Attn:
Address
CC: (ESI)
Mr. Feroz. K. Kagadagar, Mr. Balakrishna Shetty, Mr. Asad Sayyad, Mr. Yogendra
Mishra
Report No
EISC/02/15
CC: (Ion Exchange) Mr. C.S Murthy, Mr. Suneeth Nair, Mr. V. Srinivasa, Mr. Bibin Baby
Date of Report
1-Jun-15
Report Prepared By
Treated System
Analysis Parameters
Units
DRP-3 WTP
ECW
Design Values
QCW
PCW
Actual
Control Limits
Actual
Control Limits
8.0 to 8.3
7.2
7.8 to 8.5
7.56
7.8 to 8.5
7.85
<1500
980
<1500
990
<2000
2650
<450
138
<450
135
<800
340
<5.0
3.6
Temperature
pH
Conductivity
PPM
PPM
M Alkalinity- Malk
PPM
Chloride - Cl-
PPM
Phosphate - PO4
PPM
4.0 to 8.0
2.8
4.0 to 8.0
2.8
PPM
<2.0
1.2
<2.0
0.52
Turbidity
NTU
PPM
10
Actual
oC
uS/cm
<50
<50
78
Analyzed By
Comments
Action
ECW
ECW
No action required
QCW
QCW
No action required
PCW
PCW
No action required
Dosed in to
Dosage Schedule
Attn:
Address
CC: (ESI)
Mr. Feroz. K. Kagadagar, Mr. Balakrishna Shetty, Mr. Asad Sayyad, Mr. Yogendra Mishra
Report No
EISC/02/15
Mr. C.S Murthy, Mr. Suneeth Nair, Mr. V. Srinivasa, Mr. Bibin Baby
Date of Report
1-Jun-15
Report Prepared By
Treated System
Analysis Parameters
Units
Temperature
pH
Conductivity
PPM
PPM
M Alkalinity- Malk
PPM
Chloride - Cl-
PPM
Nitrite - NO2
PPM
Phosphate - PO4
PPM
PPM
10
SMP III
CCM Primary Non Contact
Open Loop
Design Values
Actual
Control Limits
7.5 to 8.5
7.68
<200
155
<1.0
ADWEA Make Up
Actual
Control Limits
Actaul
Control Limits
Actaul
Control Limits
8.5 to 9.5
8.1
8.5 to 9.5
7.78
7.5 to 8.5
7.79
400-500
782
900-1400
230
<200
135
<10
15
<5
50
2.0 to 5.0
3.4
Actual
Control Limits
8.0 to 9.0
7.68
600-800
1017
100-200
Actual
Control Limits
Actual
8.0 to 9.0
7.83
8.0 to 9.0
8.46
600-800
1007
450-850
989
230
100-200
230
4.0 to 8.0
3.4
4.0 to 8.0
3.4
2.0 to 5.0
13.2
<1.0
0.42
<1.0
0.38
<3.0
3.1
oC
uS/cm
300-400
380
18
5.78
0.1
Analyzed By
Comments
Action
Softened Water
Softened Water
CCM Primary
CCM Primary
As per the control limits provided by GE, the paramters are on higher side
EAF/LRF
EAF/LRF
Corrosion inhibitor levels are very low and iron concetration is high
Corrshield NT4201 will be added to maintain the corrosion inhibitor levels in the system.
ICW -I
ICW -I
As per the control limits provided by GE, the paramters are on higher side
ICW-II
ICW-II
As per the control limits provided by GE, the paramters are on higher side
CCM Spray
CCM Spray
Stock of Chemicals
Sr No Chemical Name
Dosed in to
Dosage
Schedule
Dosage Qty
(Kg/Dose)
Telephone: 0097165261606
Attn:
Address
CC: (ESI)
Mr. Feroz. K. Kagadagar, Mr. Balakrishna Shetty, Mr. Asad Sayyad, Mr. Yogendra Mishra
Report No
EISC/02/15
Mr. C.S Murthy, Mr. Suneeth Nair, Mr. V. Srinivasa, Mr. Bibin Baby
1-Jun-15
Report Prepared By
Date of Report
Date of Last Report
Sr. No
Treated System
Analysis Parameters
Units
Temperature
pH
Conductivity
PPM
PPM
M Alkalinity- Malk
PPM
Chloride - Cl-
PPM
Nitrite - NO2
PPM
Phosphate - PO4
PPM
PPM
10
RM-V
ADWEA
Design Values
Actual
Control Limits
Actual
7.5 to 8.5
8.32
8.0 to 9.0
8.36
8.0 to 9.0
8.6
129
160 to 220
217
700 to 800
581
110-160
90
480-560
240
3.0 to 5.0
7.1
1.0 to 2.0
1.4
oC
uS/cm
Analyzed By
Comments
Actions
QW / B02
KW/CO1
Stock of Chemicals
Sr No Chemical Name
Dosed in to
Dosage Schedule
Telephone: 0097165261606
Attn:
Address
CC: (ESI)
Mr. Feroz. K. Kagadagar, Mr. Balakrishna Shetty, Mr. Asad Sayyad, Mr. Yogendra Mishra
Report No
EISC/02/15
Mr. C.S Murthy, Mr. Suneeth Nair, Mr. V. Srinivasa, Mr. Bibin Baby
Date of Report
1-Jun-15
Report Prepared By
Treated System
Analysis Parameters
Units
Design Values
1
Temperature
pH
Conductivity
Total Hardness
Chloride - Cl-
8
9
10
Oxygen Scavenger
DRP-3 Boiler
Softened Water
Deaerator Outlet
Boiler Blowdown
Condensate
Actual
Control Limits
Actaul
Control Limits
Actual
Control Limits
Actual
7.0 to 8.5
8.4
8.5 to 9.5
9.7
10.5 to 11.5
10.74
8.5 to 9.5
9.3
<200
156
60
<5000
2579
<5.0
<2.0
oC
uS/cm
30
ppm
ppm
<5.0
<5.0
Nill
ppm
ppm PO4
15-25
ppm
Silica
ppm
<0.02
ppm
<0.02
Analyzed By
26
30-40
15
<10.0
3.1
<1.0
0.5
<10.0
<1.0
Comments
Action
Deaerator Inlet
Deaerator Inlet
No action required
Deaerator Outlet
Deaerator Outlet
No action required
Boiler Blowdown
Boiler Blowdown
No action required
Condensate Return
Condensate Return
No action required
Dosed in to
Dosage Schedule
Telephone: 0097165261606