PT. PHE ONWJ

Generic Maintenance Strategy Firewater Distribution System

mk.herbert.silitonga
Paper Copies are Uncontrolled | EDMS | 24/07/2015 11:51:19

Revision Log Register

Page

Date

All

23-Dec-2011

All

23-Dec-2011

All

23-Dec-2011

PHEONWJ-U-GMS-0060 Rev.2
Paper Copies are Uncontrolled

Revise
All PHE ONWJ Ltd. change to PT. PHE ONWJ
Change document number from PHEONWJ-U-PRC-0137 to PHEONWJU-GMS-0060
Change document type from Procedure (PRC) to Generic Maintenance
Strategy (GMS)

Page 2

PT. PHE ONWJ

Generic Maintenance Strategy Firewater Distribution System

This document is a development of the PT.


PHE ONWJ, Inspection & Maintenance
Strategy (IMS) for offshore platform and
provides specific detail of the maintenance
to
be
applied
to
FIREWATER
DISTRIBUTION SYSTEMS.

mk.herbert.silitonga
Paper Copies are Uncontrolled | EDMS | 24/07/2015 11:51:19

Scope

The firewater distribution system is a pipe


network dedicated to supply water for fire
fighting purpose from the 1fire pumps to
systems or equipment.
Field devices supplied by the firewater
system include sprinkler, deluge, monitor,
hose-reel and hydrant systems.
The pipe network has been calculated to
supply a determined quantity of pumped
water at pressure during an emergency
event.
3

Required Performance

a) Reliability

100%.

The Reliability is high as the system is


critical to life safety and asset protection.

b) Availability

100%.

Loss of the firewater system would


require
the
platform
Production
Supervisor to assess for reduced or
shutdown of production.
Partial loss would require a contingency
plan to be put in operation i.e. assess and

PHEONWJ-U-GMS-0060 Rev.2
Paper Copies are Uncontrolled

Maintenance Strategy

The system should be flowed annually with


seawater to flush debris and objects
internally then flowed with potable water
and chemically treated.
All valves should be maintained for
operability and availability annually.
Maintenance will be carried out to a
Planned Preventive Maintenance (PPM).
6

Maintenance / Inspection Schedule


and Activities

Description
Inspection of complete system
Flushing pipe work and
chemically treated for corrosion
protection.
Maintenance of valves

Equipment Function

The firewater system should be available


during an emergency event on demand.
Isolating valves in the system allow small
sections of the network to be temporarily
isolated without shutting down the total
system.
Delay or failure of this system to function
effectively would allow serious escalation
of a fire with unacceptable risk to
personnel.
4

deploy suitable portable fire equipment


and fire fighters to replace the short fall in
protection.

Purpose

Maintenance
2
Routine
PHEONWJ-UPRC-0223
PHEONWJ-UPRC-0224
PHEONWJ-UPRC-0225

Interval
6 months
12 months

12 months

Required Resource

Personnel can carry out inspection of the


Firewater system with pipe and valve
experience guided by an inspection
checklist.
On-site mechanical technicians can
perform maintenance work to the firewater
distribution network.
8

Related Standards/Reference

NFPA 24, Standard for the Installation of


Private Fire Service Mains and Their
Appurtenances
NFPA 25, Standard for the Inspection,
Testing, and Maintenance of Water-Based
Fire Protection Systems
API RP 14G, Fire Protection Systems for
Offshore Platforms.
PHEONWJ-U-DNX-0100,
Firewater
System Maintenance Job Plan Index