at D I F F : I d i f f > P S x and is on
the intersection with the tripping characteristic for single-side feed.
If the new current transformer supervision (CTS) function - as of version P63x -606 - is
used, the basic pick-up sensitivity D IF F : Id i ff> can be increased to a set value
(D IF F : Id i ff> ( C T S) ) when a CT fault is detected. See details given in the section
describing the CTS function group.
The second knee of the tripping characteristic is defined by the setting at
DIFF: IR,m2 PSx.
The characteristic equations for the three different ranges are given below. Figure 3-85
shows the tripping characteristic.
Characteristics equation for the range 0 IR 0.5 I diff > :
Id
I >
= diff
I ref
Iref
3-134
3 Operation
(continued)
Iref:
m1:
reference current
gradient of the characteristic in range 0.5 Idiff >< IR IH ,m 2
m2:
8.00
Id / Iref
Tripping area
2.00
m2
7
0.
Blocking area
0.3
m1 =
12200e.DS4
4.00
Fau
for lt cur
sin ren
gle
t
-sid char
e f acte
eed
rist
ic
6.00
2.00
4.00
II
6.00
IR / Iref
8.00
III
3-135
3 Operation
(continued)
If the current transformer supervision (CTS) function is used, the basic pick-up sensitivity
D IF F : Id i ff> can be increased to a value set at D IF F : Id i ff> ( C T S) .
Idiff
m2
Idiff>(CTS)
1
m1
Idiff>
0
IR,m2
IR
64Z6030A_EN
3-86
3-136
Above the adjustable threshold D I F F : I d i f f > > P S x of the differential current, the
P63x will trip without taking into account either the harmonic restraint or the overfluxing
stabilization. If the differential current exceeds the adjustable threshold
D I F F : I d i f f > > > P S x , the restraining current and the saturation discriminator are no
longer taken into account either, that is the P63x will trip regardless of the restraining
value and the saturation discriminator.
3 Operation
(continued)
3-87 Forming the differential and restraining currents for the three measuring systems
3-137
3 Operation
(continued)
DIFF: Sat.discr.
1 trigg.
[ 041 115 ]
DIFF: Sat.discr.
2 trigg.
[ 041 116 ]
DIFF: Sat.discr.
3 trigg.
[ 041 117 ]
DIFF: Op.mode
rush rst.PSx
[
*
]
DIFF: Harm.block
1 trigg.
[ 041 118 ]
DIFF: Harm.block
2 trigg.
[ 041 119 ]
DIFF: Harm.block
3 trigg.
[ 041 120 ]
0: Without
1: Not phase-selective
2: Phase-selective
DIFF: Idiff>(#)
PSx
[
*
]
DIFF: Overflux.bl.1
trigg.
[ 041 121 ]
DIFF: Overflux.bl.2
trigg.
[ 041 122 ]
DIFF: Overflux.bl.3
trigg.
[ 041 123 ]
DIFF: Enabled
[ 041 210 ]
DIFF: m1
PSx
[
*
DIFF: m2
PSx
[
*
DIFF: IR,m2
PSx
[
*
DIFF: Op.del.,
trip sig.PSx
[
*
]
MAIN: Protection
active
306 001
DIFF: Trip
signal 1
[ 041 002 ]
DIFF: Id,1
303 303
DIFF: IR,1
DIFF: Trip
signal 2
[ 041 003 ]
303 305
DIFF: Id,2
DIFF: Trip
signal 3
[ 041 004 ]
303 304
DIFF: IR,2
303 306
DIFF: Id,3
303 307
DIFF: Idiff>>
PSx
[
*
]
DIFF: IR,3
303 308
DIFF: Id>>
triggered
[ 041 221 ]
DIFF: Idiff>>>
PSx
[
*
]
#
or
DIFF: Idiff>(CTS)PSx
if
CTS: Idiff>(CTS)active
=yes
[ 036 203 ]
Parameter
set
set
set
set
1
2
3
4
Parameter
set
set
set
set
1
2
3
4
DIFF: Meas.system
1 trigg.
[ 041 124 ]
DIFF: Meas.system
2 trigg.
[ 041 125 ]
DIFF: Meas.system
3 trigg.
[ 041 126 ]
DIFF: Op.mode
rush rst.PSx
072 148
073 148
074 148
075 148
DIFF: Idiff>
PSx
072 142
073 142
074 142
075 142
DIFF: Idiff>(CTS)
PSx
080 000
081 000
082 000
083 000
DIFF: m1
PSx
072 145
073 145
074 145
075 145
DIFF: m2
PSx
072 146
073 146
074 146
075 146
DIFF: IR,m2
PSx
072 147
073 147
074 147
075 147
DIFF: Id>>>
triggered
[ 041 222 ]
DIFF: Idiff>>
PSx
072 143
073 143
074 143
075 143
DIFF: Idiff>>>
PSx
072 144
073 144
074 144
075 144
DIFF: Op.del.,
trip sig.PSx
010 162
010 163
010 164
010 165
64Z6012 A_EN
3-138
3 Operation
(continued)
Inrush stabilization
(harmonic restraint)
There will be no blocking if the differential current exceeds the set threshold
DIFF: Idiff>> PSx.
3-139
3 Operation
(continued)
DIFF: Id,1
f0
f0
f0
&
30ms
&
30ms
&
I(2*f0)/ I(f0)
&
I(f0)
2*f0 I(2*f0)
DIFF: Id,3
30ms
&
I(f0)
2*f0 I(2*f0)
DIFF: Id,2
I(2*f0)/ I(f0)
DIFF: Harm.block
1 trigg.
[ 041 118 ]
DIFF: Harm.block
2 trigg.
[ 041 119 ]
DIFF: Harm.block
3 trigg.
[ 041 120 ]
&
I(f0)
2*f0 I(2*f0)
I(2*f0)/ I(f0)
DIFF: I(2*f0),1
*
Parameter
set
set
set
set
1
2
3
4
DIFF: Rush
I(2f0)/I(f0) PSx
072 159
073 159
074 159
075 159
303 301
DIFF: I(2*f0),2
303 302
DIFF: I(2*f0),3
303 309
Q6Z0110 C_EN
3-140
3 Operation
(continued)
Saturation discriminator
Up to a certain limit, stability in the event of external faults is ensured by means of the
bias. Due to the triple-slope tripping characteristic, the stabilization is particularly
pronounced for high currents. However, as an additional safeguard for through-currents
with transformer saturation, the P63x is provided with a saturation discriminator.
After each zero crossing of the restraining current, the saturation discriminator monitors
the occurrence of the differential current over time. For internal faults, the differential
current appears after a zero crossing together with the restraining current. In the case of
passing currents with transformer saturation, however, a differential current will not
appear until transformer saturation begins. Accordingly, a locking signal is generated on
the basis of level monitoring of the differential current as compared to the restraining
current, and thus the desired through-stabilization is achieved. Locking is restricted to
the measuring system where an external fault was detected.
There will be no blocking if the differential current exceeds the set threshold
DIFF: Idiff>> PSx.
3-141
3 Operation
(continued)
Overfluxing stabilization
If the transformer is loaded with a voltage in excess of the nominal voltage, saturation
effects occur. Without stabilization, these could lead to differential protection tripping.
The fact that the current of the protected object under saturation conditions has a high
proportion of harmonics having five times the system frequency serves as the basis of
stabilization.
The P63x filters the differential current. The fundamental wave I(f0) and second
harmonic components I(5*f0) of the differential current are determined. If the ratio
I(5*f0) / I(f0) exceeds the set value D I F F : O v e r I ( 5 f 0 ) / I ( f 0 ) P S x in at least one
measuring system, and if the restraining current is smaller than 4Iref, then tripping is
blocked selectively for one measuring system.
There will be no blocking if the differential current exceeds the set threshold
DIFF: Idiff>> PSx.
3-142
3 Operation
(continued)
3-143
3 Operation
(continued)
The differential and restraining currents are displayed as measured operating data
provided that the set thresholds are exceeded.
3-144
3 Operation
(continued)
3-145
3 Operation
(continued)
Disabling or enabling
ground differential
protection
3-93
3-146
3 Operation
(continued)
Amplitude matching
For amplitude matching, the nominal power of the transformer end should first be set as
the reference power. The reference current is then calculated by the P63x on the basis
of the set reference power and the set primary nominal voltage of the transformer end.
I ref,N ,a =
Sref
3 Vnom ,a
reference power
Sref:
Iref,N,a: reference current of the ground differential protection function, end a
Vnom,a: nominal voltage, end a
The P63x calculates the matching factors on the basis of the reference currents and the
set primary nominal currents of the system transformers.
k am ,N ,a =
I nom ,a
I ref,N ,a
k am ,Y ,a =
I nom ,Y ,a
I ref,N,a
with
am:
amplitude-matched
Inom,a: primary nominal current of the main current transformer
Inom,Y,a: primary nominal current of current transformer in the neutral-point-to-ground
connection
Reference currents and matching factors are displayed at the P63x.
The P63x checks that the reference current and matching factor are within their
permissible ranges. The acceptable range for the reference current can be read out
from the S&R 103 operating program. The following applies to the matching factors:
The value for the smaller matching factor (kam,min) must always be 0.5.
Should the P63x calculate a reference current or matching factors not meeting the above
conditions then an alarm will be issued and the P63x will be blocked automatically.
The measured values are multiplied by the relevant matching factors and are then
available for further processing. Consequently, all threshold values and measured
values always refer back to the relevant reference current rather than to the transformer
nominal current or the nominal current of the device.
3-147
3 Operation
(continued)
REF_1: Reference
power Sref
[ 019 031 ]
MAIN: Vnom
prim., end a
[ 019 017 ]
Iref,N,a=Sref/
(Vnom*3)
MAIN: Inom
C.T.prim.,end a
[ 019 020 ]
MAIN: Inom
C.T.Yprim,end a
[ 019 027 ]
kam,N,a =
Inom,a/
Iref,N,a
REF_1: Matching
fact. kam,N
[ 004 160 ]
kam,N,a =
Inom,Y,a/
Iref,N,a
REF_1: Matching
fact.kam,Y
[ 004 163 ]
kam,N,a > 16
SFMON: Match.f.
kam,N REF_1
[ 091 101 ]
kam,N,a > 16
SFMON: Match.f.
kam,Y REF_1
[ 091 102 ]
kam,min
SFMON: Min.mtch.
f.inv.REF_1
[ 091 104 ]
64Z6020 A_EN
3-94
3-148
3 Operation
(continued)
Operating modes
As of version P63x -603 a new parameter makes it possible for the user to choose
among three operating modes.
PS1
Address
PS2
PS3
Description
Range of Values
PS4
072 149
073 149
074 149
075 149 E D I F 1 : O p e r a t i n g m o d e P S x
072 169
073 169
074 169
075 169 E D I F 2 : O p e r a t i n g m o d e P S x
072 049
073 049
074 049
075 049 E D I F 3 : O p e r a t i n g m o d e P S x
The 'Low imped. / sum(IP)' operating mode is the same as the (low impedance) ground
differential protection function previously provided by version P63x -602.
3-149
3 Operation
(continued)
From the amplitude-matched resultant currents Iam,N,a and Iam,Y,a , the differential and
restraining currents are calculated as follows:
I d ,N ,a = I am ,N,a + I am ,Y,a
I R ,N,a = I am ,N,a
Again, the equation for the differential current applies under the condition of uniformly
defined current arrows relative to the protected object. Both current arrows point either
towards the protected object or away from it.
Figure 3-95 shows the tripping characteristic of the ground differential protection
function. The characteristic equation is as follows:
I d ,N ,a
I ref
with
Idiff>,N,a:
3-150
+ 1.005
IR ,N,a
I ref ,N ,a
setting at R E F _ 1 : I d i f f > P S x
3 Operation
(continued)
Id,N / Iref
cu
rre
nt
tra
ns
fo
rm
er
s
8.00
Tripping area
3-95
2.00
Blocking area
12201e.DS4
2.00
Fa
ul
tc
ur
re
nt
ch
ar
ac
te
ris
tic
5
00
.
1
fo
rt
ra
ns
ie
nt
4.00
sa
tu
ra
tio
n
of
th
e
m
ai
n
6.00
4.00
6.00
IR,N / Iref
8.00
Tripping characteristic of ground differential protection with the 'Low imped. / sum(IP)' operating mode
3-151
3 Operation
(continued)
Using this operating mode differential current Id and restraining current IR are defined as
follows:
Id = k am ,P {I A ,I B ,I C }+ k am ,Y I Y
IR =
1
(k am ,P max{I A , I B , I C }+ k am ,Y I Y
2
When compared to the 'Low imped. / sum(IP)' operating mode, a double slope tripping
characteristic can be used here because of the definition of the restraining current (see
Figure 3-96). In particular, this tripping characteristic permits a tripping test under load
current by shorting a phase current (to simulate residual current) without the need of star
point current IY.
Besides the Idiff> parameter, already available to set the basic pick-up sensitivity, the
following parameters are also provided with the 'Low imped. / IP,max' operating mode to
set the tripping characteristic; in this case IR,m2 is equivalent to Iref.
PS1
3-152
Address
PS2
PS3
Description
Range of Values
PS4
072 162
073 162
074 162
PSx
072 163
073 163
074 163
075 163 R E F _ 1 : m 2
PSx
0.15 1.50
072 164
073 164
074 164
075 164 R E F _ 1 : I R , m 2
PSx
072 172
073 172
074 172
PSx
072 165
073 165
074 165
075 165 R E F _ 1 : m 2
PSx
0.15 1.50
072 166
073 166
074 166
075 166 R E F _ 1 : I R , m 2
PSx
072 192
073 192
074 192
PSx
072 193
073 193
074 193
075 193 R E F _ 1 : m 2
PSx
0.15 1.50
072 194
073 194
074 194
075 194 R E F _ 1 : I R , m 2
PSx
3 Operation
(continued)
Id/Iref
1.5
m
0.5
I diff>
IR,m2
0.5
1.5
IR/Iref
64Z6021A_EN
3-96
Tripping characteristic of the ground differential protection with the 'Low imped. / IP,max' operating mode
'High impedance'
operating mode
This operating mode is provided for application with the high impedance current
measuring approach. The pick-up sensitivity is set via the Idiff> parameter which is
already available.
3-153
3 Operation
(continued)
Idiff>>> threshold
Applying Current
Transformer Supervision
The restraining quantity is no longer taken into account when the differential current
value exceeds the threshold set at R E F _ 1 : I d i f f > > > P S x . Therefore the P63x will
issue a trip signal independently of the restraining quantity.
When applying current transformer supervision (CTS) (as of version P63x -606), the
ground differential protection function may be blocked for the relevant end where a CT
fault is detected. See details given in the section describing the CTS function group.
When a C T S : A l a r m e n d y signals is issued, the associated ground differential
protection function is then blocked, if if it has been set accordingly
(R E F _ n : C T S e f f e c t i v e P S x = 'Yes' by assigning REF_n to end y).
3-154
3 Operation
(continued)
REF_1: Idiff>
PSx
[
*
]
REF_1: m1
PSx
[
*
REF_1: m2
PSx
[
*
REF_1: IR,m2
PSx
[
*
]
REF_1: Enabled
[ 041 132 ]
MAIN: Protection
active
306 001
IA, a
IN,a
IB, a
kam,N,a*IN,a
Id,N,a
kam,Y,a*IN,a
IR,Y,a
REF_1: Trip
signal
[ 041 005 ]
IC, a
IY, a
REF_1: Idif>>>
PSx
[
*
]
REF_1: IR,N,a
402 551
REF_1: Id,N,a
402 550
Parameter
set
set
set
set
3-97
1
2
3
4
REF_1: Idiff>
PSx
072 150
073 150
074 150
075 150
REF_1: m1
PSx
072 162
073 162
074 162
075 162
DIFF: m2
PSx
072 163
073 163
074 163
075 163
REF_1: IR,m2
PSx
072 164
073 164
074 164
075 164
REF_1: Idiff>>>
PSx
072 151
073 151
074 151
075 151
64Z6022 A_EN
3-155
3 Operation
(continued)
3-98
3-156
The differential and restraining currents are displayed as measured operating data
provided that the set thresholds are exceeded.
3 Operation
(continued)
3-99
3-157
3 Operation
(continued)
Enabling or disabling
DTOC protection
3-100
3-158
3 Operation
(continued)
The three phase currents are monitored by the P63x with three-stage functions to detect
when they exceed the set thresholds. One of two different threshold types can be active.
The "dynamic" thresholds are active for the set hold time for the "dynamic parameters"
(see section "Activation of dynamic parameters") and the "normal" thresholds are active
when no hold time is running. If the current exceeds the set thresholds in one phase,
timer stages are started. Once the time delays have elapsed, a trip signal is issued.
The timer stages can be blocked by appropriately configured binary signal inputs.
The first stage of the DTOC protection function can optionally be blocked by the inrush
stabilization function of differential protection.
3-159
3 Operation
(continued)
3-101
3-160
3 Operation
(continued)
Negative-sequence current
stages
The P63x calculates the negative-sequence current from the three phase current values
according to this equation. This is based on the setting at M AIN : Ph a s e s e q u e n c e .
Phase sequence A-B-C:
1
2
Ineg = IA + a IB + a IC
3
a = e j120
a 2 = e j240
3-161
3 Operation
(continued)
DTOC1: Gen.
starting modePSx
[
*
]
1: With start. IN/
Ineg
DTOC1: Block.
tIneg> EXT
[ 036 141 ]
DTOC1: Rush
restr.enabl PSx
[
*
]
1: yes
DIFF: Harm.block
1 trigg.
[ 041 118 ]
DIFF: Harm.block
2 trigg.
[ 041 119 ]
DIFF: Harm.block
3 trigg.
[ 041 120 ]
MAIN: Protection
active
306 001
DTOC1: Enabled
[ 035 102 ]
DTOC1: Ineg>
PSx
[
*
]
MAIN: Dynam.
param. active
[ 040 090]
DTOC1: Ineg>
dynamic PSx
[
*
]
MAIN: Phase
sequence
[ 010 049 ]
DTOC1: tIneg>
PSx
[
*
]
IA,y
IB,y
DTOC1: Trip
signal tIneg>
[ 036 151 ]
DTOC1: tIneg>
elapsed
[ 036 148 ]
Ineg,y
IC,y
DTOC1: Block.
tIneg>> EXT
[ 036 142 ]
DTOC1: Starting
Ineg>
[ 036 145 ]
DTOC1: Ineg>>
PSx
[
*
]
DTOC1: Ineg>>
dynamic PSx
[
*
]
DTOC1: tIneg>>
PSx
[
*
]
DTOC1: Trip
signal tIneg>>
[ 036 152 ]
DTOC1: tIneg>>
elapsed
[ 036 149 ]
DTOC1: Block.
tIneg>>> EXT
[ 036 143 ]
DTOC1: Starting
Ineg>>
[ 036 146 ]
DTOC1: Ineg>>>
PSx
[
*
]
DTOC1: Ineg>>>
dynamic PSx
[
*
]
DTOC1: tIneg>>>
PSx
[
*
]
DTOC1: Trip
signal tIneg>>>
[ 036 153 ]
DTOC1: tIneg>>>
elapsed
[ 036 150]
DTOC1: Starting
Ineg>>>
[ 036 147 ]
DTOC1: Starting
Ineg
[ 036 144 ]
Parameter
set
set
set
set
1
2
3
4
Parameter
set
set
set
set
1
2
3
4
DTOC1: Ineg>
PSx
076 197
077 197
078 197
079 197
DTOC1: Ineg>
dynamic PSx
076 200
077 200
078 200
079 200
DTOC1: Ineg>>
PSx
076 198
077 198
078 198
079 198
DTOC1: Ineg>>
dynamic
PSx
076 201
077 201
078 201
079 201
DTOC1: Rush
restr.enabl PSx
076 063
077 063
078 063
079 063
DTOC1: Ineg>>>
PSx
076 199
077 199
078 199
079 199
DTOC1: Ineg>>>
dynamic PSx
076 202
077 202
078 202
079 202
DTOC1: tIneg>
PSx
076 203
077 203
078 203
079 203
DTOC1: tIneg>>
PSx
076 204
077 204
078 204
079 204
DTOC1: tIneg>>>
PSx
076 205
077 205
078 205
079 205
DTOC1: Gen.
starting modePSx
076 066
077 066
078 066
079 066
64Z5074 C_EN
3-102
3-162
3 Operation
(continued)
The residual current is monitored by the with three-stage functions to detect when it
exceeds the set thresholds. One of two different threshold types can be active.
The "dynamic" thresholds are active for the set hold time for the "dynamic parameters"
(see "Activation of Dynamic Parameters") and the "normal" thresholds are active when
no hold time is running. If the residual current exceeds the set thresholds, timer stages
are started. Once the time delays have elapsed, a signal is issued. If the operating
mode of the general starting decision is set to 'With starting IN', a trip signal is issued as
well.
The timer stages can be blocked by appropriately configured binary signal inputs.
In addition these timer stages can also be automatically blocked by single-pole or multipole starting (depending on the setting).
3-163
3 Operation
(continued)
3-103
3-164
3 Operation
(continued)
General starting
3-104
If the current exceeds one of the set thresholds of the phase current stages, a general
starting decision is issued. The user can select whether the starting of the negativesequence and residual current stages should be taken into account in the general
starting decision. The general starting triggers a timer stage. A signal is issued when the
time delay of this stage has elapsed.
General starting
3-165
3 Operation
(continued)
3-105
3-166
The number of general starts is counted. The counter can be reset individually.
3 Operation
(continued)
3-106
3-167
3 Operation
(continued)
Enabling or disabling
IDMT protection
3-107
Time-dependent
characteristics
3-168
IDMT protection can be disabled or enabled via setting parameters. Moreover, enabling
can be carried out separately for each parameter subset.
The measuring systems for the evaluation of the three phase currents, the negativesequence current and the residual current operate independently and can be set
separately. The user can select from a large number of characteristics. The tripping
characteristics available for selection are shown in figures 3-108 Tripping characteristics
as per IEC 255-3 to 3-11 RI-type inverse and RXIDG-type inverse tripping
characteristics.
3 Operation
(continued)
No Tripping
.
Characteristic
Constants
Characteristic settable
factor:
k = 0.05 to 10.00
0.14
0.02
2 Very Inverse
13.50
1.00
3 Extremely Inverse
80.00
2.00
120.00
1.00
0 Definite Time
Per IEC 255-3
t=k
t =k
a
I
I
ref
1 Standard Inverse
+
t = k
c
I b
1
ref
5 Moderately Inverse
tr = k
R
I
I
ref
0.0515
0.0200
0.1140
4.85
6 Very Inverse
19.6100
2.0000
0.4910
21.60
7 Extremely Inverse
28.2000
2.0000
0.1217
29.10
Per ANSI
+
t = k
c
I b
1
ref
tr = k
R
I
I
ref
8 Normally Inverse
8.9341
2.0938 0.17966
9.00
0.2663
1.2969 0.03393
0.50
5.6143
1.0000 2.18592
15.75
11 RI-Type Inverse
t =k
1
0.339
12 RXIDG-Type Inverse
0.236
I
I
ref
I
t = k 5.8 1.35 ln
I
ref
3-169
3 Operation
(continued)
1000
1000
100
100
k=10
10
10
t/s
k=1
k=10
t/s
1
k=0.1
k=0.05
0.1
k=1
0.1
k=0.1
k=0.05
0.01
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
I/IB
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50K1B
Characteristic No. 1
1000
100
100
k=10
k=1
0.1
k=0.1
k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
k=0.1
k=0.05
0.1
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
S8Z50K3B
Characteristic No. 3
3-170
k=1
t/s
I/Iref
I/Iref
3-108
k=10
10
10
t/s
0.01
S8Z50K2B
Characteristic No. 2
S8Z50K4B
Characteristic No. 4
3 Operation
(continued)
1000
100
100
10
10
k=10
k=10
t/s
t/s
1
k=1
0.1
k=0.1
k=0.05
k=1
0.1
k=0.1
k=0.05
0.01
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
I/Iref
S8Z50K5C
Characteristic No. 5
S8Z50K6C
Characteristic No. 6
100
10
t/s
k=10
k=1
0.1
0.01
k=0.1
k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50K7C
Characteristic No. 7
3-109
3-171
3 Operation
(continued)
1000
100
100
10
10
t/s
k=10
k=1
0.1
0.01
k=0.1
k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
t/s
1
k=10
0.1
k=1
0.01
k=0.1
k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50K8C
Characteristic No. 8
S8Z50K9C
Characteristic No. 9
100
k=10
10
t/s
k=0.1
1
k=1
k=0.05
0.1
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50KAC
Characteristic No. 10
3-110
3-172
3 Operation
(continued)
RXIDG-Type Inverse
RI-Type Inverse
1000
1000
100
100
k=10
k=1
t/s
t/s
k=1
1
k=0.1
k=0.05
0.1
k=0.1
k=0.05
0.1
0.01
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
I/Iref
S8Z50KBB
Characteristic No. 11
3-111
k=10
10
10
S8Z50KCB
Characteristic No. 12
3-173
3 Operation
(continued)
The three phase currents are monitored by the P63x to detect when they exceed the set
thresholds. Alternatively, two different thresholds can be active. The dynamic
threshold is active for the set hold time of the dynamic parameters (see Activation of
Dynamic Parameters); the normal threshold is active when no hold time is running.
The IDMT protection function will be triggered when the 1.05-fold of the set reference
current value is exceeded in one phase. The P63x will then determine the maximum
current flowing in the three phases and this value is used for further processing.
Depending on the characteristic selected and the current magnitude, the P63x will
determine the tripping time. Furthermore, a minimum tripping time can be set; the
tripping time will not fall below this minimum independently of the magnitude of the
current.
The IDMT protection function can optionally be blocked by the inrush stabilization
function of differential protection.
3-174
3 Operation
(continued)
3-112
3-175
3 Operation
(continued)
Negative-sequence
current stage
The P63x calculates the negative-sequence current from the three phase current values
according to this formula. This is based on the setting at M A I N : P h a s e s e q u e n c e .
Phase sequence A-B-C:
1
2
Ineg = I A + a IB + a IC
3
a = e j120
a 2 = e j240
The negative-sequence current is monitored by the P63x to detect when it exceeds the
set thresholds. Alternatively, two different thresholds can be active. The "dynamic"
thresholds are active for the set hold time for the "dynamic parameters" (see "Activation
of Dynamic Parameters") and the "normal" thresholds are active when no hold time is
running. The IDMT protection will trigger when the 1.05-fold of the set reference current
value is exceeded. Dependent on the characteristic selected and the negative-sequence
current magnitude the P63x will determine the tripping time. Furthermore, a minimum
tripping time can be set; the tripping time will not fall below this minimum independent of
the magnitude of the current.
The negative-sequence current stage of the IDMT protection function can be blocked
optionally by the inrush stabilization function of the differential protection.
3-176
3 Operation
(continued)
DIFF: Harm.block 1
trigg.
[ 041 118 ]
IDMT1: Rush
restr.enabl
[
*
]
DIFF: Harm.block 2
trigg.
[ 041 119 ]
PSx
DIFF: Harm.block 3
trigg.
[ 041 120 ]
1: yes
0: no
IDMT1: Enabled
[ 038 125 ]
MAIN: Protection
active
IDMT1: Iref,neg
PSx
[
*
]
306 001
MAIN: Dynam.
param. active
[ 040 090 ]
IDMT1: Iref,neg
dynamic PSx
[
*
]
1.05 * Iref
IDMT1: Starting
Iref,neg>
[ 038 173 ]
MAIN: Phase
sequence
[ 010 049 ]
IA,y
IB,y
IC,y
Ineg
PSx
Setting
Setting
IDMT1: Factor
kt,neg
PSx
[
*
]
1: Without delay
2: Delayed as per char.
IDMT1: Block.
tIref,neg> EXT
[ 038 178 ]
IDMT1: Character.
neg. PSx
[
*
]
PSx
Time Inv.
Ineg/Iref,neg
IDMT1: Memory
'neg' clear
[ 038 176 ]
IDMT1: Gen.
starting modePSx
[
*
]
Parameter
set
set
set
set
1
2
3
4
Parameter
set
set
set
set
3-113
1
2
3
4
IDMT1: Rush
restr.enabl
081 060
082 060
083 060
084 060
IDMT1: Factor
kt,neg
PSx
081 114
082 114
083 114
084 114
PSx
IDMT1: Iref,neg
PSx
081 111
082 111
083 111
084 111
IDMT1: Iref,neg
dynamic PSx
081 112
082 112
083 112
084 112
IDMT1: Character.
neg. PSx
081 113
082 113
083 113
084 113
IDMT1: Release
neg
PSx
081 116
082 116
083 116
084 116
IDMT1: Gen.
starting modePSx
081 059
082 059
083 059
084 059
64Z5076C_EN
Negative-sequence
current stage
3-177
3 Operation
(continued)
The residual current is monitored by the P63x to detect when it exceeds the set
thresholds. Alternatively, two different thresholds can be active. The "dynamic"
threshold is active for the set hold time for the "dynamic parameters" (see section
"Activation of dynamic parameters") and the "normal" threshold is active when no hold
time is running. The IDMT protection will trigger when the 1.05-fold of the set reference
current value is exceeded by the residual current. Dependent on the characteristic
selected and the residual current magnitude the P63x will determine the tripping time.
Moreover the tripping time will under no circumstances fall below a settable minimum
time threshold irrespective of the residual current flow magnitude.
The inverse-time stage can be blocked by an appropriately configured binary signal
input. In addition the inverse-time stage can also be automatically blocked by singlepole or multi-pole starting (depending on the setting).
3-178
3 Operation
(continued)
3-114
3-179
3 Operation
(continued)
Hold time
3-180
The setting of the hold time defines the time period during which the IDMT protection
starting time is stored after the starting has dropped out. Should starting recur during the
hold time period then the time of the renewed starting will be added to the time period
stored. When the starting times sum reach the tripping time value determined by the
P63x then the corresponding signal will be issued. Should starting not recur during the
hold time period then, depending on the setting, the memory storing the accumulated
starting times value will either be cleared without delay or according to the characteristic
set. In figure 3-115 the effect of hold time is shown by the example of a phase current
stage.
3 Operation
(continued)
3-115
The effect of the hold time illustrated for the phase current stage as an example
Case A: The determined tripping time is not reached.
Case B: The determined tripping time is reached.
3-181
3 Operation
(continued)
General starting
3-116
General starting
3-117
3-182
A general starting is triggered if the current in one phase exceeds the 1.05-fold of the set
reference current value. It can be selected whether the starting of the negativesequence and residual current stages should be taken into account in the general
starting decision. The general starting triggers a timer stage. A signal is issued when the
time period of this stage has elapsed.
The number of general starts is counted. The counter can be reset individually.
3 Operation
(continued)
3-183
3 Operation
(continued)
3-118
3-184
3 Operation
(continued)
Disabling or enabling
thermal overload protection
3-119
3-185
3 Operation
(continued)
Readiness of thermal
overload protection
3-120
3-186
The thermal replica is blocked via an appropriately configured binary signal input.
T H E R M : N o t r e a d y signal
3 Operation
(continued)
Tripping characteristics
The maximum phase current IP,max.y of the selected transformer end is used to track a
first-order thermal replica according to IEC 255-8. The following parameters will govern
the tripping parameters:
The object temperature is calculated from the current IP,max.y and can be displayed at
T H R M 1 : O b j e c t t e m p e r a t . , T H 1 . The coolant temperature is either measured via
the PT 100 input or via a 20 mA input, or a default temperature value is used instead.
This choice is governed by the setting at T H R M 1 : Se l e c t C T A PSx. The coolant
temperature is displayed at T H R M 1 : C o o l a n t te m p . T H 1 . The difference between
the settings for the maximum permissible temperatures of the protected object and the
coolant can be displayed at T H R M 1 : O / T f . I r e f p e r s i s t 1
The tripping characteristics are then defined by the equation:
I
ref
t = ln
2
I
c ,max
trip 1 c
I
max
c , max
ref
The setting for the operating mode selects an 'absolute' or 'relative' replica. If the setting
is for 'Absolute replica', the P63x will operate with a fixed trip threshold trip of 100 %.
3-187
3 Operation
(continued)
trip / %
10000
200
1000
110
/min
50
100
200
110
10
50
t/min
200
1000
110
30
50
0.1
0.01
0.00
10
11
I/Iref
D5Z50BE
3-121
3-188
Tripping characteristic of the thermal overload protection. Tripping characteristics apply to 0 = 0 % and identical settings for the
maximum permissible coolant and the updated measurement of the object temperature.
3 Operation
(continued)
Coolant temperature
acquisition
3-122
3-189
3 Operation
(continued)
Warning signal
A warning signal is issued when the thermal load reaches the warning level set at
T H R M 1 : R e l . O / T w a r n i n g P S x . Moreover, a time-to-tripping threshold (pre-trip
time) can be set. When the time left until tripping falls below the setting at
T H R M 1 : W a r n i n g p r e - tr i p PSx, a warning signal will be issued.
If the current falls below the default threshold of 0.1 Iref, the buffer is discharged with the
time constant set at T H R M 1 : T i m . c o n s t 2 , < I b l P S x . The thermal replica may
be reset from the local control panel or via an appropriately configured binary signal
input. Resetting is possible even when thermal overload protection is disabled. Thermal
overload protection can be blocked via an appropriately configured binary signal input.
3-190
3 Operation
(continued)
3-123
3-191
3 Operation
(continued)
3-124
3-192
3 Operation
(continued)
3-125
V<> protection can be disabled or enabled via setting parameters. Moreover, enabling
can be carried out separately for each parameter subset.
V<> protection is ready if it is enabled and no fault has been detected in the voltagemeasuring circuit by the measuring-circuit monitoring function.
3-193
3 Operation
(continued)
Voltage monitoring
The P63x checks the voltage to determine whether it exceeds or falls below a set
threshold. The triggers are followed by timer stages that can be blocked via
appropriately configured binary signal inputs.
If undervoltage monitoring decisions are to be included in the trip commands, then it is
recommended that transient signals be used. Otherwise the trip command would always
be present when the system voltage was disconnected, and it would therefore not be
possible to close the circuit breaker again.
Furthermore, time-voltage protection provides a time-window for each timer stage.
The windows are defined by the setting V< > : Vm i n PSx as lower threshold for both
timer stages and by the set operate value V< or V< < of the relevant timer stage and
parameter subset as upper threshold. With an appropriate setting of the successive
timer stages, this provision can be used to bridge short periods of voltage failure as
encountered in switching operations.
3-126
3-194
Overvoltage monitoring
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
3 Operation
(continued)
3-127
Undervoltage monitoring
3-195
3 Operation
(continued)
3-128
3-196
3 Operation
(continued)
3-129
3-197
3 Operation
(continued)
Frequency monitoring
Frequency monitoring
combined with differential
frequency gradient
monitoring (df/dt)
3-198
For each stage of the over-/underfrequency protection function, the user can choose
between the following operating modes:
Frequency monitoring
Depending on the setting, the P63x monitors the frequency to determine whether it
exceeds or falls below set thresholds. If an operate threshold in excess of the set
nominal frequency is set, the P63x checks to determine whether the frequency exceeds
the operate threshold. If an operate threshold below the set nominal frequency is set,
the P63x checks to determine whether the frequency falls below the operate threshold.
If it exceeds or falls below the set threshold, a set timer stage is started. The timer stage
can be blocked by way of an appropriately configured binary signal input.
In this operating mode of the over-/ underfrequency protection function, the frequency is
also checked to determine whether the set frequency gradient is reached (in addition to
being monitored for exceeding or falling below the set threshold). Monitoring for
overfrequency is combined with monitoring for a frequency increase; monitoring for
underfrequency is combined with monitoring for a frequency decrease. If both operate
conditions are satisfied, a set timer stage is started. The timer stage can be blocked by
way of an appropriately configured binary signal input.
3 Operation
(continued)
Frequency monitoring
combined with mean
frequency gradient
monitoring (f/t)
The frequency gradient can differ for system disturbances in individual substations and
may vary over time due to power swings. Therefore it makes sense to take the mean
value of the frequency gradient into account for load-shedding systems.
In this operating mode of over-/underfrequency protection, frequency monitoring must be
set for 'underfrequency monitoring'.
Monitoring the mean value of the frequency gradient is started with the starting of
frequency monitoring. If the frequency decreases by the set value f within the set
time t, then the t/f monitoring function operates instantaneously and generates a trip
signal. If a frequency change does not lead to an operate decision of the monitoring
function, then the t/f monitoring function will be blocked until the underfrequency
monitoring function drops out. The trip signal can be blocked by way of an appropriately
configured binary signal input.
3-130
3-199
3 Operation
(continued)
3-131
3-200
3 Operation
(continued)
fmin/fmax measurement
For the acquisition of the minimum frequency during an underfrequency condition and for
the acquisition of the maximum frequency during an overfrequency condition, the two
following measured event values are available:
f<>: Max. frequ. for f>
f<>: Min. frequ. for f<
Both measured event values are reset automatically at the onset of a new overfrequency
or underfrequency situation. A manual reset is also possible:
f<>: Reset meas.val. USER
3-201
3 Operation
(continued)
3-132
202
The overfluxing protection function can be disabled or enabled using setting parameters.
Moreover, enabling can be carried out separately for each parameter subset.
3 Operation
(continued)
3-133
The overfluxing protection function will evaluate the voltage to frequency (V/f) ratio
referred to nominal values. This ratio is proportional to the induction in the iron core of a
transformer. The overfluxing measurement is not enabled unless the voltage and
frequency values are within limits for admissible values.
203
3 Operation
(continued)
3-134
204
The overfluxing value (V/f) is monitored to determine whether it exceeds a set threshold.
A timer stage is triggered when the overfluxing value exceeds this threshold and a signal
is issued when the time delay has elapsed.
Warning stage
3 Operation
(continued)
3-135
The overfluxing value (V/f) is monitored to determine whether it exceeds a set threshold.
A timer stage is triggered when the overfluxing value exceeds this threshold and a signal
is issued when the time delay has elapsed.
205
3 Operation
(continued)
The overfluxing value (V/f) is monitored to determine whether it exceeds the set
threshold. When the overfluxing value exceeds this threshold the P63x will determine
the tripping time according to the overfluxing magnitude value and the set characteristic.
The variable-time tripping characteristic is set by defining 12 pairs of overfluxing values
and their associated tripping time values. Intermediate values are obtained by
interpolation. The setting of the characteristic is checked for plausibility with regard to a
monotonically decreasing characteristic. With values of V/f > 1.6 the tripping time is
limited to the value set for V/f = 1.6. The tripping characteristic with default setting
values is displayed in Figure 3-136.
100
t/s 10
1.00
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
2.10
V/f
64Z5198A_EN
3-136
206
3 Operation
(continued)
After a starting, the elapsed starting time is accumulated in a buffer. When the starting
drops out, the buffer memory is discharged. The discharge gradient is defined by the set
cooling time. When the starting recurs the buffer memory is again accumulated with
starting time values. If the accumulated starting time reaches the tripping time value
determined by the P63x then the trip signal will be issued. The buffer memory content
during an interrupted starting is shown in Figure 3-137. In case A, the tripping time
determined by the P63x is not reached by the accumulated starting time. In case B, on
the other hand, a trip signal is issued
3-137
207
3 Operation
(continued)
3-138
208
3 Operation
(continued)
3-139
209
3 Operation
(continued)
This function can only be used if the new processor board with DSP coprocessor is
fitted!
The current transformer supervision function can be disabled or enabled using setting
parameters. Moreover, enabling can be carried out separately for each parameter
subset.
CTS: General
enable USER
[ 031 085 ]
0
1
CTS: Enabled
[ 036 080 ]
&
0: no
1: yes
CTS: Enable
PSx
[
*
]
0
1
0: no
x
1: yes
1
2
3
4
PSS: PS x active
[
*
]
PSS: PS x active
eingeschaltet
036 090
036 091
036 092
036 093
Parameter
set
set
set
set
1
2
3
4
CTS:
PSx
001
001
001
001
Enable
118
119
120
121
64Z5300 B_EN
3-140
3-210
3 Operation
(continued)
Blocking CTS
MAIN: Protection
active
>1
CTS: blocked
CTS: Enabled
[ 036 080 ]
CTS: Blocking EXT
[ 036 160 ]
MAIN: Gen. trip
signal
[ 036 251 ]
DIFF: Harm.block 1
trigg.
[ 041 118 ]
DIFF: Harm.block 2
trigg.
[ 041 119 ]
DIFF: Harm.block 3
trigg.
[ 041 120 ]
DIFF: Overflux.bl.1
trigg.
[ 041 121 ]
DIFF: Overflux.bl.2
trigg.
[ 041 122 ]
DIFF: Overflux.bl.3
trigg.
[ 041 123 ]
3-141
>1
>1
64Z5301 A_EN
3-211
3 Operation
(continued)
Monitoring condition
If CTS is ready, it will monitor the positive- and negative-sequence currents from all
transformer ends (2 to 4 ends depending on the device type). A CT fault is detected
when the following conditions are simultaneously present:
The positive-sequence current exceeds the set threshold Ipos> in at least 2 winding
ends. This means that CTS can operate only if a minimum load current is present in
the protected object.
The negative- to positive-sequence current ratio exceeds a high set threshold value
Ineg/Ipos>> in a single winding end.
In all the other ends, the negative- to positive-sequence current ratio is smaller than
the low set threshold value Ineg/Ipos>, or no significant current is present (i.e. the
positive-sequence current is lower than the Ipos> threshold).
In such a case, there is a fault in the secondary circuit of the CT at the transformer end
where a high negative-sequence current is present.
Because this function uses negative-sequence currents, it can only detect unbalanced
CT faults. In practice, this does not present a problem as the occurrence of a three-pole
CT fault is very unlikely.
3-212
3 Operation
(continued)
CTS:
blocked
MAIN: Phase
sequence
[ 010 049
CTS: Ipos>
c [
*
IA,y
IC,y
IC,y
PSx
]
Ipos
Ipos>,y
Ineg
CTS: Ineg/Ipos>
c PSx
[
*
]
Ineg/Ipos
Ineg/Ipos>,y
CTS: Ineg/Ipos>>
c PSx
[
*
]
*
Parameter
set
set
set
set
1
2
3
4
CTS: Ipos>
PSx
001 111
001 115
001 116
001 117
CTS: Ineg/Ipos>
PSx
001 102
001 103
001 104
001 105
CTS: Ineg/
Ipos>>
PSx
001 122
001 123
001 124
001 125
Ineg/Ipos>>,y
64Z5302 A
3-142
3-213
3 Operation
(continued)
&
CTS: blocked
Ipos>,a
Ipos>,b
Ipos>,c
Ipos>,d
>2
>1
Ineg/Ipos>,a
>1
=(N-1)
Note
N = Number of ends:
P631, P632: N = 2 (a and b)
P633: N = 3 (a ... c)
P634: N = 4 (a ... d)
Ineg/Ipos>,b
>1
Ineg/Ipos>,c
>1
Ineg/Ipos>,d
Ineg/Ipos>>,a
Ineg/Ipos>>,b
Ineg/Ipos>>,c
Ineg/Ipos>>,d
=1
&
&
&
&
64Z5303A
3-143
3-214
3 Operation
(continued)
Triggering of the CTS function is signaled by multiple signals as well as by single signals
referring to the respective ends. Beside the updated signals latched signals are also
available in order to achieve stable signaling behavior and a permanent differential
protection characteristic with reduced sensitivity when, for instance, intermittent faults
have occurred. The updated signal as well as the stored signal are time-delayed in order
to suppress any signaling caused by a transient event. On the other hand,
instantaneous signals are used to block or restrain the differential protection functions as
fast as possible.
As soon as a CTS condition is detected (C T S : I d i f f > ( C T S ) a c t i v e is present),
the function will raise the differential protection low set threshold to the
D I F F : I d i f f > ( C T S ) setting:
Idiff
m2
Idiff>(CTS)
1
m1
Idiff>
0
IR,m2
IR
64Z6030A_EN
3-144
The setting for this value determines the CTS operating mode:
Signaling only: D I F F : Id i f f > ( C T S ) PSx = D I F F : I d i f f> P S x .
Differential protection remains unrestricted, but there is a risk of unwanted
tripping occurring under load current.
Restricted operation: DIFF : Idi ff> (CT S) PSx = maximum load current.
This will permit the safe differential protection behavior, even during CT failure:
there will be no unwanted trip under any load condition, but protection will remain
operational for internal faults with currents exceeding the load current).
Blocking: D IF F : Id i f f>( C T S) P S x = D IF F : Id if f > > P S x .
In practice differential protection is blocked for all currents under normal
operating conditions.
When one of the C T S : A l a r m e n d y signals is issued, the associated ground
differential protection function is then blocked, if it has been set accordingly
(R E F _ n : C T S e f f e c t i v e P S x = 'Yes' by assigning REF_n to end y).
3-215
3 Operation
(continued)
Reset
Latched CTS signals can be reset using control parameters or through an appropriately
configured binary signal input as well as by a general reset command.
The signals issued by the CTS function (and/or measuring circuit monitoring, see
description of MCM_x) are combined into the M A I N : M e a s . c i r c . I f a u l t y signal.
A signal is simultaneously issued by the self-monitoring function.
CTS: t(Alarm)
PSx
[
*
]
>1
CTS: Operated
(updating)
[ 036 099 ]
MAIN: Meas. circ.I
faulty
[ 036 155 ]
0
S
11
CTS: Operated
(latched)
[ 036 202 ]
CTS: Idiff>(CTS)
active
[ 036 203 ]
>1
0
1
100 ms
>1
500 ms
CTS: Reset
0: don't execute
1: execute
CTS: Reset
latching EXT
[ 036 158 ]
MAIN: General
reset
[ 003 002 ]
1: execute
3-145
3-216
Parameter
set
set
set
set
1
2
3
4
CTS: t(Alarm)
PSx
001 126
001 127
001 128
001 129
CTS: t(Latch)
PSx
001 130
001 131
001 132
001 133
64Z5304 B_EN
3 Operation
(continued)
CTS: t(Alarm)
PSx
[
*
]
CTS: Meas. c. I
faulty, y
[
*
]
CTS: t(Latch)
PSx
[
*
]
CTS: Reset
0
S
1 1
>1
End
a
b
c
d
036
036
036
036
036
036
036
036
081
082
083
084
204
206
208
210
CTS: Alarm
end y
036 205
036 207
036 209
036 211
CTS: Meas. c.
I faulty, y
091 026
091 027
091 028
091 029
Parameter
set
set
set
set
1
2
3
4
CTS: t(Alarm)
PSx
001 126
001 127
001 128
001 129
CTS: t(Latch)
PSx
001 130
001 131
001 132
001 133
64Z5305 B_EN
3-146
3-217
3 Operation
(continued)
3-147
3-218
3 Operation
(continued)
Measuring circuit
monitoring
The negative- to positive-sequence current ratio is used as a criterion for measuringcircuit monitoring. The measuring-circuit monitoring function is triggered when the set
ratio value, Ineg / Ipos, is exceeded and either the negative- or the positive-sequence
current exceeds 0.02 Inom. After the set operate time-delay has elapsed, a warning is
issued.
MCM_1: Enabled
[ 036 194 ]
MAIN: Phase
sequence
[ 010 049
IA,a
IB,a
IC,a
Ineg
> 0.02
Inom
Ipos
> 0.02
Inom
>1
MCM_1: Ineg/Ipos>
c PSx
[
*
]
MCM_1: Operate
c delay PSx
[
*
]
5s
Ineg/Ipos
Parameter
set
set
set
set
1
2
3
4
MCM_1: Ineg/
Ipos>
PSx
081 042
082 042
083 042
084 042
MCM_1: Operate
delay PSx
081 046
082 046
083 046
084 046
MCM_1: Starting
[ 036 212 ]
64Z5187 B_EN
3-148
3-219
3 Operation
(continued)
3-149
3-220
The signals issued by the measuring circuit monitoring function (and/or current
transformer supervision, see description of CTS) are grouped to form the
M A I N : M e a s . c i r c . I f a u l t y multiple signal. A signal is simultaneously issued by
the self-monitoring function.
3 Operation
(continued)
The Limit Value Monitoring function can be disabled or enabled via setting parameters.
The direct current, linearized by the analog measured data input, is monitored by two
stages to determine if it exceeds or falls below set thresholds. If any of the measured
values exceed or fall below the thresholds then a signal is issued after the associated
time-delay has elapsed.
3-221
3 Operation
(continued)
3-150
3-222
3 Operation
(continued)
3-151
3-223
3 Operation
(continued)
Limit value monitoring functions LIM_n can be disabled or enabled using setting
parameters.
In the P631 and P632, two limit value monitoring functions (LIM_1 and LIM_2) are
implemented and can be assigned to both transformer ends.
In the P633 and the P634, three limit value monitoring functions (LIM_1, LIM_2 and
LIM_3) are implemented. These can each be assigned to one of the transformer ends
(a, b or c for the P633; a, b, c or d for the P634) or to the virtual transformer end formed
by current summation over two user-selected transformer ends.
For each limit value monitoring function, a setting parameter is provided for this
assignment by the user. The function will then monitor the minimum and maximum
phase currents for the selection. If a maximum phase current exceeds the relevant set
threshold or if a minimum phase current falls below the relevant set threshold, a signal is
issued once a set time has elapsed. Function group LIM_1 will serve as an example to
illustrate the operation of the limit value monitoring functions in the following figures.
3-224
3 Operation
(continued)
3-152
3-225
3 Operation
(continued)
3-153
3-226
3 Operation
(continued)
When using the programmable logic, the user must carry out a functional type test to
conform with the requirements of the relevant protection/control application.
In particular, it is necessary to verify that the requirements for the implementation of logic
linking (by setting) as well as the time performance during device startup, during
operation and when there is a fault (device blocking) are fulfilled.
3-227
3 Operation
(continued)
3-154
3-228
3 Operation
(continued)
LOGIC: General
enable USER
[ 031 099 ]
LOGIC: Enabled
[ 034 046 ]
0: no
1: yes
MAIN: Protection
active
LOGIC: Fct.
assignm. outp. 1
[ 030 000 ]
306 001
Signal 1
Signal 2
Signal 3
Signal n
LOGIC: Input 1
EXT
[ 034 000 ]
LOGIC: Input 40
EXT
[ 034 109 ]
0: Without timer
stage
1: Oper./
releas.delay
LOGIC: 1 set
externally
[ 034 075 ]
2: Oper.del./
puls.dur.
LOGIC: Time t1
output 1
[ 030 002 ]
LOGIC: Time t2
output 1
[ 030 003 ]
3: Op./
rel.delay,retrig
LOGIC: 8 set
externally
[ 034 082 ]
4: Op.del./
puls.dur.,rt
5: Minimum time
LOGIC: Output
1(t)
[ 042 033 ]
LOGIC: Output 1
[ 042 032 ]
0: don't execute
1: execute
LOGIC: Trigger 8
[ 034 045 ]
0: don't execute
1: execute
3-155
64Z60CDA_EN
3-229
3 Operation
(continued)
The output signal of an equation can be fed into a further, higher order equation as an
input signal thus creating a sequence of interlinked Boolean equations. The equations
are processed in the sequence defined by the order of each equation. It should be noted
that in the case of overlapping equations, the result is provided by the equation with the
highest order.
The output signal of each equation is fed to a separate timer stage with two timer
elements and a choice of operating modes. This makes it possible to assign a freely
configurable time characteristic to the output signal of each Boolean equation. In the
'Minimum time' operating mode, the setting of timer stage t2 has no effect. Figures 3156 to 3-160 show the time characteristics for the various timer stage operating modes.
Note:
3-156
3-230
If the device is switched to "offline" the equations are not processed and all
outputs are set to a logic value of ' 0 '.
3 Operation
(continued)
3-157
3-158
3-231
3 Operation
(continued)
3-159
3-160
3-232
3 Operation
(continued)
3-161
3-233
3 Operation
(continued)
3-234
4 Design
Design
The P63x is available in different types of cases and with different combinations of
modules.
The P63x like all other device types in the MiCOM Px30 range is equipped with the
standard local control panel (LOC). The local control panel is covered with a tough film
so that the specified degree of IP protection will be maintained. In addition to the
essential control and display elements, a parallel display consisting of a total of 17 LED
indicators is also incorporated into the local control panel. The meaning of the various
LED indications is shown in plain text on a label strip.
The PC interface (9-pin D-Sub female connector) is located under the hinged cover at
the bottom of the local control panel.
4.1
Designs
Surface-Mounted Case
Electrical connections are made via plug-in threaded terminal blocks. The threaded
terminal blocks in the surface-mounted case are accessible from the front of the device
after unscrewing the crosshead screws on the sides (see Figure 4-1, c) and removing
the local control panel. The local control panel can then be secured by inserting the tabs
in the slots in the left side wall (see Figure 4-1, d). The flush-mounted case is
connected at the back of the case.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
The threaded terminal block for system current transformer connection is not a shorting
block! Therefore always short-circuit the system current transformers before loosening
the threaded terminals.
4-1
4 Design
(continued)
4-1
4-2
4 Design
(continued)
4-2
4-3
4 Design
(continued)
62Y5001A_Xa_EN
4-3
4-4
4 Design
(continued)
4-4
Panel cutout for the flush-mounted 40TE case, flush-mount method 1 (without angle brackets and frame)
As of May 2005, the P63x has increased mechanical robustness if flush-mount method 2 (with angle brackets and frame, shown on the next
page) is used for the flush-mounted cases.
4-5
4 Design
(continued)
4-5
Panel cutout for the flush-mounted 40TE case, flush-mount method 2 (using the angle brackets and frame)
As of May 2005, the P63x has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this
page) is used for the flush-mounted cases.
4-6
4 Design
(continued)
4-6
Panel cutout for the flush-mounted 84TE case, flush-mount method 1 (without angle brackets and frame)
As of May 2005, the P63x has increased mechanical robustness if flush-mount method 2 (with angle brackets and frame, shown on the next
page) is used for the flush-mounted cases.
4-7
4 Design
(continued)
62Y5103B_Xa_EN
4-7
Panel cutout for the flush-mounted 84TE case, flush-mount method 2 (using the angle brackets and frame)
As of May 2005, the P63x has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this
page) is used for the flush-mounted cases.
4-8
4 Design
(continued)
4.2
Modules
The P63x is constructed from standard hardware modules. The following table gives an
overview of the modules relevant for the P63x.
(*: modules that are not shown in the location diagrams, {: optional, z: standard
equipment, : depending on order).
Index Description
0336 426
J ff
9650 107
A
A
0336 428
9650 356
A
A
A
P634
P634
4T
4T
G ff
4T
ff
4T
9650 354
ff
9650 355
X 9651 426
A
A
A
X 9651 427
Communication module 2
4T
ff
4T
ff
4T
ff
4T
ff
4T
0336 187
4T
z 40TE
only
0336 188
4T
0337 870
4T
4T
4T
ff
4T
ff
4T
T 9650 329
D
C
B
B
C
B
A
A
A
A
A
A
A
A
9650 353
L 9650 443
P 0337 875
P 9650 135
z 84TE
only
z
z
z
ff
4T
ff
8T
ff
8T
ff
8T
ff
8T
ff
8T
ff
8T
ff
8T
ff
8T
V 0337 437
E ff
4T
V 9651 300
ff
V 9651 328
ff
V 9651 439
V 9651 356
P 9651 428
T 9650 310
T 9650 311
T 9650 312
T 9650 328
T 9650 324
T 9650 325
T 9650 326
P631 P632
L 9650 194
ff
Width
4T
4T
ff
4T
ff
4T
4-9
4 Design
(continued)
P634
P634
V 0337 191
Index Description
M ff
4T
V 9651 301
ff
4T
V 9651 329
ff
4T
V 9651 437
ff
4T
V 9651 357
ff
4T
X 0337 971
ff
4T
X 9651 306
ff
4T
X 9651 334
ff
4T
X 9651 445
ff
4T
X 9651 362
ff
4T
X 0336 973
ff
4T
ff
X 0337 612
B
B
A
ff
4T
X 9651 304
ff
4T
X 9651 332
ff
4T
X 9651 443
ff
4T
X 9651 360
ff
4T
Y 0337 406
ff
4T
84TE
Y 9651 307
ff
4T
84TE
Y 9651 335
ff
4T
84TE
Y 9651 446
ff
4T
84TE
Y 9651 363
ff
4T
84TE
X 9650 341
Width
P631 P632
only
only
only
only
only
The space available for the modules measures 4 H in height by 40TE in width
(H = 44.45 mm, T = 5.08 mm). The location of the individual modules and the position of
the threaded terminal blocks in the P63x are shown in figures 4-8 to 4-17.
4-10
4 Design
(continued)
4-8
4-11
4 Design
(continued)
4-9
4-12
4 Design
(continued)
4-13
4 Design
(continued)
4-14
4 Design
(continued)
4-15
4 Design
(continued)
4-16
4 Design
(continued)
4-17
4 Design
(continued)
4-18
4 Design
(continued)
4-19
4 Design
(continued)
02
-X8 *
-X12
-X13 *
-X7 *
-X10
01
Type
A
*
01
02
: Alternative module
Type
Designation
Communication module
Slot
Item
02
Px3x_Ethernet_01A_EN
4-20
case,
case,
case,
case,
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
The instructions given in the Protective and Operational Grounding section should be
noted. In particular, check that the protective ground connection is secured with a tooth
lock washer, as per the diagram Installing the protective grounding conductor terminal.
If a cable screen is added to this connection or removed from it, then the protective
grounding should be checked again.
The SC connector and RJ45 wire of the Ethernet module cannot be connected at the
same time. (The selection for IEC : Eth e r n e t M e d i a should be noted.)
5.1
All P63x units are packaged separately in their own cartons and shipped inside outer
packaging. Use special care when opening cartons and unpacking devices, and do not
use force. In addition, make sure to remove supporting documents and the type
identification label supplied with each individual device from the inside carton.
The design revision level of each module included in the device when shipped can be
determined from the list of components (assembly list). This list of components should
be filed in carefully.
After unpacking, each device should be inspected visually to confirm it is in proper
mechanical condition.
If the P63x needs to be shipped, both inner and outer packaging must be used. If the
original packaging is no longer available, make sure that packaging conforms to
DIN ISO 2248 specifications for a drop height 0.8 m.
5.2
The nominal data and design type of the P63x can be determined by checking the type
identification label (see Figure 5-1). One type identification label is located under the
upper hinged cover on the front panel and a second label can be found on the side of the
device. Another copy of the type identification label is fixed to the outside of the P63x
packaging.
5-1
P63x
P634-XXXXXXX-304-403-610-801
Inom = 1 / 5 A
Diagram
IN,nom = 1 / 5
A
UH,nom =
UN,nom = 24
Specification
EN 60255-6 / IEC 255-6
5-1
IEP,nom =
P634.403
xx.yy
fnom = 50/60 Hz
... 250 V DC
CE
F 6.xxxxxx.y
P63x type identification label; illustrated for the example of a P634 with order number P634-XXXXXXX-304-403-610-801
The P63x design version can be determined from the order number. A breakdown of the
order number is given in Chapter 14 of this manual and in the supporting documents
supplied with the unit.
5.3
Location Requirements
The P63x has been designed to conform to DIN 57 435 part 303. Therefore it is
important when choosing the installation location to make certain that it provides the
operating conditions as specified in above DIN norm sections 3.2 to 3.4. Several of
these important operating conditions are listed below.
Environmental Conditions
Mechanical conditions
Electromagnetic conditions
5-2
Ambient temperature:
Air pressure:
Relative humidity:
Ambient air:
Solar radiation:
Vibration stress:
or
Earthquake resistance:
Operating range:
Substation secondary system design must follow the best of modern practices,
especially with respect to grounding and EMC.
5.4
Installation
The dimensions and mounting dimensions for surface-mounted cases are given in
Chapter 4. When the P63x is surface-mounted on a panel, the wiring to the P63x is
normally run along the front side of the mounting plane. If the wiring is to be at the back,
an opening can be provided above or below the surface-mounted case. Figures 5-2 and
5-3 show such an opening below the surface-mounted case.
5-2
(dimensions in mm)
5-3
5-3
5-4
(dimensions in mm)
Flush-mounted cases are designed for control panels. The dimensions and mounting
dimensions are given in Chapter 4. When the P63x is mounted on a cabinet door,
special sealing measures are necessary to provide the degree of protection required for
the cabinet (IP 51). Figures 5-4 to 5-6 show the required panel cutouts for flushmounted cases of different case widths.
Instructions for selecting the flush-mount method:
As of May 2005, the P63x has increased mechanical robustness if either the surfacemounted case or for the flush-mounted case flush-mount method 2 (with angle
brackets and frame) is used. In this case, test severity class 2 of the vibration test, test
severity class of the shock resistance test on operability as well as test severity class 1
of the shock resistance test on permanent shock are applied additionally.
5-4
Panel cutout for the flush-mounted 40TE case, flush-mount method 1 (without angle brackets and frame)
As of May 2005, the P63x has increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this
page) is used for the flush-mounted cases.
5-5
5-5
Panel cutout for the flush-mounted 40TE case, flush-mount method 2 (with angle brackets and frame) (dimensions in mm)
As of May 2005, the P63x has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on
this page) is used for the flush-mounted cases.
5-6
5-6
Panel cutout for the flush-mounted 84TE case, flush-mount method 1 (without angle brackets and frame)
As of May 2005, the P63x has increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this
page) is used for the flush-mounted cases.
5-7
5-7
Panel cutout for the flush-mounted 84TE case, flush-mount method 2 (with angle brackets and frame) (dimensions in mm)
As of May 2005, the P63x has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on
this page) is used for the flush-mounted cases.
For flush-mount method 1 (without angle brackets and frame), the procedure is as
follows:
Before the P63x can be installed into a control panel, the local control panel must be
removed. The local control panel is removed as described below:
5-8
Remove both top and bottom hinged flaps from the device. (Lift/lower both hinged
flaps 180up/down. Hold them in the middle and bend them slightly. The side
mountings of both hinged flaps can then be disengaged.)
Then remove the lower M4 screws and loosen the upper M4 screws (see Figure 5-8).
Now insert the P63x into the panel opening from the rear so that the upper M4 screws fit
into the corresponding holes. Then tighten all the M4 screws. After this, replace the
local control panel.
Note:
5-8
If the control panel thickness is 2 mm, the longer M3 and M4 bolts must be
used. Longer screws are enclosed within the device packing.
Installation of a 40TE case into a control panel. Flush-mount method 1 (without the angle brackets and frame ).
Example for a device with a 40TE case.
As of May 2005, the P63x has increased mechanical robustness if flush-mount method 2 (with angle brackets and frame, shown on the
next page) is used for the flush-mounted cases.
Connection of protective grounding conductor: see figure 5-13
5-9
For flush-mount method 2 (using the angle brackets and frame), the procedure is as
follows:
5-9
5-10
Remove the screws as shown in Figure 5-9, c and mount the enclosed angle
brackets using these same screws.
Then push the device into the control panel cutout from the front.
Secure the device to the control panel by using the enclosed M6 screws (see
Figure 5-10).
Assemble the cover frame and snap-fasten onto the fixing screws.
5-10
Installation of a 40TE case into a control panel, flush-mount method 2 (with angle brackets and frame).
As of May 2005, the P63x has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on
this page) is used for the flush-mounted cases.
Connection of protective grounding conductor: see figure 5-13
5-11
A rack mounting kit can be used to combine the 40TE case with a second sub-rack to
form a 19" mounting rack (see Figure 5-11). The extra sub-rack can be another device,
for example, or an empty sub-rack with a blank front panel. Fit the 19" mounting rack to a
cabinet as shown in Figure P63x.
5-11
5-12
5-12
5-13
5.5
19Y5220A_EN
5-13
5-14
5.6
Connection
The P63x must be connected in accordance with the terminal connection diagram
indicated on the type identification label. The terminal connection diagram is included in
the supporting documents supplied with the device. The terminal connection diagrams
that apply to the P63x are also to be found in the Appendix to this operating manual.
In general copper conductors with a cross section of 2.5 mm are sufficient to connect a
system current transformer to a current input on the P63x. To reduce CT knee-point
voltage requirements, it may be necessary to install shorter copper conductors with a
greater cross section between the system current transformers and the current inputs on
the P63x. Copper conductors with a cross section of 1.5 mm2 are adequate to connect
the binary signal inputs, the signaling and tripping circuits and the power supply input.
All connections run into the system must always have a defined potential. Connections
that are pre-wired but not used should preferably be grounded when binary inputs and
output relays are isolated. When binary inputs and output relays are connected to
common potential, the pre-wired but unused connections should be connected to the
common potential of the grouped connections.
5.6.1
Power supply
Current-measuring inputs
Before connecting the auxiliary voltage VA for the P63x power supply, it must be ensured
that the nominal value of the auxiliary device voltage corresponds with the nominal value
of the auxiliary system voltage.
When connecting the system transformers, it must be ensured that the secondary
nominal currents of the system and the device correspond.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
The threaded terminal block for system current transformer connection is not a shorting
block! Therefore always short-circuit the system current transformers before loosening
the threaded terminals.
The system current transformers must be connected in accordance with the standard
schematic diagram shown in Figure 5-14 . It is essential that the grounding configuration
shown in the diagram be followed. If the CT or VT connection is reversed, this can be
taken into account when making settings (see Chapter 7).
5-15
5-14
5-16
Connecting a resistance
thermometer
5-15
A resistance thermometer can be connected if the device is fitted with analog module Y.
This analog I/O module input is designed to connect a PT 100 resistance thermometer.
The PT 100 should be connected using the 3-wire method (see Figure 5-15). No supply
conductor compensation is required in this case.
5-17
5.6.2
The PC interface is provided so that personnel can operate the device from a personal
computer (PC).
Communication interface
5-18
The fiber-optic interface may only be connected or disconnected when the supply
voltage for the device is shut off.
An RS485 data transmission link between a master and several slave devices can be
established by using the optional communication interface. The communication master
could be, for instance, a central control station. Devices linked to the communication
master, e.g. P63x, are set-up as slave devices.
The RS 485 interface available on the P63x was designed so that data transfer in a full
duplex transmission mode is possible using a 4-wire data link between devices.
Data transfer between devices using the RS 485 interface is set up only for a half duplex
transmission mode. To connect the RS485 communication interface the following must
be observed:
Only twisted pair shielded cables must be used, that are common in
telecommunication installations.
Strip cable cores and cable shield right at the connection point and connect properly
in accordance with specifications.
5-19
P63x
Last participant
connected to the line
First participant
connected to the line
(e.g. the master)
P63x
Device with half-duplex
interface
64Z608 0A_EN
5-16
5-20
P63x
First participant
connected to the line
(e.g. the master)
Last participant
connected to the line
P63x
Device with half-duplex
interface
64Z6081 A_EN
5-17
5-21
5-22
6
Local control panel
All data required for operation of the protection device is entered from the local control
panel, and the data important for system management is read out there as well.
The following tasks can be handled from the local control panel:
Readout of cyclically updated measured operating data and logic status signals
Readout of event logs after overload situations, ground faults, or short circuits in the
power system
Device resetting and triggering of additional control functions used in testing and
commissioning
Control is also possible through the PC interface. This requires a suitable PC and a
specific operating program.
6-1
6.1
Control and display
elements
TRIP
ALARM
OUT OF SERVICE
HEALTHY
EDIT MODE
= CLEAR
= REAS
G
G
= ENTR
6-1
6-2
Display levels
All data relevant for operation and all device settings are displayed on two levels.
At the Panel level, data such as measurements are displayed in Panels that provide a
quick overview of the current state of the bay. The menu tree level below the panel level
allows the user to select all data points (settings, signals, measured values, etc.) and to
change them, if appropriate. To access a selected event recording from either the panel
.
level or from any other point in the menu tree, press the "READ" key
Measured Value
Panels
Recordings
Oper/Rec/OP_RC
Operat. data record.
Parameters
Operation
Events
Device ID
Cyclic measurements
Event counters
Configuration parameters
Function parameters
Global
General functions
Parameter subset 1
Menu tree
6-2
6-3
Display panels
The P63x can display 'Measured Value Panels' which are selected automatically by the
device according to system conditions.
Selected measured values are displayed on the Measured Value Panels. The system
condition determines which Panel is called up (examples are the Operation Panel and
the Fault Panel). Only the Measured Value Panels relevant for the particular design
version of the given device and its associated range of functions are actually available.
The Operation Panel is always provided.
6-4
All data points (setting values, signals, measured values, etc.) are selected using a
menu tree. When navigating through the menu tree, the first two lines of the LC-Display
always show the branch of the menu tree that is active, as selected by the user.
The data points are found at the lowest level of a menu tree branch and they are
displayed either with their plain text description or in numerically encoded form, as
selected by the user. The value associated with the selected data point, its meaning,
and its unit of measurement are displayed in the line below.
List data points are a special category. In contrast to other data points, list data points
generally have more than one associated value element. This category includes tripping
matrices, programmable logic functions, and event logs. When a list data point is
selected, the symbol is displayed in the bottom line of the LCD, indicating that a sublevel is situated below this displayed level. The individual value elements of a list data
point are found at this sub-level. In the case of a list parameter, the individual value
elements are linked by operators such as OR.
/
Left and Right Keys
Menu Tree Level:
Press the left and right keys to navigate through the menu tree in a horizontal
direction. If the unit is in input mode, the left and right keys have a different
function.
Input mode:
Settings can only be changed in the input mode, which is signaled by the LED
indicator labeled EDIT MODE. When the left and right keys are pressed, the cursor
positioned below one of the digits in the change-enabled value moves one digit to the
right or left.
(Left key:
The cursor moves to the next digit on the left.
Right key:
The cursor moves to the next digit on the right.)
In the case of a list parameter, the user can navigate through the list of items
available for selection by pressing the left and right keys.
G
ENTER Key
Panel Level:
Press the ENTER key at the Panel level to go to the menu tree.
Menu Tree Level:
Press the ENTER key to enter the input mode. Press the ENTER key a second time
to accept the changes as entered and exit the input mode. The LED indicator labeled
EDIT MODE signals that the input mode is active.
CLEAR Key C
Press the CLEAR key to reset the LED indicators and clear all measured event data.
The records in the recording memories are not affected by this action.
Input mode:
When the CLEAR key is pressed all changes entered are rejected and the input
mode is exited.
6-5
READ Key
Press the READ key to access a selected event recording from either the Panel level
or from any other point in the menu tree.
The following presentation of the individual control steps shows which displays can
be changed in each case by pressing keys. A small black square to the right of the
enter key indicates that the LED indicator labeled EDIT MODE is illuminated.
The examples used here are not necessarily valid for the device type described in
this manual; they merely serve to illustrate the control principles involved.
6.2
Display
Par/Func/Glob/MAIN
Device on-line
No (=off)
Control
Action
Note:
It is important to press the up key first and
release it last in order to avoid unintentional
resetting of stored data.
XX YYY
After the set return time has elapsed (setting in menu tree: 'Par/Conf/LOC'), the display
will automatically switch to the Panel level if a Measured Value Panel has been
configured.
6-6
6.3
Display Illumination
If none of the control keys is pressed, the display illumination will switch off once the set
"hold" time has elapsed (Backlight time setting in the menu tree at Par/Conf/LOC).
Pressing any of the control keys will turn the display illumination on again. In this case
the control action that is normally triggered by that key will not be executed. Reactivation
of the display illumination is also possible by using a binary input.
If continuous display illumination is required, the function return time illumination is set
to blocked.
6.4
The measured values that will be displayed on the Measured Value Panels can first be
selected in the menu tree under Par/Conf/LOC. The user can select different sets of
measured values for the Operation Panel, the Overload Panel, the Ground Fault Panel,
and the Fault Panel. Only the Measured Value Panels relevant for the particular design
version of the given device and its associated range of functions are actually available.
The selected set of values for the Operation Panel is always available. Please see the
section entitled Setting a List Parameter for instructions regarding selection. If the
M A I N : W i t h o u t f u n c t i o n setting has been selected for a given panel, then that
panel is disabled.
The Measured Value Panels are called up according to system conditions. If, for
example, the device detects an overload or a ground fault, then the corresponding
Measured Value Panel will be displayed as long as the overload or ground fault situation
exists. If the device detects a fault, then the Fault Panel is displayed and remains active
until the measured fault values are reset, by pressing the CLEAR key, for example.
Control Step / Description
Control
Action
Display
or
6-7
6.5
6.5.1
Folders and function
groups
All data points are organized in different folders based on practical control requirements.
At the root of the menu tree is the unit type; the tree branches into the three main folders
Parameters, Operation and Events, which form the first folder level. Up to two further
folder levels follow so that the entire folder structure consists of three main branches and
a maximum of three folder levels.
At the end of each branch of folders are the various function groups in which the
individual data points (settings) are combined.
PX yyy
Unit
type
Folder
level 1
PX yyy
Parameters
Folder
level 2
Folder
level 3
Function
groups
Data
points
6-3
6-8
PX yyy
Operation
PX yyy
Events
Oper/
Cyclic measurements
Oper/Cycl/
Meas. operating data
Oper/Cycl/Data/
MAIN
Oper/Cycl/Data/MAIN
Date
01.01.99 dd.mm.yy
6.5.2
The display on the local control panel can be switched between address mode and plain
text mode. In the address mode the display shows settings, signals, and measured
values in numerically coded form, that is, as addresses. In plain text mode the settings,
signals, and measured values are displayed in the form of plain text descriptions.
In either case, control is guided by the menu tree. The active branch of the menu tree is
displayed in plain text in both modes. In the following examples, the display is shown in
plain text mode only.
Control Step / Description
Control
Action
Par/Func/Glob/MAIN
Device on-line
No (=off)
Display
Par/Func/Glob/MAIN
003.030
0
6-9
9
6.5.3
Change-Enabling Function
Although it is possible to select any data point in the menu tree and read the associated
value by pressing the keys, it is not possible to switch directly to the input mode.
This safeguard prevents unintended changes in the settings.
There are two ways to enter the input mode.
Global change-enabling
function
To activate the global change-enabling function, set the Param. change enabl.
parameter to Yes (menu tree: Oper/CtrlTest/LOC).
The change can only be made after the password has been entered. Thereafter, all
further changes with the exception of specially protected control actions (see the
section entitled Password-Protected Control Actions) are enabled without entering
the password.
Selective change-enabling
function
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The following example is based on the
factory-set password. If the password has been changed by the user (see the section
entitled 'Changing the Password'), the following description will apply accordingly.
Control Step / Description
Control
Action
Oper/CtrlTest/LOC
Param. change enabl.
No
right
left
up
6-10
down.
The display will change as shown in the
column on the right.
Display
Oper/CtrlTest/LOC
Param. change enabl.
No
********
Oper/CtrlTest/LOC
Param. change enabl.
No
*
Oper/CtrlTest/LOC
Param. change enabl.
No
*
Oper/CtrlTest/LOC
Param. change enabl.
No
*
Oper/CtrlTest/LOC
Param. change enabl.
No
*
Control
Action
Display
Oper/CtrlTest/LOC
Param. change enabl.
No
The LED
indicator will go out. The unit is enabled for
further setting changes.
Oper/CtrlTest/LOC
Param. change enabl.
Yes
Oper/CtrlTest/LOC
Param. change enabl.
Yes
The same procedure applies to any setting change unless the global change-enabling
function has been activated. This method is recommended for a single setting change
only. If several settings are to be changed, then the global change-enabling function is
preferable. In the following examples, the global change-enabling function has been
activated.
6-11
11
Automatic return
Forced return
The automatic return function prevents the change-enabling function from remaining
activated after a change of settings has been completed. Once the set return time
(menu tree Par/Conf/LOC) has elapsed, the change-enabling function is automatically
disabled, and the display switches to a Measured Value Panel corresponding to the
current system condition. The return time is restarted when any of the control keys is
pressed.
The return described above can be forced from the local control panel by first pressing
the up key and then holding it down while pressing the CLEAR key.
Note:
It is important to press the up key first and release it last in order to avoid
unintentional deletion of stored data.
Even when the change-enabling function is activated, not all settings can be changed.
For some settings it is also necessary to disable the protective function (menu tree:
Par/Func/Glob/MAIN, 'Protection enabled'). Such settings include the configuration
settings, by means of which the device interfaces can be adapted to the system.
The following entries in the "Change" column of the address list indicate whether values
can be changed or not:
"on": The value can be changed even when the protective function is enabled.
"off": The value can only be changed when the protective function is disabled.
6-12
6.5.4
Changing Parameters
If all the conditions for a value change are satisfied (see above), the desired setting can
be entered.
Control Step / Description
Control
Action
0 Example of a display.
Oper/CtrlTest/LOC
Param. change enabl.
Yes
keys.
Par/Conf/LOC
Autom. return time
50000 s
Par/Conf/LOC
Autom. return time
50010 s
Par/Conf/LOC
Autom. return time
50000 s
Par/Conf/LOC
Autom. return time
50000 s
Display
Par/Conf/LOC
Autom. return time
50010 s
Par/Conf/LOC
Autom. return time
50000 s
6-13
13
6.5.5
Using list settings, the user is able to select several elements from a list in order to
perform tasks such as defining a trip command or defining the measurements that will be
displayed on Measured Value Panels. The maximum possible number m that can be
selected out of the total number n of the set is given in the address list in the Remarks
column. As a rule, the selected elements are linked by an OR operator.
Other operators (NOT, OR, AND, NOT OR and NOT AND) are available in the LOGIC
function group for linking the selected list items. In this way binary signals and binary
input signals can be processed in a Boolean equation tailored to meet user
requirements. For the DNP 3.0 communication protocol, the user defines the class of a
setting instead of assigning operators. The definition of a trip command shall be used
here as an illustration.
Control Step / Description
Control
Action
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
G
G
6-14
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR
#02 DIST
Trip zone 2
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
#02 DIST
Trip zone 2
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
#01 DIST
Trip zone 1
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
#05 MAIN
?????
Display
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
#02 DIST
Trip zone 4
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR
#02 DIST
Trip zone 4
Control
Action
G
Display
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR
#02 DIST
Trip zone 4
in the list.
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR
#02 DIST
Trip zone 2
If MAIN: Without function is assigned to a given item, then all the following items are
deleted. If this occurs for item #01, everything is deleted.
6.5.6
Memory Readout
Memories can be read out after going to the corresponding entry point. This does not
necessitate activating the change-enabling function or even disabling the protective
functions. Inadvertent clearing of a memory at the entry point is not possible.
The following memories are available:
Event memories
6-15
15
The operating data memory contains stored signals of actions that occur during
operation, such as the enabling or disabling of a device function. A maximum of
100 entries is possible, after which the oldest entry is overwritten.
Control Step / Description
Control
Action
Oper/Rec/OP_RC
Operat. data record.
memory.
G
G
entry.
6-16
Display
Oper/Rec/OP_RC
01.01.97 11:33 ARC
Enabled USER
No
Oper/Rec/OP_RC
01.01.97 10:01 PSIG
Enabled USER
Yes
Oper/Rec/OP_RC
01.01.97 11:33 ARC
Enabled USER
No
Oper/Rec/OP_RC
Operat. data record.
If the unit detects an internal fault in the course of internal self-monitoring routines or if it
detects power system conditions that prevent flawless functioning of the unit, then an
entry is made in the monitoring signal memory. A maximum of 30 entries is possible.
After that an overflow signal is issued.
Control Step / Description
Control
Action
Oper/Rec/MT_RC
Mon. signal record.
signal memory.
entry.
G
G
Display
First:
13:33:59.744
Active: Yes
Reset:
No
Number:
5
Oper/Rec/MT_RC
Mon. signal record.
6-17
17
There are eight event memories for each type of event. The latest event is stored in
event memory 1, the previous one in event memory 2, and so forth.
Readout of event memories is illustrated using the fault memory as an example.
Control Step / Description
Control
Action
Events/Rec/FT_RC
Fault recording 1
01.01.99 10:00:33
G
G
G
G
6-18
Display
Fault recording 1
FT_RC
Event
22
Fault recording 1
200 ms
FT_DA
Running time
0.17 s
Fault recording 1
0 ms
FT_RC
Record. in progress
Start
Fault recording 1
241 ms
FT_RC
Record. in progress
End
Fault recording 1
0 ms
FT_RC
Record. in progress
Start
Events/Rec/FT_RC
Fault recording 1
01.01.99 10:00:33
6.5.7
Resetting
All information memories including the event memories and the monitoring signal
memory as well as the LED indicators can be reset manually. In addition, the LED
indicators are automatically cleared and initialized at the onset of a new fault provided
that the appropriate operating mode has been selected so that they always indicate the
latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which is
always possible in the standard control mode. This action also triggers an LED indicator
test and an LCD display test. The event memories are not affected by this action, so that
inadvertent deletion of the records associated with the reset signal pattern is reliably
prevented.
Because of the ring structure of the event memories, the data for eight consecutive
events are updated automatically so that manual resetting should not be necessary, in
principle. If the event memories need to be cleared completely, however, as would be
the case after injection testing, this can be done after selecting the appropriate setting.
The resetting procedure will now be illustrated using the fault memory as an example.
In this example the global change-enabling function has already been activated.
Control Step / Description
Control
Action
Display
Line 3 of the
display shows the number of faults since the
last reset, 10 in this example.
Oper/CtrlTest/FT_RC
Reset recording
10
Oper/CtrlTest/FT_RC
Reset recording
10
Don't execute
Oper/CtrlTest/FT_RC
Reset recording
10
Execute
setting to Execute.
Oper/CtrlTest/FT_RC
Reset recording
0
Oper/CtrlTest/FT_RC
Reset recording
10
6-19
19
6.5.8
Certain actions from the local control panel (such as a manual trip command for testing
purposes) can only be carried out by entering a password.
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The password consists of a pre-defined
sequential key combination entered within a specific time interval. If the password has
been changed by the user (see the section entitled 'Changing the Password'), the
following description will apply accordingly.
Control Step / Description
Control
Action
Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
right
left
up
down.
The display will change as shown in the
column on the right.
Now press the ENTER key. The LED indicator
labeled EDIT MODE will light up.
This indicates that the setting can now be
changed by pressing the up or down keys.
The LED
indicator labeled EDIT MODE will go out.
The unit will execute the command.
6-20
Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
********
Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*
Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*
Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*
Oper/CtrlTest/MAIN
Man. trip cmd USER
Don't execute
*
Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
Display
Oper/CtrlTest/MAIN
Man. trip cmd. USER
Execute
Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
Control
Action
Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
Display
The password consists of a combination of keys that must be entered sequentially within
a specific time interval. The left, right, up and down keys may be used to define the
password and represent the numbers 1, 2, 3 and 4, respectively:
6-21
21
The password can be changed by the user at any time. The procedure for this change is
described below. The starting point is the factory-set password.
Control Step / Description
Control
Action
Par/Conf/LOC
Password
********
Password setting.
G
G
G
G
The LED
indicator labeled EDIT MODE will light up.
The third line shows an underscore character
( _ ) as the prompt for entering a new
password.
G
Asterisks
appear in the third line, and a cursor
(underscore) in the fourth line prompts the user
to enter the new password again.
6-22
Par/Conf/LOC
Password
********
********
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
_
Display
Par/Conf/LOC
Password
*
Par/Conf/LOC
Password
**
Par/Conf/LOC
Password
**
_
Control
Action
G
If the
password has been re-entered correctly, the
LED indicator labeled EDIT MODE goes out
and the display appears as shown on the right.
The new Password L/R is now valid.
Par/Conf/LOC
Password
**
*
Par/Conf/LOC
Password
**
**
Par/Conf/LOC
Password
********
Par/Conf/LOC
Password
**
_
Display
Par/Conf/LOC
Password
********
Operation from the local control panel without password protection is also possible.
To select this option, immediately press the ENTER key a second time in steps 4 and 6
without entering anything else. This will configure the local control panel without
password protection, and no control actions involving changes will be possible until the
global change-enabling function has been activated (see the section entitled
Change-Enabling Function).
6-23
23
If the configured password has been forgotten, it can be called up on the LCD display as
described below. The procedure involves turning the device off and then on again.
Control Step / Description
Control
Action
Display
6-24
TEST
Password
1234
TEST
7 Settings
Settings
7.1
Parameters
The P63x must be adjusted to the system and to the protected equipment by appropriate
settings. This chapter gives instructions for determining the settings, which are located
in the folder titled Parameters in the menu tree. The sequence in which the settings are
listed and described in this chapter corresponds to their sequence in the menu tree.
The default settings are activated after a cold restart. The P63x is blocked in that case.
All settings must be re-entered after a cold restart.
Note:
In the following tables (except for function group DVICE) an indication for the localization
of the corresponding function description is shown in the right hand side column.
"Figure: 3-xxx" refers to a logic diagram which displays the address, "Figure*: 3-xxx" to a
figure subtitle or figure report sheet, "Page: 3-xxx" to a page.
7-1
7 Settings
(continued)
7.1.1
Device Identification
The device identification settings are used to record the ordering information and the
design version of the P63x. They have no effect on the device functions. These settings
should only be changed if the design version of the P63x is modified.
Device
000 000
002 120
002 122
002 103
DVICE: SW version communic.
Software version for the device's communication software. This display
cannot be altered.
002 059
DVICE: DM IEC 61850 version
Software version of the communication software based on the device's
protocol per IEC 61850. This display cannot be altered.
002 123
DVICE: Language version
Identification of the change level of the texts of the data model. This display
cannot be altered.
002 121
DVICE: Text vers.data model
Using the text replacement tool provided by the support software, the user
can change the parameter descriptors (plain text designations) and load
them into the device. These customized data models contain an identifier
defined by the user while preparing the data model. This identifier is
displayed at this point in the menu tree. Standard data models have the
identifier 0 (factory-set default).
002 124
DVICE: F number
The F number is the serial number of the device. This display cannot be
altered.
7-2
000 001
001 200
7 Settings
(continued)
000 003
000 004
000 005
000 006
000 007
000 008
000 009
000 010
000 011
000 012
000 013
000 014
000 015
000 016
000 017
000 018
000 019
000 020
000 021
000 022
000 023
000 024
000 025
000 026
000 027
000 028
000 029
086 050
DVICE: Module var. slot 1
086 051
DVICE: Module var. slot 2
086 052
DVICE: Module var. slot 3
086 053
DVICE: Module var. slot 4
086 054
DVICE: Module var. slot 5
086 055
DVICE: Module var. slot 6
086 056
DVICE: Module var. slot 7
086 057
DVICE: Module var. slot 8
086 058
DVICE: Module var. slot 9
086 059
DVICE: Module var. slot 10
086 060
DVICE: Module var. slot 11
086 061
DVICE: Module var. slot 12
086 062
DVICE: Module var. slot 13
086 063
DVICE: Module var. slot 14
086 064
DVICE: Module var. slot 15
086 065
DVICE: Module var. slot 16
086 066
DVICE: Module var. slot 17
086 067
DVICE: Module var. slot 18
086 068
DVICE: Module var. slot 19
086 069
DVICE: Module var. slot 20
086 070
DVICE: Module var. slot 21
Item number of the module fitted to the respective slot. The display always
shows the actual component configuration at any given time.
7-3
7 Settings
(continued)
086 193
DVICE: Module vers. slot 1
086 194
DVICE: Module vers. slot 2
086 195
DVICE: Module vers. slot 3
086 196
DVICE: Module vers. slot 4
086 197
DVICE: Module vers. slot 5
086 198
DVICE: Module vers. slot 6
086 199
DVICE: Module vers. slot 7
086 200
DVICE: Module vers. slot 8
086 201
DVICE: Module vers. slot 9
086 202
DVICE: Module vers. slot 10
086 203
DVICE: Module vers. slot 11
086 204
DVICE: Module vers. slot 12
086 205
DVICE: Module vers. slot 13
086 206
DVICE: Module vers. slot 14
086 207
DVICE: Module vers. slot 15
086 208
DVICE: Module vers. slot 16
086 209
DVICE: Module vers. slot 17
086 210
DVICE: Module vers. slot 18
086 211
DVICE: Module vers. slot 19
086 212
DVICE: Module vers. slot 20
086 213
DVICE: Module vers. slot 21
Index letter specifying the version of the module fitted to the respective slot.
7-4
086 047
104 061
086 191
086 049
086 046
086 189
086 190
086 048
086 192
7 Settings
(continued)
000 040
DVICE: Location
Reference input for the devices location as selected by user.
001 201
DVICE: Device ID
ID code used by the support software for identification purposes. See
description of the relevant support software for more detailed setting
instructions.
000 035
DVICE: Substation ID
ID code used by the support software for identification purposes. See
description of the relevant support software for more detailed setting
instructions.
000 036
DVICE: Feeder ID
ID code used by the support software for identification purposes. See
description of the relevant support software for more detailed setting
instructions.
DVICE: Device password 1
DVICE: Device password 2
ID code used by the support software for identification purposes. See
description of the relevant support software for more detailed setting
instructions.
000 037
000 041
000 042
000 043
000 044
000 045
000 046
000 047
000 048
000 049
7-5
7 Settings
(continued)
7.1.2
Local control panel
Configuration Parameters
LOC: Language
Language in which texts will be displayed on the local control panel.
003 020
003 021
LOC: Decimal delimiter
Character to be used as decimal separator on the local control panel.
003 035
LOC: Password
The password to be used for changing settings from the local control panel
can be defined here. Further information on changing the password is
given in Chapter 6.
080 110
LOC: Assignment read key
Selection of the event log that will be displayed when the READ key is
pressed.
053 007 Fig. 3-2
LOC: Fct. Operation Panel
Definition of the values to be displayed on the Measured Value Panel also
referred to as the Operation Panel.
053 005
Fig. 3-4
PC link
003 183
Fig. 3-5
7-6
003 081
Fig. 3-5
7 Settings
(continued)
003 185
Fig. 3-5
003 155
Fig. 3-5
Communication interface 1
056 026
COMM1: Function group COMM1
Cancelling function group COMM1 or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
003 170
003 215
Fig. 3-6
7-7
7 Settings
(continued)
003 216
Fig. 3-6
003 217
Fig. 3-6
003 220
Fig. 3-6
003 231
Fig. 3-6
003 214
Fig. 3-10
003 165
Fig: 3-7,
3-8,3-9,3-10,
3-11,3-12
003 071
Fig: 3-7,
3-8,3-9,3-10,
3-11,3-12
003 171
Fig: 3-7,
3-8,3-9,3-10,
3-11,3-12
Set the same parity that is set at the interface of the control system
connected to the P63x.
COMM1: Dead time monitoring
003 176
Fig: 3-7,
3-8,3-9,
3-10,3-11,
3-12
Note:
003 202
Fig: 3-7,
3-8,3-9,3-10,
3-11,3-12
The time between two polling calls from the communication master must be
less than the time set here.
7-8
7 Settings
(continued)
003 072
Fig: 3-7,
3-8,3-9,3-11,
3-12
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
Note:
The former designation for C O M M 1 : O c t e t c o m m . a d d r e s s was:
ILSA: Bay address
"ASDU": Application Service Data Unit
003 240 Fig. 3-11
COMM1: Oct.2 comm.addr.DNP3
In the DNP 3.0 protocol, a 16-bit address is used to identify devices. The
address that can be set here is the higher-order octet, whereas the address
set at C OMM1 : Oc te t co mm. addr ess is the lower-order octet of the
DNP address.
Note:
003 166
Fig: 3-7,
3-8,3-9,3-10,
3-11,3-12
003 161
Fig: 3-7,
3-8,3-9
003 073
Fig: 3-7,
3-8,3-9
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
Note:
This setting visible only if an IEC 870-5 protocol is enabled.
The former designation for C O M M 1 : O c t e t a d d r e s s A S D U was
ILSA: Device address.
"ASDU": Application Service Data Unit
COMM1: Spontan. sig. enable
003 177
Fig: 3-7,
3-8,3-9
003 179
Fig: 3-7,3-8,
3-9
7-9
7 Settings
(continued)
COMM1: Transm.enab.cycl.dat
003 074
Fig: 3-7,
3-8,3-9
003 175
Fig: 3-7,
3-8,3-9
003 050
Fig: 3-7,
3-8,3-9
COMM1: Delta V
COMM1: Delta I
003 051
Fig: 3-7,
3-8,3-9
COMM1: Delta f
003 052
Fig: 3-7,
3-8,3-9
003 150
Fig: 3-7,
3-8,3-9
003 053
Fig: 3-7,
3-8,3-9
COMM1: Delta t
All measured values are transmitted again via the communication interface
after this time-delay has elapsed provided that transmission has not been
triggered by the other delta conditions.
Note:
7-10
7 Settings
(continued)
003 077
Fig: 3-7,
3-8,3-9
A continuous or background general scan means that the P63x transmits all
settings, signals, and monitoring signals through the communication
interface during slow periods when there is not much activity. This ensures
that there will be data consistency with a connected control system. The
time to be set defines the minimum time difference between two telegrams.
Note:
Fig. 3-8
003 201
003 200
Fig. 3-8
003 192
Fig. 3-8
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
003 193 Fig. 3-8
COMM1: Address length ASDU
Setting for the length of the common address for identification of telegram
structures.
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
"ASDU": Application Service Data Unit
003 194 Fig. 3-8
COMM1: Octet 2 addr. ASDU
Setting for the length of the common higher-order address for identification
of telegram structures.
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
"ASDU": Application Service Data Unit
COMM1: Addr.length inf.obj.
Setting for the length of the address for information objects.
003 196
Fig. 3-8
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
003 197 Fig. 3-8
COMM1: Oct.3 addr. inf.obj.
Setting for the length of the higher-order address for information objects.
Note:
7-11
7 Settings
(continued)
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
003 198 Fig. 3-8
COMM1: Time tag length
Setting for the time tag length.
Note:
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
"ASDU": Application Service Data Unit
COMM1: ASDU2 conversion
Setting specifying whether telegram structure 2 shall be converted as a
single signal or double signal.
003 191
Fig. 3-8
003 199
Fig. 3-8
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
"ASDU": Application Service Data Unit
COMM1: Initializ. signal
Setting specifying whether an initialization signal shall be issued.
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
003 226 Fig. 3-8
COMM1: Balanced operation
Setting that determines whether communication takes place on a balanced
basis (full duplex operation).
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
003 227 Fig. 3-8
COMM1: Direction bit
Setting for the transmission direction. Normally this value will be set to '1' at
the control center and to '0' at the substation.
Note:
This setting visible only if the IEC 870-5-101 protocol is enabled.
003 228 Fig. 3-8
COMM1: Time-out interval
Setting for the maximum time that will elapse until the status signal for the
acknowledgment command is issued.
Note:
7-12
7 Settings
(continued)
Note:
Note:
Note:
Note:
003 152
Fig. 3-10
Note:
Note:
003 242
Fig. 3-11
7-13
7 Settings
(continued)
003 243
Fig. 3-11
Note:
Note:
Note:
Note:
Note:
This setting visible only if the DNP 3.0 protocol is enabled.
003 233 Fig. 3-11
COMM1: Ind./cl. bin.outputs
Selection of data points and data classes for object 10 binary outputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note:
This setting visible only if the DNP 3.0 protocol is enabled.
003 235 Fig. 3-11
COMM1: Ind./cl. analog inp.
Selection of data points and data classes for object 30 analog inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note:
7-14
7 Settings
(continued)
Note:
This setting visible only if the DNP 3.0 protocol is enabled.
003 250 Fig. 3-11
COMM1: Delta meas.v. (DNP3)
Initialization value of threshold values for transmission of measured values
in object 30. The threshold values can be changed separately by the master
for each measured value by writing to object 34, 'analog input reporting
deadband'.
Note:
Fig. 3-11
103 042
Fig. 3-12
103 043
Fig. 3-12
003 248
Note:
103 045
Fig. 3-12
Note:
7-15
7 Settings
(continued)
Communication interface 2
056 057
COMM2: Function group COMM2
Cancelling function group COMM2 or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
103 170 Fig. 3-14
COMM2: General enable USER
Disabling or enabling communication interface 2.
103 165
Fig. 3-14
103 071
Fig. 3-14
103 171
Fig. 3-14
Note:
This setting is only necessary for modem transmission.
103 202 Fig. 3-14
COMM2: Mon. time polling
The time between two polling calls from the communication master must be
less than the time set here.
103 203
COMM2: Positive ackn. fault
It is possible to set whether or not faults can be acknowledged positively
after transmission (and consequently deleted from the fault overview at the
COMM2/PC interface).
103 072 Fig. 3-14
COMM2: Octet comm. address
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Name of manufacturer
Setting for the manufacturer's name.
103 161
Fig. 3-14
Note:
This setting can be changed to ensure compatibility.
103 073 Fig. 3-14
COMM2: Octet address ASDU
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
103 177 Fig. 3-14
COMM2: Spontan. sig. enable
Enable for the transmission of spontaneous signals via the communication
interface.
103 179 Fig. 3-14
COMM2: Select. spontan.sig.
Selection of spontaneous signals for transmission via communication
interface 2.
7-16
7 Settings
(continued)
COMM2: Transm.enab.cycl.dat
Enable for the cyclic transmission of measured values via the
communication interface.
103 074
Fig. 3-14
103 175
Fig. 3-14
103 150
Fig. 3-14
7-17
7 Settings
(continued)
056 059
104 000
104 058
IEC: Enable configuration
This parameter can only be sent individually. In order to maintain
consistency among all the parameters in function groups IEC, GSSE and
GOOSE, they are only enabled mutually by this parameter. After this
command is sent to the device, the actual state of the previously changed
setting parameter of the three function groups is enabled in the
communication data model of the connected device. This function is carried
out automatically with the off-line/on-line switching of the device.
104 050
IEC: Inactivity timer
Additional communication monitor at Ethernet. Should a logged-on client
issue no further request message after this time-delay has elapsed, this
client will automatically be logged-off, i.e. no further reports will be issued to
him. To re-establish communication the client is required to perform a new
log-on procedure with the device (IED).
104 056
IEC: Ethernet media
Selecting the physical communication channel on the Ethernet module from
either wired (RJ45) or optical fiber (ST/SC connector depending on ordering
option) connection.
104 057
IEC: IED name
Name of the device (IED has server function). This device name serves as
device identification in the IEC 61850 system; it is included in the Logical
Device Name in the IEC data model and must therefore be unambiguous.
All devices logged-on to the network should have non-recurring IED names.
104 001
IEC: IP address
IP address for the device (IED has server function).
Note:
In the S&R 103 support software, the complete IP address is displayed
here. The devices front panel display only displays the IP address
distributed to the following four data model addresses:
IEC: I P a d d r e s s , I E C : IP Address 1,
IEC: IP address 2, IEC: IP address 3
(104 001, 104 002, 104 003, 104 004).
104 005
IEC: Subnet mask
The subnet mask defines which part of the IP address is addressed by the
sub-network and which part by the device that is logged-on to the network.
Note:
In the S&R 103 support software, the complete IP address is displayed
here. The devices front panel display only displays the IP address
distributed to four data model addresses.
7-18
7 Settings
(continued)
104 010
IEC: Number of routes
Number of network routes that can be contacted outside of the sub-network,
between the device (IED) and a client or server, communicating with this
device, and situated in an exterior target network.
Such a configuration is required only then when this device must contact an
external client/server direct without having its own network router to convert
an IP address.
Addressing of the router and the target network however are always
necessary.
Up to four such external target networks can be contacted.
IEC: Router address 1
IEC: Router address 2
IEC: Router address 3
IEC: Router address 4
IP address of network router # 1, 2, 3 or 4.
104 011
104 019
104 027
104 035
Note:
In the S&R 103 support software, the complete IP address is displayed
here. The devices front panel display only displays the IP address
distributed to each of the four data model addresses.
IEC: Target network 1
IEC: Target network 2
IEC: Target network 3
IEC: Target network 4
IP address of target network # 1, 2, 3 or 4.
104 015
104 023
104 031
104 039
Note:
In the S&R 103 support software, the complete IP address is displayed
here. The devices front panel display only displays the IP address
distributed to each of the four data model addresses.
104 200
IEC: SNTP operating mode
Operating mode for the time synchronization telegram. When set to
Broadcast synchronization occurs cyclically with the clock server
transmitting a broadcast signal and, when set to Request from Server each
device (IED has client function) individually requests a synchronization
signal after its own cycle time.
104 201
IEC: SNTP poll cycle time
Device (IED) poll cycle time for time synchronization when operating mode
is set to Request from Server.
104 202
IEC: SNTP Server 1 IP.
104 210
IEC: SNTP Server 2 IP.
IP address of synchronizing clock server 1 or 2.
Note:
In the S&R 103 support software, the complete IP address is displayed
here. The devices front panel display only displays the IP address
distributed to each of the four data model addresses.
7-19
7 Settings
(continued)
104 206
104 207
IEC: Diff. dayl.sav. time
Time difference when changing to daylight saving time.
104 051
IEC: Deadband value
Setting to calculate the filter value for all measured value Report Control
Blocks (RCB) except the measured value for energy. Should a change
occur in one of the measured values, which is greater than the filter value,
the RCB is again sent to all clients. For each measured value the filter
value is calculated according to this formula:
Step size measured value setting IEC: Deadband value
104 060
IEC: Update cycle energy
Cycle time to send energy value by Report Control Block (RCB).
No RCB transmission with setting to blocked!
7-20
7 Settings
(continued)
056 068
GOOSE: Function group GOOSE
Cancelling function group GOOSE or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden. The parameters of this function group are
only active if function group IEC has been configured and is activated, and if
the parameters of this function group have been activated through the
parameter I E C : E n a b l e c o n f i g u r a t i o n or by switching the device
off-line/on-line.
106 001
GOOSE: Application ID
Application ID of GOOSE being sent by this device (IED).
106 004
Fig. 3-16
106 007
Fig. 3-16
106 008
Fig. 3-16
7-21
7 Settings
(continued)
106 011
GOOSE: Output 1 fct.assig.
106 013
GOOSE: Output 2 fct.assig.
106 015
GOOSE: Output 3 fct.assig.
106 017
GOOSE: Output 4 fct.assig.
106 019
GOOSE: Output 5 fct.assig.
106 021
GOOSE: Output 6 fct.assig.
106 023
GOOSE: Output 7 fct.assig.
106 025
GOOSE: Output 8 fct.assig.
106 027
GOOSE: Output 9 fct.assig.
106 029
GOOSE: Output 10 fct.assig.
106 031
GOOSE: Output 11 fct.assig.
106 033
GOOSE: Output 12 fct.assig.
106 035
GOOSE: Output 13 fct.assig.
106 037
GOOSE: Output 14 fct.assig.
106 039
GOOSE: Output 15 fct.assig.
106 041
GOOSE: Output 16 fct.assig.
106 043
GOOSE: Output 17 fct.assig.
106 045
GOOSE: Output 18 fct.assig.
106 047
GOOSE: Output 19 fct.assig.
106 049
GOOSE: Output 20 fct.assig.
106 051
GOOSE: Output 21 fct.assig.
106 053
GOOSE: Output 22 fct.assig.
106 055
GOOSE: Output 23 fct.assig.
106 057
GOOSE: Output 24 fct.assig.
106 059
GOOSE: Output 25 fct.assig.
106 061
GOOSE: Output 26 fct.assig.
106 063
GOOSE: Output 27 fct.assig.
106 065
GOOSE: Output 28 fct.assig.
106 067
GOOSE: Output 29 fct.assig.
106 069
GOOSE: Output 30 fct.assig.
106 071
GOOSE: Output 31 fct.assig.
106 073
GOOSE: Output 32 fct.assig.
Function assignment of a binary logical state signal to the virtual GOOSE
outputs. The signal configured here is sent with the permanently configured
Dataset of GOOSE.
7-22
7 Settings
(continued)
107 000
GOOSE: Input 1 Applic. ID
107 010
GOOSE: Input 2 Applic. ID
107 020
GOOSE: Input 3 Applic. ID
107 030
GOOSE: Input 4 Applic. ID
107 040
GOOSE: Input 5 Applic. ID
107 050
GOOSE: Input 6 Applic. ID
107 060
GOOSE: Input 7 Applic. ID
107 070
GOOSE: Input 8 Applic. ID
107 080
GOOSE: Input 9 Applic. ID
107 090
GOOSE: Input 10 Applic. ID
107 100
GOOSE: Input 11 Applic. ID
107 110
GOOSE: Input 12 Applic. ID
107 120
GOOSE: Input 13 Applic. ID
107 130
GOOSE: Input 14 Applic. ID
107 140
GOOSE: Input 15 Applic. ID
107 150
GOOSE: Input 16 Applic. ID
Application ID for GOOSE, which is to be received by this device (IED) for
the virtual binary GOOSE input.
107 001
GOOSE: Input 1 Goose ID
107 011
GOOSE: Input 2 Goose ID
107 021
GOOSE: Input 3 Goose ID
107 031
GOOSE: Input 4 Goose ID
107 041
GOOSE: Input 5 Goose ID
107 051
GOOSE: Input 6 Goose ID
107 061
GOOSE: Input 7 Goose ID
107 071
GOOSE: Input 8 Goose ID
107 081
GOOSE: Input 9 Goose ID
107 091
GOOSE: Input 10 Goose ID
107 101
GOOSE: Input 11 Goose ID
107 111
GOOSE: Input 12 Goose ID
107 121
GOOSE: Input 13 Goose ID
107 131
GOOSE: Input 14 Goose ID
107 141
GOOSE: Input 15 Goose ID
107 151
GOOSE: Input 16 Goose ID
Goose ID for GOOSE, which is to be received by this device (IED) for the
virtual binary GOOSE input.
7-23
7 Settings
(continued)
107 002
GOOSE: Input 1 DataSet Ref
107 012
GOOSE: Input 2 DataSet Ref
107 022
GOOSE: Input 3 DataSet Ref
107 032
GOOSE: Input 4 DataSet Ref
107 042
GOOSE: Input 5 DataSet Ref
107 052
GOOSE: Input 6 DataSet Ref
107 062
GOOSE: Input 7 DataSet Ref
107 072
GOOSE: Input 8 DataSet Ref
107 082
GOOSE: Input 9 DataSet Ref
107 092
GOOSE: Input 10 DataSet Ref
107 102
GOOSE: Input 11 DataSet Ref
107 112
GOOSE: Input 12 DataSet Ref
107 122
GOOSE: Input 13 DataSet Ref
107 132
GOOSE: Input 14 DataSet Ref
107 142
GOOSE: Input 15 DataSet Ref
107 152
GOOSE: Input 16 DataSet Ref
'Dataset Reference' for GOOSE, which is to be received by this device (IED)
for the virtual binary GOOSE input. A 'Dataset Reference' consists of a
chain of characters including the full path of the state value from the device
(IED) situated on the opposite side with the logical device/logical node/data
object/data attribute. If a path is made up of more than 20 characters, then
only the first 20 characters are to be entered.
107 003
GOOSE: Input 1 DataObj Ind
107 013
GOOSE: Input 2 DataObj Ind
107 023
GOOSE: Input 3 DataObj Ind
107 033
GOOSE: Input 4 DataObj Ind
107 043
GOOSE: Input 5 DataObj Ind
107 053
GOOSE: Input 6 DataObj Ind
107 063
GOOSE: Input 7 DataObj Ind
107 073
GOOSE: Input 8 DataObj Ind
107 083
GOOSE: Input 9 DataObj Ind
107 093
GOOSE: Input 10 DataObj Ind
107 103
GOOSE: Input 11 DataObj Ind
107 113
GOOSE: Input 12 DataObj Ind
107 123
GOOSE: Input 13 DataObj Ind
107 133
GOOSE: Input 14 DataObj Ind
107 143
GOOSE: Input 15 DataObj Ind
107 153
GOOSE: Input 16 DataObj Ind
Data object index of a Dataset for GOOSE, which is to be received by this
device (IED) for the virtual binary GOOSE input. A data object index
indicates which data object element in the Dataset is to be evaluated.
7-24
7 Settings
(continued)
107 004
GOOSE: Input 1 DatAttr Ind
107 014
GOOSE: Input 2 DatAttr Ind
107 024
GOOSE: Input 3 DatAttr Ind
107 034
GOOSE: Input 4 DatAttr Ind
107 044
GOOSE: Input 5 DatAttr Ind
107 054
GOOSE: Input 6 DatAttr Ind
107 064
GOOSE: Input 7 DatAttr Ind
107 074
GOOSE: Input 8 DatAttr Ind
107 084
GOOSE: Input 9 DatAttr Ind
107 094
GOOSE: Input 10 DatAttr Ind
107 104
GOOSE: Input 11 DatAttr Ind
107 114
GOOSE: Input 12 DatAttr Ind
107 124
GOOSE: Input 13 DatAttr Ind
107 134
GOOSE: Input 14 DatAttr Ind
107 144
GOOSE: Input 15 DatAttr Ind
107 154
GOOSE: Input 16 DatAttr Ind
Data attribute index of a Dataset for GOOSE, which is to be received by this
device (IED) for the virtual binary GOOSE input. A data attribute index
indicates which data attribute element in the data object is to be evaluated.
107 005
GOOSE: Input 1 default
107 015
GOOSE: Input 2 default
107 025
GOOSE: Input 3 default
107 035
GOOSE: Input 4 default
107 045
GOOSE: Input 5 default
107 055
GOOSE: Input 6 default
107 065
GOOSE: Input 7 default
107 075
GOOSE: Input 8 default
107 085
GOOSE: Input 9 default
107 095
GOOSE: Input 10 default
107 105
GOOSE: Input 11 default
107 115
GOOSE: Input 12 default
107 125
GOOSE: Input 13 default
107 135
GOOSE: Input 14 default
107 145
GOOSE: Input 15 default
107 155
GOOSE: Input 16 default
Default for the virtual binary GOOSE input. The state of a virtual two-pole
GOOSE input will revert to default as soon as the continuously monitored
communication link to a GOOSE sending device (IED situated on the
opposite side) is in fault or has disappeared altogether.
7-25
7 Settings
(continued)
107 006
GOOSE: Input 1 fct.assig.
107 016
GOOSE: Input 2 fct.assig.
107 026
GOOSE: Input 3 fct.assig.
107 036
GOOSE: Input 4 fct.assig.
107 046
GOOSE: Input 5 fct.assig.
107 056
GOOSE: Input 6 fct.assig.
107 066
GOOSE: Input 7 fct.assig.
107 076
GOOSE: Input 8 fct.assig.
107 086
GOOSE: Input 9 fct.assig.
107 096
GOOSE: Input 10 fct.assig.
107 106
GOOSE: Input 11 fct.assig.
107 116
GOOSE: Input 12 fct.assig.
107 126
GOOSE: Input 13 fct.assig.
107 136
GOOSE: Input 14 fct.assig.
107 146
GOOSE: Input 15 fct.assig.
107 156
GOOSE: Input 16 fct.assig.
Function assignment of the virtual binary GOOSE input to a binary logical
state signal on the device (IED) so that it can be processed further by the
protection, control or logic functions. The signal configured at this point will
receive the state of the data attribute, as configured above, and which was
received with the Dataset of GOOSE
7-26
7 Settings
(continued)
056 060
GSSE: Function group GSSE
Cancelling function group GSSC or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden. The parameters in this function group are
active only if function group IEC has been configured and is activated, and if
the parameters of this function group have been activated through the
parameter I E C : E n a b l e c o n f i g u r a t i o n or by switching the device
off-line/on-line.
104 049
104 052
GSSE: Min. cycle
Minimum value for the GSSE repetition cycle time in ms. The repetition
cycle time for a GSSE message is calculated, according to a standard, with
this formula:
7-27
7 Settings
(continued)
104 101
GSSE: Output 1 bit pair
104 104
GSSE: Output 2 bit pair
104 107
GSSE: Output 3 bit pair
104 110
GSSE: Output 4 bit pair
104 113
GSSE: Output 5 bit pair
104 116
GSSE: Output 6 bit pair
104 119
GSSE: Output 7 bit pair
104 122
GSSE: Output 8 bit pair
104 125
GSSE: Output 9 bit pair
104 128
GSSE: Output 10 bit pair
104 131
GSSE: Output 11 bit pair
104 134
GSSE: Output 12 bit pair
104 137
GSSE: Output 13 bit pair
104 140
GSSE: Output 14 bit pair
104 143
GSSE: Output 15 bit pair
104 146
GSSE: Output 16 bit pair
104 149
GSSE: Output 17 bit pair
104 152
GSSE: Output 18 bit pair
104 155
GSSE: Output 19 bit pair
104 158
GSSE: Output 20 bit pair
104 161
GSSE: Output 21 bit pair
104 164
GSSE: Output 22 bit pair
104 167
GSSE: Output 23 bit pair
104 170
GSSE: Output 24 bit pair
104 173
GSSE: Output 25 bit pair
104 176
GSSE: Output 26 bit pair
104 179
GSSE: Output 27 bit pair
104 182
GSSE: Output 28 bit pair
104 185
GSSE: Output 29 bit pair
104 188
GSSE: Output 30 bit pair
104 191
GSSE: Output 31 bit pair
104 194
GSSE: Output 32 bit pair
Setting with which GSSE bit pair the configured binary signal of the virtual
GSSE outputs is to be transmitted. A GSSE is always transmitted
consisting of a fixed number of 96 bit pairs, of which a maximum of 32 are
used by this device (IED) during a send operation.
7-28
7 Settings
(continued)
104 102
GSSE: Output 1 fct.assig.
104 105
GSSE: Output 2 fct.assig.
104 108
GSSE: Output 3 fct.assig.
104 111
GSSE: Output 4 fct.assig.
104 114
GSSE: Output 5 fct.assig.
104 117
GSSE: Output 6 fct.assig.
104 120
GSSE: Output 7 fct.assig.
104 123
GSSE: Output 8 fct.assig.
104 126
GSSE: Output 9 fct.assig.
104 129
GSSE: Output 10 fct.assig.
104 132
GSSE: Output 11 fct.assig.
104 135
GSSE: Output 12 fct.assig.
104 138
GSSE: Output 13 fct.assig.
104 141
GSSE: Output 14 fct.assig.
104 144
GSSE: Output 15 fct.assig.
104 147
GSSE: Output 16 fct.assig.
104 150
GSSE: Output 17 fct.assig.
104 153
GSSE: Output 18 fct.assig.
104 156
GSSE: Output 19 fct.assig.
104 159
GSSE: Output 20 fct.assig.
104 162
GSSE: Output 21 fct.assig.
104 165
GSSE: Output 22 fct.assig.
104 168
GSSE: Output 23 fct.assig.
104 171
GSSE: Output 24 fct.assig.
104 174
GSSE: Output 25 fct.assig.
104 177
GSSE: Output 26 fct.assig.
104 180
GSSE: Output 27 fct.assig.
104 183
GSSE: Output 28 fct.assig.
104 186
GSSE: Output 29 fct.assig.
104 189
GSSE: Output 30 fct.assig.
104 192
GSSE: Output 31 fct.assig.
104 195
GSSE: Output 32 fct.assig.
Function assignment of a binary logical state signal to the virtual GSSE
outputs. The signal configured here is sent through the GSSE bit pair as
configured above.
7-29
7 Settings
(continued)
105 001
GSSE: Input 1 bit pair
105 006
GSSE: Input 2 bit pair
105 011
GSSE: Input 3 bit pair
105 016
GSSE: Input 4 bit pair
105 021
GSSE: Input 5 bit pair
105 026
GSSE: Input 6 bit pair
105 031
GSSE: Input 7 bit pair
105 036
GSSE: Input 8 bit pair
105 041
GSSE: Input 9 bit pair
105 046
GSSE: Input 10 bit pair
105 051
GSSE: Input 11 bit pair
105 056
GSSE: Input 12 bit pair
105 061
GSSE: Input 13 bit pair
105 066
GSSE: Input 14 bit pair
105 071
GSSE: Input 15 bit pair
105 076
GSSE: Input 16 bit pair
105 081
GSSE: Input 17 bit pair
105 086
GSSE: Input 18 bit pair
105 091
GSSE: Input 19 bit pair
105 096
GSSE: Input 20 bit pair
105 101
GSSE: Input 21 bit pair
105 106
GSSE: Input 22 bit pair
105 111
GSSE: Input 23 bit pair
105 116
GSSE: Input 24 bit pair
105 121
GSSE: Input 25 bit pair
105 126
GSSE: Input 26 bit pair
105 131
GSSE: Input 27 bit pair
105 136
GSSE: Input 28 bit pair
105 141
GSSE: Input 29 bit pair
105 146
GSSE: Input 30 bit pair
105 151
GSSE: Input 31 bit pair
105 156
GSSE: Input 32 bit pair
Setting which GSSE bit pair is assigned to which virtual GSSE input.
A GSSE is always received consisting of a fixed number of 96 bit pairs, of
which a maximum of 32 are processed by this device (IED).
7-30
7 Settings
(continued)
105 002
105 007
105 012
105 017
105 022
105 027
105 032
105 037
105 042
105 047
105 052
105 057
105 062
105 067
105 072
105 077
105 082
105 087
105 092
105 097
105 102
105 107
105 112
105 117
105 122
105 127
105 132
105 137
105 142
105 147
105 152
105 157
7-31
7 Settings
(continued)
105 003
GSSE: Input 1 default
105 008
GSSE: Input 2 default
105 013
GSSE: Input 3 default
105 018
GSSE: Input 4 default
105 023
GSSE: Input 5 default
105 028
GSSE: Input 6 default
105 033
GSSE: Input 7 default
105 038
GSSE: Input 8 default
105 043
GSSE: Input 9 default
105 048
GSSE: Input 10 default
105 053
GSSE: Input 11 default
105 058
GSSE: Input 12 default
105 063
GSSE: Input 13 default
105 068
GSSE: Input 14 default
105 073
GSSE: Input 15 default
105 078
GSSE: Input 16 default
105 083
GSSE: Input 17 default
105 088
GSSE: Input 18 default
105 093
GSSE: Input 19 default
105 098
GSSE: Input 20 default
105 103
GSSE: Input 21 default
105 108
GSSE: Input 22 default
105 113
GSSE: Input 23 default
105 118
GSSE: Input 24 default
105 123
GSSE: Input 25 default
105 128
GSSE: Input 26 default
105 133
GSSE: Input 27 default
105 138
GSSE: Input 28 default
105 143
GSSE: Input 29 default
105 148
GSSE: Input 30 default
105 153
GSSE: Input 31 default
105 158
GSSE: Input 32 default
Default for the virtual binary GSSE input. The state of a virtual two-pole
GSSE input will revert to default as soon as the continuously monitored
communication link to a GSSE sending device (IED situated on the opposite
side) is in fault or has disappeared altogether.
7-32
7 Settings
(continued)
105 004
GSSE: Input 1 fct.assig.
105 009
GSSE: Input 2 fct.assig.
105 014
GSSE: Input 3 fct.assig.
105 019
GSSE: Input 4 fct.assig.
105 024
GSSE: Input 5 fct.assig.
105 029
GSSE: Input 6 fct.assig.
105 034
GSSE: Input 7 fct.assig.
105 039
GSSE: Input 8 fct.assig.
105 044
GSSE: Input 9 fct.assig.
105 049
GSSE: Input 10 fct.assig.
105 054
GSSE: Input 11 fct.assig.
105 059
GSSE: Input 12 fct.assig.
105 064
GSSE: Input 13 fct.assig.
105 069
GSSE: Input 14 fct.assig.
105 074
GSSE: Input 15 fct.assig.
105 079
GSSE: Input 16 fct.assig.
105 084
GSSE: Input 17 fct.assig.
105 089
GSSE: Input 18 fct.assig.
105 094
GSSE: Input 19 fct.assig.
105 099
GSSE: Input 20 fct.assig.
105 104
GSSE: Input 21 fct.assig.
105 109
GSSE: Input 22 fct.assig.
105 114
GSSE: Input 23 fct.assig.
105 119
GSSE: Input 24 fct.assig.
105 124
GSSE: Input 25 fct.assig.
105 129
GSSE: Input 26 fct.assig.
105 134
GSSE: Input 27 fct.assig.
105 139
GSSE: Input 28 fct.assig.
105 144
GSSE: Input 29 fct.assig.
105 149
GSSE: Input 30 fct.assig.
105 154
GSSE: Input 31 fct.assig.
105 159
GSSE: Input 32 fct.assig.
Function assignment of the virtual GSSE input to a binary logical state
signal on the device (IED) so that it can be processed further by the
protection or logic functions. The signal configured at this point will receive
the state of the bit pair, as configured above, and which was received with
GSSE
IRIG-B interface
056 072
IRIGB: Function group IRIGB
Cancelling function group IRIGB or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
023 200
Fig. 3-17
7-33
7 Settings
(continued)
Binary input
The P63x has opto-coupler inputs for processing binary signals from the substation.
The number and connection schemes for the available binary signal inputs are shown in
the terminal connection diagrams. The configuration options for all binary inputs can be
displayed in the support software.
The P63x identifies the installed modules during startup. If a given binary I/O module is
not installed or has fewer binary signal inputs than the maximum number possible at this
slot, then the configuration addresses for the missing binary signal inputs are
automatically hidden in the menu tree.
When configuring binary inputs, one should keep in mind that the same function can be
assigned to several signal inputs. Thus one function can be activated from several
control points having different signal voltages.
In order to ensure that the device will recognize the input signals, the triggering signals
must persist for at least 30 ms.
The operating mode for each binary signal input can be defined. The user can specify
whether the presence (active high mode) or absence (active low mode) of a voltage
shall be interpreted as the logic 1 signal.
7-34
7 Settings
(continued)
152 199
152 202
152 205
152 208
190 002
190 006
190 010
190 014
190 018
190 022
190 026
190 030
190 034
190 038
190 042
190 046
190 050
190 054
190 058
190 062
190 066
190 070
190 074
190 078
190 082
190 086
190 090
190 094
192 002
192 006
192 010
192 014
192 018
192 022
153 087
153 090
153 093
153 096
7-35
7 Settings
(continued)
7-36
152 200
152 203
152 206
152 209
190 003
190 007
190 011
190 015
190 019
190 023
190 027
190 031
190 035
190 039
190 043
190 047
190 051
190 055
190 059
190 063
190 067
190 071
190 075
190 079
190 083
190 087
190 091
190 095
192 003
192 007
192 011
192 015
192 019
192 023
153 088
153 091
153 094
153 097
7 Settings
(continued)
056 030
MEASI: Function group MEASI
Cancelling function group MEASI or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
011 100 Fig. 3-19
MEASI: General enable USER
Disabling or enabling analog measured data input.
037 190
Fig: 3-21,
3-22
Setting for the minimum current that must flow in order for the P63x to
display a measured value > 0 (zero suppression).
037 191 Fig. 3-22
MEASI: IDC< open circuit
If the input current falls below the set threshold, the P63x will issue an open
circuit signal.
MEASI: IDC 1
037 150
Fig: 3-20,
3-21,3-22
Fig. 3-22
037 152
MEASI: IDC 2
037 154 Fig. 3-22
MEASI: IDC 3
037 156 Fig. 3-22
MEASI: IDC 4
037 158 Fig. 3-22
MEASI: IDC 5
037 160 Fig. 3-22
MEASI: IDC 6
037 162 Fig. 3-22
MEASI: IDC 7
037 164 Fig. 3-22
MEASI: IDC 8
037 166 Fig. 3-22
MEASI: IDC 9
037 168 Fig. 3-22
MEASI: IDC 10
037 170 Fig. 3-22
MEASI: IDC 11
037 172 Fig. 3-22
MEASI: IDC 12
037 174 Fig. 3-22
MEASI: IDC 13
037 176 Fig. 3-22
MEASI: IDC 14
037 178 Fig. 3-22
MEASI: IDC 15
037 180 Fig. 3-22
MEASI: IDC 16
037 182 Fig. 3-22
MEASI: IDC 17
037 184 Fig. 3-22
MEASI: IDC 18
037 186 Fig. 3-22
MEASI: IDC 19
037 188 Fig. 3-22
MEASI: IDC 20
Setting for the input current that will correspond to a linearized value that
has been set accordingly.
7-37
7 Settings
(continued)
MEASI: IDC,lin 1
037 151
Fig: 3-20,
3-21,3-22
Fig. 3-22
037 153
MEASI: IDC,lin 2
037 155 Fig. 3-22
MEASI: IDC,lin 3
037 157 Fig. 3-22
MEASI: IDC,lin 4
037 159 Fig. 3-22
MEASI: IDC,lin 5
037 161 Fig. 3-22
MEASI: IDC,lin 6
037 163 Fig. 3-22
MEASI: IDC,lin 7
037 165 Fig. 3-22
MEASI: IDC,lin 8
037 167 Fig. 3-22
MEASI: IDC,lin 9
037 169 Fig. 3-22
MEASI: IDC,lin 10
037 171 Fig. 3-22
MEASI: IDC,lin 11
037 173 Fig. 3-22
MEASI: IDC,lin 12
037 175 Fig. 3-22
MEASI: IDC,lin 13
037 177 Fig. 3-22
MEASI: IDC,lin 14
037 179 Fig. 3-22
MEASI: IDC,lin 15
037 181 Fig. 3-22
MEASI: IDC,lin 16
037 183 Fig. 3-22
MEASI: IDC,lin 17
037 185 Fig. 3-22
MEASI: IDC,lin 18
037 187 Fig. 3-22
MEASI: IDC,lin 19
037 189 Fig. 3-22
MEASI: IDC,lin 20
Setting for the linearized current that will correspond to an input current that
has been set accordingly.
7-38
037 192
Fig. 3-23
037 193
Fig. 3-23
7 Settings
(continued)
Binary outputs
The P63x has output relays for the output of binary signals. The number and connection
schemes for the available output relays are shown in the terminal connection diagrams.
The configuration options for all binary outputs can be displayed in the support software.
The P63x identifies the installed modules during startup. If a given binary I/O module is
not installed or has fewer output relays than the maximum number possible at that slot,
then the configuration addresses for the missing output relays are automatically hidden
in the menu tree.
The contact data for the all-or-nothing relays permits them to be used either as
command relays or as signal relays. One signal can also be assigned simultaneously to
several output relays for the purpose of contact multiplication.
An operating mode can be defined for each output relay. Depending on the selected
operating mode, the output relay will operate in either an energize-on-signal (ES) mode
or a normally-energized (NE) mode and in either a latching or non-latching mode. For
output relays operating in latching mode, the operating mode setting also determines
when latching will be cancelled.
OUTP: Fct. assignm. K 1201
OUTP: Fct. assignm. K 1202
OUTP: Fct. assignm. K 1601
OUTP: Fct. assignm. K 1602
OUTP: Fct. assignm. K 1603
OUTP: Fct. assignm. K 1604
OUTP: Fct. assignm. K 1605
OUTP: Fct. assignm. K 1606
OUTP: Fct. assignm. K 1607
OUTP: Fct. assignm. K 1608
OUTP: Fct. assignm. K 1801
OUTP: Fct. assignm. K 1802
OUTP: Fct. assignm. K 1803
OUTP: Fct. assignm. K 1804
OUTP: Fct. assignm. K 1805
OUTP: Fct. assignm. K 1806
OUTP: Fct. assignm. K 2001
OUTP: Fct. assignm. K 2002
OUTP: Fct. assignm. K 2003
OUTP: Fct. assignm. K 2004
OUTP: Fct. assignm. K 2005
OUTP: Fct. assignm. K 2006
OUTP: Fct. assignm. K 2007
OUTP: Fct. assignm. K 2008
Assignment of functions to output relays.
151 009
151 012
171 002
171 006
171 010
171 014
171 018
171 022
171 026
171 030
173 002
173 006
173 010
173 014
173 018
173 022
151 201
151 204
151 207
151 210
151 213
151 216
151 219
151 222
7-39
7 Settings
(continued)
7-40
151 010
151 013
171 003
171 007
171 011
171 015
171 019
171 023
171 027
171 031
173 003
173 007
173 011
173 015
173 019
173 023
151 202
151 205
151 208
151 211
151 214
151 217
151 220
151 223
7 Settings
(continued)
056 020
MEASO: Function group MEASO
Cancelling function group MEASI or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden. If the function group is cancelled from the
configuration, then all associated settings and signals are hidden.
031 074
Fig. 3-27
where:
Mx,scal :
Mx,max :
053 000
Fig. 3-32
053 001
where:
Mx,min :
M x,RL :
7-41
7 Settings
(continued)
where:
M x,knee :
M x,RL :
measured value
range limit value of the selected measured value
Measured values
Range
0 ... 1
Range
with:
Mx,scal,min = (Mx,min - Mx,RL1) / (Mx,RL2 - Mx,RL1
Mx,scal,max = (Mx,max - Mx,RL1) / (Mx,RL2 - Mx,RL1
Designation
Mx,knee
Mx,scaled,knee
with:
Mx,scaled,knee = (Mx,min - Mx,RL1) / (Mx,RL2 - Mx,RL1
7-42
7 Settings
(continued)
037 107
Fig. 3-32
037 113
037 109
Fig. 3-32
037 115
Display values
with:
Mx,min ... Mx,max : measured values to be issued
037 120
037 121
037 122
Fig: 3-30,
3-32
Fig: 3-30,
3-32
Fig: 3-30,
3-32
7-43
7 Settings
(continued)
LED indicators
The P63x has a total of 17 LED indicators for parallel display of binary signals.
The configuration options for all LED indicators can be displayed in the support software.
LED indicator H 1 is not configurable. It is labeled "HEALTHY" and signals the
operational readiness of the protection unit (supply voltage present). LED indicators H 2
and H 3 are not configurable either. H 2 is labeled "OUT OF SERVICE" and signals a
blocking or malfunction; H 3 is labeled "ALARM" and signals a warning alarm.
LED indicator H 17 indicates that the user is in the "EDIT MODE".
The factory setting for LED indicator H 4 is shown in the terminal connection drawings
included in the documentation or the appendix.
The layout of the LED indicators is shown in the dimensional drawings in chapter 4.
An operating mode can be defined for each LED indicator. Depending on the set
operating mode, the LED indicator will operate in either energize-on-signal (ES) mode
('open-circuit principle') or normally-energized (NE) mode ('closed-circuit principle') and
in either latching or non-latching mode. For LED indicators operating in latching mode,
the operating mode setting also determines when latching will be cancelled.
7-44
7 Settings
(continued)
085 001
Fig. 3-33
085 004
Fig. 3-33
085 007
Fig. 3-33
085 002
085 010
085 013
085 016
085 019
085 022
085 025
085 028
085 031
085 034
085 037
085 040
085 043
085 005
085 008
085 011
085 014
085 017
085 020
085 023
085 026
085 029
085 032
085 035
085 038
085 041
085 044
7-45
7 Settings
(continued)
Main function
MAIN: Chann.assign.COMM1/2
Assignment of communication interfaces to physical communication
channels.
003 169
Fig. 3-61
7-46
103 212
Page: 3-91
7 Settings
(continued)
Cancelling protection
functions
By means of a configuration procedure, the user can adapt the device functions flexibly
to the scope of protection functions required in each particular h.v. system.
The following conditions must be met before a protection function can be cancelled:
None of the elements of the protection function being cancelled may be assigned to a
binary input.
None of the signals of the protection function may be assigned to a binary output or
an LED indicator.
None of the signals of the protection function may be linked to other signals.
056 027
056 037
Ground differential protection REF_1: Function group REF_1
(Br: Restricted earth fault protection) REF_2: Function group REF_2
056 038
056 039
REF_3: Function group REF_3
Cancelling function groups REF_1 to REF_3 or including them in the
configuration. If a function group is cancelled, then all associated settings
and signals are hidden, with the exception of this setting.
Note:
Ground differential protection is not available with the P631.
Function group REF_3 is available with the P633 and the P634 only.
Definite-time overcurrent
protection
056 031
DTOC1: Function group DTOC1
056 032
DTOC2: Function group DTOC2:
056 053
DTOC3: Function group DTOC3
Cancelling function groups DTOC1 to DTOC3 or including them in the
configuration. If a function group is cancelled, then all associated settings
and signals are hidden, with the exception of this setting.
Note:
Function group DTOC3 is available with the P633 and the P634 only.
7-47
7 Settings
(continued)
Inverse-Time Overcurrent
Protection
056 051
IDMT1: Function group IDMT1
056 061
IDMT2: Function group IDMT2
056 071
IDMT3: Function group IDMT3
Cancelling function groups IDMT1 to IDMT3 or including them in the
configuration. If a function group is cancelled, then all associated settings
and signals are hidden, with the exception of this setting.
Note:
Function group IDMT3 is available with the P633 and the P634 only.
056 054
Thermal Overload Protection THRM1: Function group THRM1
056 055
THRM2: Function group THRM2
Cancelling function groups THR_1 to THRM_2 or including them in the
configuration. If the function group is cancelled from the configuration, then
all associated settings and signals are hidden.
Note:
Function group THRM2 is available with the P633 and the P634 only.
Time-Voltage Protection
056 010
Note:
Time-voltage protection is not available with the P631.
Frequency Protection
056 033
Note:
Frequency protection is not available with the P631.
Overfluxing protection
056 056
Current Transformer
Supervision
056 077
7-48
7 Settings
(continued)
056 073
056 074
MCM_2: Function group MCM_2
056 075
MCM_3: Function group MCM_3
056 076
MCM_4: Function group MCM_4
Cancelling function groups MCM_1 to MCM_4 or including them in the
configuration. If the function group is cancelled from the configuration, then
all associated settings and signals are hidden, with the exception of this
setting.
Note:
056 025
LIMIT: Function group LIMIT
Cancelling function group LIMIT or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
056 042
Limit Value Monitoring, 1 to 3 LIM_1: Function group LIM_1
056 043
LIM_2: Function group LIM_2
056 050
LIM_3: Function group LIM_3
Cancelling function groups LIM_1 to LIM_3 or including them in the
configuration. If a function group is cancelled, then all associated settings
and signals are hidden, with the exception of this setting.
Note:
Logic
056 017
LOGIC: Function group LOGIC
Cancelling function group LOGIC or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
7-49
7 Settings
(continued)
7.1.3
7.1.3.1
PC link
Function Parameters
Global
PC: Sig./meas.val.block.
When signal and measured value blocking is activated, no signals or
measured data are transmitted through the PC interface.
Communication interface 1
003 086
Fig. 3-5
3-8,3-9
Binary outputs
021 014
Fig. 3-25
Main function
003 030
Fig: 3-26,
3-50, 3-54
010 030
010 049
Fig: 3-83,
3-84, 3-102,
3-113, 3-142,
3-148
7-50
7 Settings
(continued)
019 020
019 021
019 022
019 026
Fig: 3-41,
3-80, 3-94
Fig: 3-41,
3-80
Fig: 3-41,
3-80
Fig: 3-41,
3-80
Setting for the primary nominal current of the main current transformer
(phase currents) of end a or b .
MAIN: Inom C.T.Yprim,end a
019 027
Fig: 3-42,
3-80
Fig. 3-42
019 028
MAIN: Inom C.T.Yprim,end b
019 029 Fig. 3-42
MAIN: Inom C.T.Yprim,end c
Setting for the primary nominal current of the main current transformer at
the neutral-point-to-ground connection.
010 002
Fig. 3-45
010 024
010 025
010 029
010 047
Fig: 3-35,
3-36a
Fig: 3-35,
3-36b
Fig: 3-35,
3-36b
Fig: 3-36b
010 142
010 143
010 144
010 009
Fig: 3-35,
3-36a
Fig: 3-35,
3-36b
Fig: 3-35,
3-36b
Fig: 3-35,
3-45
Setting for the secondary nominal voltage of the system transformer for
voltage measurement.
MAIN: Conn.meas.circ. IP,a
010 140
010 150
010 160
010 170
MAIN: Conn.meas.circ. IP,d
The vectorial sum of the phase currents of end a to d is governed by the
connection of the measuring circuits. If the connection is as shown in
Chapter 5, then the setting must be 'Standard'. If the connection direction is
reversed then the setting must be 'Opposite'. Instead of accounting for
connection reversal applied to one end in the settings for DIFF: Vector grp.
ends z1-z2 (where z1-z2 stands for a-b, a-c or a-d), it is possible to account
for it in the settings for connection of the measuring circuits.
Fig: 3-35,
3-36a
Fig: 3-35,
3-36b
Fig: 3-35,
3-36b
Fig: 3-36b
7-51
7 Settings
(continued)
010 141
010 151
010 161
Fig: 3-35,
3-36a
Fig: 3-35,
3-36b
Fig: 3-35,
3-36b
Setting for the minimum current that must be exceeded in order for the
measured operating values of the phase currents to be displayed.
MAIN: Meas.value rel. Ineg
MAIN: Meas.value rel. Ipos
MAIN: Meas. value rel. IN
011 048
Page: 3-74
011 058
Page: 3-74
011 031
Fig: 3-42,
3-43,3-44
011 036
Fig. 3-42
011 032
Fig. 3-45
010 113
Fig: 3-40,
3-41
Setting for the minimum current that must be exceeded in order for the
measured operating value of the residual current to be displayed.
Setting for the time after which the delayed maximum current display shall
reach 95% of the maximum current IP,max.
021 021 Fig. 3-52
MAIN: Fct.assign. block. 1
Assignment of functions that will be blocked together when blocking input 1
(M A I N : B l o c k i n g 1 E X T ) is activated.
021 022 Fig. 3-52
MAIN: Fct.assign. block. 2
Assignment of functions that will be blocked together when blocking input 2
(M A I N : B l o c k i n g 2 E X T ) is activated.
021 048 Fig. 3-52
MAIN: Fct.assign. block. 3
Assignment of functions that will be blocked together when blocking input 3
(M A I N : B l o c k i n g 3 E X T ) is activated.
021 049 Fig. 3-52
MAIN: Fct.assign. block. 4
Assignment of functions that will be blocked together when blocking input 4
(M A I N : B l o c k i n g 4 E X T ) is activated.
7-52
021 012
Fig. 3-57
7 Settings
(continued)
021 001
Fig. 3-57
021 002
Fig. 3-57
021 046
Fig. 3-57
021 047
Fig. 3-57
021 003
Fig. 3-57
021 004
Fig. 3-57
021 032
Fig. 3-57
021 033
Fig. 3-57
021 023
Fig. 3-57
021 024
Fig. 3-57
021 025
Fig. 3-57
021 026
Fig. 3-57
003 060
Fig. 3-63
7-53
7 Settings
(continued)
Self-Monitoring
021 018
Page: 3-99
7-54
7 Settings
(continued)
7.1.3.2
Main function
General Functions
019 017
Fig: 3-80,
3-94
019 018
Fig. 3-80
019 019
Fig. 3-80
019 037
Fig. 3-80
Note:
This setting is available for the P633 and the P634 only.
Differential Protection
019 080
Fig. 3-79
019 016
Fig. 3-80
019 023
Fig. 3-80
019 024
Fig. 3-80
019 025
Fig. 3-80
019 038
Fig. 3-80
7-55
7 Settings
(continued)
004 105
Fig: 3-80,
3-81
004 106
DIFF: Matching fact. kam,b
004 127
DIFF: Matching fact. kam,c
004 168
DIFF: Matching fact. kam,d
Display of the matching factor calculated by the P63x for end a, b, c or d.
011 037 Fig. 3-92
DIFF: Meas. value rel. Id
Setting for the minimum differential current that must be exceeded in order
for the P63x to display the differential currents as measured operating data.
011 038 Fig. 3-92
DIFF: Meas. value rel. IR
Setting for the minimum restraining current that must be exceeded in order
for the P63x to display the restraining currents as measured operating data.
019 050
Fig. 3-93
019 150
019 250
019 100
REF_1: Select. meas. input
019 101
REF_2: Select. meas. input
019 102
REF_3: Select. meas. input
Display of the measuring input that provides the measured values evaluated
by the ground differential protection function.
019 031 Fig. 3-94
REF_1: Reference power Sref
019 032
REF_2: Reference power Sref
019 033
REF_3: Reference power Sref
Setting for the reference power, usually the nominal transformer power for
the relevant transformer end.
019 034 Fig. 3-94
REF_1: Ref. current Iref
019 035
REF_2: Ref. current Iref
019 036
REF_3: Ref. current Iref
Display of the reference current calculated by the P63x.
004 160 Fig. 3-94
REF_1: Matching fact. kam,N
004 161
REF_2: Matching fact. kam,N
004 162
REF_3: Matching fact. kam,N
Display of the matching factor calculated by the P63x for the vector sum of
the phase currents.
004 163 Fig. 3-94
REF_1: Matching fact. kam,Y
004 164
REF_2: Matching fact. kam,Y
004 165
REF_3: Matching fact. kam,Y
Display of the matching factor calculated by the P63x for the neutral-point
current.
7-56
7 Settings
(continued)
Definite-time overcurrent
protection
031 135
Fig. 3-100
031 136
031 139
Note:
Function group DTOC3 is available with the P633 and the P634
only.
019 103 Fig. 3-99
DTOC1: Select. meas. input
019 104
DTOC2: Select. meas. input
019 105
DTOC3: Select. meas. input
Selection of the measuring input that provides the measured values
monitored by the definite-time overcurrent protection function.
Inverse-Time Overcurrent
Protection
Fig. 3-107
031 142
031 143
Function group IDMT3 is available with the P633 and the P634
031 141
019 106
Fig. 3-106
019 116
019 126
031 144
Fig. 3-119
031 145
Function group THRM2 is available with the P633 and the P634
7-57
7 Settings
(continued)
039 121
Fig. 3-123
039 181
004 152
THRM1: O/T f.Iref persist 1
004 172
THRM2: O/T f.Iref persist 2
Display of the difference between the settings for the maximum permissible
temperatures of the protected object and the coolant.
Time-Voltage Protection
Frequency protection
023 030
Fig. 3-125
023 031
Fig. 3-128
Note:
Frequency protection is not available with the P631.
018 201 Fig. 3-129
f<>: Evaluation time
Setting for the evaluation time. The operate conditions must be met for the
duration of the set evaluation time so that a signal is issued.
018 200 Fig. 3-129
f<>: Undervolt. block. V<
Setting for the threshold of undervoltage blocking. If the voltage falls below
this threshold, the over-/underfrequency protection function will be blocked.
Overfluxing protection
019 097
Fig. 3-132
Current Transformer
Supervision
031 085
Fig. 3-140
031 146
Fig. 3-147
7-58
031 147
031 148
031 149
031 150
031 151
031 152
031 153
7 Settings
(continued)
014 010
Fig. 3-150
LIMIT: IDC,lin>
Setting for operate value IDC,lin> for monitoring the linearized direct
current.
LIMIT: IDC,lin>>
Setting for operate value IDC,lin>> for monitoring the linearized direct
current.
014 110
Fig. 3-150
014 111
Fig. 3-150
LIMIT: tIDC,lin>
Setting for the operate delay of overcurrent stage IDC,lin>.
LIMIT: tIDC,lin>>
Setting for the operate delay of overcurrent stage IDC,lin>>.
014 112
Fig. 3-150
014 113
Fig. 3-150
LIMIT: IDC,lin<
Setting for operate value IDC,lin< for monitoring the linearized direct
current.
LIMIT: IDC,lin<<
Setting for operate value IDC,lin<< for monitoring the linearized direct
current.
014 114
Fig. 3-150
014 115
Fig. 3-150
LIMIT: tIDC,lin<
Setting for the operate delay of undercurrent stage IDC,lin<.
LIMIT: tIDC,lin<<
Setting for the operate delay of undercurrent stage IDC,lin<<.
014 116
Fig. 3-150
014 117
Fig. 3-150
LIMIT: T>
Setting for the operate value of temperature monitoring T>.
LIMIT: T>>
Setting for the operate value of temperature monitoring T>>.
014 100
Fig. 3-151
014 101
Fig. 3-151
LIMIT: tT>
Setting for the operate delay of temperature monitoring T>.
014 103
Fig. 3-151
LIMIT: tT>>
Setting for the operate delay of temperature monitoring T>>.
LIMIT: T<
Setting for the operate value of temperature monitoring T<.
014 104
Fig. 3-151
014 105
Fig. 3-151
LIMIT: T<<
Setting for the operate value of temperature monitoring T<<.
014 106
Fig. 3-151
LIMIT: tT<
Setting for the operate delay of temperature monitoring T<.
LIMIT: tT<<
Setting for the operate delay of temperature monitoring T<<.
014 107
Fig. 3-151
014 108
Fig. 3-151
7-59
7 Settings
(continued)
7-60
014 014
Fig. 3-153
014 015
014 017
019 111
LIM_1: I>>
LIM_2: I>>
LIM_3: I>>
Setting for the operate value of I>>.
015 117
LIM_1: tI>>
LIM_2: tI>>
LIM_3: tI>>
Setting for the operate delay of I>>.
015 121
LIM_1: tI>
LIM_2: tI>
LIM_3: tI>
Setting for the operate delay of I>.
015 120
LIM_1: I<
LIM_2: I<
LIM_3: I<
Setting for the operate value of I<.
LIM_1: tI<
LIM_2: tI<
LIM_3: tI<
Setting for the operate delay of I<.
015 118
LIM_1: I<<
LIM_2: I<<
LIM_3: I<<
Setting for the operate value of I<<.
015 119
LIM_1: tI<<
LIM_2: tI<<
LIM_3: tI<<
Setting for the operate delay of I<<.
015 123
Fig. 3-152
019 112
019 113
015 116
Fig. 3-153
016 116
017 114
Fig. 3-153
016 117
017 117
Fig. 3-153
016 121
017 121
Fig. 3-153
016 120
017 120
Fig. 3-153
016 118
017 118
015 122
Fig. 3-153
016 122
017 122
Fig. 3-153
016 119
017 119
Fig. 3-153
016 123
017 123
7 Settings
(continued)
Logic
031 099
Fig. 3-155
034 030
Fig: 3-154,
3-155
034 031
034 037
Fig. 3-155
030 000
Fig. 3-155
034 032
034 033
034 034
034 035
034 036
030 004
030 008
030 012
030 016
030 020
030 024
030 028
030 032
030 036
030 040
030 044
030 048
030 052
030 056
030 060
030 064
030 068
030 072
030 076
030 080
030 084
030 088
030 092
030 096
031 000
031 004
031 008
031 012
031 016
031 020
031 024
7-61
7 Settings
(continued)
7-62
030 001
Fig. 3-155
030 005
030 009
030 013
030 017
030 021
030 025
030 029
030 033
030 037
030 041
030 045
030 049
030 053
030 057
030 061
030 065
030 069
030 073
030 077
030 081
030 085
030 089
030 093
030 097
031 001
031 005
031 009
031 013
031 017
031 021
031 025
7 Settings
(continued)
030 002
Fig. 3-155
030 006
030 010
030 014
030 018
030 022
030 026
030 030
030 034
030 038
030 042
030 046
030 050
030 054
030 058
030 062
030 066
030 070
030 074
030 078
030 082
030 086
030 090
030 094
030 098
031 002
031 006
031 010
031 014
031 018
031 022
031 026
7-63
7 Settings
(continued)
7-64
030 003
Fig. 3-155
030 007
030 011
030 015
030 019
030 023
030 027
030 031
030 035
030 039
030 043
030 047
030 051
030 055
030 059
030 063
030 067
030 071
030 075
030 079
030 083
030 087
030 091
030 095
030 099
031 003
031 007
031 011
031 015
031 019
031 023
031 027
7 Settings
(continued)
7-65
7 Settings
(continued)
7-66
7 Settings
(continued)
7.1.3.3
Main function
Differential Protection
Parameter Subsets
Fig. 3-37
Fig. 3-79
Fig. 3-83
Fig. 3-37
Fig. 3-37
Fig. 3-37
Fig. 3-83
Fig. 3-84
Setting = ID + 6
If the addition results in a value > 12 then:
Setting = (ID + 6) 12
If the phase currents of the low and high voltage sides are exchanged and if
this is not accounted for by the settings at M AIN : C on n .m eas ,c irc .
IP,z (where z is end a,b,c or d) a nd M AIN : C onn .me as,c irc . IY,z
(where z is end a,b or c) then the algorithm is:
Setting = 12 ID
If an A-C-B phase sequence (or "anti-clockwise rotating field") is present
then this should be entered as a setting at the P63x. In this case, the P63x
will automatically form the complementary value of the set vector group ID
to the number 12 (vector group ID = 12 set ID).
For application of the P63x as machine protection, the setting must be 0 or
6 depending on the current transformer connection.
072 142 073 142 074 142 075 142
DIFF: Idiff>
PSx
Operate value of the differential protection function as referred to the
reference current of the relevant transformer end.
Fig. 3-88
7-67
7 Settings
(continued)
Note:
If the threshold is set too high, the P63x might not trip in the presence of
internal faults with transformer saturation.
072 144 073 144 074 144 075 144
DIFF: Idiff>>>
PSx
This setting defines the threshold value for the differential current where the
differential protection is triggered regardless of restraining quantity, inrush
stabilization and saturation discriminator.
Fig. 3-88
Fig. 3-88
Note:
If the threshold is set too low, the P63x can trip in the presence of external
faults with transformer saturation.
DIFF: Idiff>(CTS)
PSx
Fig: 3-88,
3-86
7-68
Fig. 3-88
Fig. 3-88
Fig. 3-88
Fig. 3-89
Fig. 3-83
Fig. 3-83
Fig. 3-84
Fig. 3-88
Fig. 3-83
7 Settings
(continued)
Fig. 3-91
Fig. 3-91
Fig. 3-88
Fig. 3-93
Fig. 3-97
Fig. 3-97
Fig. 3-97
7-69
7 Settings
(continued)
Fig. 3-97
Definite-time overcurrent
protection
Fig. 3-97
Fig. 3-97
Fig. 3-100
Fig. 3-103
Fig: 3-102,
3-103, 3-104
7-70
Fig. 3-104
Fig: 3-101,
3-102
7 Settings
(continued)
DTOC1: I>
PSx
DTOC2: I>
PSx
DTOC3: I>
PSx
Setting for operate value I>.
DTOC1: I>>
PSx
DTOC2: I>>
PSx
DTOC3: I>>
PSx
Setting for operate value I>>.
Fig. 3-101
Fig. 3-101
Fig. 3-101
Fig. 3-101
Fig. 3-101
DTOC1: tI>
PSx
DTOC2: tI>
PSx
DTOC3: tI>
PSx
Setting for the operate delay of the I> stage.
Fig. 3-101
DTOC1: tI>>
PSx
DTOC2: tI>>
PSx
DTOC3: tI>>
PSx
Setting for the operate delay of the I>> stage.
DTOC1: tI>>>
PSx
DTOC2: tI>>>
PSx
DTOC3: tI>>>
PSx
Setting for the operate delay of the I>>> stage.
DTOC1: Ineg>
PSx
DTOC2: Ineg>
PSx
DTOC3: Ineg>
PSx
Setting for the operate value of the Ineg> stage.
DTOC1: Ineg>>
PSx
DTOC2: Ineg>>
PSx
DTOC3: Ineg>>
PSx
Setting for the operate value of the Ineg>> stage.
Fig. 3-101
Fig. 3-101
Fig. 3-101
Fig. 3-102
Fig. 3-102
7-71
7 Settings
(continued)
DTOC1: Ineg>>>
PSx
DTOC2: Ineg>>>
PSx
DTOC3: Ineg>>>
PSx
Setting for the operate value of the Ineg>>> stage.
7-72
Fig. 3-102
Fig. 3-102
Fig. 3-102
Fig. 3-102
DTOC1: tIneg>
PSx
DTOC2: tIneg>
PSx
DTOC3: tIneg>
PSx
Setting for the operate delay of the Ineg> stage.
DTOC1: tIneg>>
PSx
DTOC2: tIneg>>
PSx
DTOC3: tIneg>>
PSx
Setting for the operate delay of the Ineg>> stage.
Fig. 3-102
DTOC1: tIneg>>>
PSx
DTOC2: tIneg>>>
PSx
DTOC3: tIneg>>>
PSx
Setting for the operate delay of the Ineg>>> stage.
DTOC1: IN>
PSx
DTOC2: IN>
PSx
DTOC3: IN>
PSx
Setting for operate value IN>.
DTOC1: IN>>
PSx
DTOC2: IN>>
PSx
DTOC3: IN>>
PSx
Setting for operate value IN>>.
DTOC1: IN>>>
PSx
DTOC2: IN>>>
PSx
DTOC3: IN>>>
PSx
Setting for operate value IN>>>.
Fig. 3-102
Fig. 3-102
Fig. 3-103
Fig. 3-103
Fig. 3-103
7 Settings
(continued)
Fig. 3-103
Fig. 3-103
Fig. 3-103
DTOC1: tIN>>
PSx
DTOC2: tIN>>
PSx
DTOC3: tIN>>
PSx
Setting for the operate delay of the IN>> stage.
DTOC1: tIN>>>
PSx
DTOC2: tIN>>>
PSx
DTOC3: tIN>>>
PSx
Setting for the operate delay of the IN>>> stage.
Fig. 3-103
Fig. 3-103
Fig. 3-103
7-73
7 Settings
(continued)
Inverse-Time Overcurrent
Protection
Fig. 3-107
Fig. 3-114
Fig: 3-113,
3-114, 3-116
7-74
Fig. 3-116
Fig: 3-112,
3-113
Fig. 3-112
Fig. 3-112
Fig. 3-112
Fig. 3-112
7 Settings
(continued)
Fig. 3-112
PSx
Fig. 3-112
Fig. 3-113
Fig. 3-113
Fig. 3-113
Fig. 3-113
Fig. 3-113
Fig. 3-113
Fig. 3-113
7-75
7 Settings
(continued)
7-76
Fig. 3-114
Fig. 3-114
Fig. 3-114
Fig. 3-114
Fig. 3-114
Fig. 3-114
Fig. 3-114
7 Settings
(continued)
Fig. 3-119
Fig. 3-123
Fig. 3-123
Fig. 3-123
Fig. 3-123
Note:
This setting option is only relevant when machines are running. In all other
cases, time constant 2 must be set equal to time constant 1.
081 077 082 077 083 077 084 077
THRM1: Max.perm.obj.tmp.PSx
081 097 082 097 083 097 084 097
THRM2: Max.perm.obj.tmp.PSx
Setting for the maximum permissible temperature of the protected object.
Fig. 3-123
Fig. 3-123
Note:
This setting is active only if the coolant temperature is measured via the
PT 100 or the 20 mA input.
081 072 082 072 083 072 084 072
THRM1: Select CTA
PSx
081 092 082 092 083 092 084 092
THRM2: Select CTA
PSx
Select the mode of the coolant temperature acquisition. Select from:
No data acquisition. A default temperature value is used instead.
Data acquisition via the PT 100 input
Data acquisition via the 20 mA input.
Fig. 3-122
Fig. 3-123
7-77
7 Settings
(continued)
Fig. 3-122
Fig. 3-123
Note:
If the operating mode has been set to Absolute replica, the setting here will
be automatically set to 100% and this parameter will be hidden as far as the
local control panel is concerned.
081 078 082 078 083 078 084 078
THRM1: Hysteresis trip PSx
081 098 082 098 083 098 084 098
THRM2: Hysteresis trip PSx
Setting for the hysteresis of the trip stage.
081 085 082 085 083 085 084 085
THRM1: Warning pre-trip PSx
081 105 082 105 083 105 084 105
THRM2: Warning pre-trip PSx
A warning will be given in advance of the trip. The time difference between
the warning time and the trip time is set here.
7-78
Fig. 3-123
Fig. 3-123
Fig. 3-123
7 Settings
(continued)
Time-Voltage Protection
Fig. 3-125
V<>: V>
PSx
Setting for operate value V>.
V<>: V>>
PSx
Setting for operate value V>>.
Fig. 3-126
Fig. 3-126
Fig. 3-126
Fig. 3-126
V<>: V<<
PSx
Setting for operate value V<<.
Fig. 3-127
Fig. 3-127
Fig. 3-127
Fig. 3-126
Fig. 3-127
Fig. 3-127
Fig. 3-127
7-79
7 Settings
(continued)
Frequency protection
Fig. 3-128
Fig. 3-131
Fig. 3-131
Fig. 3-131
f<>: df1/dt
PSx
f<>: df2/dt
PSx
f<>: df3/dt
PSx
f<>: df4/dt
PSx
Setting for the frequency gradient to be monitored
Fig. 3-131
Note:
This setting is effective only if operating mode
'f with df/dt' has been selected.
f<>: Delta f1
PSx
f<>: Delta f2
PSx
f<>: Delta f3
PSx
f<>: Delta f4
PSx
Setting for Delta f.
Fig. 3-131
Note:
This setting is effective only if operating mode
'f w. Delta f/Delta t' has been selected.
f<>: Delta t1
PSx
f<>: Delta t2
PSx
f<>: Delta t3
PSx
f<>: Delta t4
PSx
Setting for Delta t.
Fig. 3-131
Note:
This setting is effective only if operating mode
'f w. Delta f/Delta t' has been selected.
7-80
7 Settings
(continued)
Overfluxing protection
Fig. 3-132
Fig. 3-134
Fig. 3-135
Fig. 3-134
Fig. 3-137
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-138
Fig. 3-135
7-81
7 Settings
(continued)
Current Transformer
Supervision
Fig. 3-140
Fig. 3-142
Fig. 3-142
Fig. 3-142
MCM_1: Ineg/Ipos>
MCM_2: Ineg/Ipos>
MCM_3: Ineg/Ipos>
MCM_4: Ineg/Ipos>
PSx
PSx
PSx
PSx
Fig. 3-147
Fig. 3-148
7-82
Fig. 3-148
The P63x generates a large number of signals, processes binary input signals, and
acquires measured data during fault-free operation of the protected object as well as
fault-related data. A number of counters are available for statistical purposes.
This information can be read out from the integrated local control panel.
All this information can be found in the Operation and Events folders in the menu tree.
Note:
In the following tables the localization of the corresponding function description is
indicated in the right hand side column. "Figure: 3-xxx" refers to a logic diagram which
displays the address, "Figure*: 3-xxx" to a figure subtitle or figure report sheet,
"Page: 3-xxx" to a page.
8.1
Healthy
8.1.1
8.1.1.1
Measured Data Input
Cyclic Values
Measured Operating Data
004 134
Fig. 3-22
004 135
Fig. 3-22
004 136
Fig: 3-22,
3-23,3-150
004 180
Fig. 3-23
004 133
Fig: 3-24,
3-151
004 221
Fig. 3-24
005 100
Fig. 3-32
MAIN: Date
Date display.
003 090
Fig. 3-59
003 091
Fig. 3-59
Main function
Note:
The date can also be set here.
MAIN: Time of day
Display of the time of day.
Note:
005 099
8-1
003 095
Fig. 3-59
8-2
005 018
Fig. 3-45
005 111
005 112
005 116
005 113
Fig: 3-40,
3-41
Fig: 3-40,
3-41
Fig: 3-40,
3-41
Fig: 3-40,
3-41
8-3
005 163
006 163
007 163
008 163
Fig: 3-40,
3-41
Fig: 3-40,
3-41
Fig: 3-40,
3-41
Fig: 3-40,
3-41
005 031
Fig. 3-41
005 032
Fig. 3-41
005 033
Fig. 3-41
005 039
Fig. 3-41
Display of residual current for the virtual end, referred to Inom. The virtual
end is formed according to the selection at M AIN : Cu rren t s umm a tion .
005 114 Fig. 3-44
MAIN: IP,max,add p.u.
Display of the maximum phase current for the virtual end, referred to Inom.
The virtual end is formed according to the selection at M AIN : Curr en t
su mma tion.
MAIN: IP,min,add p.u.
005 110
Fig. 3-44
Display of the minimum phase current for the virtual end, referred to Inom.
The virtual end is formed according to the selection at M AIN : Curr en t
su mma tion.
MAIN: Curr. Ineg,add p.u.
005 149
Page: 3-74
006 031
Fig. 3-41
006 032
Fig. 3-41
006 033
Fig. 3-41
006 034
Fig. 3-41
007 031
Fig. 3-41
007 032
Fig. 3-41
007 033
Fig. 3-41
007 034
Fig. 3-41
005 126
Page: 3-74
005 130
005 137
005 145
005 160
006 160
007 160
008 160
Fig: 3-40,
3-41
Fig: 3-40,
3-41
Fig: 3-40,
3-41
Fig: 3-40,
3-41
005 107
Fig. 3-41
005 108
Fig. 3-41
005 109
Fig. 3-41
005 118
Fig. 3-41
005 128
Page: 3-74
005 151
Fig. 3-42
005 152
Fig. 3-42
005 153
Fig. 3-42
005 135
005 139
005 147
005 089
Fig. 3-47
005 092
Fig. 3-47
005 093
Fig. 3-47
005 095
Fig. 3-47
006 089
Fig. 3-47
006 092
Fig. 3-47
006 093
Fig. 3-47
006 095
Fig. 3-47
8-5
007 089
Fig. 3-47
007 092
Fig. 3-47
007 093
Fig. 3-47
007 095
Fig. 3-47
005 090
Fig. 3-48
006 090
Fig. 3-48
007 090
Fig. 3-48
005 091
Fig. 3-48
006 091
Fig. 3-48
007 091
Fig. 3-48
005 094
Fig. 3-48
006 094
Fig. 3-48
007 094
Fig. 3-48
Differential Protection
005 080
Fig. 3-92
006 080
Fig. 3-92
007 080
Fig. 3-92
005 081
Fig. 3-92
006 081
Fig. 3-92
007 081
Fig. 3-92
008 080
Fig. 3-98
8-6
008 070
REF_1: Restrain.curr.,REF_1
REF_2: Restrain.curr.,REF_2
REF_3: Restrain.curr.,REF_3
Display of the restraining current referred to Iref.
008 081
008 060
Fig. 3-98
008 071
008 061
004 153
Fig. 3-123
004 173
If, on the other hand, the coolant temperature and the maximum permissible
coolant temperature have been set to the same value, then the coolant
temperature is not taken into account and the characteristic is a function of
the current only. The additional reserve amounts to 0 in this case.
8-7
Overfluxing protection
004 220
Fig: 3-133,
3-134,
3-135,3-138
8.1.1.2
Generic Object Oriented
Substation Event
8-8
106 010
106 012
106 014
106 016
106 018
106 020
106 022
106 024
106 026
106 028
106 030
106 032
106 034
106 036
106 038
106 040
106 042
106 044
106 046
106 048
106 050
106 052
106 054
106 056
106 058
106 060
106 062
106 064
106 066
106 068
106 070
106 072
106 200
106 201
106 202
106 203
106 204
106 205
106 206
106 207
106 208
106 209
106 210
106 211
106 212
106 213
106 214
106 215
8-9
8-10
104 100
104 103
104 106
104 109
104 112
104 115
104 118
104 121
104 124
104 127
104 130
104 133
104 136
104 139
104 142
104 145
104 148
104 151
104 154
104 157
104 160
104 163
104 166
104 169
104 172
104 175
104 178
104 181
104 184
104 187
104 190
104 193
105 000
105 005
105 010
105 015
105 020
105 025
105 030
105 035
105 040
105 045
105 050
105 055
105 060
105 065
105 070
105 075
105 080
105 085
105 090
105 095
105 100
105 105
105 110
105 115
105 120
105 125
105 130
105 135
105 140
105 145
105 150
105 155
8-11
Binary input
152 198
152 201
152 204
152 207
190 001
190 005
190 009
190 013
190 017
190 021
190 025
190 029
190 033
190 037
190 041
190 045
190 049
190 053
190 057
190 061
190 065
190 069
190 073
190 077
190 081
190 085
190 089
190 093
192 001
192 005
192 009
192 013
192 017
192 021
153 086
153 089
153 092
153 095
'Without function':
'Low':
Not energized.
'High':
Energized.
This display appears regardless of the setting for the binary signal input
mode.
8-12
Binary outputs
'Low':
'High':
151 008
151 011
171 001
171 005
171 009
171 013
171 017
171 021
171 025
171 029
173 001
173 005
173 009
173 013
173 017
173 021
151 200
151 203
151 206
151 209
151 212
151 215
151 218
151 221
This display appears regardless of the operating mode set for the output
relay.
8-13
LED indicators
8-14
LED: State H 2
LED: State H 3
LED: State H 4
LED: State H 5
LED: State H 6
LED: State H 7
LED: State H 8
LED: State H 9
LED: State H 10
LED: State H 11
LED: State H 12
LED: State H 13
LED: State H 14
LED: State H 15
LED: State H 16
The state of the LED indicators is displayed as follows:
'Inactive':
'Active':
085 000
085 003
085 006
085 009
085 012
085 015
085 018
085 021
085 024
085 027
085 030
085 033
085 036
085 039
085 042
8.1.1.3
037 101
Communication interface 1
003 173
Fig. 3-6
037 074
003 174
COMM1: Sig./meas.val.block.
037 075
003 219
Fig: 3-7,
3-8,3-9
Fig: 3-6,
3-8,3-9,3-10,
3-11,3-12
Fig: 3-7,
3-8,3-9
Fig. 3-7
003 218
Fig. 3-8
003 221
Fig. 3-9
003 223
Fig. 3-10
003 230
Fig. 3-11
103 041
Fig. 3-12
105 180
IEC: Comm. link faulty
Display when an Ethernet module has not initiated properly, i.e. if the MAC
address is missing or there is a non-plausible parameter setting!
107 250
105 181
IRIGB: Enabled
IRIGB: Synchron. ready
023 201
Fig. 3-17
023 202
Fig. 3-17
MEASI: Enabled
035 008
040 190
040 191
040 192
Fig: 3-19,
3-22,3-24
Fig: 3-24,
3-122
Fig: 3-22,
3-122
Fig: 3-22,
3-122
8-15
Binary outputs
Main function
8-16
040 014
Fig. 3-25
040 015
Fig. 3-25
021 015
Fig. 3-25
040 088
Fig. 3-25
MEASO: Enabled
037 102
036 085
Fig: 3-27,
3-30,3-32
Fig. 3-28
036 087
Fig. 3-29
037 117
Fig. 3-29
037 050
Fig. 3-30
037 051
Fig. 3-30
037 052
Fig. 3-30
037 053
Fig. 3-30
037 054
Fig. 3-30
037 055
Fig. 3-30
037 056
Fig. 3-30
037 057
Fig. 3-30
037 058
Fig. 3-30
037 059
Fig. 3-30
037 060
Fig. 3-30
069 014
Fig. 3-32
037 118
Fig. 3-32
036 174
Page: 3-86
036 175
Page: 3-86
036 176
Page: 3-86
036 220
Fig. 3-37
003 027
Fig. 3-50
003 026
Fig. 3-50
004 060
069 015
037 119
003 096
040 060
Fig. 3-52
040 061
Fig. 3-52
040 116
Fig. 3-52
040 117
Fig. 3-52
040 138
Fig. 3-57
036 045
Fig. 3-57
004 061
036 033
Fig: 3-125,
3-131,
3-134,3-135,
3-138, 3-139
Fig. 3-51
037 018
Fig. 3-57
037 070
Fig. 3-62
065 001
Fig. 3-60
060 060
Fig. 3-59
003 028
Fig. 3-50
038 046
Fig: 3-5,
3-7,3-8,
3-9,3-14,
3-25,3-50
Fig. 3-54
037 071
MAIN: Blocked/faulty
MAIN: Meas. circ. I faulty
004 065
021 013
040 139
Fig: 3-53,
3-145, 3-149
Fig: 3-54,
3-57
Fig. 3-57
034 017
Fig. 3-57
036 251
036 005
Fig: 3-57,
3-141
Fig. 3-57
036 023
Fig. 3-57
036 108
Fig. 3-57
036 109
Fig. 3-57
036 071
036 022
Fig: 3-57,
3-58,3-123
Fig. 3-57
036 113
Fig. 3-57
036 114
Fig. 3-57
036 000
040 090
Fig: 3-41,
3-42,3-43,
3-44,3-45,
3-46,3-47,
3-48,3-49,
3-55, 3-56,
3-71
Fig: 3-51,
3-101,3-102,
3-103,3-112,
3-113,3-114
036 101
Fig. 3-63
065 002
Fig. 3-63
065 003
Fig. 3-63
065 004
Fig. 3-63
065 005
Fig. 3-63
036 102
Fig. 3-63
003 061
Fig. 3-63
036 094
Fig. 3-63
036 095
Fig. 3-63
036 096
Fig. 3-63
036 097
Fig. 3-63
003 062
Fig. 3-63
036 090
PSS: PS 2 active
036 091
PSS: PS 3 active
036 092
PSS: PS 4 active
036 093
Fig: 3-63,
3-140
Fig: 3-63,
3-140
Fig: 3-63,
3-140
Fig: 3-63,
3-140
036 155
Fig: 3-5,
3-7,3-8,
3-9,3-10,
3-11,3-12,
3-14,3-62
Fig. 3-54
8-17
Self-Monitoring
8-18
093 127
093 128
036 070
Fig. 3-64
036 100
Fig. 3-64
041 202
041 201
093 024
093 025
090 019
041 200
093 040
090 010
096 121
093 081
093 082
093 080
096 100
096 101
096 102
096 103
096 104
096 105
096 106
096 107
096 108
096 109
096 110
096 111
096 112
096 113
096 114
096 115
096 116
096 117
096 118
096 119
096 120
097 000
097 001
097 002
097 003
097 004
097 005
097 006
097 007
097 008
097 009
097 010
097 011
097 012
097 013
097 014
097 015
097 016
091 026
091 027
097 017
097 018
097 019
097 020
093 070
093 071
093 110
093 111
097 118
097 119
097 150
097 151
097 152
097 153
097 154
097 155
097 156
097 157
097 166
097 167
097 168
097 169
097 170
097 171
097 182
097 183
097 184
097 185
097 186
097 187
097 188
097 189
093 010
093 011
093 012
093 013
090 021
090 003
093 041
093 026
090 012
Fig. 3-66
093 015
093 075
093 113
093 112
098 000
091 018
Fig: 3-53,
3-145,3-149
Fig: 3-146,
3-148
091 028
091 029
8-19
Overload Recording
8-20
091 011
035 003
035 007
093 114
Fig. 3-32
093 115
093 116
Fig. 3-22
098 024
Fig. 3-24
098 025
Fig. 3-22
098 026
Fig. 3-22
098 028
Fig. 3-131
098 053
098 054
098 055
098 056
098 057
098 058
091 007
Fig. 3-80
091 008
Fig. 3-80
091 009
Fig. 3-80
091 016
Fig. 3-80
091 000
Fig. 3-80
091 001
Fig. 3-80
091 002
Fig. 3-80
091 017
Fig. 3-80
091 004
091 006
Fig. 3-80
091 105
Fig. 3-94
091 115
091 125
091 101
Fig. 3-94
091 111
091 121
091 102
Fig. 3-94
091 112
091 122
091 103
091 113
091 123
091 104
Fig. 3-94
091 114
091 124
098 036
Fig. 3-122
098 037
098 038
Fig. 3-123
098 039
093 120
Fig: 3-2,
3-67,3-68,
3-69, 3-70
Fig. 3-70
Fault Recording
Differential Protection
036 089
Fig. 3-76
037 076
Fig. 3-76
035 018
Fig. 3-76
035 019
Fig. 3-76
035 000
035 004
035 001
Fig: 3-2,
3-25, 3-34,
3-70, 3-72,
3-73, 3-74,
3-75,3-76,
3-77,3-78
Fig: 3-25,
3-34,3-76
Fig. 3-77
035 002
Fig. 3-70
DIFF: Enabled
041 210
DIFF: Starting
DIFF: Meas.system 1 trigg.
041 106
Fig: 3-79,
3-88
Fig. 3-55
041 125
Fig: 3-88,
3-89, 3-90,
3-91
Fig. 3-88
041 126
Fig. 3-88
041 221
Fig. 3-88
041 222
Fig. 3-88
041 118
041 119
Fig: 3-88,
3-89,3-101,
3-102,3-112,
3-113,3-141
Fig. 3-89
041 120
Fig. 3-89
041 121
041 122
Fig: 3-88,
3-91,3-141
Fig. 3-91
041 123
Fig. 3-91
041 115
Fig. 3-90
041 116
Fig. 3-90
041 117
Fig. 3-90
041 075
041 002
Fig: 3-72,
3-88,3-89
Fig. 3-88
041 003
Fig. 3-88
041 004
Fig. 3-88
041 132
Fig: 3-93,
3-97
041 124
REF_2: Enabled
REF_3: Enabled
REF_1: Trip signal
041 133
041 016
041 067
041 134
041 005
Fig: 3-55,
3-72,3-97
Fig: 3-55,
3-72
Fig. 3-55
8-21
Definite-time overcurrent
protection
8-22
035 120
Fig. 3-101
035 121
Fig. 3-101
035 122
Fig. 3-101
036 141
Fig. 3-102
036 142
Fig. 3-102
036 143
Fig. 3-102
035 123
Fig. 3-103
035 124
Fig. 3-103
035 125
Fig. 3-103
035 102
035 128
035 129
Fig: 3-100,
3-101,
3-102,3-103
Fig: 3-55,
3-72, 3-104,
3-105
Fig. 3-104
DTOC1: Starting B
035 105
DTOC1: Starting C
035 106
DTOC1: Starting N
035 107
035 108
035 109
035 110
035 114
Fig: 3-101,
3-103
Fig: 3-101,
3-103
Fig: 3-101,
3-103
Fig: 3-103,
3-104
Fig: 3-101,
3-104
Fig: 3-101,
3-104
Fig: 3-101,
3-104
Fig. 3-101
035 115
Fig. 3-101
035 116
Fig. 3-101
036 144
Fig. 3-102
036 145
Fig. 3-102
036 146
Fig. 3-102
036 147
Fig. 3-102
036 148
Fig. 3-102
036 149
Fig. 3-102
036 150
Fig. 3-102
036 151
Fig. 3-102
036 152
Fig. 3-102
036 153
Fig. 3-102
035 111
Fig. 3-103
035 112
Fig. 3-103
035 113
Fig. 3-103
035 117
Fig. 3-103
035 118
Fig. 3-103
035 119
Fig. 3-103
035 126
Fig. 3-103
035 130
Fig. 3-103
035 131
Fig. 3-103
035 104
035 150
035 151
035 229
036 161
036 162
035 245
035 250
036 163
035 230
035 231
035 232
035 132
035 234
Fig: 3-55,
3-72
035 134
035 135
035 141
035 146
035 138
035 139
035 149
035 144
035 145
035 158
036 164
036 165
036 166
036 167
036 168
036 169
036 170
036 171
036 172
036 173
035 152
035 153
035 154
035 159
035 225
035 226
035 233
035 246
035 247
035 237
035 238
035 239
036 181
036 182
036 183
035 240
035 241
035 242
035 136
035 244
Fig: 3-55,
3-72
035 180
035 185
8-23
Inverse-Time Overcurrent
Protection
8-24
DTOC3: Starting C
DTOC3: Starting N
DTOC3: Starting I>
DTOC3: Starting I>>
DTOC3: Starting I>>>
DTOC3: Trip signal tI>
DTOC3: Trip signal tI>>
DTOC3: Trip signal tI>>>
DTOC3: Starting Ineg
DTOC3: Starting Ineg>
DTOC3: Starting Ineg>>
DTOC3: Starting Ineg>>>
DTOC3: tIneg> elapsed
DTOC3: tIneg>> elapsed
DTOC3: tIneg>>> elapsed
DTOC3: Trip signal tIneg>
DTOC3: Trip signal tIneg>>
DTOC3: Trip signal tIneg>>>
DTOC3: Starting IN>
DTOC3: Starting IN>>
DTOC3: Starting IN>>>
DTOC3: tIN> elapsed
DTOC3: tIN>> elapsed
DTOC3: tIN>>> elapsed
DTOC3: Trip signal tIN>
DTOC3: Trip signal tIN>>
DTOC3: Trip signal tIN>>>
035 186
038 114
Fig. 3-112
038 178
038 124
Fig: 3-113,
3-114
Fig. 3-114
038 115
038 116
038 117
038 118
038 119
038 111
038 112
038 113
038 174
Fig: 3-113,
3-116
Fig. 3-113
038 177
Fig. 3-113
035 187
035 188
035 189
035 190
035 205
035 206
035 208
036 184
036 185
036 186
036 187
036 188
036 189
036 190
036 191
036 192
036 193
035 202
035 203
035 204
035 209
035 235
035 236
035 243
035 251
035 252
038 125
038 110
038 173
Fig: 3-107,
3-112,3-113,
3-114
Fig: 3-55,
3-72,3-116,
3-117
Fig. 3-116
Fig: 3-112,
3-115,3-116
Fig: 3-112,
3-114
Fig: 3-112,
3-114
Fig: 3-112,
3-114
Fig: 3-112,
3-115
Fig: 3-112,
3-115
Fig. 3-112
038 175
Fig. 3-113
038 176
Fig. 3-113
038 120
038 121
Fig: 3-114,
3-116
Fig. 3-114
038 126
Fig. 3-114
038 122
Fig. 3-114
038 123
Fig. 3-114
038 136
038 156
038 134
038 188
038 144
038 145
038 135
Fig: 3-55,
3-72
038 130
038 137
038 138
038 139
038 131
038 132
038 133
038 183
038 184
038 187
038 185
038 186
038 140
038 141
038 146
038 142
038 143
038 154
038 198
038 164
038 165
038 155
Fig: 3-55,
3-72
038 150
038 157
038 158
038 159
038 151
038 152
038 153
038 193
038 194
038 197
038 195
038 196
038 160
038 161
8-25
Time-Voltage Protection
8-26
038 166
038 162
038 163
039 152
Fig: 3-120,
3-123
Fig. 3-122
039 122
Fig. 3-124
039 129
039 154
Fig: 3-119,
3-120,
3-123,3-124
Fig. 3-120
039 128
039 170
041 068
Fig. 3-126
041 069
Fig. 3-126
041 070
Fig. 3-127
041 071
Fig. 3-127
040 066
Fig. 3-125
042 003
042 004
Fig: 3-125,
3-126,3-127
Fig. 3-125
041 030
Fig. 3-126
041 096
Fig. 3-126
041 034
Fig. 3-126
041 035
Fig. 3-126
041 037
Fig. 3-127
041 099
Fig. 3-127
041 041
Fig. 3-127
041 026
Fig. 3-127
042 023
Fig. 3-127
041 110
Fig. 3-127
039 150
039 125
Fig: 3-123,
3-124
039 127
Fig. 3-122
039 151
039 153
Fig: 3-69,
3-123
Fig. 3-123
039 124
Fig. 3-123
039 123
Fig. 3-123
039 126
Fig: 3-120,
3-123
039 172
039 182
039 189
039 174
039 185
039 188
039 187
039 171
039 173
039 184
039 183
039 186
Over-/Underfrequency
Protection
Overfluxing protection
041 042
Fig. 3-127
041 066
Fig. 3-127
042 025
Fig. 3-127
041 112
Fig. 3-127
042 007
Fig. 3-127
042 103
Fig. 3-131
042 104
042 140
f<>: Starting f1
f<>: Starting f2
f<>: Starting f3
f<>: Starting f4
f<>: Starting f1/df1
f<>: Starting f2/df2
f<>: Starting f3/df3
f<>: Starting f4/df4
f<>: Delta f1 triggered
f<>: Delta f2 triggered
f<>: Delta f3 triggered
f<>: Delta f4 triggered
f<>: Delta t1 elapsed
f<>: Delta t2 elapsed
f<>: Delta t3 elapsed
f<>: Delta t4 elapsed
f<>: Trip signal f1
f<>: Trip signal f2
f<>: Trip signal f3
f<>: Trip signal f4
042 107
V/f:
V/f:
V/f:
V/f:
V/f:
035 196
Fig. 3-134
035 197
Fig. 3-138
035 199
Fig. 3-135
035 182
Fig. 3-139
041 229
042 105
042 106
042 100
Fig. 3-128
042 101
Fig: 3-128,
3-131
Fig. 3-128
042 102
Fig: 3-129,
3-131
Fig. 3-131
042 115
042 123
042 131
042 108
Fig. 3-131
042 116
042 124
042 132
042 109
Fig. 3-131
042 117
042 125
042 133
042 110
Fig. 3-131
042 118
042 126
042 134
042 111
Fig. 3-131
042 119
042 127
042 135
035 184
041 230
Fig: 3-132,
3-134,3-135
3-138,3-139
Fig: 3-138,
3-139
Fig. 3-134
041 231
Fig. 3-134
041 232
041 233
041 234
Fig: 3-137,
3-138
Fig: 3-137,
3-138
Fig. 3-135
041 235
Fig. 3-135
041 236
Fig. 3-138
8-27
Current Transformer
Supervision
036 160
Fig. 3-141
036 158
Fig. 3-145
036 080
CTS:
CTS:
CTS:
CTS:
Reset latching
Operated (updating)
Operated (latched)
Idiff>(CTS)active
Fig: 3-140,
3-141
036 159
CTS:
CTS:
CTS:
CTS:
CTS:
CTS:
CTS:
CTS:
CTS:
036 081
8-28
036 099
Fig. 3-145
036 202
Fig. 3-145
036 203
Fig: 3-88,
3-145
Fig. 3-146
036 082
036 083
036 084
036 204
Fig. 3-146
036 206
036 208
036 210
036 205
Fig: 3-97,
3-146
036 207
036 209
036 211
036 213
Fig. 3-148
036 194
Fig: 3-147,
3-148
Fig: 3-53,
3-148,3-149
Fig. 3-148
036 198
MCM_1: Starting
MCM_2: Blocking EXT
MCM_2: Enabled
MCM_2: Meas. circ. I faulty
036 212
MCM_2: Starting
MCM_3: Blocking EXT
MCM_3: Enabled
MCM_3: Meas. circ. I faulty
036 214
MCM_3: Starting
MCM_4: Blocking EXT
MCM_4: Enabled
MCM_4: Meas. circ. I faulty
036 216
MCM_4: Starting
036 218
LIMIT: Enabled
040 074
040 180
Fig: 3-150,
3-151
Fig. 3-150
040 181
Fig. 3-150
040 182
Fig. 3-150
040 183
Fig. 3-150
040 184
Fig. 3-150
040 185
Fig. 3-150
040 186
Fig. 3-150
040 187
Fig. 3-150
040 170
Fig. 3-151
036 215
036 195
036 199
Fig: 3-53,
3-149
036 217
036 196
036 200
Fig: 3-53,
3-149
036 219
036 197
036 201
Fig:
3-53,3-149
Logic
040 171
Fig. 3-151
040 172
Fig. 3-151
040 173
Fig. 3-151
040 174
Fig. 3-151
040 175
Fig. 3-151
040 176
Fig. 3-151
040 177
Fig. 3-151
LIM_1: Enabled
040 123
Fig. 3-153
040 122
Fig. 3-153
037 201
Fig. 3-153
037 202
Fig. 3-153
037 203
Fig. 3-153
034 000
040 125
040 124
038 201
038 202
038 203
040 127
040 126
039 201
039 202
039 203
Fig. 3-155
034 001
034 002
034 003
034 004
034 005
034 006
034 007
034 008
034 009
034 010
034 011
034 012
034 013
034 014
034 015
034 086
034 087
034 088
034 089
034 090
034 091
034 092
034 093
034 094
034 095
034 096
8-29
8-30
034 097
034 076
042 033
LOGIC: Output 2
LOGIC: Output 2 (t)
042 034
034 098
034 099
034 100
034 101
034 102
034 103
034 104
034 105
034 106
034 107
034 108
034 109
Fig. 3-155
034 051
Fig. 3-154
034 052
034 053
034 054
034 055
034 056
034 057
034 058
034 059
Fig. 3-154
034 060
034 061
034 062
034 063
034 064
034 065
034 066
034 067
Fig. 3-154
034 068
034 069
034 070
034 071
034 072
034 073
034 074
Fig. 3-155
034 075
Fig: 3-154,
3-155
034 077
034 078
034 079
034 080
034 081
034 082
Fig. 3-155
034 046
Fig. 3-155
042 032
Fig: 3-155,
3-161
Fig: 3-155,
3-161
042 035
LOGIC: Output 3
LOGIC: Output 3 (t)
LOGIC: Output 4
LOGIC: Output 4 (t)
LOGIC: Output 5
LOGIC: Output 5 (t)
LOGIC: Output 6
LOGIC: Output 6 (t)
LOGIC: Output 7
LOGIC: Output 7 (t)
LOGIC: Output 8
LOGIC: Output 8 (t)
LOGIC: Output 9
LOGIC: Output 9 (t)
LOGIC: Output 10
LOGIC: Output 10 (t)
LOGIC: Output 11
LOGIC: Output 11 (t)
LOGIC: Output 12
LOGIC: Output 12 (t)
LOGIC: Output 13
LOGIC: Output 13 (t)
LOGIC: Output 14
LOGIC: Output 14 (t)
LOGIC: Output 15
LOGIC: Output 15 (t)
LOGIC: Output 16
LOGIC: Output 16 (t)
LOGIC: Output 17
LOGIC: Output 17 (t)
LOGIC: Output 18
LOGIC: Output 18 (t)
LOGIC: Output 19
LOGIC: Output 19 (t)
LOGIC: Output 20
LOGIC: Output 20 (t)
LOGIC: Output 21
LOGIC: Output 21 (t)
LOGIC: Output 22
LOGIC: Output 22 (t)
LOGIC: Output 23
LOGIC: Output 23 (t)
LOGIC: Output 24
LOGIC: Output 24 (t)
LOGIC: Output 25
LOGIC: Output 25 (t)
LOGIC: Output 26
LOGIC: Output 26 (t)
LOGIC: Output 27
LOGIC: Output 27 (t)
LOGIC: Output 28
LOGIC: Output 28 (t)
042 036
042 037
042 038
042 039
042 040
042 041
042 042
042 043
042 044
042 045
042 046
042 047
042 048
042 049
042 050
042 051
042 052
042 053
042 054
042 055
042 056
042 057
042 058
042 059
042 060
042 061
042 062
042 063
042 064
042 065
042 066
042 067
042 068
042 069
042 070
042 071
042 072
042 073
042 074
042 075
042 076
042 077
042 078
042 079
042 080
042 081
042 082
042 083
042 084
042 085
042 086
042 087
8-31
LOGIC: Output 29
LOGIC: Output 29 (t)
LOGIC: Output 30
LOGIC: Output 30 (t)
LOGIC: Output 31
LOGIC: Output 31 (t)
LOGIC: Output 32
LOGIC: Output 32 (t)
8-32
042 088
042 089
042 090
042 091
042 092
042 093
042 094
042 095
8.1.2
003 010
Communication interface 1
COMM1: Sel.spontan.sig.test
Signal selection for testing purposes.
003 180
Fig. 3-13
003 184
Fig. 3-13
003 186
Fig. 3-13
COMM2: Sel.spontan.sig.test
Signal selection for testing purposes.
103 180
Fig. 3-15
103 184
Fig. 3-15
103 186
Fig. 3-15
105 171
Communication interface 2
105 162
105 163
GSSE: Rx message counter
Shows the number of GSSE messages received. This counter is reset by
GSSE: Reset counters.
105 164
GSSE: No. bin.state chang.
Number of state changes included in a GSSE sent. This counter is reset by
GSSE: Reset counters.
105 165
GSSE: Tx last sequence
State of the continuous counter sequence for the message counter sent
with each GSSE.
105 166
GSSE: Tx last message
State of the continuous counter sequence for state changes sent with each
GSSE.
8-33
105 167
GSSE: No. reject. messages
Number of telegram rejections having occurred because of non-plausible
message content. This counter is reset by G S S E : R e s e t c o u n t e r s .
105 170
GSSE: IED view selection
Setting for which GSSE sending device the following statistics information is
to be displayed.
105 172
105 173
GSSE: IED Rx last sequence
State of the continuous counter sequence for the message counter received
with each GSSE.
105 174
GSSE: IED Rx last message
State of the continuous counter sequence for state changes received with
each GSSE.
105 175
GSSE: IED missed messages
Number of missing GSSE messages (gaps in the continuous sequence
numbering). This counter is reset by G S S E : R e s e t c o u n t e r s .
105 176
105 177
GSSE: IED time-outs
Number of GSSE received after the validity time period has elapsed. This
counter is reset by G S S E : R e s e t c o u n t e r s .
8-34
Binary outputs
021 009
Fig. 3-25
003 042
Fig. 3-26
This control action is password-protected (see section entitled 'PasswordProtected Control Operations' in Chapter 6).
The test can only be carried out when protection is disabled.
OUTP: Hold-time for test
Setting the time period for which the selected output relay is triggered
during functional testing.
003 044
Fig. 3-26
037 116
Fig. 3-29
Main function
003 002
Fig: 3-2,
3-3,3-4,
3-25,3-29,
-34,3-41,
3-56,3-58,
3-60, 3-65,
3-67,3-68,
3-69,3-70,
3-71,3-72,
3-73,3-74,
3-75,3-76,
3-77,3-78,
3-105,
3-117,3-145
021 010
Fig: 3-29,
3-60
8-35
021 005
003 007
003 033
Fig. 3-57
Fig: 3-40,
3-41
The values for the delayed stored maximum phase current, ends a to d, are
reset.
003 040 Fig. 3-57
MAIN: Man. trip cmd. USER
A 100 ms trip command is issued from the local control panel. This setting
is password-protected (see section entitled 'Password-Protected Control
Operations' in Chapter 6).
Note:
The command is only executed if the manual trip command is included in
the configuration of trip commands.
003 039
MAIN: Warm restart
A warm restart is carried out. The device functions as it does when the
power supply is turned on.
000 085
MAIN: Cold restart
A cold restart is carried out. This setting is password-protected (see section
entitled 'Password-Protected Control Operations' in Chapter 6). A cold
restart means that all settings and recordings are cleared. Values that a
device utilizes after a cold restart has occurred are designated "default
settings". They are selected so as to block the device after a cold restart.
003 008
Fig. 3-66
Overload Recording
100 003
Fig: 3-4,
3-67,3-68,
3-69,3-70
8-36
Fault Recording
003 006
Fig: 3-2,
3-3,3-76,
3-77,3-78
Over-/Underfrequency
Protection
003 080
Page: 3-201
Resetting the measured event values f<> : m a x. fre qu . for f> and
f < > : m in . f r e qu . for f< .
Overfluxing protection
035 183
Fig. 3-139
Current Transformer
Supervision
036 157
Fig. 3-145
Logic
LOGIC: Trigger 1
LOGIC: Trigger 2
LOGIC: Trigger 3
LOGIC: Trigger 4
LOGIC: Trigger 5
LOGIC: Trigger 6
LOGIC: Trigger 7
LOGIC: Trigger 8
Intervention in the logic at the appropriate point of a 100 ms pulse.
034 038
Fig. 3-155
8.1.3
034 039
034 040
034 041
034 042
034 043
034 044
034 045
Fig. 3-155
003 024
Fig. 3-65
003 001
Fig. 3-66
8-37
8.2
8.2.1
Events
Event Counters
004 000
Fig. 3-56
004 006
Fig. 3-58
009 050
Fig. 3-58
009 056
Fig. 3-58
009 057
Fig. 3-58
100 002
Fig. 3-65
004 019
Fig. 3-66
Overload Recording
004 101
Fig. 3-69
Fault Recording
004 020
Fig. 3-3
004 010
Fig. 3-3
009 150
Fig. 3-105
009 160
009 151
009 161
Main function
Definite-time overcurrent
protection
Inverse-Time Overcurrent
Protection
8-38
009 170
Fig. 3-117
009 171
8.2.2
Overload Data Acquisition
004 102
Fig. 3-67
If, on the other hand, the coolant temperature and the maximum permissible
coolant temperature have been set to the same value, then the coolant
temperature is not taken into account and the characteristic is a function of
the current only. The additional reserve amounts to 0 in this case.
Fault Data Acquisition
008 010
Fig. 3-71
004 021
Fig. 3-71
004 198
Fig. 3-72
8-39
025 088
Fig. 3-73
026 088
Fig. 3-73
027 088
Fig. 3-73
005 082
Fig. 3-74
006 082
Fig. 3-74
007 082
Fig. 3-74
005 085
Fig. 3-74
006 085
Fig. 3-74
007 085
Fig. 3-74
005 083
Fig. 3-74
006 083
Fig. 3-74
007 083
Fig. 3-74
8-40
Over-/Underfrequency
Protection
005 002
005 001
8-41
8.2.3
Overload Recording
Fault Recording
8-42
Event Recording
033 020
Fig. 3-70
033 021
Fig. 3-70
033 022
Fig. 3-70
033 023
Fig. 3-70
033 024
Fig. 3-70
033 025
Fig. 3-70
033 026
Fig. 3-70
033 027
Fig. 3-70
003 000
Fig. 3-77
033 001
Fig. 3-77
033 002
Fig. 3-77
033 003
Fig. 3-77
033 004
Fig. 3-77
033 005
Fig. 3-77
033 006
Fig. 3-77
033 007
Fig. 3-77
9 Commissioning
9
9.1
Commissioning
Safety Instructions
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
The device must be reliably grounded before auxiliary voltage is turned on.
The surface-mounted case is grounded using the bolt and nut, appropriately marked, as
the ground connection. The flush-mounted case must be grounded in the area of the
rear sidepieces at the location provided. The cross-section of the ground conductor
must conform to applicable national standards. A minimum cross section of 2.5 mm2 is
required.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters "PE" on the terminal connection diagram) is required for
proper operation of the unit. The cross-section of this ground conductor must also
conform to applicable national standards. A minimum cross section of 1.5 mm2 is
required.
Before working on the device itself or in the space where the device is connected,
always disconnect the device from the supply.
The secondary circuit of live system current transformers must not be opened!
If the secondary circuit of a live CT is opened, there is the danger that the resulting
voltages will endanger personnel and damage the insulation.
In units with pin terminal connection, the threaded terminal block for connection to the
current transformers is not a shorting block. Therefore always short-circuit current
transformers before loosening the threaded terminals.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
9-1
9 Commissioning
(continued)
The fiber-optic interface may only be connected or disconnected when the supply
voltage for the device is shut off.
The SC connector and RJ45 wire of the Ethernet module cannot be connected at the
same time. (The selection for IEC : Eth e r n e t M e d i a should be noted.)
9-2
The PC interface is not designed for permanent connection. Consequently, the female
connector does not have the extra insulation from circuits connected to the system that
is required per VDE 0106 Part 101. Therefore, when connecting the prescribed
connecting cable be careful not to touch the socket contacts.
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see chapter entitled 'Technical
Data')
When using the programmable logic (function group LOGIC), the user must carry out a
functional type test to conform to the requirements of the relevant protection/control
application. In particular, it is necessary to verify that the requirements for the
implementation of logic linking (by setting) as well as the time performance during device
startup, during operation and when there is a fault (device blocking) are fulfilled.
9 Commissioning
(continued)
9.2
Preparation
Commissioning Tests
After the P63x has been installed and connected as described in Chapter 5, the
commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked again:
Does the nominal voltage of the battery agree with the nominal auxiliary voltage of
the device?
Are the current and voltage transformer connections, grounding, and phase
sequences correct?
After the wiring work is completed, check the system to make sure it is properly isolated.
The conditions given in VDE 0100 must be satisfied.
Once all checks have been made, the power supply voltage may be turned on.
After voltage has been applied, the device starts up. During startup, various startup
tests are carried out (see Chapter 3, Self-Monitoring). The LED indicators for
Operation (H1) and Blocked/Faulty (H2) will light up. After approximately 15 s, the
P63x is ready for operation. This is recognized when the text 'P63x' is shown in the first
line on the LCD screen.
Once the change enabling command has been issued (see Chapter 6, Enabling
Parameter Changes), all settings can be entered. The procedure for entering settings
from the integrated local control panel is described in Chapter 6.
9-3
9 Commissioning
(continued)
If either the PC interface or the communication interface will be used for setting the P63x
and reading out event records, then the following settings must first be made from the
integrated local control panel.
Par/DvID/ folder:
Par/Conf/ folder:
Par/Func/Glob/ folder:
PC: Sig./meas.val.block.
C O M M 1 : Sig./meas.block.USER
C O M M 2 : Sig./meas.block.USER
9-4
9 Commissioning
(continued)
After the settings have been made, the following checks should be carried out once
again before blocking is cancelled:
Does the function assignment of the binary signal inputs agree with the terminal
connection diagram?
Has the correct operating mode been selected for the binary signal inputs?
Does the function assignment of the output relays agree with the terminal connection
diagram?
Has the correct operating mode been selected for the output relays?
Testing
M A I N : P r o t e c t i o n e n a b l e d 'Yes (on)'
By using the signals and displays generated by the P63x, it is possible to determine
whether the P63x is correctly set and properly interconnected with the station. Signals
are signaled by output relays and LED indicators and entered into the event memory. In
addition, the signals can be checked by selecting the appropriate signal in the menu
tree.
If the user does not wish the circuit breaker to operate during protection testing, the trip
commands can be blocked at M A I N : T r i p c m d . b l o c k . U S E R ('Par/Func/Glob'
folder) or via an appropriately configured binary signal input. If circuit breaker testing is
desired, it is possible to issue a trip command for a set time through M AIN : M a n . tr i p
c m d . U SER (Oper/CtrlTest folder) or an appropriately configured binary signal input.
Selection of the trip command from the integrated local control panel is passwordprotected (see Chapter 6, "Password-Protected Control Operations").
Note:
The manual trip command is not executed unless the manual trip is included
in the selection of possible functions to effect a trip (in the configuration of trip
commands).
If the P63x is connected to a control station, the user is advised to activate the test mode
via M A I N : T e s t m o d e USER ("Par/Func/Glob/" folder) or an appropriately configured
binary signal input. The telegrams are then identified accordingly (cause of
transmission: test mode).
9-5
9 Commissioning
(continued)
'High': Energized.
This display appears regardless of the binary signal input mode selected.
Checking the output relays
9-6
It is possible to trigger the output relays for a settable time period for test purposes (time
setting at O U T P: H o l d - ti m e fo r te s t in Oper/CtrlTest/ folder). First select the
output relay to be tested (O U T P: R e l a y a s s i g n . f. te s t, Oper/CtrlTest/ folder).
The output relay to be tested can only be selected if the device has been set to 'off-line'
at M A I N : P r o t e c t i o n e n a b l e d ('Par/Func/Glob/' folder). Test triggering then
occurs via O U T P : R e l a y t e s t (Oper/CtrlTest/ folder).
It is password-protected (see Chapter 6, Password-Protected Control Operations).
Four parameter subsets are stored in the P63x, one of which is activated. Before
checking the protective function, the user should determine which parameter subset is
activated. The active parameter subset is displayed at P S S : A c t u a l p a r a m . s u b s e t
(Oper/Cycl/Log/' folder).
9 Commissioning
(continued)
Checking differential
protection
For single-side feed, the fault current characteristic crosses the first knee of the tripping
characteristic of the P63x so that the basic threshold value is always checked.
The current I to which the P63x responds for single-side feed is calculated as follows:
I=
z:
Idiff>:
Inom,z:
kam,z:
transformer end a, b, c or d
Set operate value
nominal current of the P63x for transformer end a, b, c or d
amplitude-matching factor of transformer end a, b, c or d
z:
Idiff>:
Inom,z:
kam,z:
k s,y ,z :
transformer end a, b, c or d
Set operate value
nominal current of the P63x for transformer end a, b, c or d
amplitude-matching factor of transformer end a, b, c or d
vector group-matching factor (see tables below)
9-7
9 Commissioning
(continued)
The differential and restraining currents formed by the P63x are displayed as measured
operating data. They aid in assessing whether the connection of the P63x to the system
current transformers and the setting of the vector group ID are correct.. The tables
below (next page) give the factors ks which serve to calculate the differential current for
single-side feed. The display of differential and restraining currents is prevented,
however, if they fall below minimum thresholds that can be set by the user.
Id,y = k am,z k s,y,z Itest,x
x:
z:
y:
Id,y :
phase A, B or C
transformer end a, b, c or d
measuring system 1, 2 or 3
differential current as displayed
kam,z:
k s,y ,z :
Itest,x:
In evaluating the test results, one should be aware that the P63x will trip as follows, if a
value of Idiff>> or Idiff>>> is exceeded.
9-8
Idiff>> exceeded:
Idiff>>> exceeded:
9 Commissioning
(continued)
Vector group ID
b, c or d
0=12
10
11
0.67 0.67
0.58 0.33 0.00 0.33 0.58 0.67 0.58 0.33 0.00 0.33 0.58
0.33 0.33
0.00 0.33 0.58 0.67 0.58 0.33 0.00 0.33 0.58 0.67 0.58
0.33 0.33
0.58 0.67 0.58 0.33 0.00 0.33 0.58 0.67 0.58 0.33 0.00
Vector group ID
b, c or d
0=12
10
11
0.00 0.00
0.58 1.00 1.15 1.00 0.58 0.00 0.58 1.00 1.15 1.00 0.58
1.00 1.00
1.15 1.00 0.58 0.00 0.58 1.00 1.15 1.00 0.58 0.00 0.58
1.00 1.00
0.58 0.00 0.58 1.00 1.15 1.00 0.58 0.00 0.58 1.00 1.15
Vector group ID
b, c or d
0=12
10
1.00 1.00
0.00 0.00
0.00 0.00
Factors for single-side, two-phase, phase-opposition feed in phases B to C, not zero sequence-filtered
Transformer end
Vector group ID
b, c or d
0=12
10
0.00 0.00
1.00 1.00
1.00 1.00
9-9
9 Commissioning
(continued)
The connection of the phase currents can be checked using the phase angles provided
as measured operating data by the P63x.
If the phase currents are connected correctly and there is an ideal balanced load on the
transformer, the phase angles between the phase currents of any one transformer end
are displayed as follows:
Phase sequence A-B-C
This is not influenced by the set value of the function parameter for the phase sequence.
9-10
9 Commissioning
(continued)
The phase angle between the phase currents of two transformer ends for a particular
phase is a function of the vector group of the transformer. This phase angle should be
displayed as follows:
Vector group
0 = 12
x ,A z = 180
x ,A z = 150
x ,A z = 120
x,A z = 90
x,A z = 60
x,A z = 30
x,A z = 0
x,A z = 30
x,A z = 60
x,A z = 90
10
x ,A z = 120
11
x ,A z = 150
This is not influenced by the set value of the function parameter for the phase sequence.
Changing the setting for the connection scheme of an involved series transformer, on the
other hand, will change the measured operating data value by 180.
9-11
9 Commissioning
(continued)
Checking ground
differential protection
The current I to which the P63x responds for single-side feed, neutral-point side, is
calculated as follows:
I
z:
Idiff>:
Inom:
kam,z:
transformer end a, b, c or d
set operate value
nominal current of the P63x
amplitude-matching factor of transformer end a, b, c or d
Before the P63x is released for operation, the user should make sure that the following
steps have been taken:
After completion of commissioning, only the green LED indicator signaling Operation
(H1) should be on.
9-12
10 Troubleshooting
10 Troubleshooting
This chapter describes problems that might be encountered, their causes, and possible
methods for eliminating them. It is intended as a general orientation only, and in cases
of doubt it is better to return the P63x to the manufacturer. Please follow the packaging
instructions in the section entitled Unpacking and Packing in Chapter 5 when returning
equipment to the manufacturer.
Problem:
Before checking further, disconnect the P63x from the power supply.
Check to make sure that fuse F1 on power supply module V is not fused.
If the fuse is defective, it should not be replaced without determining the cause of
failure. If a fuse is replaced without eliminating the problem, there is the danger
that the damage will spread.
Required fuses:
VA,nom = 24 V DC:
VA,nom = 48 to 250 V DC and 100 to 230 V AC:
Type M3.5
Type M2
10-1
10 Troubleshooting
(continued)
Identify the specific problem by reading out the monitoring signal memory (see the
section entitled Monitoring Signal Memory Readout in Chapter 6). The table below
lists possible monitoring or warning indications (provided that a configuration setting
has been entered at SF M O N : F c t. a s s i g n . w a r n i n g ) , the faulty area, the P63x
response, and the mode of the output relay configured for 'Warning' and
'Blocked/faulty'.
Self-Monitoring
036 070
036 100
Key:
-:
Yes:
Updating:
The output relay configured for 'Warning' starts only if the monitoring
signal is still present.
1)
The 'Blocked/faulty' output relay only operates if the signal has been
configured at M A I N : F c t . a s s i g n . f a u l t .
2)
The 'Warning' output relay only operates if the signal has been
configured at S F M O N : F c t . a s s i g n m . w a r n i n g .
093 024
SFMON: Cold restart
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: Cold rest./SW update
A cold restart has been carried out following a software update.
093 025
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: Blocking/ HW failure
Supplementary warning that this device is blocked.
090 019
10-2
10 Troubleshooting
(continued)
041 200
093 040
090 010
096 121
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
093 081
SFMON: +15V supply faulty
The +15 V internal supply voltage has dropped below a minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
093 082
SFMON: +24V supply faulty
The +24 V internal supply voltage has dropped below a minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: -15V supply faulty
The -15 V internal supply voltage has dropped below a minimum value.
093 080
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
10-3
10 Troubleshooting
(continued)
096 100
096 101
096 102
096 103
096 104
096 105
096 106
096 107
096 108
096 109
096 110
096 111
096 112
096 113
096 114
096 115
096 116
096 117
096 118
096 119
096 120
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
10-4
10 Troubleshooting
(continued)
097 000
097 001
097 002
097 003
097 004
097 005
097 006
097 007
097 008
097 009
097 010
097 011
097 012
097 013
097 014
097 015
097 016
097 017
097 018
097 019
097 020
093 070
093 071
093 111
10-5
10 Troubleshooting
(continued)
10-6
097 078
097 079
097 080
097 081
097 082
097 083
097 084
097 085
097 086
097 087
097 094
097 095
097 096
097 097
097 098
097 099
097 100
097 101
097 102
097 103
097 104
097 105
097 106
097 107
097 108
097 109
097 118
097 119
097 150
097 151
097 152
097 153
097 154
097 155
097 156
097 157
097 166
097 167
097 168
097 169
097 170
097 171
097 182
097 183
097 184
097 185
097 186
097 187
097 188
097 189
10 Troubleshooting
(continued)
093 010
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: Invalid arithm. op.
Invalid arithmetic operation.
093 011
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: Undefined interrupt
Undefined interrupt.
093 012
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: Exception oper.syst.
Interrupt of the operating system.
093 013
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: Protection failure
Watchdog is monitoring the periodic start of protection routines. It has
detected an error.
090 021
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: Checksum error param
A checksum error involving the settings in the memory (NOVRAM) has
been detected.
090 003
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
093 041
SFMON: Clock sync. error
In 10 consecutive clock synchronization telegrams, the difference between
the time of day given in the telegram and that of the hardware clock is
greater than 10 ms.
10-7
10 Troubleshooting
(continued)
093 026
SFMON: Interm.volt.fail.RAM
Faulty test pattern in the RAM. This can occur, for example, if the processor
module or the power supply module is removed from the bus module
(digital). This fault is only detected during device startup. After the fault is
detected, the software initializes the RAM. This means that all records are
deleted.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: Overflow MT_RC
Last entry in the monitoring signal memory in the event of overflow.
090 012
093 015
093 075
098 000
10-8
Yes / Yes 2)
-/-
10 Troubleshooting
(continued)
091 018
SFMON: Meas. circ. I faulty
The measuring-circuit monitoring function has detected a fault in the
current-measuring circuits. (See functions MCMON and CTS, measuringcircuit monitoring multiple signal.)
093 113
093 127
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
SFMON: Invalid SW vers. DSP
Incorrect or invalid software has been downloaded for the DSP coprocessor.
093 128
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay:
Yes / Yes
'Blocked/faulty' output relay:
Yes / Yes
093 114
SFMON: Invalid scaling A-1
093 115
SFMON: Invalid scaling A-2
An invalid characteristic has been set for one of the analog output channels
of analog I/O module Y.
10-9
10 Troubleshooting
(continued)
098 024
SFMON: PT100 open circuit
The P63x has detected an open circuit in the connection of the resistance
thermometer.
098 025
091 000
091 001
091 002
091 017
10-10
10 Troubleshooting
(continued)
091 006
SFMON: 2nd match.fact. inv.
The second highest amplitude matching factor for differential protection is
smaller than permitted.
091 105
091 115
091 125
091 101
091 111
091 121
091 102
091 112
091 122
10-11
10 Troubleshooting
(continued)
098 036
098 037
098 038
098 039
10-12
11 Maintenance
11 Maintenance
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
The P63x is a low-maintenance device. The components used in the units are selected
to meet exacting requirements. Recalibration is not necessary.
Maintenance procedures in
the power supply area
Electrolytic capacitors are installed in the power supply area because of dimensioning
requirements. The useful life of these capacitors is significant from a maintenance
standpoint. When the equipment is operated continuously at the upper limit of the
recommended temperature range (+55C or 131F), the useful life of these components
is 80,000 hours, or more than 9 years. Under these conditions, replacement of the
electrolytic capacitors is recommended after a period of 8 to 10 years. When the
operating temperatures are approx. +45C inside the devices, the required maintenance
interval can be increased by about 1 year.
The P63x is equipped with a lithium battery for non-volatile storage of fault data and for
keeping the internal clock running in the event of failure of the auxiliary power supply.
Loss of capacity due to module-internal self-discharging amounts to less than 1% per
year over a period of availability of 10 years. Since the terminal voltage remains virtually
constant until capacity is exhausted, usefulness is maintained until a very low residual
capacity is reached. With a nominal capacity of 850 mAh and discharge currents of only
a few A during device storage or in the range of the self-discharge current during
device operation, the result is a correspondingly long service life. It is therefore
recommended that the lithium battery only be replaced after the maintenance interval
cited above.
Replacement of the maintenance-related components named above is not possible
without soldering. Maintenance work must be carried out by trained personnel, and the
auxiliary voltage must be turned off while the work is being performed.
Always turn off the power (supply voltage) before removing a hardware module.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
11-1
11 Maintenance
(continued)
Electrolytic capacitor:
on power supply module V.
Lithium battery:
on power supply module V.
Note:
11-1
11-2
11 Maintenance
(continued)
There is a danger of explosion if the electrolytic capacitor and battery are not properly
replaced. Always check to make sure that the polarity of the electrolytic capacitor and
the battery is correct.
Note:
After the maintenance procedures described above have been completed, new
commissioning tests as described in Chapter 9 must be carried out.
11-3
11 Maintenance
(continued)
The P63x is used as a safety device and must therefore be routinely injection tested for
proper operation. The first functional tests should be carried out approximately 6 to
12 months after commissioning. Functional tests should be performed at intervals of 2 to
3 years 4 years at the maximum.
The P63x incorporates in its system a very extensive self-monitoring function for
hardware and software. The internal structure guarantees, for example, that
communication within the processor system will be checked on a continuing basis.
Nonetheless, there are a number of sub-functions that cannot be checked by the selfmonitoring feature without injection testing from the device terminals. The respective
device-specific properties and settings must be observed in such cases.
In particular, none of the control and signaling circuits that are run to the device from the
outside are checked by the self-monitoring function.
The analog inputs are fed through an analog preprocessing feature (anti-aliasing
filtering) to a common analog-to-digital converter. In conjunction with the self-monitoring
function, the CT/VT supervision function that is available for the devices general
functions can detect deviations in many cases. However, it is still necessary to test from
the device terminals in order to make sure that the analog measuring circuits are
functioning correctly.
The best way to carry out a static test of the analog input circuits is to check the primary
measured operating data using the operating data measurement function or to use a
suitable testing instrument. A "small" measured value (i.e. 0.5 Inom) and a "large"
measured value (i.e. 4 Inom) should be used to check the measuring range of the A/D
converter. This makes it possible to check the entire dynamic range.
The accuracy of operating data measurement is <1 %. An important factor in evaluating
device performance is long-term performance based on comparison with previous
measurements.
The dynamic test is not absolutely necessary, since only the stability of a few passive
components is checked. Based on reliability analysis, the statistical expectation is that
only one component in 10 years in 1000 devices will be outside the tolerance range.
Additional analog testing is not necessary, in our opinion, since information processing is
completely numerical and is based on the measured analog current and voltage values.
Proper operation was checked in conjunction with type testing. Proper operation was
checked in conjunction with type testing.
11-4
11 Maintenance
(continued)
The binary inputs are not checked by the self-monitoring function. However, a testing
function is integrated into the software so that the trigger state of each input can be read
out (Oper/Cycl/Phys folder). This check should be performed for each input being used
and can be done, if necessary, without disconnecting any device wiring.
Binary outputs
With respect to binary outputs, the integrated self-monitoring function includes even twophase triggering of the relay coils of all the relays. There is no monitoring function for
the external contact circuit. In this case, the all-or-nothing relays must be triggered by
way of device functions or integrated test functions. For these testing purposes,
triggering of the output circuits is integrated into the software through a special control
function (Oper/CtrlTest/ folder).
Serial Interfaces
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
11-5
11-6
12 Storage
12 Storage
Devices must be stored in a dry and clean environment. A temperature range of
-25C to +70C (-13F to +158F) must be maintained during storage (see chapter
entitled 'Technical Data'). The relative humidity must be controlled so that neither
condensation nor ice formation will result.
If the units are stored without being connected to auxiliary voltage, then the electrolytic
capacitors in the power supply area need to be recharged every 4 years. Recharge the
capacitors by connecting auxiliary voltage to the P63x for approximately 10 minutes.
If the units are stored during a longer time, the battery of the power supply module is
used for the continuous buffering of the event data in the working memory of the
processor module. Therefore the battery is permanently required and discharges rapidly.
In order to avoid this continuous discharge, it is recommended to remove the power
supply module from the mounting rack during long storage periods. The contents of the
event memory should be previously read out and stored separately.
12-1
12-2
Description
Order No.
Cable bushings
88512-4-0337414-301
88512-4-9650539-302
Empty subrack 40 T
88512-4-9650535-302
Cover frame 40 T
88512-4-9650545-302
Cover frame 84 T
88512-4-9650723-301
13-1
13-2
14 Order Information
14
Order Information
Order number
1234
P631- N N
N N N N
P631-
9 10 11
-305
12, 13
14
15
16
17
18
AA
-4xx
-610
-46x
-9x x -95 x
-8xx
Basic device:
Basic device 40TE, pin-terminal connection,
-403
-404
2) 12)
2)
8
9
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays
-461
8)
-462
8)
-463
8)
-464
8)
-90 0
-91
-92
4
-94
6
-801
4)
4)
4)
Russian (English)
-800
4)
4)
Spanish (English)
Polish (English)
4)
4) 7)
-802
-803
-804
-805
8) Standard variant recommended, if higher pickup threshold not explicitly required by the application
12) Current Transformer Supervision (CTS) requires DSP-Coprocessor
14-1
14 Order Information
(continued)
Order number
1234
P632- N N
N N N N
P632-
9 10 11
-305
12, 13
14
15
16
17
18
AA
-4xx
-610
-46x
-9x x -95 x
-8xx
Basic device:
Basic device 40TE, pin-terminal connection,
-403
-404
2) 12)
2)
8
9
Voltage transformer:
Vnom = 50 ... 130 V (1-pole)
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays
-461
8)
-462
8)
-463
8)
-464
8)
-90 0
-91
-92
4
-94
6
-800
4)
-801
4)
4)
Spanish (English)
Polish (English)
4)
4)
4)
Russian (English)
4) 7)
-802
-803
-804
-805
14-2
14 Order Information
(continued)
Order number
1234
P633- N N
N N N N
P633-
9 10 11
-305
12, 13
14
15
16
17
18
AA
-4xx
-610
-46x
-9x x -95 x
-8xx
Basic device:
Basic device 40TE, pin-terminal connection,
-404
-405
-406
2) 12)
2)
8
9
9
2)
Voltage transformer:
Vnom = 50 ... 130 V (1-pole)
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays
-461
8)
-462
8)
-463
8)
-464
8)
-90 0
-91
-92
4
-94
6
For connection to 100 Mbit/s Ethernet, glass fiber ST and wire RJ45
-801
4)
4)
4)
Russian (English)
-800
4)
4)
Spanish (English)
Polish (English)
4)
4) 7)
-802
-803
-804
-805
14-3
14 Order Information
(continued)
Order number
1234
P634- N N
N N N N
P634-
9 10 11
-305
12, 13
14
15
16
17
18
AA
-4xx
-610
-46x
-9x x -95 x
-8xx
Basic device:
Basic device 84TE, pin-terminal connection,
-403
-404
2)
2)
2) 12)
8
9
9
Voltage transformer:
Vnom = 50 ... 130 V (1-pole)
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays
-461
8)
-462
8)
-463
8)
-464
8)
-90 0
-91
-92
4
-94
6
-800
4)
-801
4)
4)
Spanish (English)
Polish (English)
4)
4)
4)
Russian (English)
4) 7)
-802
-803
-804
-805
14-4
14 Order Information
(continued)
14-5
14-6
Appendix
A Glossary
B Signal List
C Terminal Connection Diagrams
D Overview of Changes
AN-1
Appendix
(continued)
A
A1
A2
A3
A4
A5
Glossary
Function Groups
Modules
Symbols
Examples of Signal Names
Symbols used
B
B1
B2
List of Signals
Internal Signal Names
Telecontrol Interface per EN 60870-5-101 or
IEC 870-5-101 (Companion Standard)
Interoperability
Network Configuration (Network-Specific Parameters)
Physical Layer (Network-Specific Parameters)
Link Layer (Network-Specific Parameters)
Application Layer
Basic Application Functions
B 2.1
B 2.1.1
B 2.1.2
B 2.1.3
B 2.1.4
B 2.1.5
B3
B 3.1
B 3.1.1
B 3.1.1.1
B 3.1.1.2
B 3.1.1.3
B 3.1.2
B 3.1.3
B 3.1.3.1
B 3.1.3.2
B 3.1.3.3
B 3.1.3.3.1
B 3.1.3.3.2
B 3.1.3.3.3
B 3.1.3.3.4
B 3.1.3.3.5
B 3.1.3.3.6
B 3.1.3.3.7
B 3.1.3.3.8
B 3.1.3.4
B 3.1.3.4.1
B 3.1.3.4.2
B 3.1.3.4.3
B 3.1.3.5
B 3.1.3.6
AN-2
A-1
A-1
A-3
A-4
A-11
A-12
B-1
B-1
B-2
B-2
B-2
B-3
B-4
B-5
B-11
B-14
B-14
B-14
B-14
B-14
B-14
B-15
B-15
B-15
B-15
B-15
B-15
B-16
B-17
B-18
B-19
B-20
B-20
B-22
B-23
B-23
B-23
B-24
B-25
B-25
Appendix
(continued)
C
C1
C 1.1
C 1.2
C2
C 2-1
C 2.2
C3
C 3.1
C 3.2
C 3.3
C4
C 4.1
C 4.2
C5
C-1
C-1
C-1
C-4
C-7
C-7
C-13
C-19
C-19
C-24
C-30
C-36
C-36
C-42
C-48
D-1
AN-3
AN-4
Appendix A - Glossary
A1
Function Groups
P631 P632 P633 P634
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
A-1
Appendix A - Glossary
(continued)
A-2
9
9
9
9
-
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Self-Monitoring
Thermal Overload Protection 1
Thermal Overload Protection 2
Utility Communication Architecture 2.0
(P63x versions 604/-605/-606 only)
Overfluxing Protection (as of P63x version -602)
Time-Voltage Protection
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
-
9
9
9
9
9
9
protection) 1
protection) 2
protection) 3
Appendix A - Glossary
(continued)
A2
A:
B:
L:
P:
T:
V:
X:
Y:
Modules
Communication module
Digital bus module
MMI module
Processor module
Transformer module
Power supply module
Binary I/O module
Analog I/O module
A-3
Appendix A - Glossary
(continued)
A3
Symbols
Description
To obtain more space for representing a group of
related elements, contours of the elements may be
joined or cascaded if the following rules are met:
A-4
Appendix A - Glossary
(continued)
Symbol
Description
Control block
A control block contains an input function common to
several symbols. It is used for the collective setting of
several trigger elements, for example.
Output block
An output block contains an output function common
to several symbols.
1.0: 1.0 A
5.0: 5.0 A
D5Z08X6B
A-5
Appendix A - Glossary
(continued)
Symbol
Description
Static input
Only the state of the binary input variable is effective.
Dynamic input
Only the transition from value 0 to value 1 is effective.
Negation of an output
The value up to the border line is negated at the
output.
Negation of an input
The input value is negated before the border line.
AND element
The output variable will be 1 only if all input variables
are 1.
OR element
The output variable will be 1 only if at least one input
variable is 1.
Threshold element
The output variable will be 1 only if at least two input
variables are 1. The number in the symbol may be
replaced by any other number.
(m out of n) element
The output variable will be 1 only if just one input
variable is 1.
The number in the symbol may be replaced by any
other number if the number of inputs is increased or
decreased accordingly.
A-6
Appendix A - Glossary
(continued)
Symbol
Description
Delay element
The transition from value 0 to 1 at the output occurs
after a time delay of t1 relative to the corresponding
transition at the input.
The transition from value 1 to 0 at the output occurs
after a time delay of t2 relative to the corresponding
transition at the input.
t1 and t2 may be replaced by the actual delay values
(in seconds or strobe ticks).
Monostable flip-flop
The output variable will be 1 only if the input variable
changes to 1. The output variable will remain 1 for
100 ms, regardless of the duration of the input value
1 (non-retriggerable).
Without a 1 in the function block, the monostable
flip-flop is retriggerable.
The time is 100 ms in this example, but it may be
changed to any other duration.
Analog-digital converter
An analog input signal is converted to a binary
signal.
Subtractor
The output variable is the difference between the
two input variables.
A summing element is obtained by changing the
minus sign to a plus sign at the symbol input.
Schmitt Trigger with binary output signal
The binary output variable will be 1 if the input signal
exceeds a specific threshold. The output variable
remains 1 until the input signal drops below the
threshold again.
Memory, general
Storage of a binary or analog signal.
A-7
Appendix A - Glossary
(continued)
Symbol
Description
Non-stable flip-flop
When the input variable changes to 1, a pulse
sequence is generated at the output.
The ! to the left of the G indicates that the pulse
sequence starts with the input variable transition
(synchronized start).
If there is a ! to the right of the G, the pulse
sequence ends with the ending of the 1 signal at the
input (synchronized stop).
Amplifier
The output variable is 1 only if the input variable is
also 1.
Band pass filter
The output only transmits the 50 Hz component of
the input signals. All other frequencies (above and
below 50 Hz) are attenuated.
Counter
At the + input the input variable transitions from 0 to
1 are counted and stored in the function block.
At the R(eset) input a transition of the input variable
from 0 to 1 resets the counter to 0.
Electromechanical drive
in general, here a relay, for example.
A-8
Appendix A - Glossary
(continued)
Symbol
Description
Input transformer
with phase and item identifiers
(according to DIN EN 60445)
Phase identifiers for current inputs:
for A: A1 and A2
for B: B1 and B2
for C: C1 and C2
for N: N1 and N2
Phase identifiers for voltage inputs
via transformer 1:
for A: 1U
for B: 1V
for C: 1W
for N: 1N
via transformer 2:
for A: 2U
for B: 2V
Item identifiers for current transformers:
for A: T1
for B: T2
for C: T3
for N: T4
for voltage transformer 1:
for A: T5
for B: T6
for C: T7
for N: T8
for VG-N transformer: T90
for voltage transformer 2:
for A: T15
Change-over contact
with item identifier
Special symbol
Output relay in normally-energized arrangement
(closed-circuit operation).
A-9
Appendix A - Glossary
(continued)
Symbol
Description
PC interface
with pin connections
Multiplier
The output variable is the result of the multiplication
of the two input variables.
Divider
The output variable is the result of the division of
the two input variables.
Comparator
The output variable becomes 1 only if the input
variable(s) are equal to the function in the function
block.
Formula block
The output variable becomes 1 only if the input
variable(s) satisfy the equation in the function block
A-10
Appendix A - Glossary
(continued)
A4
All settings and signals relevant for protection are shown in the block diagrams of
Chapter 3 as follows:
Signal Name
Description
305 100
A-11
Appendix A - Glossary
(continued)
A5
A-12
Symbols used
Symbol
Meaning
Time duration
Complex voltage
Electrical current
Complex current
Complex impedance
Frequency
Temperature in C
Sum, result
Angle
Time constant
Temperature difference in K
Fig. 3-6
CTS: Blocked
Fig. 3-141
Fig. 3-143
CTS:Reset
Fig. 3-145
DIFF: Id,1
Fig. 3-87
DIFF: Id,2
Fig. 3-87
DIFF: Id,3
Fig. 3-87
DIFF: IR,1
Fig. 3-87
DIFF: IR,2
Fig. 3-87
DIFF: IR,3
Fig. 3-87
DIFF: I(2*f0),1
Fig. 3-89
DIFF: I(2*f0),2
Fig. 3-89
DIFF: I(2*f0),3
Fig. 3-89
DIFF: I(5*f0),1
Fig. 3-91
DIFF: I(5*f0),2
Fig. 3-91
DIFF: I(5*f0),3
Fig. 3-91
Fig. 3-80
Fig. 3-129
Fig. 3-72
Fig. 3-142
Fig. 3-142
Fig. 3-142
LOGIC: Output n
Fig. 3-60
Fig. 3-50
Fig. 3-59
MEASO: Enable
Fig. 3-28
Fig. 3-29
REF_1: Id,N,a
Fig. 3-97
REF_1: IR,N,a
Fig. 3-97
Fig. 3-122
THRM1: I
Fig. 3-123
Fig. 3-122
Fig. 3-133
B-1
B2
This section incorporates Section 8 of EN 60870-5-101 (1996), which includes a general definition of the telecontrol
interface for substation control systems.
B 2.1
Interoperability
This application-based standard (companion standard) specifies parameter sets and other options from which subsets
are to be selected in order to implement specific telecontrol systems.Certain parameters such as the number of bytes
(octets) in the COMMON ADDRESS of the ASDU are mutually exclusive. This means that only one value of the defined
parameter is allowed per system. Other parameters, such as the listed set of different process information in the
command and monitor direction, permit definition of the total number or of subsets that are suitable for the given
application. This section combines the parameters given in the previous sections in order to facilitate an appropriate
selection for a specific application. If a system is made up of several system components supplied by different
manufacturers, then it is necessary for all partners to agree on the selected parameters.
The boxes for the selected parameters should be checked. 1
The overall definition of a system may also require individual selection of certain parameters for specific
parts of a system such as individual selection of scaling factors for individually addressable measured
values.
Note:
B 2.1.1
Point-to-point configuration
B-2
B 2.1.2
Unbalanced
interface V.24/V.28
interface V.24/V.28
Standardized
2,400 bit/s
2,400 bit/s
56,000 bit/s
200 bit/s
4,800 bit/s
4,800 bit/s
64,000 bit/s
300 bit/s
9,600 bit/s
9,600 bit/s
600 bit/s
19,200 bit/s
1,200 bit/s
38,400 bit/s
1
2
Unbalanced
Unbalanced
interface V.24/V.28
interface V.24/V.28
Standardized
2,400 bit/s
2,400 bit/s
56,000 bit/s
200 bit/s
4,800 bit/s
4,800 bit/s
64,000 bit/s
300 bit/s
9,600 bit/s
9,600 bit/s
600 bit/s
19,200 bit/s
1,200 bit/s
38,400 bit/s
B-3
B 2.1.3
Frame format FT 1.2, single character 1, and the fixed time-out interval are used exclusively in this companion
standard.
Link Transmission Procedure
x Balanced transmission
x Not present
(balanced transmission only)
x Unbalanced transmission
x One octet
x Two octets 2
1
2
Frame Length
x Structured
240
x Unstructured
B-4
B 2.1.4
Application Layer1
x Two octets
x Structured
x Two octets
x Unstructured
x Three octets
Cause of Transmission (System-Specific Parameter)
x One octet
B-5
<1>
Single-point information
M_SP_NA_1
<2>
M_SP_TA_1
<3>
Double-point information
M_DP_NA_1
<4>
M_DP_TA_1
=
x
<5>
M_ST_NA_1
<6>
M_ST_TA_1
<7>
M_BO_NA_1
<8>
M_BO_TA_1
<9>
M_ME_NA_1
<10>
M_ME_TA_1
<11>
M_ME_NB_1
<12>
M_ME_TB_1
<13>
M_ME_NC_1
<14>
M_ME_TC_1
<15>
Integrated totals
M_IT_NA_1
<16>
M_IT_TA_1
B-6
<17>
M_EP_TA_1
<18>
ME_EP_TB_1
<19>
M_EP_TC_1
<20>
M_PS_NA_1
<21>
M_ME_ND_1
B-7
<45>
Single command
C_SC_NA_1
<46>
Double command
C_DC_NA_1
<47>
C_IT_NA_1
<48>
C_RC_NA_1
<49>
C_SE_NB_1
<50>
C_SE_NC_1
<51>
C_BO_NA_1
<70>
End of initialization
ME_EI_NA_1
B-8
1
2
<100>
Interrogation command
C_IC_NA_1
<101>
C_CI_NA_1
<102>
Read command
C_RD_NA_1
<103>
C_CS_NA_1
<104>
Test command
C_TS_NB_1
<105>
C_RP_NC_1
<106>
C_CD_NA_1
The command procedure is formally processed, but there is no change in the local time in the station.
See National Preface of EN 60870-5-101.
B-9
<110>
P_ME_NA_1
<111>
P_ME_NB_1
<112>
P_ME_NC_1
<113>
Parameter activation
P_AC_NA_1
B-10
<120>
File ready
F_FR_NA_1
<121>
Section ready
F_SR_NA_1
<122>
F_SC_NA_1
<123>
F_LS_NA_1
<124>
F_AF_NA_1
<125>
Segment
F_SG_NA_1
<126>
Directory
F_DR_TA_1
B 2.1.5
Remote initialization
Global
Group 1
Group 7
Group 13
Group 2
Group 8
Group 14
Group 3
Group 9
Group 15
Group 4
Group 10
Group 16
Group 5
Group 11
Group 6
Group 12
Clock synchronization
B-11
No additional definition
Short pulse duration
(Execution duration determined by a system parameter in the outstation)
Long pulse duration
(Execution duration determined by a system parameter in the outstation)
Persistent output
Counter request
Counter reset
B-12
Threshold value
Smoothing value
Low limit for transmission of measured value
High limit for transmission of measured value
F_FR_NA_1
F_FR_NA_1
B-13
B3
This section incorporates Section 8 of IEC 60870-5-103, including definitions applicable to the P63x.
B 3.1
Interoperability
B 3.1.1
Physical Layer
EIA RS 485
No. of loads
Note: EIA RS 485 defines the loads in such a way that 32 of them can be operated on one line. For detailed information
see EIA RS 485, Section 3.
B 3.1.1.2 Optical Interface
x
Glass fiber
Plastic fiber
F-SMA connector
BFOC/2.5 connector
9,600 bit/s
19,200 bit/s
B-14
B 3.1.2
Link Layer
Application Layer
Description
<0>
<0>
Time synchronization
<2>
Reset FCB
<3>
Reset CU
<4>
Start / restart
<5>
Power on
B-15
INF
Description
<16>
Auto-recloser active
<17>
Teleprotection active
<18>
Protection active
003 030
<19>
LED reset
021 010
<20>
037 075
COMM1: Sig./meas.val.block.
<21>
Test mode
037 071
<22>
<23>
Characteristic 1
036 090
PSS: PS 1 active
<24>
Characteristic 2
036 091
PSS: PS 2 active
<25>
Characteristic 3
036 092
PSS: PS 3 active
<26>
Characteristic 4
036 093
PSS: PS 4 active
<27>
Auxiliary input 1
034 000
<28>
Auxiliary input 2
034 001
<29>
Auxiliary input 3
034 002
<30>
Auxiliary input 4
034 003
B-16
INF
Description
<32>
<33>
<35>
<36>1
<37>
<38>
VT fuse failure
<39>
Teleprotection disturbed
<46>
<47>
041 200
004 061
Group warning
036 100
Group alarm
004 065
MAIN: Blocked/Faulty
The message content is formed from the OR operation of the individual signals.
B-17
B-18
INF
Description
<48>
Ground fault L1
<49>
Ground fault L2
<50>
Ground fault L3
<51>
<52>
INF
Description
<64>
Start /pick-up L1
<65>
Start /pick-up L2
<66>
Start /pick-up L3
<67>
Start /pick-up N
<68>
General trip
<69>
Trip L1
<70>
Trip L2
<71>
Trip L3
<72>
<73>
<74>
Fault forward/line
<75>
Fault reverse/busbar
<76>
<77>
<78>
Zone 1
<79>
Zone 2
<80>
Zone 3
<81>
Zone 4
<82>
Zone 5
<83>
Zone 6
036 071
B-19
INF
Description
<84>
General starting
036 000
<85>
Breaker failure
<86>
041 002
<87>
041 003
<88>
041 004
<89>
<90>
Trip I>
<91>
Trip I>>
<92>
Trip IN>
<93>
Trip IN>>
B-20
INF
Description
<128>
CB on by AR
<129>
CB on by long-time AR
<130>
AR blocked
INF
Description
<144>
Measured value I
<145>
Measured values I, V
<146>
Measured values I, V, P, Q
<147>
<148>
B-21
B-22
INF
Description
<240>
<241>
<243>
<244>
<245>
<249>
<250>
<251>
Description
<0>
<0>
Time synchronization
INF
Description
<16>
Auto-recloser on/off
<17>
Teleprotection on/off
<18>
Protection on/off
003 030
<19>
LED reset
021 010
<23>1
Activate characteristic 1
003 060
<24>2
Activate characteristic 2
003 060
<25>3
Activate characteristic 3
003 060
<26>4
Activate characteristic 4
003 060
Switches
Switches
3
Switches
4
Switches
2
PSS:
PSS:
PSS:
PSS:
Param.subs.sel.USER
Param.subs.sel.USER
Param.subs.sel.USER
Param.subs.sel.USER
B-23
B-24
INF
Description
<240>
<241>
<243>
<244>
<245>
<248>
Write entry
<249>
<250>
<251>
Test mode
Disturbance data
Generic services
Private data
B 3.1.3.6 Miscellaneous
Measured values are transmitted both with ASDU 3 and ASDU 9. As defined in Sec. 7.2.6.8, the maximum MVAL can
be either 1.2 or 2.4 times the rated value. In ASDU 3 and ASDU 9, different ratings may not be used; in other words,
there is only one choice for each measured value.
Measured value
Max. MVAL =
nom. value multiplied by
1.2
or
2.4
Current A
Current B
Current C
Voltage A-G
Voltage B-G
Voltage C-G
Enabled power P
Reactive power Q
Frequency f
Voltage A-B
B-25
B-26
C-1
Terminal connection diagram for P631 in 40TE case, pin-terminal connection, diagram P631.403, part 1 of 3
C-1
C-2
C-2
Terminal connection diagram for P631 in 40TE case, pin-terminal connection, diagram P631.403, part 2 of 3
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-3
Terminal connection diagram for P631 in 40TE case, pin-terminal connection, diagram P631.403, part 3 of 3
The location diagram for the Ethernet module is shown in Figure C-48
C-3
C-4
C-4
Terminal connection diagram for P631 in 40TE case, ring-terminal connection, diagram P631.404, part 1 of 3
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-5
Terminal connection diagram for P631 in 40TE case, ring-terminal connection, diagram P631.404, part 2 of 3
C-5
C-6
C-6
Terminal connection diagram for P631 in 40TE case, ring-terminal connection, diagram P631.404, part 3 of 3
The location diagram for the Ethernet module is shown in Figure C-48
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-7
Terminal connection diagram for P632 in 40TE case, pin-terminal connection, diagram P632.403, part 1 of 6
C-7
C-8
C-8
Terminal connection diagram for P632 in 40TE case, pin-terminal connection, diagram P632.403, part 2 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-9
Terminal connection diagram for P632 in 40TE case, pin-terminal connection, diagram P632.403, part 3 of 6
C-9
C-10 Terminal connection diagram for P632 in 40TE case, pin-terminal connection, diagram P632.403, part 4 of 6
C-10
C-11 Terminal connection diagram for P632 in 40TE case, pin-terminal connection, diagram P632.403, part 5 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-11
C-12 Terminal connection diagram for P632 in 40TE case, pin-terminal connection, diagram P632.403, part 6 of 6
The location diagram for the Ethernet module is shown in Figure C-48
C-12
C-13 Terminal connection diagram for P632 in 84TE case, ring-terminal connection, diagram P632.404, part 1 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-13
C-14 Terminal connection diagram for P632 in 84TE case, ring-terminal connection, diagram P632.404, part 2 of 6
C-14
C-15 Terminal connection diagram for P632 in 84TE case, ring-terminal connection, diagram P632.404, part 3 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-15
C-16 Terminal connection diagram for P632 in 84TE case, ring-terminal connection, diagram P632.404, part 4 of 6
C-16
C-17 Terminal connection diagram for P632 in 84TE case, ring-terminal connection, diagram P632.404, part 5 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-17
C-18 Terminal connection diagram for P632 in 84TE case, ring-terminal connection, diagram P632.404, part 6 of 6
The location diagram for the Ethernet module is shown in Figure C-48
C-18
C-19 Terminal connection diagram for P633 in 40TE case, pin-terminal connection, diagram P633.404, part 1 of 5
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-19
C-20 Terminal connection diagram for P633 in 40TE case, pin-terminal connection, diagram P633.404, part 2 of 5
C-20
C-21 Terminal connection diagram for P633 in 40TE case, pin-terminal connection, diagram P633.404, part 3 of 5
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-21
C-22 Terminal connection diagram for P633 in 40TE case, pin-terminal connection, diagram P633.404, part 4 of 5
C-22
C-23 Terminal connection diagram for P633 in 40TE case, pin-terminal connection, diagram P633.404, part 5 of 5
The location diagram for the Ethernet module is shown in Figure C-48
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-23
C-24 Terminal connection diagram for P633 in 84TE case, pin-terminal connection, diagram P633.405, part 1 of 6
C-24
C-25 Terminal connection diagram for P633 in 84TE case, pin-terminal connection, diagram P633.405, part 2 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-25
C-26 Terminal connection diagram for P633 in 84TE case, pin-terminal connection, diagram P633.405, part 3 of 6
C-26
C-27 Terminal connection diagram for P633 in 84TE case, pin-terminal connection, diagram P633.405, part 4 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-27
C-28 Terminal connection diagram for P633 in 84TE case, pin-terminal connection, diagram P633.405, part 5 of 6
C-28
C-29 Terminal connection diagram for P633 in 84TE case, pin-terminal connection, diagram P633.405, part 6 of 6
The location diagram for the Ethernet module is shown in Figure C-48
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-29
C-30 Terminal connection diagram for P633 in 84TE case, ring-terminal connection, diagram P633.406, part 1 of 6
C-30
C-31 Terminal connection diagram for P633 in 84TE case, ring-terminal connection, diagram P633.406, part 2 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-31
C-32 Terminal connection diagram for P633 in 84TE case, ring-terminal connection, diagram P633.406, part 3 of 6
C-32
C-33 Terminal connection diagram for P633 in 84TE case, ring-terminal connection, diagram P633.406, part 4 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-33
C-34 Terminal connection diagram for P633 in 84TE case, ring-terminal connection, diagram P633.406, part 5 of 6
C-34
C-35 Terminal connection diagram for P633 in 84TE case, ring-terminal connection, diagram P633.406, part 6 of 6
The location diagram for the Ethernet module is shown in Figure C-48
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-35
C-36 Terminal connection diagram for P634 in 84TE case, pin-terminal connection, diagram P634.403, part 1 of 6
C-36
C-37 Terminal connection diagram for P634 in 84TE case, pin-terminal connection, diagram P634.403, part 2 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-37
C-38 Terminal connection diagram for P634 in 84TE case, pin-terminal connection, diagram P634.403, part 3 of 6
C-38
C-39 Terminal connection diagram for P634 in 84TE case, pin-terminal connection, diagram P634.403, part 4 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-39
C-40 Terminal connection diagram for P634 in 84TE case, pin-terminal connection, diagram P634.403, part 5 of 6
C-40
C-41 Terminal connection diagram for P634 in 84TE case, pin-terminal connection, diagram P634.403, part 6 of 6
The location diagram for the Ethernet module is shown in Figure C-48
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-41
C-42 Terminal connection diagram for P634 in 84TE case, ring-terminal connection, diagram P634.404, part 1 of 6
C-42
C-43 Terminal connection diagram for P634 in 84TE case, ring-terminal connection, diagram P634.404, part 2 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-43
C-44 Terminal connection diagram for P634 in 84TE case, ring-terminal connection, diagram P634.404, part 3 of 6
C-44
C-45 Terminal connection diagram for P634 in 84TE case, ring-terminal connection, diagram P634.404, part 4 of 6
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-45
C-46 Terminal connection diagram for P634 in 84TE case, ring-terminal connection, diagram P634.404, part 5 of 6
C-46
C-47 Terminal connection diagram for P634 in 84TE case, ring-terminal connection, diagram P634.404, part 6 of 6
The location diagram for the Ethernet module is shown in Figure C-48
P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610
C-47
C 5 Ethernet Module
ITEM DESIGN.
CONNECTOR
-X7
MEANING
ITEM
REFER.
STATU S
LOCATION
REFER.
RX
X/Y
-U17
X/Y
-U18
X/Y
-U26
ST
ITEM DESIGN.
CONNECTOR
-X8
MEANING
ITEM
REFER.
STATUS
LOCATION
REFER.
TX
ST
ITEM DESIGN.
CONNECTOR
-X13
MEANING
ITEM
REFER.
STATUS
LOCATION
REFER.
RX
TX
SC
ITEM DESIGN.
CONNECTOR
-X12
MEANING
ITEM
REFER.
STATUS
LOCATION
REFER.
X // Y
-U25
RJ45
ITEM DESIGN.
CONNECTOR
-X10
MEANING
Comm. interface
Channel 2
ITEM
REFER.
STATUS
LOCATION
REFER.
X // Y
1
D2[R]
3
4
-U20
D1[T]
RS 485
: Alternative module
(see order inform.)
Px3x_Ethernet _02B_EN
C-48
Changes
P631-301-401601
P632-301-401601
P633-301-401/402601
Release: 15.01.01
P631-301-401601-701
P632-301-401601-701
P633-301-401/402601-701
Release: 03.04.01
Hardware
No changes
Diagram
No changes
Software
Device
COMM1
IRIG-B
P634-301-401601-702
Release: 17.05.01
P631-301-401601-703
P632-301-401601-703
P633-301-401/402601-703
P634-301-401601-703
Release: 02.08.01
P631-301-401601-704
P632-301-401601-704
P633-301-401/402601-704
P634-301-401601-704
Release: 17.12.01
Hardware
No changes
Diagram
No changes
Software
Device
Hardware
No changes
Diagram
No changes
Software
Device
D- 1
Version
P631-302-401/402 602
P632-302-401/402 602
P633-302-401/402/403 602
P634-302-401/402 602
Release: 25.01.02
Changes
Hardware
Diagram
Software
DVICE
COMM1
COMM2
MEASI
MAIN
Separate setting for the secondary nominal current value of the system
transformers for measurement of phase currents and residual currents.
Assignment of the 'logical' communication interfaces COMM1 and
COMM2 to the communication channels of module A.
Grouping of the signals issued by measuring circuit monitoring (MCMON)
to form a multiple signal.
DIFF
THRM1
to
THRM2
MCM_1
to
MCM_4
V/f
LOGIC
P631-302-401/402-602-705
Hardware
P632-302-401/402-602-705
P633-302-401/402/403-602-705 Diagram
P634-302-401/402-602-705
Release: 19.04.2002
D-2
No changes
No changes
Software
DVICE
Bug fixing:
The device was blocked following a start-up if either one of the
protections V<> or f<> were enabled, due to erroneous hardware selfidentification.
Version
Changes
P631-302-401/402-602-706
Hardware
P632-302-401/402-602-706
P633-302-401/402/403-602-706 Diagram
P634-302-401/402-602-706
No changes
Release: 06.06.2002
P631-302-401/402-603
P632-302-401/402-603
P633-302-401/402/403-603
P634-302-401/402-603
Release: 27.11.2002
No changes
Software
LOC
Bug fixing:
Two pixels in the Cyrillic characters were displayed incorrectly. This bug
affected only the language variant -805.
Hardware
No changes
Diagram
No changes
Software
DVICE
Bug fixing:
A device ID for the entry of an order extension number was missing.
DIFF
REF_1
REF_2
REF_3
IDMT1
IDMT2
IDMT3
f<>
V/f
D- 3
Version
Changes
P634-303-403/404-604
Release: 09.10.2003
There is no software version 604 available for the devices P631, P632,
P633!
Hardware
Diagram
The updated connection diagrams now include the interfaces for the
Ethernet communication module:
P434.403 (for 84TE case, pin-terminal connection)
P434.404 (for 84TE case, ring-terminal connection)
Software
P631-303-403/404-605
P632-303-403/404-605
P633-303-404/405/406-605
P634-303-403/404-605
UCA2
Hardware
The new hardware variants now offer, per ordering option, additional
operating thresholds for the binary signal inputs:
>18 V (standard variant)
(no order ext. No.)
>90 V (60...70% of VA,nom = 125...150 V)
(Order ext. No. 461)
>155 V (60...70% of VA,nom = 220...250 V)
(Order ext. No. 462)
Installation of the standard variant is generally recommended if the
application does not specifically require such binary signal inputs with
higher operate thresholds.
Release: 30.04.2004
The updated connection diagrams now include the interfaces for the
Ethernet communication module:
P631 -403 (for 40TE case, pin-terminal connection)
P631 -404 (for 40TE case, ring-terminal connection)
P632 -403 (for 40TE case, pin-terminal connection)
P632 -404 (for 84TE case, ring-terminal connection)
P633 -403 (for 40TE case, pin-terminal connection)
P633 -404 (for 84TE case, pin-terminal connection)
P633 -404 (for 84TE case, ring-terminal connection)
Software
UCA2
DIFF
D-4
Version
P631-304-403/404-606
P632-304-403/404-606
P633-304-404/405/406-606
P634-304-403/404-606
Changes
Hardware
Release: 09.05.2005
The new hardware variants now offer, per ordering option, additional
operating thresholds for the binary signal inputs:
>73 V (67% of VA,nom = 110 V)
(Order ext. No. -463)
>146 V (67% of VA,nom = 220 V)
(Order ext. No. -464)
Installation of the standard variant is still generally recommended if the
application does not specifically require such binary signal inputs with
higher operating thresholds.
An optional processor board with a DSP coprocessor is now available.
This coprocessor provides a better overall performance of the
supplementary functions of the device. It is the hardware requirement for
the use of the new current transformer supervision function (CTS).
Diagram
No changes
Software
Note:
COMM1
Addendum:
As of version 605 the 'memory function' for the warning signal memory
may be set. After the associated timer stage has elapsed, a renewed
occurrence of a warning is processed the same way as if it where a first
occurrence.
FT_RC
D- 5
Version
Changes
MAIN
SFMON
SFMON:
SFMON:
SFMON:
SFMON:
SFMON:
SFMON:
Output
Output
Output
Output
Output
Output
30
~ 042 092 L O G I C :
3 0 ( t ) ~ 042 092 L O G I C :
31
~ 042 092 L O G I C :
3 1 ( t ) ~ 042 092 L O G I C :
32
~ 042 092 L O G I C :
3 2 ( t ) ~ 042 092 L O G I C :
Output 30
Output 30 (t)
Output 31
Output 31 (t)
Output 32
Output 32 (t)
DIFF
Overload and fault recording now have a joint and complete list of
possible entries (merged list of all previous signals).
In practice it became apparent that limitations with regard to possible
entries in both recording memories would bring no advantages but make
analyzing more difficult, as both recording memories could be open at
the same time (e.g. a thermal overload situation could lead to a loss of
insulation which would cause a fault).
The minimum setting value for the characteristic gradients m1 and m2
have been modified to 0.10 (previously 0.15).
The starting condition for the saturation discriminator was modified so
that the DIFF protection testing may now be carried out again with
conventional test sets (which do not provide correct transient signals).
Along with the new CTS function, an additional threshold, I d i f f > ( C T S ) ,
is provided in order to de-sensitize differential protection in case there is
a fault in the CT's secondary circuit. For more information about this
feature please refer to CTS description.
Bug fixing:
In some cases the overreaching inrush stabilization function did not
operate properly. In addition the signal from the inrush stabilization was
sometimes immediately reset when a differential protection trip was
issued.
REF_1
REF_2
REF_3
D-6
Version
Changes
CTS
MCM_1
MCM_2
MCM_3
MCM_4
D- 7
Version
P631-305-403/404-610
P632-305-403/404-610
P633-305-404/405/406-610
P634-305-403/404-610
Changes
Hardware
No changes
Software
Note:
IEC
GOOSE
GSSE
UCA2
MAIN
DIFF
Bug fixing:
The trip signals issued by the 3 measuring systems
(D I F F : T r i p s i g n a l n , with n = 1, 2, or 3) were previously issued
instantly, regardless of the set time-delays.
(Note: D IFF : T r i p s i g n a l was issued correctly, including the timedelay.)
IDMTn
D-8
+33 (0) 1 41 29 70 00
+33 (0) 1 41 29 71 00
www.schneider-electric.com
Publication: P63x/EN M/Ca4 Version: -610
Schneider Electric
http://www.schneider-electric.com/CCC
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone:
Fax:
+33 (0) 1 41 29 70 00
+33 (0) 1 41 29 71 00
www.schneider-electric.com
Publication: P63x/EN M/Aq6 Version: -610 -611 -620 -621 -622 -630, Volume 1