BY :
KETANKUMAR WANKHEDE
1.)
7401 Alarm
Syntex
Type
Severity
Colour
Pin
Root
Mains Failure
N/C
Major
Green & Green/White
7, 25
PIU
DDF
BTS
2.)
7402 Alarm
Syntex
Type
Severity
Colour
Pin
Rectifier Fail
N/O
Minor
Blue & Blue /White
8, 26
Root
Alarm panel
Of P.P.
DDF
BTS
Root cause Alarm occurs when any one of the SMPS gets
failure.
Cause
1. Any SMPS gets failure.
2. Due to failure of MCB.
3. Due to any s/c.
Verification
To check the alarm firstly remove the
rectifier from the SMPS or switch off the
MCB of rectifier from SMPS.
To remove alarm switch on the.MCB of
the rectifier moduleor insert the new
rectifier module.
3.)
7403 Alarm
Syntex
Type
Severity
Colour
Pin
Root
DDF
BTS
4.)
7404 Alarm
Syntex
Type
Severity
Colour
Pin
Root
Site On Battery
N/O
Major
Gray & Gray /White
10, 28
Alarm panel
Of P.P.
DDF
BTS
Root cause Alarm occurs when all SMPS & Rectifiers gets
failure.
Cause
1. When AC gets failure and D.G. does not
start.
2. AC gets fail DG is off.
3. DG is not working properly.
4. AC gets failure & DG is not available at
site.
5. All SMPS & rectifires gets failure.
Verification
To check the alarm switch off the mains
MCB from PIU & switch off DG also.
To remove alarm switch on the mains
MCB or DG (if mains is not available).
5.)
7405 Alarm
Syntex
Type
Severity
Colour
Pin
Site On DG
N/O
Minor
Pink & Pink /White
11, 29
Root
PIU
DDF
BTS
6.)
7406 Alarm
Syntex
Type
Severity
Colour
Pin
Root
DG LLOP
N/O
Criticle
Light Green & Black /Green
12, 30
LLOP Sensor
BTS
PIU
DDF
Root cause Alarm occurs when lube oil pressure gets below
then specified level.
Cause
1. Due to leakage of lubricant.
2. Due to overflow of lubricant.
3. Due to no service on time.
4. Due to no oil change on the time.
Verification
To check the alarm switch off the mains
MCB from PIU & switch off the DG also.
To remove alarm maintain the lubricant
oil pressure till specified level.
7.)
7407 Alarm
Syntex
Type
Severity
Colour
Pin
Root
PIU
DDF
Root cause Alarm occurs when fuel level goes below then
40% of the capacity.
Cause
1. When site on DG from long time.
2. When fuel tank is not fully filled.
3. Tank have leakage.
Verification
To check the alarm see if the desired fuel
level of DG is set on 40% or not.
To remove alarm fill the tank of DG.
8.)
7408 Alarm
Syntex
Type
Severity
Colour
Pin
Root
DG Fails To Start
N/O
Major
White & Black /White
13, 31
PIU
DDF
BTS
Verification
9.)
7409 Alarm
Syntex
Type
Severity
Colour
Pin
Root
AC Failure
N/O
Major
Light Gray & Black /light gray
15, 33
C
DDF
BTS
10.)
7410 Alarm
Syntex
Type
Severity
Colour
Pin
Door Open
N/C
Minor/Major/Criticle (Accd. to condition)
Red/ Black & Red/Blue
16, 34
Root
Door Sensor
BTS
PIU
DDF
11.)
7411 Alarm
Syntex
Type
Severity
Colour
Pin
Root
c of AC
DDF
12.)
7412 Alarm
Syntex
Type
Severity
Colour
Pin
Root
PIU
DDF