Ground Fault
Monitor
IRDH265
IRDH365
k
MONITOR
A-ISOMETER
Serie 360
1 ALARM
TEST
RESET
k
MONITOR
IND.CONT.EQ., 12PA
Quality System
Certified
ISO 9001
Operating Manual
TGH1249A
BENDER INC.
700 Fox Chase
Coatesville, PA 19320
Tel: 610-383-9200
Toll-free: 800-356-4266
Fax: 610-383-7100
Edition: 12/99
Right to modifications reserved
2
Table of Contents
Operating Manual ........................................................................................ 1
1.
2.
2.1
2.2
2.3
2.4
2.5
2.6
General ........................................................................................... 7
The Fundamental Functions ............................................................. 7
Product Description ......................................................................... 8
Function ........................................................................................... 8
Self-test ........................................................................................... 10
Connection Monitoring ................................................................. 10
System Fault ................................................................................... 10
3.
3.1
3.1.1
3.1.2
3.2
3.3
3.4
Connection ................................................................................... 11
Wiring Diagrams
IRDH265 ....................................................................................... 11
IRDH365 ....................................................................................... 12
Connection to Various System Types .............................................. 14
Connection via Coupling Devices .................................................. 15
Operation with Coupling Device AGH204S-4
AC System with Rectifier ................................................................ 16
4.
4.1.1
4.1.2
4.2
4.3
4.4
4.4.1
4.4.2
4.4.3
4.4.4
4.5
4.5.1
4.5.2
4.5.3
Table of Contents
4.5.4
4.5.5
4.5.6
4.5.7
4.5.8
4.5.9
4.5.10
4.5.11
4.5.12
4.5.13
4.6
4.6.1
4.6.1.1
4.6.1.2
4.6.1.3
4.6.1.4
4.6.2
5.
Interface ....................................................................................... 33
6.
7.
7.1.1
7.1.2
7.1.3
7.1.4
7.2
8.
9.
26
26
26
27
27
27
27
27
27
28
29
30
30
30
31
31
1. Safety Information
1.
-3..
-4..
40 / 10
180 / 40
-7..
-8..
= 500 F
150 F
2 F
2 F
Please check, whether the basic setting of the BENDER Ground Fault Monitors,
IRDH265/IRDH365 complies with the requirements of the system being
monitored.
Insulation faults in DC circuits which are directly connected to the AC system
are only monitored correctly when the rectifiers carry a load current > 5 mA
2. General
2.1
2. General
2.2
Product Description
The BENDER Ground Fault Monitors IRDH265 and IRDH365 monitor the
insulation resistance of ungrounded 3(N)AC, AC/DC and DC systems. The AC
systems may include extensive DC-supplied loads (e.g. rectifiers, converters,
thyristor-controlles DC drives, see 2.3). The devices automatically adjust to the
system leakage capacitance.
Coupling devices are available to extend the voltage range.
The Ground Fault Monitor IRDH265 is fitted into a standard plastic casing
suitable for DIN rail mounting according to DIN EN 50022 or for screw
mounting.
The IRDH365 version is fitted into a flush-mounting casing, 144 x 72mm
(WxH).
2.3
Function
The BENDER Ground Fault Monitors IRDH265 and IRDH365 are connected
between the ungrounded (floating) system and the equipment grounding conductor
(PE/GND).
The setting of the response values and other parameters can be carried out via the
function keys. The parameters are indicated on the LC display and are stored in
a non-volatile memory (EEPROM) after setting.
A specially clocked, very low frequency measuring voltage is superimposed on the
system (AMP measuring principle*). The measuring pulse consists of positive and
negative pulses of the same amplitude. The period depends on the respective
leakage capacitances and the insulation resistance of the system to be monitored.
An insulation fault between system and ground closes the measuring circuit. An
electronic evaluation circuit calculates the insulation resistance which is indicated
on a LC display or an external ohmmeter after the response time.
2. General
The response time depends on the system leakage capacitance, the insulation
resistance, and the system related interference disturbances. System leakage
capacitances do not influence the measuring accuracy.
If the reading is below the selected response values ALARM1/ALARM2, the
appropriate alarm relays are activated, the alarm LEDs ALARM 1/2 illuminate
and the measuring value is indicated on the LC display (in the event of DC
insulation faults, the faulty supply line is indicated, too). If the terminals LT are
bridged (external RESET button (Normally Closed contact) or wire jumper), the
fault indication will be stored.
By pressing the test button, the function of the Ground Fault Monitors IRDH265
(IRDH365) can be tested. After pressing the test button (> 2s), the display
indicates "TEST". If no fault has been found, the display indicates "TEST OK
R<1k", the alarm relays switch and both alarm LEDs illuminate after the expiry
of the time delay. If a system fault has been detected during the test, the LC display
indicates "TEST ALARM". The fault indications can be reset by pushing the
"TEST/RESET" button (<1s).
The terminals M+/M- for the external k indication are not galvanically
separated. If measuring transducers are to be connected for the purpose of
evaluation in process control systems, these must be properly galvanically separated
(e.g. RK170).
*)
2. General
2.4
Self-test
If the insulation resistance exceeds 20 times the maximum response value, resp.
every 24 h, the IRDH265 (IRDH365), automatically carry out a self-test (applies
only to versions -3..., -4...) provided that the alarm relay has been set to system
fault alarm. Please note that some new systems may have an insulation resistance
level greater than 20 times the maximum response value. In this case it is
recommended that this feature not be selected.
2.5
Connection Monitoring (applies only to versions -3.., -4..
including R3.. and R4.. versions)
The connections to the ungrounded system and ground (PE/GND)
are continuously monitored. If the connections are broken or are not
connected or are of high-resistance, the display indicates "ALARM EKE" or "ALARM L1-L3". This alarm will only be initiated in the event of failure
of all connecting leads. In this case, please check the connecting leads immediately
as otherwise the insulation resistance will not be measured correctly.
Note: If the insulation resistance is in the range of 20 times the maximum
response value, which may be the case in new or small systems, an alarm will be
initiated, too. In this case, the connection monitoring can be switched off in the
Setup 2 menu.
2.6
System Fault
3. Connection
3.1
3.1.1
Wiring Diagrams
IRDH265
alarm LED yellow, illuminates
when the insulation level falls
below the preset response
value RALARM1
US
11
14
(see nameplate)
+/
fuse 6 A
(recommendation)
A1(+)
21
24
A2(-)
combined TEST/RESET-button
short-time pressing (<1s) =RESET
long-time pressing (>2s) = TEST
operator buttons
Isolatio
M+
KE
M-
<LT LT>
<PT PT>
RS485
k
50
30 10
100
200
500
1000
-1,5
external test
button, if required
external
k-measuring
instrument
(analog 0...400 A)
11
3. Connection
3.1.2
IRDH365
11
US
(see nameplate)
+/
fuse 6 A
(recommendation)
A1(+)
14
21
A2(-)
24
combined TEST/RESET-button
short-time pressing (<1s) = RESET
long-time pressing (>2s) = TEST
A-ISOMETER
Serie 360
1 ALARM
TEST
RESET
k
MONITOR
operator buttons
Isolation
KE
M+
M-
k
50
30 10
<LT
LT>
<PT
PT>
RS485
100
200
500
1000
-1,5
external k-measuring
instrument
(analog 0...400 A)
12
3. Connection
Wiring
The supply voltage input is to be protected against short-circuit by protective devices
in accordance with IEC 60364-4-473 (a 6 A fuse is recommended).
For the measuring connection of the insulation monitoring device to the system, it is
not necessary, according to IEC 60364-4-473, to use protective devices as protection
against short-circuit provided that the wire or cable is realized in a way which restricts
the risk of a short-circuit to a minimum. In this case, a short-circuit proof and earthfault proof wiring is recommended.
If required, the enclosed terminal covers (only for IRDH265) for protection against
direct contact can be used.
The terminals of the test and reset buttons of several insulation monitoring devices
must not be connected in parallel for a group test.
13
3. Connection
3.2
3.2.1
3.2.2
3 AC - System
3N AC - System
UN
L1
L2
L1
L2
L3
N
L1
L2
L3
L3
3.2.3
L1
L2
3.2.4
DC - System
AC - System
(L/+)
(L/-)
L1
L+
L2
L-
(L/+)
(L/-)
14
L3
3. Connection
3.3
AK160
Ankopplungsgert
Typ AGH150W-4
AK
Achtung Hochspannung
Danger High Voltage
AGH150W-4
Un
DC 0...1760 V
L+
L-
3.3.2
3.3.3
AK
Un AC 0...7200 V
AK80 Un AC 0...1650 V
L1
L2
AGH520S
2
Achtung Hochspannung
Danger High Voltage
Ankopplungsgert
Typ AGH520S
AGH204S-4
AK
U3
V3
W3
Un
L1
L2
L3
15
3. Connection
3.4
The maximum DC voltage is the voltage which may appear in the AC part of the system to
ground (PE/GND), if the IRDH265 and/or IRDH365 is coupled with AGH204S-4.
This voltage is dependent on the level of the nominal voltage, the type of rectification (6
pulse, 12 pulse, etc.), the type of inverter intermediate circuit (current or voltage) and the
inverter technology. In the case of inverters with voltage intermediate circuits it usually
corresponds to the phase to phase voltage of the AC system multiplied by 2.
In the case of current-controlled intermediate circuits there may be higher DC voltages.
The given voltage values for AC/DC systems take into account values found by previous
experience (factor 2 between DC voltage and AC voltage).
The maximum DC voltage in the case of insulation failures in the DC part of the system
e.g. inverter intermediate circuit is DC 1840 V. From this, the maximum nominal AC
voltage is calculated:
Umax = DC 1840 V / 2 = AC 1300 V
16
8
7
fault location
"R"
= AC insulation fault
"R+" = DC insulation fault at L+
"R-"
= DC insulation fault at L"Rs" = new measuring value is being calculated
(measuring cycle active)
Measuring value
6, 7, 8
function keys
TEST/RESET button
10
A-ISOMETER
Serie 360
1 ALARM
TEST
RESET
MONITOR
fault location
"R"
= AC insulation fault
"R+" = DC insulation fault at L+
"R-"
= DC insulation fault at L"Rs" = a new measuring value is being calculated
(measuring cycle active)
Mewert
6, 7, 8
function keys
TEST/RESET button
10
alarmLEDs Alarm1/Alarm 2
18
Function Keys
Use these keys to change a parameter or to select the next
setting.
Use this key to activate the next menu or to save the
parameter modification.
TEST
RESET
4.3
After commissioning, the actual measuring value and one response value will be
displayed. The second response value is displayed by pressing the
keys.
Call up the Setup1 menu by pressing the
key.
19
AL2=040k
SETUP1[Y/N]
R= 150k
SETUP1[Y/N]
R= 150k
AL1=180k
SETUP1
4.4
PASSWORD: X X
ALARM1=990k
ALARM2=10k
ALARM2=990k
K1: 12 11 - 14
K1: 12 - 11 14
K2: 22 21 - 24
K2: 22 - 21 24
SETUP2[Y/N]
SETUP2[Y/N]
AL1=180k
20
R= 150k
SETUP2
ALARM1=10k
Password [PASSWORD: XX ]
The password query cannot be carried out unless the function in the Setup2
menu has been set to ON position. The password consists of two letters (e.g.
key. After pressing the
AB). The flashing letter can be changed using the
key, the second letter will flash and can also be changed. The password entry can
be quitted by pressing the key.
If a wrong password is used, the IRDH265/365 returns to the display of the
measuring values.
4.4.2
Use the
keys for setting the response values 1 and 2 and by the
for saving the response values.
4.4.3
key
The hyphen between the contact designations indicates which contacts are
closed in no-alarm condition.
Normally Deenergized Mode:
"12 - 11 14",
Normally Energized Mode (FAILSAFE)
"12 11 - 14".
Please note: Same set-up applies for Alarm Relay #2 [22 - 21 24]
4.4.4
ALARM1: AC OR DC
ALARM1: ONLY AC
ALARM1: ONLY DC
ALARM1: ONLY DC+
ALARM1: ONLY DC-
ALARM2: AC OR DC
ALARM2: ONLY AC
AGH: AK...AK80
AGH: AK...AK160
COUPLING TEST : ON
FLASH:
FLASH:
(-3.., -4..)
(-4..)
*)
ALARM1: SYST-TEST
K2
FLASH:
K1/K2
K1
FLASH:
RELAYTEST: OFF
TIME DELAY: ON
TIME: t = 1s
TIME: t = 10s
CE MAX: 150F
CE MAX: 500F
PASSWORD: OFF
PASSWORD: ON
NEW WORD: XX
RESET [Y/N] N
RESET [Y/N] Y
SETUP3[Y/N]
(-3.., -4..)
(-4..)
(-3.., -4..)
RELAYTEST: ON
OFF
SETUP3[Y/N]
SOFTWARE V XXXX
AL1=180k
22
R= 150k
SETUP3
4.5.1
Use this menu to specify which types of insulation faults are to be signalled.
The following indications are possible:
AC OR DC
ONLY AC
ONLY DC
ONLY DC+
ONLY DC-
SYST
23
ALARM 1
ALARM2
AC OR DC
AC OR DC
AC OR DC
AC OR DC
ONLY AC
ONLY AC
ONLY DC
ONLY DC
ONLY DC+
ONLY DCSYST
AC OR DC
ONLY DC
ONLY AC
SYST
AC OR DC
ONLY DC
AC OR DC
ONLY AC
ONLY DCONLY DC+
AC OR DC
24
*)
*)
[AGH: AK...AK160]
When the terminal AK of IRDH265 and/or IRDH365 is connected to the
terminal AK 160 of AGH204S-4, the operating range of the nominal voltage will
be extended to 3AC 0 ... . 1300 V. Power converters with DC 0...1840 V may
be connected to the system.
or
If the terminal AK of IRDH265 and/or IRDH365 is connceted to the terminal
AK 160 of AGH150W-5, the operating range of the nominal voltage will be
extended to DC 0 ... 1760 V.
25
The alarm relays K1/K2 and the associated alarm LEDs can be set to flashing
function (pulse frequency 1 Hz).
Flash OFF
Flash K1
Flash K2
Flash K1/K2
4.5.5
=
=
=
=
In this menu, the operation of the alarm relays can be switched off during
functional tests (= Relay test : OFF).
4.5.6
Use this menu to activate the time delay for the alarm relays. Before
activating the time delay, the IRDH265/365 must be set to the
asymmetry measuring principle (UG/AMP AMP/UG) or
superimposed DC measuring voltage. The time delay only has an
effect on the alarm steps according to this measuring principle and
adds to the measuring time.
26
After activating the time delay, the adequate time can be set.
4.5.8
Use this menu to activate a password query. This protects against unauthorized
modifications and settings.
4.5.10 Entering the Password [ NEW WORD : XX ]
Use this menu to enter a new password (see also 4.4.1).The password will only be
stored after the password query has been confirmed. Please remember to write
down your new password and save it for future reference.
4.5.11 RESET for Basic Setting [ RESET [Y/N] N ]
Use this menu to reset to the manufacturer`s basic settings. All user
modifications will be erased.
Warning
Description
Number
N/E mode
N/D mode
N/E mode
N/D mode
AC or DC
ONLY AC
System test
AC or DC
ONLY AC
System test
Connection monitoring
OFF
ON
OFF
ON
OFF
ON
Time delay
OFF
ON
OFF
10*
11*
500 F
12
Measuring principle
AMP
ON
150 F
500 F
150 F
AMP/UG
UG/AMP
DC
MESSP: AMP
MESSP: DC
Ian = 5,0 mA
Ian = 0,1 mA
MESSP: AMP/UG
MESSP: UG/AMP
AL1=180k R=150k
4.6.2
In this menu, the alarm current level for the DC fast response can be set. The set
value of the current is the DC current IFDC which in case of single-pole insulation
fault flows via the internal resistance of the IRDH265/365 driven by the system
voltage. The respective values for the insulation resistance in AC systems in case
of insulation faults behind directly connected rectifiers are shown in the diagram
given below.
IF DC (mA)
and -R4..
3
UN AC 690 V
UN AC 500 V
UN AC 400 V
1
0,8
0,6
UN DC 220 V
0,4
UN DC 110 V
0,2
0
RF DC (k)
0
20
40
60
80
100
31
3AC 400 V
4
3,5
3
2,5
AC 230 V
DC 220 V
1,5
DC 110 V
AC 120 V
DC 60 V
0,5
0
RF DC (k)
0
32
10
15
20
25
30
5. Interface
Serial Interface
Transmission protocol
9600 Baud - 1 Starbit - 1 Stopbit - 8 Databits
US
US
02H 0FH 30H 30H 30H 31H 32H 38H 0FH 30H 30H 30H 30H 36H 30H 0FH
response value
Alarm 1 z.B. 60 k
measuring value
z.B. 128 k
US
US
US
US
End
LF
CR
30H 30H 30H 31H 32H 30H 0FH 30H 0FH 30H 0FH 30H 0FH 03H 10H 13H
30H = no Alarm
31H = Alarm 1
32H = Alarm 2
33H = Alarm 1/2
response value
Alarm 2 z.B. 120 k
30H = K1 off, K2 off
31H = K1 on, K2 off
32H = K1 off, K2 on
33H = K1 on, K2 on
30H = AC fault
31H = DC- fault
32H = DC+ fault
000128000060000120000
measuring value
128 K
Alarm 1
60 K
Alarm 2
120 K
AC Fault
no Alarm
K1, K2 off
33
6. Technical Data
Insulation coordination acc. to IEC 60664-1
Rated insulation voltage
Rated impulse withstand voltage/contamination level
Dielelectric test acc. to IEC 60255-5
Operation class
AC 800 V
8 kV / 3
3 kV
continuous operation
3AC 0...793 V
50...400 Hz
DC 0...650 V
Supply voltage
Supply voltage US (for IRDH265/365-...13) see ordering guide
Supply voltage US (for IRDH265/365-...21) see ordering guide
Operating range (for AC supply)
Max. power consumption
AC 120 V
DC 10.5 ... 80 V
0.8...1.15 US
6 VA
Response values
Response value RALARM1/ALARM2
10 ... 990 k
Hysteresis
ca. 25%
Response time (CE=1F)
8 s see characteristic curves
Response value asymmetry measuring principle
0.1 ... 5 mA
Response time asymmetry measuring principle
(in case of direct earth fault, 0k, 0...150F)
<1s
Time delay, adjustable for asymmetry measuring principle
and superimposition of a DC measuring voltage
1 ... 10 s
System leakage capacitance
max. 500 F
Pre-set by factory
150 F
Measuring circuit
Measuring voltage UM (peak value)
Measuring current IM
Internal DC resistance Ri acc. to IEC 61557-8
Impedance Zi, 50 Hz IEC 61557-8
34
27 V
max. 230 A
120 k
> 250 k
6. Technical Data
-3.. -R3..
-499
-R4.. -4921
-7..
-8..
0...506 V
0...793 V
0...793 V
0...793 V
0...793 V
0...286 V
0...650 V
0...650 V
0...750 V
0...780 V
2...200 k
10...990 k
10...990 k
0.2...10 M
0.5...20 M
0.1...10 mA
0.1...5 mA
0.1...5 mA
1...10 s
500 F
500 F
1...10 s
500 F
150 F
1...10 s
500 F
150 F
2 F
2 F
2 F
2 F
1 mA
28 k
230 A
120 k
230 A
120 k
10 A
2.8 M
5 A
5.6 M
35
6. Technical Data
Outputs
Measuring instrument SKMP
Current output (max. load)
Display range
Display accuracy (10K...990K)
Terminal AK for coupling device
Contact circuit
Switching components
Contact class
Rated contact voltage
Admissible number of operations
Making capacity
Breaking capacity
AC 230 V, cos phi = 0.4
DC 220 V, L/R = 0.04s
Operating principle, Selectable
Pre-set by factory
standard
120 k
400 A (12.5 k)
< 1 k ... > 5 M
+/-20%
yes
2 voltage free change-over contacts
IIB acc. to DIN IEC 60255 Teil 0-20
AC 250 V / DC 300 V
12000 cycles
UC 5 A
AC 2 A
DC 0.2 A
N/D or N/E (failsafe) Mode
(N/D Mode) Normally Deenergized Mode
Type tests
Test of the Electromagnetic Compatibility (EMC)
Immunity against electromagnetic interferences EN 50082-2
Emissions acc. to EN 50081:
Emissions acc. to EN 55011/CISPR11
class A 2)
Mechanical test
Shock resistance acc. to IEC 6068-2-27
15 g / 11 ms
Bumping acc. to IEC 6068-2-29
40 g / 6 ms
Vibration strength acc. to IEC 6068-2-6
10...150 Hz / 0.15 mm - 2 g
Environmental conditions
Ambient temperature, during operation
Storage temperature range
Climatic class acc. to IEC 60721
36
6. Technical Data
-3.. -R3..
28 k
-499
120 k
-R4.. -4921
120 k
-7..
2.8 M
-8..
5.6 M
<1k...>500k
<1k...>5M
<1k...>5M
<0.2M...>20M
<0.5M...>30M
N/D mode
N/D mode
N/D mode
N/E mode
N/D mode
37
6. Technical Data
General
Mounting
Connection
Cross sectional area of connecting cable
single wire
flexible
DIN rail mounting IRDH265
Screw mounting IRDH265
Protection class acc. to DIN EN 60529
Built-in components
Terminals
Type of enclosure
IRDH265
IRDH365
Flammability class
XM112
X300
Weight approx.
IRDH265
IRDH365
any position
screw terminals
0.2 ... 4 mm2
0.2 ... 2.5 mm2
acc. to DIN EN 50 022
mounting plate Art. No. 990 056
IP 30
IP 20
X M112
X300
UL94V-0
UL94V-1
825 g
1075 g
2)
Class A devices are designed for industrial use. For any other use, it may be
necessary to take additional measures for interference suppression.
38
6. Technical Data
6.1
Standards
IND.CONT.EQ., 12PA
39
7. Characteristic Curves
7.1.1
RF = 0...10 k
10
CE (F)
1
1
10
100
150
Setting CE = 500 F
t (s)
10000
RF = 1 M
RF = 100 k
1000
RF = 0...10 k
100
10
1
1
40
CE (F)
10
100
500
7. Characteristic Curves
7.1.2
100
RF = 0 k
10
CE (F)
1
1
10
100
500
41
7. Characteristic Curves
7.1.3
RF=10M
140.00
RF=5M
120.00
100.00
80.00
60.00
RF=1M
40.00
RF<0.2M
20.00
0.00
0
7.1.4
0.5
1.5
2
CE(F)
RF= 20 M
300.00
250.00
RF= 5 M
200.00
150.00
100.00
RF= 1 M
RF= 0.5 M
50.00
0.00
0
42
0.5
1.5
2
CE(F)
7. Characteristic Curves
7.2
1000
IRDH1065B-4
100
10
1
0,1
Hz
1
10
100
100
10
1
0,1
Hz
1
10
100
43
8. Dimension Diagrams
Dimension Diagram IRDH365
72
2...10
144
13
133
81
74
5
10
For screw mounting, a mounting plate, Art.-Nr. 990056, is available. The device type IRDH265-4921 has
to be mounted by screws according to DIN EN 50155 / VDE 0115 T.200.
44
9. Ordering Details
Standard Type
Supply voltage US
Art. No.
AC 230 V
B 9106 8001
IRDH265-413
AC 90...132 V*
B 9106 8004
IRDH265-415
AC 400 V
B 9106 8017
IRDH265-416
AC 500 V
B 9106 8009
IRDH265-422
DC 19.2 ... 84 V*
B 9106 8002
IRDH265-423
DC 77 ... 286 V*
B 9106 8003
AC 230 V
B 9106 8006
IRDH365-413
AC 90...132 V*
B 9106 8011
IRDH365-415
AC 400 V
B 9106 8012
IRDH365-416
AC 500 V
B 9106 8025
Type
IRDH265-4
IRDH365-4
45
9. Ordering Details
Options
Type
Supply voltage US
Art. No.
IRDH265-3
IRDH265-311
IRDH265-313
IRDH265-322
IRDH265-323
AC 230 V
AC 24 V
AC 90...132 V*
DC 19.2...84 V*
DC 77 ... 286 V*
B 9106 8008
B 9106 8035
B 9106 8024
B 9106 6005
B 9106 8019
IRDH265-R313
IRDH265-R321
AC 90...132 V*
DC 10.5...80 V*
B 9106 6004
B 9106 6001
IRDH265-R413
IRDH265-R421
AC 90...132 V*
DC 10.5 ... 80 V*
B 9106 8022
B 9106 8062
IRDH265-4921
IRDH265-499
DC 10.5...80 V*
DC 77...130 V*
B 9106 8023
B 9106 8032
IRDH265-7
IRDH265-722
AC 230 V
DC 19.2...84 V*
B 9106 8034
B 9106 8026
IRDH265-8
IRDH265-822
AC 230 V
DC 19.2...84 V*
B 9106 9003
B 9106 9001
IRDH365-3
IRDH365-313
IRDH365-315
IRDH365-322
AC 230 V
AC 90...132 V*
AC 400 V
DC 19.2...84 V*
B 9106 8013
B 9106 8020
B 9106 8016
B 9106 8018
IRDH365-422
IRDH365-423
DC 19.2...84 V*
DC 77 ... 286 V*
B 9106 8014
B 9106 8021
AC 230 V
B 9106 9004
IRDH365-8
9. Ordering Details
Coupling Devices
Type
Nominal
voltage range Un
Art. No.
AGH204S-4
AGH520S
AGH150W-4
AC 0 ... 1650 V
AC 0 ... 7200 V
DC 0 ... 1760 V
B 914 013
B 913 033
B 98 018 006
Dimensions
Art. No.
7204-1421
9604-1421
72x72 mm
96x96 mm
B 986 763
B 986 764
7204S-1421
9604S-1421
72x72 mm
96x96 mm
B 986 804
B 986 784
Dimensions
Art. No.
7204-1311
9604-1311
7204S-1311
9604S-1311
72x72 mm
96x96 mm
72x72 mm
96x96 mm
B 986 755
B 986 753
B 986 705
B 986 779
The measuring instruments 7204S and 9604S are shock and vibration
resistant.
47
BENDER INC.
700 Fox Chase
Coatsville, PA 19320
Tel: 610-383-9200
Toll-free: 800-356-4266
Fax: 610-383-7100
Edition: 12/99
Right to modifications reserved
48