SE DUARTINA
06/07/14
REV.
DATA
EMISSO INICIAL
NATUREZA DA REVISO
ECC
ECC
ELAB.
APROV.
SUMRIO
1. INTRODUO ................................................................................................................... 3
2. DADOS GERAIS ................................................................................................................ 3
2.1. DADOS DAS LINHAS DE TRANSMISSO ...................................................................... 3
2.2. DADOS DOS TCS E TPS ............................................................................................. 3
2.3. REL UTILIZADO........................................................................................................ 5
3. VALORES DE CURTOS-CIRCUITOS UTILIZADOS ................................................................. 5
3.1. VALORES DE CONTRIBUIO VISTO PELO REL DO BAY DA LT CITROSUCO ................ 5
3.2. VALORES DE CONTRIBUIO NOS PRIMRIOS DOS TRANSFORMADORES DA SE
DUARTINA (138/34,5 Kv) E DA SE CITROSUCO (34,5/13,8 kV)............................................ 5
4. SYSTEM DATA .................................................................................................................. 6
5. CB CONTROL .................................................................................................................... 7
6. CONFIGURATION ............................................................................................................. 8
7. CT AND VT RATIO ............................................................................................................ 9
8. MEASURE'T SETUP ......................................................................................................... 10
9. CRITRIOS DE AJUSTE DAS FUNES DE PROTEO ...................................................... 11
9.1. LINE PARAMETERS ................................................................................................... 11
9.2. DISTANCE SETUP ..................................................................................................... 12
9.3. DISTANCE ELEMENTS .............................................................................................. 14
9.4. SCHEME LOGIC ........................................................................................................ 17
9.5. OVERCURRENT ........................................................................................................ 19
9.6. EARTH FAULT .......................................................................................................... 21
9.7. AIDED DEF .............................................................................................................. 23
9.8. SEF/REF PROTN ...................................................................................................... 23
9.9. CB FAIL & I< & P.DEAD............................................................................................ 25
9.10. SUPERVISION ........................................................................................................ 26
9.11. AUTORECLOSE ....................................................................................................... 27
10. CURTOS-CIRCUITOS UTILIZADOS NESTE ESTUDO DE PROTEO .................................. 29
Pgina 2 de 36
1. INTRODUO
Este estudo de seletividade tem como objetivo definir os critrios de ajustes para todos os
parmetros que sero utilizados no rel, proteo principal, que ser instalado no terminal da SE
Duartina da LT 34,5 kV Duartina - Citrosuco C1/C2.
Sero definidos por este documento os ajustes relativos s funes de distncia de fase e neutro
(21P/21N), de sobrecorrente direcional de neutro instantnea (67NI), de sobrecorrente direcional
de neutro temporizada (67NT), de sobrecorrente direcional de fase temporizada (67T), de falha
de disjuntor (50BF) e de religamento (79).
Primeiramente sero apresentados todos os dados gerais do sistema (como impedncia de
sequncia positiva e zero da linha, os dados e as relaes de TCS e TPS utilizadas e o modelo
do rel adotado). Aps, sero definidos os valores de curtos-circuitos utilizados neste estudo. Em
seguida sero definidos os critrios de ajustes para cada funo de proteo.
2. DADOS GERAIS
Pgina 3 de 36
Pgina 4 de 36
Tipo
Z (
SEC)
Corrente IA (APRIM)
0.05
3883
0.05
4061
4061
1.41
2376
1.41
1562
1562
3.76
1406
3.76
756
756
4.65
1216
4.65
632
632
4.70
1208
4.70
626
626
10.92
639
15.86
446
Pgina 5 de 36
Local do
Curto-Circuito
SE Duartina
Barra 34.5 kV
Sada
LT Duartina
Citrosuco C1/C2
30% da LT
Duartina
Citrosuco C1/C2
80% da LT
Duartina
Citrosuco C1/C2
Fim da LT
Duartina
Citrosuco C1/C2
Barra 34.5 kV da
SE Citrosuco
Barra de 13.8 kV
da SE Citrosuco
Tipo
Corrente IA/3 I0
(APRIM) do lado
de alta do TR
138/34,5 kV da
SE Duartina
Corrente IA
(APRIM) no
local do
defeito
Corrente IA/3I0
(APRIM) do lado de
alta do TR
34,5/13,8 kV da SE
Citrosuco
992/0
3967
620/0
4295
971/0
3883
586/0
4061
594/0
2376
225/0
1562
352/0
1406
109/0
756
304/0
1216
91/0
632
302/0
1208
90/0
626
160/0
1596
639/0
64/0
1931
446/0
4. SYSTEM DATA
Neste mdulo sero apresentados os ajustes gerais referentes a esta unidade de proteo, os
quais esto descritos abaixo.
Endereo 00.01 - (Language) Define a linguagem usada para este rel.
Ajuste: English
Endereo 00.03 - (Sys Fn Links) Define o ajuste que permitir o led da funo de trip seja
reiniciado.
Ajuste: 0
Endereo 00.04 - (Description) Descrio que se deseja para o rel.
Ajuste: SE DUA P443 21PP
Endereo 00.05 - (Plant Reference) Descrio do local de instalao para o rel.
Ajuste: LT CITROSUCO C1/C2
Endereo 00.09 - (Frequency) Define a frequencia em que o rel ir trabalhar.
Ajuste: 60 Hz
Resumo dos ajustes deste grupo
Endereo
00.01
00.03
00.04
Funo
Language
Sys Fn Links
Description
Ajuste
English
0
SE DUA P443 21PP
Pgina 6 de 36
00.05
00.09
Plant Reference
Frequency
LT CITROSUCO C1/C2
60 Hz
5. CB CONTROL
Neste mdulo sero apresentados os ajustes referentes ao controle do disjuntor deste bay.
Endereo 07.01 - (CB Control by) Este ajuste define se haver comando do disjuntor.
Considerou-se que haver comando do disjuntor.
Ajuste: Opto + local
Endereo 07.02 - (Close Pulse Time) Este ajuste define o pulso de fechamento do disjuntor.
Para esta aplicao este pulso ser utilizado para o fechamento do disjuntor do bay e ser de
500 ms.
Ajuste: 500.0 ms
Endereo 07.03 - (Trip Pulse Time) Este ajuste define o pulso de comando de trip. Para este
ajuste o mnimo comando de trip ser de 100 ms.
Ajuste: 500.0 ms
Endereo 07.05 - (Man Close Delay) Este ajuste define o tempo em que o rel reconhece que
houve uma falha no comando de fechamento do disjuntor. Deve ser maior que o tempo mximo
permitido para verificao de sincronismo, portanto ser mantido o ajuste 10 segundos.
Ajuste: 10.00 s
Endereo 07.06 - (CB Healthy Time) Este ajuste define o tempo em que o disjuntor deve indicar
uma condio saudvel para realizao do fechamento.
Ajuste: 5.000 s
Endereo 07.07 - (Check Sync Time) Este ajuste define o tempo mximo para verificao de
sincronismo durante fechamento manual.
Ajuste: 5.000 s
Endereo 07.09 - (Reset Lockout by) Define como ser realizado o reset do sinal de lockout.
Ajuste: CB Close
Endereo 07.0A - (Man Close RstDly) Este ajuste define o tempo que deve ser transcorrido
aps o comando de fechamento do disjuntor para que possa ocorrer o reset do sinal de lockout
automaticamente.
Ajuste: 5.000 s
Endereo 07.0C - (Single Pole A/R) Este ajuste define se o religamento monopolar ser
habilitado.
Ajuste: Disabled
Endereo 07.0D - (Three Pole A/R) Este ajuste define se o religamento tripolar ser habilitado.
Ajuste: Enabled
Endereo 07.11 - (CB Status Input) Este ajuste define como sero aquisitado os contatos
auxiliares do disjuntor.
Ajuste: 52A 1 pole
Endereo 07.7F - (CB Status Time) Este ajuste define o tempo no qual haver a transio de
posio fechado/aberto ou aberto/fechado. Caso ocorra um problema nos contatos auxiliares do
disjuntor aps o tempo ajustado neste parmetro, o rel gerar um alarme informando que h
algum problema nos contatos auxiliares do mesmo.
Ajuste: 5.000 s
Pgina 7 de 36
Ajuste
Opto + local
500.0 ms
500.0 ms
10.00 s
5.000 s
5.000 s
CB Close
5.000 s
Disabled
Enabled
52A 1 pole
5.000 s
6. CONFIGURATION
Neste mdulo sero apresentadas as funes de proteo que sero utilizadas, habilitando-as ou
no, ou visualizando-as ou no. Para esta aplicao, sero habilitadas as funes de distncia de
fase e neutro, de sobrecorrente direcional de fase e neutro, de falha de disjuntor e de
religamento. As funes de proteo habilitadas na tabela abaixo, sero detalhadas
posteriormente.
Resumo dos ajustes deste grupo
Endereo
Funo
09.02
Setting Group
09.03
Active Settings
09.07
Setting Group 1
09.08
Setting Group 2
09.09
Setting Group 3
09.0A
Setting Group 4
09.0B
Distance
09.0C
Directional E/F
09.10
Overcurrent
09.11
Neg Sequence O/C
09.12
Broken Conductor
09.13
Earth Fault
09.15
SEF/REF Prot'n
09.16
Residual O/V NVD
09.17
Thermal Overload
09.18
PowerSwing Block
09.1D
Volt Protection
09.1E
Freq Protection
09.1F
df/dt Protection
09.20
CB Fail
09.21
Supervision
09.23
System Checks
09.24
Auto-Reclose
09.25
Input Labels
09.26
Output Labels
09.28
CT & VT Ratios
09.29
Record Control
09.2A
Disturb Recorder
09.2B
Measure't Setup
09.2C
Comms Settings
09.2D
Commission Tests
09.2E
Setting Values
09.2F
Control Inputs
Pgina 8 de 36
Ajuste
Select via Menu
Group 1
Enabled
Disabled
Disabled
Disabled
Enabled
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Enabled
Enabled
Disabled
Enabled
Visible
Visible
Visible
Visible
Visible
Visible
Visible
Visible
Secondary
Visible
09.35
09.36
09.39
09.41
09.50
09.FF
Visible
Visible
Enabled
Disabled
Visible
11
7. CT AND VT RATIO
Neste captulo sero apresentados os ajustes de proteo relacionados aos transformadores de
corrente e potencial para esta LT.
Endereo 0A.01 - (Main VT Primary) Este parmetro define a tenso primria do transformador
de potencial.
Ajuste: 34.50 kV
Endereo 0A.02 - (Main VT Sec'y) Este parmetro define a tenso secundria do transformador
de potencial.
Ajuste: 115.0 V
Endereo 0A.03 - (CS VT Primary) Este parmetro define a tenso de sincronismo primria do
transformador de potencial.
Ajuste: 19.92 kV
Endereo 0A.04 - (CS VT Secondary) Este parmetro define a tenso de sincronismo secundria
do transformador de potencial.
Ajuste: 115.0 V
Endereo 0A.07 - (Phase CT Primary) Este parmetro define a corrente primria do
transformador de corrente.
Ajuste: 600.0 A
Endereo 0A.08 - (Phase CT Sec'y) Este parmetro define a corrente secundria do
transformador de corrente.
Ajuste: 5.000 A
Endereo 0A.0B - (SEF CT Primary) Este parmetro define a corrente primria do transformador
de corrente sensvel.
Ajuste: 600.0 A
Endereo 0A.0C - (SEF CT Secondary) Este parmetro define a corrente secundria do
transformador de corrente sensvel.
Ajuste: 5.000 A
Endereo 0A.0D - (MComp CT Primary) Este parmetro define a corrente primria do
transformador de corrente para compensao da impedncia mtua.
Ajuste: 600.0 A
Endereo 0A.0E - (MComp CT Sec'y) Este parmetro define a corrente secundria do
transformador de corrente para compensao da impedncia mtua.
Ajuste: 5.000 A
Endereo 0A.0F - (CS Input) Este ajuste define a tenso da barra que ser utilizada para a
realizao da funo 25.
Ajuste: A-N (fase do meio)
Endereo 0A.10 - (Main VT Location) Este parmetro define a posio do TP nesta aplicao.
Ajuste: Bus
Pgina 9 de 36
Endereo 0A.11 - (CT Polarity) Este parmetro define como o transformador de corrente ser
ligado. Para o ajuste "Standard" a corrente para uma falta na linha entra no rel. Para a posio
"Inverted", uma falta na linha a corrente sai do rel.
Ajuste: Standard
Endereo 0A.13 - (SEF CT Polarity) Este parmetro define como o transformador de corrente
para entrada sensitiva ser ligado. Para o ajuste "Standard" a corrente para uma falta na linha
entra no rel, ao contrrio a posio "Inverted" para uma falta na linha a corrente sai do rel.
Ajuste: Standard
Endereo 0A.14 - (M CT Polarity) Este parmetro define como o transformador de corrente
para entrada da corrente de compensao da mtua ser ligado. Para o ajuste "Standard" a
corrente para uma falta na linha entra no rel, ao contrrio a posio "Inverted" para uma falta
na linha a corrente sai do rel.
Ajuste: Standard
Resumo dos ajustes deste grupo
Endereo
Funo
0A.01
Main VT Primary
0A.02
Main VT Sec'y
0A.03
CS VT Primary
0A.04
CS VT Secondary
0A.07
Phase CT Primary
0A.08
Phase CT Sec'y
0A.0B
SEF CT Primary
0A.0C
SEF CT Secondary
0A.0D
MComp CT Primary
0A.0E
MComp CT Sec'y
0A.0F
CS Input
0A.10
Main VT Location
0A.11
CT Polarity
0A.13
SEF CT Polarity
0A.14
M CT Polarity
Ajuste
34.50 kV
115.0 V
19.92 kV
115.0 V
600.0 A
5.000 A
600.0 A
5.000 A
600.0 A
5.000 A
A-N
Bus
Standard
Standard
Standard
8. MEASURE'T SETUP
Neste mdulo ser ajustado somente o parmetro referente unidade de distncia, ajuste 0D.09,
a qual para esta aplicao ser em quilmetros.
Endereo 0D.01 - (Default Display) Essa configurao pode ser usada para selecionar a exibio
de medio padro desejada, de uma srie de opes disponveis.
Ajuste: Description
Endereo 0D.02 - (Local Values) Define se os valores medidos atravs da porta dianteira e
mostrados no painel frontal so valores primrios ou secundrios.
Ajuste: Primary
Endereo 0D.03 - (Remote Values) Define se os valores medidos remotamente, atravs da
porta de comunicao traseira so amostrados como valores primrios ou secundrios.
Ajuste: Primary
Endereo 0D.04 - (Measurement Ref) Define a referncia de fase a medio angular.
Ajuste: VA
Endereo 0D.05 - (Measurement Mode) Este ajuste usado para controlar a medio de
quantidade de potncia ativa e reativa.
Ajuste: 0
Endereo 0D.06 - (Fix Dem Period) Define o tempo da janela para a medio da demanda.
Ajuste: 30.00 min
Pgina 10 de 36
Endereo 0D.07 - (Roll Sub Period) Define o tempo usado para o clculo do valor da demanda.
Ajuste: 30.00 min
Endereo 0D.08 - (Num Sub Periods) Este ajuste usado na resoluo da captura para o clculo
do valor da demanda.
Ajuste: 1
Endereo 0D.09 - (Distance Unit) Ajuste utilizado para definir a unidade de distncia na
localizao de faltas.
Ajuste: Kilometres
Endereo 0D.0A - (Fault Location) Quando o ajuste da localizao de faltas acionado, este
parmetro define se o valor ser em distncia ou em porcentagem da linha.
Ajuste: Distance
Resumo dos ajustes deste grupo
Endereo
Funo
0D.01
Default Display
0D.02
Local Values
0D.03
Remote Values
0D.04
Measurement Ref
0D.05
Measurement Mode
0D.06
Fix Dem Period
0D.07
Roll Sub Period
0D.08
Num Sub Periods
0D.09
Distance Unit
0D.0A
Fault Location
Ajuste
Description
Primary
Primary
VA
0
30.00 min
30.00 min
1
Kilometres
Distance
Endereo 30.07 - (Mutual Comp) Este ajuste define se a compensao para a impedncia mtua
ser habilitada. Para que este ajuste seja habilitado necessrio aquisitar a corrente de sequncia
zero da linha paralela.
Ajuste: Disabled
Endereo 30.0B - (Phase Sequence) Este ajuste define a sequncia de fase deste sistema.
Ajuste: Standard ABC
Endereo 30.0C - (Tripping Mode) Este ajuste define como ser o comando de trip desta
unidade de proteo.
Ajuste: 3 Pole
Endereo 30.10 - (Line Charging Y) Este ajuste define a susceptncia da linha, a qual utilizada
na funo de sobretenso para calcular a tenso de sequncia positiva da linha utilizando a
corrente, a tenso de sequncia positiva do terminal local, a impedncia e a susceptncia da
linha. Esta proteo de sobretenso pode ser utilizada para linhas longas, quando a mesma opera
com o terminal remoto aberto.
Ajuste: 0 S
Resumo dos ajustes deste grupo
Endereo
Funo
30.01
Line Length
30.03
Line Impedance
30.04
Line Angle
30.05
kZN Res Comp
30.06
kZN Res Angle
30.07
Mutual Comp
30.0B
Phase Sequence
30.0C
Tripping Mode
30.10
Line Charging Y
Ajuste
27.85 km
23.50/In
= 4.700 Ohm
63.20 deg
1.360
20.95 deg
Disabled
Standard ABC
3 Pole
0S
Pgina 12 de 36
"Standard Filter". Isto garante que o rel P443 opera com um tempo abaixo de um ciclo "subcycle tripping". Por outro lado, em aplicaes onde a corrente e tenso so extremamente
distorcidas devido a HVDC, compensao srie este ajuste pode ser configurado como "Special
Applics". Porm, nestas condies um nmero maior de amostras requerido para garantir a
estabilidade do rel nestas condies, entretanto isto acarreta um atraso maior no comando de
trip em torno de 1/4 de ciclo. Para esta aplicao ser utilizado os filtros convencionais.
Ajuste: Standard
Endereo 31.D1 - (CVT Filters) Este ajuste define o tipo de transformador de potencial que est
sendo utilizado nesta aplicao. Este parmetro pode ser ajustado de trs maneiras: "disable",
"passive" ou "active". Para transformadores de potencial que no possuem nenhum filtro para
eliminar efeitos de ferroressonncia este ajuste deve ser configurado como "disable". Por outro
lado, caso o transformador de potencial possuir um filtro para suprimir efeitos de ferroressonncia
passivo o ajuste deve ser configurado como "passive". Neste caso, os transitrios gerados por
estes filtros so pequenos para um valor de SIR (Source Impedance Ratio) at 30. Por outro lado,
em transformadores de potencial que possuem filtros para suprimir efeitos de ferroressonncia
ativo, neste caso os transientes de tenso no inicio de um curto-circuito so maiores, provocando
uma reduo na tenso fundamental provocando um sobrealcance na medio da impedncia
vista pelo rel. Desta forma, dependendo do valor do SIR, o rel modifica a estratgia de medio
consequentemente aumentando o tempo de trip em torno de 1/4 de ciclo.
Ajuste: Disabled
Endereo 31.D3 - (Load Blinders) Define se o bloqueio de carga "Load Blinder" ser
habilitado/desabilitado. Este ajuste deve ser habilitado, apenas se o pickup das zonas de
proteo estiver ajustado maior que a menor impedncia de carga (mximo carregamento).
Ajuste: Disabled
Endereo 31.D7 - (Dist. Polarizing) Este ajuste define a expanso da caracterstica MHO.
Entretanto, nesta aplicao est sendo utilizada a caracterstica de proteo "Quadrilateral", desta
maneira este ajuste no ser utilizado.
Ajuste: 1.000
Endereo 31.E1 - (Dir. Status) Este ajuste define se o mtodo de clculo da direcionalidade
pelo algoritmo DELTA ser habilitado/desabilitado. Com este mtodo, a direcionalidade ser
calculada comparando-se a corrente e tenso de superposio I e V no incio da falta. O delta
est presente somente no incio da falta, pois h uma variao das grandezas de corrente e
tenso comparando-as com os valores de pr-falta. Nesta aplicao o mtodo DELTA ser
habilitado.
Ajuste: Disabled
Resumo dos ajustes deste grupo
Endereo
Funo
31.0C
Setting Mode
31.11
Phase Chars.
31.20
Zone 1 Ph Status
31.30
Zone 2 Ph Status
Pgina 13 de 36
Ajuste
Advanced
Mho
Enabled
Enabled
31.40
31.42
31.50
31.60
31.71
31.80
31.90
31.A0
31.A2
31.B0
31.C0
31.D0
31.D1
31.D3
31.D7
31.E1
Zone 3 Ph Status
Zone 3 Ph Offset
Zone P Ph Status
Zone 4 Ph Status
Ground Chars.
Zone 1 Gnd Stat.
Zone 2 Gnd Stat.
Zone 3 Gnd Stat.
Zone3 Gnd Offset
Zone P Gnd Stat.
Zone 4 Gnd Stat.
Digital Filter
CVT Filters
Load Blinders
Dist. Polarizing
Dir. Status
Enabled
Disabled
Disabled
Disabled
Quad
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Standard
Disabled
Disabled
1.000
Disabled
Pgina 14 de 36
Endereo 32.28 - (Z3 Sensit. Iph>3) A corrente mnima de operao ser igual a mnima
corrente definida para a zona 1, ou seja 10% da corrente nominal do TC.
Ajuste: 500.0 mA
Endereo 32.51 - (Z1 Gnd. Reach) Este ajuste define o alcance no eixo da reatncia para a
zona 1, de falta fase-terra. Sabe-se que esta linha est inserida em um circuito no qual possui
outra linha em paralelo, portanto devem ser levados em considerao os efeitos das mtuas de
sequncia zero. Por ser uma linha radial, para esse ajuste considerar-se- 100% da impedncia
da linha.
Ajuste: 4.700 Ohm
Endereo 32.52 - (Z1 Gnd. Angle) Este ajuste define o ngulo da linha para a zona 1. Ser
considerado o prprio ngulo da linha.
Ajuste: 63.20 deg
Endereo 32.53 - (Z1 Dynamic Tilt) Define se ser habilitado Tilt dinmico para faltas terra.
Ele ser habilitado, pois dependendo das condies da falta, o rel pode alterar o valor do Tilt, o
que acarreta um melhor funcionamento do algoritmo.
Ajuste: Enabled
Endereo 32.54 - (Z1 Tilt Top Line) Ser considerado o valor 0, uma vez que o tilt est sendo
calculado de forma dinmica.
Ajuste: 0 deg
Endereo 32.55 - (kZN1 Res. Comp.) Define o valor de compensao k, para falta fase-terra
dentro da zona 1. Definiu-se o k idntico para todas as zonas de proteo e portanto igual ao
definido no endereo 30.05.
Ajuste: 1.360
Endereo 32.56 - (kZN1 Res. Angle) Define o ngulo do valor de compensao k, para falta
fase-terra dentro da zona 1. Definiu-se o ngulo de k idntico para todas as zonas de proteo e
portanto igual ao definido no endereo 30.06.
Ajuste: 20.95 deg
Endereo 32.59 - (R1 Gnd Resistive) Define o alcance resistivo de zona 1 para falta fase-terra.
Os valores j obtidos anteriormente das resistncias de carga, de arco e indicada pelo rel esto
apresentados abaixo:
Ajuste: 12.35 Ohm
Endereo 32.5B - (Z1 Sensit Ignd>1) Este ajuste define o menor valor de corrente para
sensibilizar o rel para esta funo. Este parmetro deve ser o mais sensvel possvel, de forma
que o rel possa detectar falta com baixo nvel de corrente. Um valor igual a 5% da corrente
nominal do TC (250 mA) adequado para este ajuste.
Ajuste: 250.0 mA
Endereo 32.60 - (Z2 Gnd. Reach) Este ajuste define o alcance do eixo de reatncia para zona
2 para falta fase-terra. Por ser uma linha radial, a zona 2 dever alcanar 30% da impedncia do
transformador da SE Citrosuco.
Ajuste: 5.400 Ohm
Endereo 32.61 - (Z2 Gnd. Angle) Este ajuste define o ngulo para a zona 2. Ser considerado
o ngulo da linha.
Ajuste: 63.20 deg
Endereo 32.63 - (Z2 Dynamic Tilt) Define se ser habilitado Tilt dinmico para faltas terra.
Ele ser habilitado, pois dependendo das condies da falta, o rel pode alterar o valor do Tilt, o
que acarreta um melhor funcionamento do algoritmo.
Ajuste: Enabled
Pgina 15 de 36
Endereo 32.64 - (Z2 Tilt Top Line) Ser considerado o valor 0, uma vez que o tilt est sendo
calculado de forma dinmica.
Ajuste: 0 deg
Endereo 32.65 - (kZN2 Res. Comp.) Define o valor de compensao k, para falta fase-terra
dentro da zona 2. Definiu-se o k idntico para todas as zonas de proteo e portanto igual ao
definido no endereo 30.05.
Ajuste: 1.360
Endereo 32.66 - (kZN2 Res. Angle) Define o ngulo do valor de compensao k, para falta
fase-terra dentro da zona 2. Definiu-se o ngulo de k idntico para todas as zonas de proteo e
portanto igual ao definido no endereo 30.06.
Ajuste: 20.95 deg
Endereo 32.69 - (R2 Gnd Resistive) Define o alcance resistivo de zona 2 para falta fase-terra.
Os valores j obtidos anteriormente das resistncias de carga, de arco e indicada pelo rel esto
apresentados abaixo:
Ajuste: 17.50 Ohm
Endereo 32.6B - (Z2 Sensit Ignd>2) Este ajuste define o menor valor de corrente para
sensibilizar o rel para esta funo. Este parmetro deve ser o mais sensvel possvel, de forma
que o rel possa detectar falta com baixo nvel de corrente. Um valor igual a 5% da corrente
nominal do TC (250 mA) adequado para este ajuste.
Ajuste: 250.0 mA
Endereo 32.70 - (Z3 Gnd. Reach) Este ajuste define o alcance do eixo de reatncia para zona
3. Por ser uma linha radial, a zona 3 dever alcanar 50% da impedncia do transformador da
SE Citrosuco e no alcanar o lado de 13,8 kV do transformador da SE Citrosuco.
Ajuste: 6.850 Ohm
Endereo 32.71 - (Z3 Gnd. Angle) Este ajuste define o ngulo de inclinao para a zona 3. Ser
considerado o prprio ngulo da linha.
Ajuste: 63.20 deg
Endereo 32.73 - (Z3 Dynamic Tilt) Define se ser habilitado Tilt dinmico para faltas terra.
Ele ser habilitado, pois dependendo das condies da falta, o rel pode alterar o valor do Tilt, o
que acarreta um melhor funcionamento do algoritmo.
Ajuste: Enabled
Endereo 32.74 - (Z3 Tilt Top Line) Ser considerado o valor 0, uma vez que o tilt est sendo
calculado de forma dinmica.
Ajuste: 0 deg
Endereo 32.75 - (kZN3 Res. Comp.) Define o valor de compensao k, para falta fase-terra
dentro da zona 2. Definiu-se o k idntico para todas as zonas de proteo e portanto igual ao
definido no endereo 30.05.
Ajuste: 1.360
Endereo 32.76 - (kZN3 Res. Angle) Define o ngulo do valor de compensao k, para falta
fase-terra dentro da zona 2. Definiu-se o ngulo de k idntico para todas as zonas de proteo e
portanto igual ao definido no endereo 30.06.
Ajuste: 20.95 deg
Endereo 32.79 - (R3 Gnd. Res. Fwd) Define o alcance resistivo de zona 3 para falta fase-terra.
Os valores j obtidos anteriormente das resistncias de carga, de arco e indicada pelo rel esto
apresentados abaixo:
Ajuste: 22.50 Ohm
Endereo 32.7C - (Z3 Sensit Ignd>3) Este ajuste define o menor valor de corrente para
sensibilizar o rel para esta funo. Este parmetro deve ser o mais sensvel possvel, de forma
Pgina 16 de 36
que o rel possa detectar falta com baixo nvel de corrente. Um valor igual a 5% da corrente
nominal do TC (250 mA) adequado para este ajuste.
Ajuste: 250.0 mA
Resumo dos ajustes deste grupo
Endereo
Funo
32.02
Z1 Ph. Reach
32.03
Z1 Ph. Angle
32.09
Z1 Sensit. Iph>1
32.10
Z2 Ph. Reach
32.11
Z2 Ph. Angle
32.17
Z2 Sensit. Iph>2
32.20
Z3 Ph. Reach
32.21
Z3 Ph. Angle
32.28
Z3 Sensit. Iph>3
32.51
Z1 Gnd. Reach
32.52
Z1 Gnd. Angle
32.53
Z1 Dynamic Tilt
32.54
Z1 Tilt Top Line
32.55
kZN1 Res. Comp.
32.56
kZN1 Res. Angle
32.59
R1 Gnd Resistive
32.5B
Z1 Sensit Ignd>1
32.60
Z2 Gnd. Reach
32.61
Z2 Gnd. Angle
32.63
Z2 Dynamic Tilt
32.64
Z2 Tilt Top Line
32.65
kZN2 Res. Comp.
32.66
kZN2 Res. Angle
32.69
R2 Gnd Resistive
32.6B
Z2 Sensit Ignd>2
32.70
Z3 Gnd. Reach
32.71
Z3 Gnd. Angle
32.73
Z3 Dynamic Tilt
32.74
Z3 Tilt Top Line
32.75
kZN3 Res. Comp.
32.76
kZN3 Res. Angle
32.79
R3 Gnd. Res. Fwd
32.7C
Z3 Sensit Ignd>3
Ajuste
23,50/In
63.20 deg
100.0 x In
27.00/In
63.20 deg
100.0 x In
34.25/In
63.20 deg
100.0 x In
23,50/In
63.20 deg
Enabled
0 deg
1.360
20.95 deg
61.75/In
50.00 x In
27.00/In
63.20 deg
Enabled
0 deg
1.360
20.95 deg
87.50/In
50.00 x In
34.25/In
63.20 deg
Enabled
0 deg
1.360
20.95 deg
112.5/In
50.00 x In
= 4.700 Ohm
= 500.0 mA
= 5.400 Ohm
= 500.0 mA
= 6.850 Ohm
= 500.0 mA
= 4.700 Ohm
= 12.35 Ohm
= 250.0 mA
= 5.400 Ohm
= 17.50 Ohm
= 250.0 mA
= 6.850 Ohm
= 22.50 Ohm
= 250.0 mA
Ajuste: 000001
Endereo 34.86 - (TOC Reset Delay) Este ajuste define o temporizador tanto da funo SOTF
quanto da funo TOR, ou seja, estas protees iro permanecer ativas somente pelo tempo
ajustado neste parmetro. Este parmetro ser ajustado em 500ms.
Ajuste: 500.0 ms
Endereo 34.88 - (TOC Delay) Este ajuste define o tempo que deve ser transcorrido aps a
abertura do disjuntor para que a funo TOR seja ativada. Deve-se lembrar que este tempo
dever ser menor que o menor dead time. Como o tempo morto ser ajustado em 250 ms, este
ajuste ser configurado em 200 ms.
Ajuste: 200.00 ms
Endereo 34.B1 - (Z1 Ext Scheme) Este ajuste permite uma extenso da zona 1, caso haja
falha nos canais de proteo. Neste caso, ser desabilitado, de forma a evitar atuaes indevidas.
Ajuste: Disabled
Endereo Funo Ajuste
Endereo 34.C1 - (LOL Scheme) Este ajuste permite que o rel reconhea uma condio de
perda de carga de forma a identificar que o disjuntor do outro terminal est aberto e por isso,
enviar um sinal de trip para o prprio disjuntor. Neste projeto este ajuste ser desabilitado.
Ajuste: Disabled
Resumo dos ajustes deste grupo
Endereo
Funo
34.08
Zone1 Tripping
34.09
tZ1 Ph. Delay
34.0A
tZ1 Gnd. Delay
34.10
Zone2 Tripping
34.11
tZ2 Ph. Delay
34.12
tZ2 Gnd. Delay
34.18
Zone3 Tripping
34.19
tZ3 Ph. Delay
34.1A
tZ3 Gnd. Delay
34.20
ZoneP Tripping
34.28
Zone4 Tripping
34.41
Aid. 1 Selection
34.61
Aid. 2 Selection
34.81
SOTF Status
34.82
SOTF Delay
34.83
SOTF Tripping
34.84
TOR Status
34.85
TOR Tripping
34.86
TOC Reset Delay
34.88
TOC Delay
34.B1
Z1 Ext Scheme
34.C1
LOL Scheme
Ajuste
Phase And Ground
0s
0s
Phase And Ground
500.0 ms
500.0 ms
Phase And Ground
1.000 s
1.000 s
Disabled
Disabled
Disabled
Disabled
Enabled PoleDead
10.00 s
000011
Enabled
000001
500.0 ms
200.00 ms
Disabled
Disabled
9.5. OVERCURRENT
Esse grupo define os ajustes relativos proteo de sobrecorrente de fase. Para esta aplicao,
ser utilizado um dos seus grupos para fazer a funo de sobrecorrente direcional de fase
temporizada (67T retaguarda) e os demais sero desabilitados.
Endereo 35.01 - (I>1 Status) Este ajuste define se a funo Overcurrent grupo 1 ser
habilitada ou desabilitada. Para este projeto, esta funo ser habilitada como sendo de
sobrecorrente direcional de fase temporizada. Esta proteo tem o objetivo de fazer a retaguarda
da proteo de distncia para faltas entre fases.
Pgina 19 de 36
Ajuste: Enabled
Endereo 35.02 - (I>1 Function) Este ajuste define qual a curva ser utilizada para esta funo.
Neste projeto ser utilizada a curva normal inversa da norma IEC.
Ajuste: IEC S Inverse
Endereo 35.03 - (I>1 Directional) Este ajuste define a direcionalidade desta funo. Deve ser
definida de forma a atuar para faltas frente, ou seja, na direo da linha de transmisso.
Ajuste: Directional Fwd
Endereo 35.04 - (I>1 Current Set) Este ajuste define o pickup desta funo. Para o clculo
deste pickup utilizou-se o seguinte critrio: ser definido como 1.2 vezes a corrente do limite
trmico do cabo da linha, de forma a evitar atuao da funo para uma condio de carga.
Ajuste: 5.000 A
Endereo 35.06 - (I>1 TMS) Este ajuste define o dial de tempo da funo. Abaixo ser
demonstrado o critrio que definir este parmetro. Para o clculo deste critrio ser utilizada a
maior das correntes de curto-circuito trifsico para faltas externas que circulam pelo rel.
Corrente em Amp primrio, "vista" pelo rel para falta trifsica na barra de Citrosuco.
I3CITROS = 1208 A
Com a corrente obtida acima, ser calculado um dial de tempo de forma que para a curva normal
inversa o tempo de atuao seja igual a 1000 ms.
Tp = {1.0 * [(I3CITROS Ipickup 67prim)0,02 1]} 0.14
Tp = {1.0 * [(1208 600)0,02 1]} 0.14 Tp = {1.0 * 0.0141} 0.14 Tp = 0.1007
Tp = 0.1 (curva definida)
O tempo de atuao, para uma falta trifsica na barra de Citrosuco, com o dial de tempo obtido
de 990 ms.
Endereo 35.09 - (I>1 tRESET) Este ajuste define o tempo de reset desta funo. Para este
projeto o tempo de reset ser 0.
Ajuste: 0 s
Endereo 35.0A - (I>2 Status) Este ajuste define se a funo Overcurrent grupo 2 ser
habilitada ou desabilitada. Ficar desabilitado.
Ajuste: Disabled
Endereo 35.13 - (I>3 Status) Este ajuste define se a funo Overcurrent grupo 3 ser
habilitada ou desabilitada. Esta ser habilitada para realizar a funo 67 instantnea (67I).
Ajuste: Enabled
Endereo 35.14 - (I>3 Directional) Este ajuste define a direcionalidade desta funo. Deve ser
definida de forma a atuar para faltas frente, ou seja, na direo da linha de transmisso.
Ajuste: Directional Fwd
Endereo 35.15 - (I>3 Current Set) Este ajuste define o pickup da funo 67 instantnea (67I).
Para o clculo do pickup desta funo utilizou-se o seguinte critrio: ser definido igual a 1.25
vezes a corrente de sequencia positiva que circula pelo rel, para um curto-circuito trifsico na
barra da SE Citrosuco.
Ajuste: 12.50 A
Endereo 35.16 - (I>3 Time Delay) Este ajuste define o atraso de tempo da funo. No haver
nenhuma temporizao para este ajuste.
Ajuste: 0 s
Pgina 20 de 36
Endereo 35.18 - (I>4 Status) Este ajuste define se a funo Overcurrent grupo 4 ser
habilitada ou desabilitada. Ficar desabilitado.
Ajuste: Disabled
Endereo 35.1C - (I> Char Angle) Este ajuste define o ngulo de mximo torque da funo
Overcurrent. Ser ajustado em 30.
Ajuste: 30.00 deg
Endereo 35.1D - (I> Blocking) Este ajuste determina se o sinal de bloqueio oriundo da
superviso do TP afetam certos estgios de sobrecorrente.
VTS Block - Afeta somente a proteo de sobrecorrente direcional. Com o bit relevante ajustado
em 1, a operao da superviso do TP (VTS) bloquear o estgio. Quando o bit ajustado em 0,
o estgio ser revertido para no direcional durante a operao do VTS.
Se I>Status ajustado em "Enabled VTS", nenhum bloqueio deve ser selecionado para fornecer
a interrupo da falta pela proteo de sobrecorrente durante a condio de VTS.
O Bit 0 = VTS Bloqueia >1, o Bit 1 = VTS Bloqueia >2, o Bit 2 = VTS Bloqueia >3, o Bit 3 =
VTS Bloqueia >4 e os Bits 5 e 6 no so usados.
Para este rel, como se trata de linha radial, no teremos bloqueio em nenhuma situao.
Ajuste: 000000
Resumo dos ajustes deste grupo
Endereo
Funo
35.01
I>1 Status
35.02
I>1 Function
35.03
I>1 Directional
35.04
I>1 Current Set
35.06
I>1 TMS
35.09
I>1 tRESET
35.0A
I>2 Status
35.13
I>3 Status
35.14
I>3 Directional
35.15
I>3 Current Set
35.16
I>3 Time Delay
35.18
I>4 Status
35.1C
I> Char Angle
35.1D
I> Blocking
Ajuste
Enabled
IEC S Inverse
Directional Fwd
1.000 x In
= 5.000 A
100.0e-3
0s
Disabled
Enabled
Directional Fwd
2.500 x In
= 12.50 A
0s
Disabled
30.00 deg
000000
Pgina 21 de 36
de segurana e evitar atuaes indevidas por erros de medies ser configurado em 10% da
corrente nominal do TC, o que equivale a 60 A primrios ou 0.5 A secundrios.
Ajuste: 500.0 mA
Endereo 38.2D - (IN>1 TMS) Este ajuste define o dial de tempo da funo. Abaixo ser
demonstrado o critrio que definir este parmetro. Para clculo deste critrio ser utilizada a
maior das correntes de sequncia zero de curto-circuito fase-terra para faltas externas que
circulam pelo rel.
Corrente de sequncia zero em Amp primrio, "vista" pelo rel para falta fase-terra na barra de
Citrosuco.
I1CITROS = 626
Com a corrente obtida acima, ser calculado um dial de tempo de forma que para a curva normal
inversa o tempo de atuao seja igual a 500 ms.
Tp = {0.5 * [(I1CITROS Ipickup 67Nprim)0,02 1]} 0.14
Tp = {0.5 * [(626 60)0,02 1]} 0.14 Tp = {0.5 * 0.0480} 0.14 Tp = 0.1715
Tp = 0.17 (curva definida)
O tempo de atuao, para uma falta trifsica na barra de Citrosuco, com o dial de tempo obtido
de 500 ms.
Endereo 38.33 - (IN>1 tRESET) Este ajuste define o tempo de reset desta funo. Para este
projeto o tempo de reset ser 0 s.
Ajuste: 0 s
Endereo 38.35 - (IN>2 Status) Este ajuste define se a funo Earth Fault grupo 2 ser
habilitada ou desabilitada. Ficar desabilitado.
Ajuste: Disabled
Endereo 38.46 - (IN>3 Status) Este ajuste define se a funo Earth Fault grupo 3 ser
habilitada ou desabilitada. Esta ser habilitada para realizar a funo 67N instantnea (67NI).
Ajuste: Enabled
Endereo 38.47 - (IN>3 Directional) Este ajuste define a direcionalidade desta funo. Deve
ser definida de forma a atuar para faltas frente, ou seja, na direo da linha de transmisso.
Ajuste: Directional Fwd
Endereo 38.4A - (IN>3 Current Set) Este ajuste define o pickup da funo 67N instantnea
(67NI). Para o clculo do pickup desta funo utilizou-se o seguinte critrio: ser definido igual a
1.2 vezes a corrente de sequncia zero que circula pelo rel, para um curto-circuito na barra da
SE Citrosuco.
Ajuste: 6.300 A
Endereo 38.4B - (IN>3 Time Delay) Este ajuste define o atraso de tempo da funo. No
haver nenhuma temporizao para este ajuste.
Ajuste: 0 s
Endereo 38.4D - (IN>4 Status) Este ajuste define se a funo Earth Fault grupo 4 ser
habilitada ou desabilitada. Ficar desabilitado.
Ajuste: Disabled
Endereo 38.54 - (IN> Blocking) Este ajuste determina se o sinal de bloqueio oriundo da
superviso do TP afetam certos estgios de sobrecorrente.
VTS Block - Afeta somente a proteo de sobrecorrente direcional. Com o bit relevante ajustado
em 1, a operao da superviso do TP (VTS) bloquear o estgio. Quando o bit ajustado em 0,
o estgio ser revertido para no direcional durante a operao do VTS.
Pgina 22 de 36
Se IN>Status ajustado em "Enabled VTS", nenhum bloqueio deve ser selecionado para fornecer
a interrupo da falta pela proteo de sobrecorrente durante a condio de VTS.
O Bit 0 = VTS Bloqueia N>1, o Bit 1 = VTS Bloqueia N>2, o Bit 2 = VTS Bloqueia N>3, o Bit
3 = VTS Bloqueia N>4 e os Bits 5 e 6 no so usados.
Para este rel, como se trata de linha radial, no teremos bloqueio em nenhuma situao.
Ajuste: 000000
Endereo 38.56 - (IN> Char Angle) Este ajuste define o ngulo de mximo torque da funo
Earth Fault. Ser ajustado para um ngulo de -60 graus.
Ajuste: -60.00 deg
Endereo 38.57 - (IN> Polarisation) Define se a polarizao para determinao da direo, ser
realizada por sequncia zero ou por sequncia negativa. Ser utilizada por sequncia zero.
Ajuste: Zero Sequence
Endereo 38.59 - (IN> VNpol Set) Define o menor valor de tenso de sequncia zero que o
rel deve medir para determinao da direo pelas componentes de sequncia zero.
Ajuste: 1.000 V
Resumo dos ajustes deste grupo
Endereo
Funo
38.01
IN>1 Status
38.25
IN>1 Function
38.26
IN>1 Directional
38.29
IN>1 Current Set
38.2D
IN>1 TMS
38.33
IN>1 tRESET
38.35
IN>2 Status
38.46
IN>3 Status
38.47
IN>3 Directional
38.4A
IN>3 Current Set
38.4B
IN>3 Time Delay
38.4D
IN>4 Status
38.54
IN> Blocking
38.56
IN> Char Angle
38.57
IN> Polarisation
38.59
IN> VNpol Set
Ajuste
Enabled
IEC S Inverse
Directional Fwd
100.0 x In
= 500.0 mA
170.0e-3
0s
Disabled
Enabled
Directional Fwd
1.300 x In
= 6.500 A
0s
Disabled
000000
-60.00 deg
Zero Sequence
1.000 V
Ajuste
Disabled
Ajuste
SEF Enabled
DT
Directional Fwd
20.00 x InSEF = 100.0 mA
3A.31
3A.37
3A.3A
3A.49
3A.50
3A.57
3A.59
3A.5B
ISEF>1 Delay
ISEF>1 tRESET
ISEF>2 Function
ISEF>3 Status
ISEF>4 Status
ISEF> Blocking
ISEF> Char Angle
ISEF> VNpol Set
4.000 s
0s
Disabled
Disabled
Disabled
000000
-60.00 deg
1.000 V
Ajuste
Enabled
200.0 ms
Disabled
Pgina 25 de 36
45.06
45.07
45.08
45.0B
45.0D
45.10
9.10. SUPERVISION
Neste mdulo sero apresentados os ajustes referentes superviso dos TCS e TPS.
Endereo 46.01 - (VTS Mode) Este ajuste define como a funo VTS ir operar. Neste projeto,
a funo VTS ir operar atravs da medio de tenso.
Ajuste: Measured Only
Endereo 46.02 - (VTS Status) Este ajuste define se a funo VTS ir bloquear as unidades de
sobrecorrente caso o rel detectar uma falha fuso fusvel.
Ajuste: Blocking
Endereo 46.03 - (VTS Reset Mode) Este ajuste define como ser o reset da funo VTS. Neste
projeto o reset desta funo ser automtico, ou seja, quando ocorrer o retorno trifsico da
tenso.
Ajuste: Auto
Endereo 46.04 - (VTS Time Delay) Este ajuste define um temporizador que aps ter sido
transcorrido o tempo ajustado, ocorre o selo da funo VTS. Desta forma, todas as funes
dependentes de tenso permanecem bloqueadas. Este selo ser desfeito somente quando o rel
identificar as condies de reset da funo VTS. Para esta aplicao o ajuste ser de 5 segundos.
Ajuste: 5.000 s
Endereo 46.05 - (VTS I> Inhibit) A ausncia de tenso durante a energizao da linha pode
ser causada por duas situaes: falha no circuito de potencial ou uma falta trifsica. Para
diferenciar VTS de curto-circuito existe este ajuste que define um valor de corrente que dever
ser ultrapassado para que o rel compreenda que h um curto-circuito ao invs de uma falha no
circuito de potencial. Desta forma, este valor de corrente ser ajustado conforme o seguinte
critrio:
Corrente mxima de carga de acordo com o limite trmico
ICarga_mximo = 637 A
Corrente que circula pelo rel para falta trifsica na barra de Citrosuco
ICC_3P_CTR := 1208 A
Este parmetro deve ser ajustado entre 80% da corrente de falta obtida acima e 120% da
corrente de mximo carregamento, portanto:
764.40 < Iajuste < 966.40
Ento, ser definido em 865 A primrios.
VTSI_Inhibit = 865 / RTC = 7.21 A
Ajuste: 30.00 A
Endereo 46.06 - (VTS I2> Inhibit) Este ajuste utilizado para by-passar a unidade de VTS
quando ocorrer um curto-circuito no sistema que pode operar esta unidade. Desta forma, este
valor de corrente dever ser baixo para que possa detectar todos os tipos de curtos-circuitos,
inclusive os de maior resistncia.
Ajuste: 250.0 mA
Endereo 46.0E - (Inrush Detection) Este parmetro define se a restrio de Inrush ser
habilitada. Nesta aplicao, o parmetro ser habilitado.
Ajuste: Enabled
Pgina 26 de 36
Endereo 46.0F - (I>2nd Harmonic) Este ajuste define em porcentagem o valor de corrente de
segunda harmnica. Ser ajustado em 15%.
Ajuste: 15.00%
Endereo 46.11 - (WI Inhibit) Este parmetro utilizado em sistemas onde h uma fonte fraca
de sequncia negativa ou positiva, para uma fonte forte de sequncia zero. Como se trata de
linha radial, este parmetro ser desabilitado.
Ajuste: Disabled
Endereo 46.31 - (CTS Mode) Este parmetro define se o algoritmo de deteco de falhas dos
TCS ser habilitado ou no. Esta funo ficar habilitada.
Ajuste: Enabled
Endereo 46.32 - (CTS Status) Este ajuste determina se o status do algoritmo de deteco de
falhas dos TCS ter ou no indicao de falha. Neste estudo contemplara indicao.
Ajuste: Indication
Endereo 46.33 - (CTS Reset Mode) Determina se o modo reset do algoritmo de deteco de
falhas dos TCS ser manual ou automtico. Neste caso ser manual.
Ajuste: Manual
Endereo 46.35 - (CTS VN< Inhibit) O ajuste usado para inibir o elemento de superviso da
corrente do transformador quando a tenso de sequncia zero superar esse ajuste. Ajustado em
5 V.
Ajuste: 5.000 V
Endereo 46.36 - (CTS IN> Set) Esse ajuste determina o nvel de corrente de sequncia zero
que deve estar presente para validar a condio de superviso do transformador. Ajustado em
500 mA.
Ajuste: 500.0 mA
Resumo dos ajustes deste grupo
Endereo
Funo
46.01
VTS Mode
46.02
VTS Status
46.03
VTS Reset Mode
46.04
VTS Time Delay
46.05
VTS I> Inhibit
46.06
VTS I2> Inhibit
46.0E
Inrush Detection
46.0F
I>2nd Harmonic
46.11
WI Inhibit
46.31
CTS Mode
46.32
CTS Status
46.33
CTS Reset Mode
46.35
CTS VN< Inhibit
46.36
CTS IN> Set
Ajuste
Measured Only
Blocking
Auto
5.000 s
30.00 A
250.0 mA
Enabled
15.00 %
Disabled
Enabled
Indication
Manual
5.000 V
500.0 mA
9.11. AUTORECLOSE
Neste mdulo sero apresentados os ajustes referentes funo de religamento automtico.
Ser configurado apenas um ciclo de religamento com tempo morto definido em 250 ms e para
religar em qualquer condio. Apenas as funes de atuao instantnea iro partir o
religamento, as demais iro bloquear. A princpio o reclaim time ser configurado em 15
segundos. Abaixo, segue os ajustes da funo religamento a serem configurados.
Endereo 49.05 - (Single Pole Shot) Este ajuste define o nmero de religamentos para abertura
monopolar.
Ajuste: 1
Pgina 27 de 36
Endereo 49.06 - (Three Pole Shot) O ajuste define o nmero de religamentos para abertura
tripolar.
Ajuste: 1
Endereo 49.08 - (Dead Time 1) Define o tempo morto para o primeiro ciclo de religamento,
exceto onde o trip monopolar.
Ajuste: 250.0 ms
Endereo 49.09 - (Dead Time 2) Define o tempo morto para o segundo ciclo de religamento.
Ajuste: 60.00 s
Endereo 49.0A - (Dead Time 3) Define o tempo morto para o terceiro ciclo de religamento.
Ajuste: 60.00 s
Endereo 49.0B - (Dead Time 4) Este ajuste define o tempo morto para o quarto ciclo de
religamento.
Ajuste: 60.00 s
Endereo 49.0C - (AR CBHealthyTime) Tempo em que a binria de entrada do disjuntor deve
permanecer saudvel aps a concluso do tempo morto. Se a entrada for baixa e permanecer
baixa aps o tempo ajustado, resultar no bloqueio e o disjuntor permanecer aberto.
Ajuste: 5.000 s
Endereo 49.0F - (Reclaim Time) Este ajuste define o tempo em que o religamento retorna ao
incio do ciclo.
Ajuste: 15.00 s
Endereo 49.10 - (AR Inhibit Time) Aps o fechamento manual do disjuntor, o incio do
religamento inibido por um perodo igual configurao do ajuste do A/R Inhibit Time .
Ajuste: 60.00 s
Endereo 49.25 - (AR CheckSyncTime) Durante a condio de verificao do sistema, este
tempo solicitado para que a condio de religamento seja satisfatria. Se no for satisfatria,
o religamento ir a bloqueio aps este tempo.
Ajuste: 5.000 s
Endereo 49.27 - (Z2T AR) Determina se a zona 2 inicia ou bloqueia o religamento, ou se no
haver nenhuma ao da zona 2 sobre o religamento.
Ajuste: No Action
Endereo 49.28 - (Z3T AR) Determina se a zona 3 inicia ou bloqueia o religamento, ou se no
haver nenhuma ao da zona 3 sobre o religamento.
Ajuste: No Action
Endereo 49.2B - (DEF Aided AR) Ajuste que determina o impacto da proteo direcional de
terra no religamento.
Ajuste: Initiate AR
Endereo 49.2C - (Dir Aided AR) Ajuste que determina o impacto da proteo direcional no
religamento.
Ajuste: Block AR
Endereo 49.2D - (TOR AR) Este ajuste determina o impacto do Trip On Reclose (TOR) no
religamento.
Ajuste: Block AR
Endereo 49.2F - (I>1 AR) Determina se o ajuste do primeiro estgio da proteo de
sobrecorrente impacta no religamento.
Ajuste: No Action
Pgina 28 de 36
Ajuste
1
1
250.0 ms
60.00 s
60.00 s
60.00 s
5.000 s
15.00 s
60.00 s
5.000 s
No Action
No Action
Initiate AR
Block AR
Block AR
No Action
No Action
Initiate AR
Allow Autoclose
Protection Op
Pgina 29 de 36
TER.BRANC138
12312
DUARTINA-138
12554
0.937
DUARTINA--13
80125
30.0
-699.4
1
-55.5
-0.0
1
-63.4
0.0
1
-82.9
0.773
CITROSUCO-34
92238
12372
991.8
1
-55.6
DUARTINA--34
92237
0.0
1
-89.7
-0.0
1
-89.7
292.4
1
-55.8
CITROSUC1-13
92239
30.0
-292.4
1
-55.8
-991.8
1
-55.6
0.773
30.0
3967.1
1
-85.6
0.0
1
-61.5
-0.0
1
-91.5
0.000
VITORIA--138
12565
12368
0.0
1
0.0
0.000
0.000
0.861
-292.4
1
-55.8
292.4
1
-55.8
3967.1
-85.6
ITAMBE---138
12558
12367
0.0
1
0.0
0.934
0.0
-292.4
1
-55.8
0.0
0.0
1
1
0.0
MARILIA--138
12314
DUARTINA--13
80125
30.0
-437.1
1
-86.7
-0.0
1
-90.0
-0.0
1
0.0
0.837
CITROSUCO-34
92238
12372
619.9
1
-86.8
DUARTINA--34
92237
0.0
1
-89.7
-0.0
1
-89.7
182.8
1
-87.1
CITROSUC1-13
92239
30.0
-182.8
1
-87.1
-619.9
1
-86.8
30.0
4294.7
1
-86.8
0.0
1
0.0
VITORIA--138
12565
12368
0.0
1
0.0
0.000
0.000
0.938
-182.8
1
-87.1
182.8
1
-87.1
4294.7
-86.8
ITAMBE---138
12558
12367
0.0
1
0.0
0.969
-182.8
1
-87.1
0.0
-0.0
1
-90.0
0.543
0.903
0.0
0.0
1
1
0.0
MARILIA--138
12314
Pgina 30 de 36
TER.BRANC138
12312
DUARTINA-138
12554
0.938
DUARTINA--13
80125
30.0
-684.5
1
-55.0
0.0
1
0.0
-0.0
1
-76.0
0.777
CITROSUCO-34
92238
12372
970.8
1
-55.1
DUARTINA--34
92237
286.2
1
-55.3
-3883.0
1
-85.1
-286.2
1
-55.3
CITROSUC1-13
92239
3883.0
-85.1
30.0
-970.8
1
-55.1
-0.0
1
-113.3
3883.0
1
-85.1
30.0
0.0
1
-57.1
-0.0
1
-87.1
0.000
0.777
VITORIA--138
12565
12368
0.0
1
0.0
0.023
0.000
-286.2
1
-55.3
286.2
1
-55.3
0.864
ITAMBE---138
12558
12367
0.0
1
0.0
0.935
0.0
-286.2
1
-55.3
0.0
0.0
1
1
0.0
MARILIA--138
12314
DUARTINA--13
80125
30.0
-413.3
1
-86.1
-0.0
1
-135.0
0.0
1
-63.4
0.845
CITROSUCO-34
92238
12372
586.1
1
-86.2
DUARTINA--34
92237
172.8
1
-86.4
-4060.7
1
-86.2
4060.7
-86.2
30.0
-172.8
1
-86.4
-586.1
1
-86.2
0.907
0.0
1
-21.5
4060.7
1
-86.2
CITROSUC1-13
92239
30.0
0.0
1
-100.6
0.555
VITORIA--138
12565
12368
0.0
1
0.0
0.056
0.000
-172.8
1
-86.4
172.8
1
-86.4
0.941
ITAMBE---138
12558
12367
0.0
1
0.0
0.970
-172.8
1
-86.4
0.0
-0.0
1
-108.4
0.0
0.0
1
1
0.0
MARILIA--138
12314
Pgina 31 de 36
TER.BRANC138
12312
DUARTINA-138
12554
0.962
DUARTINA--13
80125
30.0
-418.8
1
-46.3
0.0
1
0.0
0.0
1
0.0
0.859
CITROSUCO-34
92238
12372
593.9
1
-46.4
DUARTINA--34
92237
175.1
1
-46.6
-2375.6
1
-76.4
-175.1
1
-46.6
CITROSUC1-13
92239
2375.6
-76.4
30.0
-593.9
1
-46.4
0.859
-0.0
1
-89.2
2375.6
1
-76.4
30.0
0.0
1
-71.5
-0.0
1
-101.5
0.000
VITORIA--138
12565
12368
0.0
1
0.0
0.420
0.000
-175.1
1
-46.6
175.1
1
-46.6
0.915
ITAMBE---138
12558
12367
0.0
1
0.0
0.960
0.0
-175.1
1
-46.6
0.0
0.0
1
1
0.0
MARILIA--138
12314
DUARTINA-138
12554
0.988
DUARTINA--13
80125
30.0
-159.0
1
-79.3
0.0
1
0.0
0.0
1
0.0
0.938
CITROSUCO-34
92238
12372
225.4
1
-79.4
DUARTINA--34
92237
66.5
1
-79.7
-1561.8
1
-79.4
1561.8
-79.4
30.0
-66.5
1
-79.7
-225.4
1
-79.4
0.958
-0.0
1
-78.8
1561.8
1
-79.4
CITROSUC1-13
92239
30.0
0.0
1
-150.3
0.684
VITORIA--138
12565
12368
0.0
1
0.0
0.641
0.000
-66.5
1
-79.7
66.5
1
-79.7
0.974
ITAMBE---138
12558
12367
0.0
1
0.0
0.987
-66.5
1
-79.7
0.0
1
-0.0
1
-90.0
0.0
0.0
1
0.0
MARILIA--138
12314
TER.BRANC138
12312
DUARTINA-138
12554
0.977
DUARTINA--13
80125
30.0
-247.9
1
-40.8
0.0
1
0.0
-0.0
1
0.0
0.916
CITROSUCO-34
92238
12372
351.6
1
-40.9
DUARTINA--34
92237
103.7
1
-41.2
-1406.4
1
-70.9
1406.4
-70.9
30.0
-103.7
1
-41.2
-351.6
1
-40.9
0.0
1
-153.2
1406.4
1
-70.9
CITROSUC1-13
92239
30.0
0.0
1
-75.9
-0.0
1
-105.9
0.000
0.916
VITORIA--138
12565
12368
0.0
1
0.0
0.663
0.000
-103.7
1
-41.2
103.7
1
-41.2
0.949
ITAMBE---138
12558
12367
0.0
1
0.0
0.976
0.0
-103.7
1
-41.2
0.0
0.0
1
1
0.0
MARILIA--138
12314
DUARTINA--13
80125
30.0
-76.9
1
-77.2
-0.0
1
-90.9
0.0
1
-178.3
0.970
CITROSUCO-34
92238
12372
109.1
1
-77.3
DUARTINA--34
92237
32.2
1
-77.5
-755.5
1
-77.3
755.5
-77.3
30.0
-32.2
1
-77.5
-109.1
1
-77.3
0.979
-0.0
1
-74.5
755.5
1
-77.3
CITROSUC1-13
92239
30.0
0.0
1
-76.0
0.727
VITORIA--138
12565
12368
0.0
1
0.0
0.827
0.000
-32.2
1
-77.5
32.2
1
-77.5
0.987
ITAMBE---138
12558
12367
0.0
1
0.0
0.994
-32.2
1
-77.5
0.0
0.0
1
0.0
0.0
0.0
1
1
0.0
MARILIA--138
12314
TER.BRANC138
12312
DUARTINA-138
12554
0.980
DUARTINA--13
80125
30.0
-214.4
1
-39.8
0.0
1
0.0
-0.0
1
-81.1
0.927
CITROSUCO-34
92238
12372
304.1
1
-39.9
DUARTINA--34
92237
89.7
1
-40.1
-1216.4
1
-69.9
-0.0
1
-153.2
1216.4
-69.9
30.0
-89.7
1
-40.1
-304.1
1
-39.9
0.927
CITROSUC1-13
92239
30.0
1216.4
1
-69.9
0.0
1
-72.0
-0.0
1
-102.0
0.000
VITORIA--138
12565
12368
0.0
1
0.0
0.710
0.000
-89.7
1
-40.1
89.7
1
-40.1
0.956
ITAMBE---138
12558
12367
0.0
1
0.0
0.980
0.0
-89.7
1
-40.1
0.0
0.0
1
1
0.0
MARILIA--138
12314
DUARTINA--13
80125
30.0
-64.3
1
-76.8
-0.0
1
-90.0
0.0
1
0.0
0.975
CITROSUCO-34
92238
12372
91.2
1
-77.0
DUARTINA--34
92237
26.9
1
-77.2
-631.6
1
-77.0
0.0
1
-75.2
30.0
-26.9
1
-77.2
-91.2
1
-77.0
631.6
1
-77.0
-0.0
1
0.0
0.0
1
0.0
0.733
0.982
VITORIA--138
12565
0.0
1
0.0
0.855
0.000
-26.9
1
-77.2
26.9
1
-77.2
0.989
ITAMBE---138
12558
12367
0.0
1
0.0
0.995
0.0
CITROSUC1-13
92239
30.0
12368
-26.9
1
-77.2
631.6
-77.0
0.0
0.0
1
1
0.0
MARILIA--138
12314
Pgina 34 de 36
TER.BRANC138
12312
DUARTINA-138
12554
0.981
DUARTINA--13
80125
30.0
-212.9
1
-39.7
0.0
1
0.0
0.0
1
0.0
0.928
CITROSUCO-34
92238
12372
301.9
1
-39.8
DUARTINA--34
92237
-1207.8
1
-69.8
1207.8
1
-69.8
89.0
1
-40.1
CITROSUC1-13
92239
30.0
-89.0
1
-40.1
-301.9
1
-39.8
30.0
1207.8
1
-69.8
0.0
1
-72.1
-0.0
1
-102.1
0.000
0.928
VITORIA--138
12565
12368
0.0
1
0.0
0.712
0.000
0.957
-89.0
1
-40.1
89.0
1
-40.1
1207.8
-69.8
ITAMBE---138
12558
12367
0.0
1
0.0
0.980
0.0
-89.0
1
-40.1
0.0
0.0
1
1
0.0
MARILIA--138
12314
DUARTINA--13
80125
30.0
-63.7
1
-76.8
-0.0
1
-63.4
0.0
1
-90.5
0.975
CITROSUCO-34
92238
12372
90.4
1
-76.9
DUARTINA--34
92237
-626.2
1
-76.9
626.2
1
-76.9
26.6
1
-77.2
CITROSUC1-13
92239
30.0
-26.6
1
-77.2
-90.4
1
-76.9
30.0
626.2
1
-76.9
-0.0
1
-76.0
VITORIA--138
12565
12368
0.0
1
0.0
0.857
0.000
0.989
-26.6
1
-77.2
26.6
1
-77.2
626.2
-76.9
ITAMBE---138
12558
12367
0.0
1
0.0
0.995
-26.6
1
-77.2
0.0
0.0
1
0.0
0.734
0.983
0.0
0.0
1
1
0.0
MARILIA--138
12314
TER.BRANC138
12312
DUARTINA-138
12554
DUARTINA--13
80125
30.0
0.0
1
-153.4
1
0.962
CITROSUCO-34
92238
12372
159.6
1
-19.5
DUARTINA--34
92237
-638.6
1
-49.5
638.6
1
-49.5
CITROSUC1-13
92239
30.0
-159.6
1
-19.5
0.962
30.0
638.6
1
-49.5
-638.6
1
-49.5
1596.5
1
-79.5
0.000
1596.5
-79.5
VITORIA--138
12565
12368
1
0.840
0.487
ITAMBE---138
12558
12367
1
1
1
MARILIA--138
12314
DUARTINA--13
80125
30.0
0.0
1
-90.0
1
0.980
CITROSUCO-34
92238
12372
64.4
1
-81.5
DUARTINA--34
92237
-445.9
1
-81.6
445.9
1
-81.5
CITROSUC1-13
92239
30.0
-64.4
1
-81.6
30.0
445.9
1
-81.5
-445.9
1
-81.6
1930.9
1
-81.5
0.000
0.995
1930.9
-81.5
VITORIA--138
12565
12368
1
0.900
0.765
ITAMBE---138
12558
12367
1
1
1
MARILIA--138
12314
Pgina 36 de 36