Академический Документы
Профессиональный Документы
Культура Документы
system
Littelfuse Startco | January 21, 2015
PeopleMine
Share
Comments
Sign up for Suppliers Email & Alerts
Fig. 1: In a resistance-grounded system the neutral point is connected to ground via a neutral grounding
resistor.
To detect high-impedance faults and provide machinewinding protection, the desired ground-fault-current
pickup level for the ground-fault relay should be less
than 20% of the prospective ground-fault current. To
put it another way, a good rule of thumb is to multiply
the desired ground-fault-current pickup level by an
acceptable tripping ratio (say, 5x), and then use the
next-largest available standard let-through current
rating for the neutral-grounding resistor. For low- to
medium-voltage systems, standard NGR current
ratings are typically 1, 2, 5, 10, 15, and 25 amps.
For example, consider a system with a charging
current of 0.5 amps (which is quite common on a 480
V system) and a desired ground-fault pickup level of 1
amp. Using a trip ratio of 5, the value of the NGR
should be selected to allow five times the desired
pickup
level
current,
or
5
amps.
Another example: in potash mining the trailing cables
can become quite long, and as such will have
correspondingly large charging currents in the range
from 1 to 2 amps (or more). The tripping current on
each feeder must be above charging current to avoid
nuisance or sympathetic tripping; a tripping value of 3
A would be reasonable. . In this case the NGR should
be selected for a let-through current five times the
desired pickup level, or 15 amps.
It is worth noting that the 2009 edition of Canadian
Electrical Code (CEC) rule 10-1102 says that for
systems up to 5 kV the system may continue to
operate with NGR currents up to 10 amps, but that a
visual or audible alarm must be activated;
The case of mobile equipment in mining
inShare
0
Comments
Sign up for Suppliers Email & Alerts