Вы находитесь на странице: 1из 6

ccrd Mechanical Checklist

Job Name : ________________________________________________________

Date : ________________________________________

Job Number : ______________________________________________________

Estimated % Complete : _________________________

Designed By : ______________________________________________________

Project Manager : ______________________________


Discipline Coordination

General Coord.
Item
Item
#
Ductwork Specialties/Services/Dampers:
1
Canvas wrap indicated in M.E. rooms
2
Fire Dampers: Combination Fire/Smoke type,
3
Class I, Dynamic
F/S dampers coordinated with electrical
4
5
Motorized dampers coordinated with elec.
Shaft Walls: 3 levels require smoke damper
6
AHU's about 15,000 CFM require smoke
7
damper
Elevators require separate system
8
Stairway requires separate system
9
Shaft corridors treat like stairway
10
11
Chiller:
12
Starter & disconnect Indicated
13
Refrigerant Monitor Indicated
14
Tube Pull Accommodated
15
Chiller Voltage Coord. With Elec.
16
Refrigerant Relief (purge) Indicated
17
Chiller Room Ventilation Indicated
18
16 degree delta T (Medical Center)
19
Chiller Room Controls at doors
20
Electrical power source indicated
21
Electrical power source voltage coordinated
22
with division 16
Starter & disconnect coordinated with
23
electrical (div. 16)
Sequence Of Operation Included
24
25
Chilled Water Appurtenances:
26
CHW Expansion Tank Included
27
CHW Isolation Valves Indicated
28
CHW Flow Measuring Indicated
29

NA

Spec.
Section

Detail
Included

Reviewer Comments

Discipline Coordination

General Coord.
Item
#
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67

Item
CHW Diff. Pressure Bypass Ind.
16 degree delta T (Medical Center)
CHW Flow Diagram Complete
Cooling Tower:
Water Side Economizer Indicated
CW Heat Trace Indicated
CW Heat Trace elec power provided
CT Controls Indicated
CT Controls power circuit provided
CT Fan(s) Power Indicated
CT Basin Heater Power Indicated
CT VFD or 2 Speed Control Ind.
CT Bypass Indicated
CT Clearance Coordinated
CT Support Coordinated
CT Make-up Water Indicated
CT Location Coordinated
Sequence Of Operation Included
Air Handling Unit (Indoor / Outdoor):
SAF Power Indicated (emergency?)
RAF Power Indicated (emergency?)
Double wall casing indicated
VFD(s) Indicated (bypass on supply fan)
Pre-Filters Indicated (30% cube type)
Final-Filters Indicated
Economizer Indicated
Housekeeping Pad Indicated (6")
Condensate Drain Indicated (cooling coil)
Unit Clearances Coordinated
Access section between Htg & Clg coil
SSteel coil & drain pan indicated
Air-Flow Monitoring Indicated (Sup/Ret/OA
min. only.....NOT max)
Chilled Water Valve Type Indicated
Hot Water Valve Type Indicated
Preheat Steam Valve Indicated
Steam Pressure Indicated
Steam Condensate Returned (steam
pressure powered pump)

NA

Spec.
Section

Detail
Included

Reviewer Comments

Discipline Coordination

General Coord.
Item
Item
#
Smoke Detectors Indicated
68
Smoke Detector power circuit(s) provided
69
Return Fan sized for smoke purge duty
70
Sequence Of Operation Included (Smoke
71
purge indicated)
Premium Efficiency Motors Indicated
Verify NO autoflow device on coils !!! Check
detail
Power provided for motorized dampers
72
Dedicated 120V emergency power circuit
73
provided for controls cabinet(s)
Power circuit provided for unit lighting
74
75
76
77
78
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86

NA

Power circuit provided for unit control (BAS)


Humidifiers:
Humidifier generator Indicated (Dri-Steem
STS with duct mtd dispersion unit)
15 psi steam supply indicated
Humidifier Water Source Indicated
Humidifier Power Indicated
Control Panel Indicated (provide additional
contacts for alarm monitoring)
Dual condensate traps indicated
Condensate Drain Cooler Indicated
Disconnect coordinated with elec.
Mounting height allows gravity drainage
Sequence Of Operation Included
Steam Condensate Returned (steam
pressure powered pump)
High limit humidistat provided by Carrier (not
Dri-Steem)
Controls power circuit provided (120V)
Heat Exchangers:
Steam to Water type
1/3 - 2/3 steam control indicated
70 psi steam supply indicated
Dual condensate traps indicated
Mounting height allows gravity drainage
Sequence Of Operation Included

Spec.
Section

Detail
Included

Reviewer Comments

Discipline Coordination

General Coord.
Item
#

Item

87

Steam Condensate Returned (steam


pressure powered pump)

88
89
90
91
92
93
94
95
96
97

Boilers:
Steam Pressure Indicated\coordinated
Natural gas indicated (Dual fuel?)
Condensate return coordinated
Feed water indicated
Expansion tank indicated
Isolation valves indicated
Combustion air indicated

98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121

Boiler
routingand
indicated
Boiler flue
clearance
tube pull area
accommodated
Boiler gas pressure coordinated with
plumbing
Dearator indicated
Heating water and/or steam flow diagrams
complete
Space for steam PRV's and control valves
indicated
Control panel power provided (Div. 16)
Blower motor power provided (Div. 16)
Sequence Of Operation Included
VAV Boxes:
Double wall casing indicated
Hot water re-heat coil indicated
Tags / indentifiers coordinated
Sequence Of Operation Included
Autoflow valve on reheat coil indicated
95 degree DAT (interior)
100 degree DAT (exterior)
Don't use for stairs, exits, elevators, etc.
Exhaust Fans:
Code required clearances coordinated
Roof penetrations coordinated
ZAM's indicated in spec.
High temperature applications: fan motor
located out of air stream

NA

Spec.
Section

Detail
Included

Reviewer Comments

Discipline Coordination

General Coord.
Item
#
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155

Item
Starter & disconnect coordinated with
electrical (div. 16)
Power provided (Div. 16)
Sequence Of Operation Included - Must be
fan specific
Steam Specialties:
F & T traps indicated (no exceptions)
70 psi steam supply indicated
All condensate lines double trapped
All equipment mounted to allow gravity
drainage to receiver and pump
Details included
PRV's included (stations)
All condensate returned to system
Spirex/Sarco equipment indicated
Valves (hydronic):
Ball valves 4" and smaller
Butterfly valves 6" and larger
Autoflow on VAV reheat coils
Stem extensions indicated
Piping Specialties:
Canvas wrap indicated in M.E. rooms
Painting scheme indicated (spec)
Expansion loops indicated (straight runs over
100' long)
Insulation:
Canvas wrap indicated in M.E. rooms
(piping and ductwork below 8'-0" AFF)
Removable "plugs" indicated at valves
Verify weld-pins are specified (NO stick-pins)
Variable Frequency Drives:
By-pass indicated (SAF's only)
Power wiring indicated from power source to
VFD and from VFD to equipment
Code required clearances provided

NA

Spec.
Section

Detail
Included

Reviewer Comments

Discipline Coordination

General Coord.
Item
#
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183

Item
Line reactors indicated (input & output)
Filter indicated (input only)
Unit Heaters:
Power provided & coordinated (Div. 16)
Summer fan switch indicated
AutoFlow valve indicated
Two-way control valve indicated
Sequence Of Operation Included
Pressure Sensitive rooms
TSI sensor indicated over door
Wall pressure indicator located
TSI sensor monitored by central EMS (add
verbiage to drawing and/or spec)
Positive / Negative pressurization
reguirements confirmed and reviewed?
Isolation Room exhaust fan warning labeling
specified?
Medical Equipment Chiller (process)
Quick connect panel utilized
Quick connect panel located and coordinated
with architectural
Power provided by div. 16
Chiller model coordinated with medical
equipment served (MRI, CT, etc.)
Mounting detail provided
Auxiliary alarms interlocked into BAS
Piping diagram (detail) provided
City water by-pass indicated
City water by-pass coord. with PLBG.

NA

Spec.
Section

Detail
Included

Reviewer Comments

Вам также может понравиться