1. Line Data
Page 1 of 32
Description
Positive Sequence
Zero Sequence
(for single line)
Mutual coupling
resistance
Mutual coupling
reactance
Line distance
Bakun-Murum
Junction
Murum-Murum
Junction
Similajau-Murum
Junction
R1
X1
C1
Calculated
Xc1
ohm/km
ohm/km
nF/km
Megaohm.
km
0.0190
0.2463
14.8024
0.0190
0.2463
14.8024
0.0190
0.2463
14.8024
0.2150
0.2150
0.2150
R0
X0
C0
Calculated
Xc0
ohm/km
ohm/km
nF/km
Megaohm.
km
0.2079
0.7758
8.7031
0.2079
0.7758
8.7031
0.2079
0.7758
8.7031
0.3657
0.3657
0.3657
R0m
ohm/km
0.1879
0.1879
0.1879
X0m
ohm/km
km
0.4405
20.780
0.4405
47.626
0.4405
90.450
Page 2 of 32
3. Differential Protection
Where;
Page 3 of 32
Line Parameter
Length
(km)
Imp
R ()
X ()
Z ()
Angle(o)
Calculat
ed
I c (A)
Remark
s
Z1
0.9049
11.730
2
11.77
85.58
35.187
Z0
9.9014
36.9483
38.25
74.99
N/R
47.626
Distance Characteristic
Page 4 of 32
iii.
-
Resistive reach for Phase fault (RFPP) is set to Rf/X factor times X1 of each
respective Zone
resistive reach for earth fault (RFPE) is set to Rf/X factor times (1+KN)X1 of each
respective Zone, where KN = (Z0 Z1)/3Z1
iv.
Page 5 of 32
function
RLdInFw = (0.8)(45.35)
= 36.28
AND
AND
Page 7 of 32
PSB Characteristic
Setting Group N1: Differential Protection (PDIF, 87L) under general setting
Basic parameter group settings for the Differential function
(Differential Protection setting (LDIF) under general setting
Parameter
Range
Step
Default
Propos
e
Unit
Description
NoOfTerminal
2
3
Chan2IsLocal
No
Yes
No
No
Ibase
50.09999.9
0.1
3000.00
2500
Number of current
terminals of the protected
circuit
2-nd local current
connected to input channel
2, Yes/No
Base (reference) current of
the differential protection
Setting Group N1: Differential Protection (PDIF, 87L) under group setting
Basic parameter group settings for the Differential function
(Differential Protection setting (LDIF) under group setting
Parameter
Range
Step
Default
Propos
e
Unit
Description
Page 8 of 32
Off
On
0.20-2.00
On
On
Operation Off/On
0.01
0.3
0.2
IB
0.2010.00
0.00060.000
1.0050.00
0.01
0.8
0.8
IB
0.001
1.000
1.000
0.01
10.00
10.00
IB
NegSeqDiffEn
Off
On
On
On
NegSeqROA
30.0120.0
1.0
60
60
Deg
IMinNegSeq
0.01-0.20
0.01
0.04
0.05
IB
CrossBlockEn
No
Yes
Off
On
No
No
Off
Off
Off
On
0.20-5.00
Off
Off
0.01
1.00
1.00
IB
0.0006.000
0.0016.000
0.001
0.000
0.000
0.001
0.001
0.01
IdMin
IdMinHigh
tIdMinHigh
IdUnre
ChargCurEnabl
e
AddDelay
IMaxAddDelay
tDefTime
tMinInv
Page 9 of 32
IEC
Def.Tim
e
IEC
Def.Tim
e
ANSI Ext.
inv
ANSI Very
inv
ANSI
Norm. inv
ANSI
Mod.inv.
ANSI
Def.Time
L.T.E. inv.
L.T.V. inv
L.T. inv
IEC
Norm.inv
IEC Very
inv.
IEC Inv
IEC
Ext.inv.
IEC S.T.inv
IEC L.T.
Inv
IEC
Def.Time
Programm
able
RI type
RD type
0.05-1.10
0.01
1.00
1.00
IdiffAlarm
0.05-1.00
0.01
0.15
0.15
IB
tAlarmdelay
0.00060.000
0.001
10.000
10.000
Time Multiplier
setting(TMS) for inverse
delays
Sustained differential
current alarm, factor of
Ibase
Delay for alarm due to
sustained differential
current, in s
Setting Group N1: Differential Protection (PDIF, 87L) under group setting
(advanced)
Basic parameter group settings for the Differential function
(Differential Protection setting (LDIF) under group setting (advanced)
Parameter
Range
Step
Default
Propos
e
Unit
Description
EndSection1
0.20-1.50
0.01
1.25
0.60
IB
EndSection2
1.0010.00
0.01
3.00
2.50
IB
SlopeSection2
10.0-50.0
0.1
40.0
50.0
SlopeSection3
30.0100.0
0.1
80.0
80.0
End of section 1, as
multiple of reference
current Ibase
End of section 2, as
multiple of reference
current Ibase
Slope in section 2 of
operate-restrain
characteristic, in %
Slope in section 3 of
operate-restrain
characteristic, in %
Page 10 of 32
5.0-100.0
1.0
10.0
15
I5/I1Ratio
5.0-100.0
1.0
25.0
25
0.01-1000
0.01
0.02
0.02
0.01-1000
0.01
0.14
0.14
0.01-1000
0.01
1.00
1.00
0.01-1000
0.01
1.00
1.00
OpenCTEnable
On
On
tOCTAlarmDela
y
Off
On
0.10010.000
0.001
1.000
1.000
tOCTResetDela
y
0.10010.000
0.001
0.250
0.250
Range
Step
Default
Propos
e
Unit
Description
Operation
Off
On
1-99999
On
On
Operation Off/On
3000
2500
0.052000.00
Off
Nondirection
al
Forward
Reserse
0.103000.00
0.05
400.00
275
kV
Forward
Forwar
d
0.01
30.00
9.97
Ohm/p
Positive sequence
reactance reach
0.101000.00
0.109000.00
0.503000.00
1.003000.00
0.01
5.00
0.77
Ohm/p
0.01
100.00
31.41
Ohm/p
0.01
15.00
8.42
Ohm/p
0.01
30.00
19.94
Ohm/l
IBase
UBase
OperationDir
X1
R1
X0
R0
RFPP
Page 11 of 32
1.009000.00
Off
On
Off
On
0.00060.000
0.01
100.00
34.50
Ohm/l
On
On
On
On
0.001
0.000
0.000
Off
On
Off
On
0.00060.000
On
On
On
On
0.001
0.000
0.000
IMinOpPP
10-30
20
10
%IB
IMinOpPE
10-30
20
10
%IB
IMinOpIN
5-30
%IB
OperationPP
Timer tPP
tPP
OperationPE
Timer tPE
tPE
Range
Step
Default
Propos
e
Unit
Description
Operation
Off
On
1-99999
On
On
Operation Off/On
3000
2500
0.052000.00
Off
Nondirection
al
Forward
Reserse
0.103000.00
0.101000.00
0.05
400.00
275
kV
Forward
Forwar
d
0.01
30.00
14.08
Ohm/p
0.01
5.00
1.09
Ohm/p
IBase
UBase
OperationDir
X1
R1
Positive sequence
reactance reach
Positive seq. resistance for
zone characteristic angle
Page 12 of 32
0.01
100.00
44.34
Ohm/p
0.01
15.00
11.88
Ohm/p
0.01
30.00
28.15
Ohm/l
0.01
100.00
48.70
Ohm/l
On
On
On
On
0.001
0.000
0.3
On
On
On
On
0.001
0.000
0.3
IMinOpPP
0.109000.00
0.503000.00
1.003000.00
1.009000.00
Off
On
Off
On
0.00060.000
Off
On
Off
On
0.00060.000
10-30
20
10
%IB
IMinOpPE
10-30
20
10
%IB
R0
RFPP
RFPE
OperationPP
Timer tPP
tPP
OperationPE
Timer tPE
tPE
Range
Step
Default
Propos
e
Unit
Description
Operation
Off
On
1-99999
On
On
Operation Off/On
3000
2500
0.052000.00
Off
Nondirection
al
Forward
Reserse
0.103000.00
0.101000.00
0.109000.00
0.503000.00
0.05
400.00
275
kV
Forward
Forwar
d
0.01
30.00
21.11
Ohm/p
0.01
5.00
1.63
Ohm/p
0.01
100.00
66.51
Ohm/p
0.01
15.00
17.82
Ohm/p
IBase
UBase
OperationDir
X1
R1
X0
R0
Positive sequence
reactance reach
Positive seq. resistance for
zone characteristic angle
Zero sequence reactance
reach
Zero seq. resistance for
zone characteristic angle
Page 13 of 32
0.01
30.00
42.23
Ohm/l
0.01
100.00
73.06
Ohm/l
On
On
On
On
0.001
0.000
0.900
On
On
On
On
0.001
0.000
0.900
IMinOpPP
1.003000.00
1.009000.00
Off
On
Off
On
0.00060.000
Off
On
Off
On
0.00060.000
10-30
20
10
%IB
IMinOpPE
10-30
20
10
%IB
RFPE
OperationPP
Timer tPP
tPP
OperationPE
Timer tPE
tPE
Range
Step
Default
Propos
e
Unit
Description
Operation
Off
On
1-99999
On
On
Operation Off/On
3000
2500
0.052000.00
Off
Nondirection
al
Forward
Reverse
0.103000.00
0.101000.00
0.109000.00
0.503000.00
1.003000.00
1.009000.00
Off
On
0.05
400.00
275.00
kV
Forward
Revers
e
0.01
30.00
4.69
Ohm/p
0.01
5.00
0.36
Ohm/p
0.01
100.00
14.78
Ohm/p
0.01
15.00
3.96
Ohm/p
0.01
30.00
9.38
Ohm/l
0.01
100.00
16.23
Ohm/l
On
On
IBase
UBase
OperationDir
X1
R1
X0
R0
RFPP
RFPE
OperationPP
Positive sequence
reactance reach
Positive seq. resistance for
zone characteristic angle
Zero sequence reactance
reach
Zero seq. resistance for
zone characteristic angle
Fault resistance reach in
ohm/loop, Ph-Ph
Fault resistance reach in
ohm/loop, Ph-E
Operation mode Off/On of
Phase-Phase loops
Page 14 of 32
On
On
0.001
0.000
1.000
On
On
On
On
0.001
0.000
1.000
IMinOpPP
Off
On
0.00060.000
Off
On
Off
On
0.00060.000
10-30
20
10
%IB
IMinOpPE
10-30
20
10
%IB
tPP
OperationPE
Timer tPE
tPE
Page 15 of 32
Setting Group N1: Impedance Protection Phase Selection (PDIS, 21)- PHS1
Basic parameter group settings for the FDPSPDIS_21(PHS--) function
Parameter
Range
Step
Default
Propose
Unit
Description
IBase
1-99999
3000
2500
UBase
0.05
400.00
275
kV
INBlockPP
0.052000.00
10-100
40
40
%IPh
INReleasePE
10-100
20
10
%IPh
RLdFw
1.003000.00
0.01
80.00
48.27
Ohm/
p
RLdRv
1.003000.00
0.01
80.00
48.27
Ohm/
p
ArgLd
5-70
30
20
Deg
X1
0.503000.00
0.01
40.00
30.40
Ohm/
p
X0
0.503000.00
0.01
120.00
95.77
Ohm/
p
Zero sequence
reactance reach 1.44 x
Xmax
RFFwPP
0.503000.00
0.01
30.00
52.79
Ohm/l
RFRvPP
0.503000.00
0.01
30.00
52.79
Ohm/l
RFFwPE
1.009000.00
0.01
100.00
91.32
Ohm/l
RFRvPE
1.009000.00
0.01
100.00
91.32
Ohm/l
Timer PP
Off
On
On
Off
tPP
0.00060.000
0.00
1
0.000
0.000
Page 16 of 32
Off
On
On
Off
tPE
0.00
1
1
0.000
0.000
IMinOpPP
0.00060.000
10-30
20
10
%IB
IMinOpPE
10-30
20
%IB
Range
Step
Default
Propos
e
Unit
Description
ArgNegRes
90-175
115
115
Deg
ArgDir
5-45
15
15
Deg
IMinOp
1-99999
10
10
%IB
IBase
1-99999
3000
2500
UBase
0.052000.00
0.05
400.00
275.00
kV
Range
Step
Default
Propose
Unit
Description
Operation
Off
On
1-99999
On
ON
Operation Off/On
3000
2500
0.052000.00
Impedanc
e
UlLevel
UlLvl&Im
p
Off
On
1-100
0.05
400.00
275.00
kV
UlLevel
Impedanc
e
Mode of operation of
SOTF Function. Start by
zone 2 non-dir. Refer to
config ZM02-STND
Off
Off
20
20
%IB
IBase
UBase
Mode
AutoInit
IPh<
Page 17 of 32
1-100
70
60
%UB
tDuration
0.00060.000
0.001
0.020
0.150
tSOTF
0.000
0.001
1.000
0.150
tDLD
0.000
0.001
0.200
0.150
Range
Step
Default
Propose
Unit
Description
Operation
Off
On
0.10
3000.00
Off
On
0.01
30.00
22.17
ohm
R1LIn
0.10
1000.00
0.01
30.00
1.71
ohm
R1FInFw
0.10
1000.00
0.01
30.00
18.71
ohm
X1InRv
0.10
3000.00
0.01
30.00
22.17
ohm
R1FInRv
0.10
1000.00
0.01
30.00
18.71
ohm
OperationLdCh
Off
On
RLdOutFw
0.10 3000.00
5 70
0.01
30.00
45.35
ohm
25
16
Deg
0.10 3000.00
0.01
30.00
45.35
ohm
X1lnFw
ArgLd
RLdOutRv
On
On
Page 18 of 32
0.50 0.90
0.01
0.75
0.80
Mult
kLdRRv
0.50 0.90
0.01
0.75
0.80
Mult
tEF
0.000 60.000
0.001
3.000
2.000
IMinOpPE
5 30
10
20
%IB
IBase
1 - 99999
3000
2500
Setting Group N1: Secondary System Supervision: Fuse Failure (RFUF) Group
settings (basic)
SDDRFUF Group settings (basic)
Parameter
Range
Operation
IBase
Off
On
1 - 99999
UBase
0.05 - 2000.00
OpMode
3U0>
Off
UNsINs
UZsIZs
UZsIZs OR
UNsINs
UZsIZs AND
UNsINs
OptimZsNs
1 - 100
3I0<
Step
Default
Propose
On
On
3000
2500
Base current
0.05
400.00
275
kV
Base voltage
UZsIZs
UZsIZs
30
20
%UB
1 100
10
10
%IB
3U2>
1 100
30
20
%UB
3I2<
1 100
10
10
%IB
OpDUDI
Off
On
Off
On
DU>
1 - 100
60
20
%UB
DI<
1 - 100
15
10
%IB
UPh>
1 100
70
70
%UB
Unit
Description
Operation Off / On
Operating mode
selection
Operate level of
residual overvoltage
element in % of UBase
Operate level of
residual undercurrent
element in % of IBase
Operate level of neg
seq overvoltage
element in % of UBase
Operate level of neg
seq undercurrent
element in % of IBase
Operation of change
based function Off/
On
Operate level of change
in phase voltage
in % of UBase
Operate level of change
in phase current
in % of IBase
Operate level of phase
voltage in % of
UBase
Page 19 of 32
1 100
10
10
%IB
SealIn
On
On
USealln<
Off
On
1 100
70
60
%UB
IDLD<
1 100
20
%IB
UDLD<
1 100
60
60
%UB
Range
Step
Default
Propose
Unit
Description
R1A
0.001 1500.000
0.001 1500.000
0.001 1500.000
0.001 1500.000
0.001 1500.000
0.001 1500.000
0.001 1500.000
0.001 1500.000
0.001 1500.000
0.001 1500.000
0.0 - 10000.0
0.00
1
0.00
1
0.00
1
0.00
1
0.00
1
0.00
1
0.00
1
0.00
1
0.00
1
0.00
1
0.1
2.000
TBA
12.000
TBA
2.000
TBA
12.000
TBA
2.000
0.905
12.500
11.730
8.750
9.901
50.000
36.948
0.000
8.949
0.000
20.979
40.0
47.626
ohm/
p
ohm/
p
ohm/
p
ohm/
p
ohm/
p
ohm/
p
ohm/
p
ohm/
p
ohm/
p
ohm/
p
-
Source resistance A
(near end)
Source reactance A
(near end)
Source resistance B (far
end)
Source reactance B (far
end)
Positive sequence line
resistance
Positive sequence line
reactance
Zero sequence line
resistance
Zero sequence line
reactance
Zero sequence mutual
resistance
Zero sequence mutual
reactance
Length of line
X1A
R1B
X1B
R1L
X1L
R0L
X0L
R0M
X0M
LineLength
Range
Step
Default
Propose
Unit
Description
DrepChNoIL1
1 - 30
Ch
DrepChNoIL2
1 30
Ch
Page 20 of 32
1 30
Ch
DrepChNoIN
0 - 30
Ch
DrepChNoIP
0 30
Ch
DrepChNoUL1
1 - 30
Ch
DrepChNoUL2
1 - 30
Ch
DrepChNoUL3
1 - 30
Ch
Range
Operation
IBase
Off
On
1 - 99999
UBase
Default
Propose
Off
Off
3000
2500
Base current
0.05 - 2000.00
0.05
400.00
275
kV
Base voltage
AngleRCA
40 65
55
55
Deg
AngleROA
40 89
80
80
Deg
StartPhSel
1 out of 3
2 out of 3
3 out of 3
Off
Non-directional
Forward
Reverse
1 out of 3
1 out of 3
Nondirection
al
Nondirection
al
Relay characteristic
angle (RCA)
Relay operation angle
(ROA)
Number of phases
required for op (1 of
3, 2 of 3, 3 of 3)
Directional mode of
step 1 (off, nodir,
forward, reverse)
DirMode1
Step
Unit
Description
Operation Off / On
Page 21 of 32
I1>
t1
0.000 - 60.000
k1
0.05 - 999.00
0.00
1
0.01
IMin1
1 - 10000
100
100
%IB
t1Min
0.000 - 60.000
0.00
1
0.000
0.000
I1Mult
1.0 - 10.0
0.1
2.0
2.0
DirMode2
Off
Non-directional
Forward
Reverse
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Nondirection
al
Nondirection
al
ANSI Def.
Time
ANSI Def.
Time
Characterist2
ANSI Def.
Time
ANSI Def.
Time
1000
1000
%IB
0.000
0.000
0.05
0.05
Page 22 of 32
1 2500
1000
1000
%IB
t2
0.000 - 60.000
0.000
0.000
k2
0.05 - 999.00
0.00
1
0.01
0.05
0.05
IMin2
1 - 10000
100
100
%IB
t2Min
0.000 - 60.000
0.00
1
0.000
0.000
I2Mult
1.0 - 10.0
0.1
2.0
2.0
DirMode3
Nondirection
al
Nondirection
al
ANSI Def.
Time
ANSI Def.
Time
I3>
Off
Non-directional
Forward
Reverse
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
1 2500
1000
1000
%IB
t3
0.000 - 60.000
0.000
0.000
k3
0.05 - 999.00
0.00
1
0.01
0.05
0.05
IMin3
1 - 10000
100
100
%IB
t3Min
0.000 - 60.000
0.00
1
0.000
0.000
I3Mult
1.0 - 10.0
0.1
2.0
2.0
Characterist3
Page 23 of 32
I4>
Off
Non-directional
Forward
Reverse
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
1 2500
t4
0.000 - 60.000
k4
0.05 - 999.00
0.00
1
0.01
IMin4
1 - 10000
100
100
%IB
t4Min
0.000 - 60.000
0.00
1
0.000
0.000
I4Mult
1.0 - 10.0
0.1
2.0
2.0
Characterist4
Nondirection
al
Nondirection
al
Directional mode of
step 4 (off, nodir,
forward, reverse)
ANSI Def.
Time
ANSI Def.
Time
1000
1000
%IB
0.000
0.000
0.05
0.05
Range
Step
Default
Propose
Unit
Description
Operation
Off
On
IBase
Off
On
1 99999
3000
2500
UBase
0.05 - 2000.00
0.05
400
275
kV
AngleRCA
-180 180
65
65
Deg
Operation Off/On
Only used for DEFC
Base value for current
settings
Base value for voltage
settings
Relay characteristic
angle (RCA)
Page 24 of 32
Voltage
Current
Dual
1 100
IPolMin
Voltage
Voltage
%UB
2 100
%IB
RNPol
0.50 - 1000.00
0.01
5.00
1000.00
ohm
XNPol
0.50 - 3000.00
0.01
40.00
3000.00
ohm
IN>Dir
1 100
10
20
%IB
2ndHarmStab
5 - 100
20
15
BlkParTransf
Off
On
IN1>
IN2>
IN3>
IN4>
Off
SOTF
UnderTime
SOTF&UnderTim
e
Open
Closed
CloseCommand
Step 2
Step 3
Off
On
Off
Off
IN4>
IN4>
Off
Off
Open
Open
Step 2
Step 2
Off
Off
0.200
0.200
1.000
1.000
Nondirection
al
Forward
UseStartValue
SOTF
ActivationSOT
F
StepForSOTF
HarmResSOTF
tSOTF
0.000 - 60.000
t4U
0.000 - 60.000
DirMode1
Off
Non-directional
Forward
Reverse
0.00
1
0.00
1
-
Type of polarization
Minimum voltage level
for polarization in
% of UBase
Minimum current level
for polarization in
% of IBase.
Typical 5-10% of I base
Real part of source Z to
be used for
current polarisation
Imaginary part of
source Z to be used for
current polarisation
Residual current level
for Direction
release in % of IBase
Second harmonic
restrain operation in %
of IN amplitude
Enable blocking at
parallel transformers
Current level blk at
parallel transf (step1,
2, 3 or 4)
Switch-onto-fault active
time
Directional mode of
step1 (off, nodir,
forward, reverse)
Page 25 of 32
IN1>
ANSI Def.
Time
IEC Def.
Time
100
10
%IB
t1
0.000 - 60.000
0.00
1
0.000
2.000
k1
0.05 - 999.00
0.01
0.05
1.00
t1Min
0.000 - 60.000
0.00
1
0.000
60.000
IN1Mult
1.0 - 10.0
0.1
2.0
10.0
HarmRestrain
1
Off
On
On
On
DirMode2
Off
Non-directional
Forward
Reverse
Nondirection
al
Off
Operate residual
current level for step 1
in % of IBase
Independent (defenite)
time delay of step
1
Time multiplier for the
dependent time
delay for step 1
Minimum operate time
for inverse curves
for step 1
Multiplier for scaling the
current setting
value for step 1
Enable block of step 1
from harmonic
Restrain
Directional mode of
step2 (off, nodir,
forward, reverse)
Page 26 of 32
IN2>
ANSI Def.
Time
IEC Def.
Time
100
10
%IB
t2
0.000 - 60.000
0.00
1
0.000
2.000
k2
0.05 - 999.00
0.01
0.05
999.00
t2Min
0.000 - 60.000
0.00
1
0.000
60.000
IN2Mult
1.0 - 10.0
0.1
2.0
10.0
HarmRestrain
2
Off
On
On
On
DirMode3
Off
Non-directional
Forward
Reverse
Nondirection
al
Off
Operate residual
current level for step 2
in % of IBase
Independent (defenite)
time delay of step
2
Time multiplier for the
dependent time
delay for step 2
Minimum operate time
for inverse curves
for step 2
Multiplier for scaling the
current setting
value for step 2
Enable block of step 2
from harmonic
Restrain
Directional mode of
step3 (off, nodir,
forward, reverse)
Page 27 of 32
IN3>
ANSI Def.
Time
ANSI
Def.
Time
100
33
%IB
t3
0.000 - 60.000
0.00
1
0.000
0.800
k3
0.05 - 999.00
0.01
0.05
0.05
t3Min
0.000 - 60.000
0.00
1
0.000
2.000
IN3Mult
1.0 - 10.0
0.1
2.0
2.0
HarmRestrain
3
Off
On
On
On
DirMode4
Off
Non-directional
Forward
Reverse
Nondirection
al
Off
Operate residual
current level for step 3
in % of IBase
Independent (defenite)
time delay of step
3
Time multiplier for the
dependent time
delay for step 3
Minimum operate time
for inverse curves
for step 3
Multiplier for scaling the
current setting
value for step 3
Enable block of step 3
from harmonic
Restrain
Directional mode of
step4 (off, nodir,
forward, reverse)
Page 28 of 32
IN4>
ANSI Def.
Time
ANSI
Def.
Time
100
13
%IB
t4
0.000 - 60.000
0.00
1
0.000
1.200
k4
0.05 - 999.00
0.01
0.05
0.50
t4Min
0.000 - 60.000
0.00
1
0.000
0.000
IN4Mult
1.0 - 10.0
0.1
2.0
2.0
HarmRestrain
4
Off
On
On
On
Operate residual
current level for step 4
in % of IBase
Independent (defenite)
time delay of step
4
Time multiplier for the
dependent time
delay for step 4
Minimum operate time
for inverse curves
for step 4
Multiplier for scaling the
current setting
value for step 4
Enable block of step 4
from harmonic
Restrain
Range
Step
Default
Propose
Unit
Description
Operation
Off
On
0 99999
Off
Off
3000
2500
Operation Off/On
Not used.
Base current in A
IBase
Page 29 of 32
0 600
90
90
Deg
IRef
0 400
100
100
%IB
IMult
15
Tau
0 1000
45
Min
AlarmTemp
0 200
80
80
Deg
TripTemp
0 600
90
90
Deg
ReclTemp
0 600
75
75
Deg
tPulse
0.05 - 0.30
0.01
0.1
0.1
AmbiSens
Off
On
-50 250
Off
Off
20
20
Deg
-50 600
50
50
Deg
DefaultAmbTe
mp
DefaultTemp
Range
Step
Default
Propose
Unit
Description
Operation
Off
On
Off
On
Operation Off/On
Not used.
Scheme Type
Permissiv
e UR
Permissiv
e OR
tCoord
Off
Intertrip
Permissive UR
Permissive OR
Blocking
0.000 - 60.000
0.00
1
0.035
0.050
tSendMin
0.000 - 60.000
0.00
1
0.100
0.100
Communication scheme
coordination
time
Minimum duration of a
carrier send signal
Page 30 of 32
Range
Step
Default
Propose
Unit
Description
Operation
On
On
Operation Off / On
Program
Off
On
3 phase
1ph/3ph
1Ph/2Ph/3Ph
1ph/3ph
1ph/3ph
tTripMin
0.000 - 60.000
0.00
1
0.150
0.060
Minimum duration of
trip
output signal.
Use recommended
Range
Step
Default
Propose
Unit
Description
Operation
ON
On
Operation Off / On
PulseTime
Off
ON
0.050 - 60.000
0.000
0.150
OnDelay
0.000 - 60.000
0.000
0.000
OffDelay
0.000 - 60.000
0.000
0.000
ModeOutput1
Steady
Pulsed
0.00
1
0.00
1
0.00
1
-
Steady
Steady
ModeOutput2
Steady
Pulsed
Steady
Steady
ModeOutput3
Steady
Pulsed
Steady
Steady
Page 31 of 32
Page 32 of 32